Abstract
Hybrid multi-infeed HVDC systems may have insufficient transient voltage support, especially in receiving-end grids, where disturbances at one converter bus can spread through the interconnected AC network and increase the voltage drop at nearby converter stations. To improve the transient voltage response of such systems, this paper proposes a VSC-HVDC-based voltage-support strategy for a receiving-end system containing both line-commutated-converter-based HVDC (LCC-HVDC) and voltage-source-converter-based HVDC (VSC-HVDC) links. The voltage-support mechanism is analyzed based on the commutation-voltage waveform, voltage-time area, and extinction-angle margin of the LCC inverter. During an AC fault, the nearby VSC-HVDC terminal responds through its AC-voltage controller and increases its reactive current output, thereby reducing the receiving-end voltage drop and improving the voltage recovery process. The improved AC-voltage condition also increases the available voltage-time area and helps maintain the extinction-angle margin of the LCC inverter. A PSCAD/EMTDC model is used to compare the conventional multi-infeed HVDC system with the hybrid-infeed HVDC system. Simulation results show that the proposed strategy reduces the AC-voltage drop, improves the recovery of active power and DC voltage, and lowers the instantaneous critical transition resistance.