Climate-Responsive Design of PCM-Integrated Walls for Thermal Load Reduction in Hot Desert Climates

,
,
,
,
and
1
Mechanical Engineering Department, College of Engineering and Technology, Arab Academy for Science, Technology and Maritime Transport, Alexandria P.O. Box 1029, Egypt
2
Mechanical Engineering Department, Faculty of Engineering, Alexandria University, Alexandria 21544, Egypt
*
Author to whom correspondence should be addressed.
Buildings2026, 16(23), 4720;https://doi.org/10.3390/buildings16234720 
(registering DOI)
This article belongs to the Special Issue Advanced Sustainable Building Materials for Energy Efficiency, Thermal Comfort and Net-Zero Buildings

Abstract

Phase change materials (PCMs) can attenuate building envelope heat transfer, but their performance depends on configuration and seasonal exposure. This study used DesignBuilder/EnergyPlus to evaluate 240 BioPCM-integrated wall configurations under Cairo’s hot desert climate, varying melting grade (Q21–Q29), thickness (1.12–7.42 cm), layer position, and wall orientation. Performance was assessed using daily net wall energy transfer, warm-season inward heat gain, signed cool-season transfer, combined seasonal thermal benefit, and surface temperatures, followed by a material-level cost comparison. Outermost PCM placement generally provided the greatest warm-season heat-gain attenuation, although cool-season effects differed by orientation. In the West-facing wall, outermost Q21 M182 reduced warm-season inward heat gain by 85.4%, while increasing cool-season outward transfer. The M182 layer reduced wall thermal transmittance from 2.000 to 1.148 W/(m2·K), corresponding to a 42.6% reduction. The West-facing wall exhibited the highest combined seasonal thermal benefit, whereas the South-facing wall favored inner-layer placement under this indicator. Q21 M182 was selected as a preferred high-performance configuration, given the small differences among closely performing melting grades. Although M182 provided the greatest combined benefit among the investigated Q21 thicknesses, M27 achieved the highest thermal benefit per unit material cost. These findings emphasize orientation-specific PCM selection and distinguish wall-level thermal performance from whole-building HVAC energy savings.

1. Introduction

Buildings account for a major share of energy use, with a considerable portion of this demand linked to cooling and indoor thermal comfort. In a period marked by heightened concern over energy security and increasing pressure on power systems [1,2], improving building energy efficiency has become more urgent [3], particularly in hot-climate countries that rely heavily on conventional energy sources. This challenge is especially relevant in the Middle East and North Africa, where electricity demand is rising rapidly under the combined effects of urbanization, population growth, and increasing temperatures, with cooling becoming a major driver of future demand. Under these conditions, limiting heat gain through the building envelope is a key pathway for reducing cooling requirements. Accordingly, passive thermal-regulation strategies have gained increasing importance as practical solutions for improving building performance without additional operating energy [4,5].
Buildings represent one of the largest energy-consuming sectors worldwide, accounting for nearly 40% of total global energy use [6]. A considerable part of this demand is attributed to heating, ventilation, and air-conditioning (HVAC) systems, which play a key role in maintaining indoor thermal comfort in residential, commercial, and public facilities [7,8,9]. The issue is particularly significant in Egypt, where electricity generation is still predominantly dependent on fossil-fuel-based sources, highlighting the importance of improving energy efficiency in buildings [10,11,12]. In hot climates, cooling systems are required to offset both internal and external thermal loads, while a major part of the external load originates from heat transfer through the building envelope [13]. Consequently, passive cooling strategies have become increasingly important because they can reduce cooling energy demand without additional operational power input [14,15]. In this context, envelope-based approaches, including façade enhancement and phase change material (PCM) integration, have emerged as promising solutions for limiting heat gain and improving building thermal performance [14].
Among passive cooling strategies, the achievable thermal benefit varies considerably depending on the applied technique and the surrounding climatic conditions. Cooling shelters and façade-based modifications have shown noticeable potential for reducing heat gain and cooling demand in some applications [14,16]. However, the effectiveness of such strategies is often restricted by building type and climate characteristics [14,16]. In contrast, phase change materials (PCM) provide a different thermal regulation mechanism through latent heat storage, whereby part of the incoming heat is absorbed during the melting process and later released during solidification [17]. This process enables PCM to reduce temperature fluctuations and delay heat transfer through the building envelope [17]. Nevertheless, the thermal response of PCM is more difficult to generalize than that of other passive techniques because its performance depends strongly on the compatibility between its thermo-physical properties and the local climatic conditions [18,19,20]. As a result, PCM-based cooling performance cannot be assessed independently of climate, and careful selection of the phase-change temperature is essential for effective thermal regulation [19,20,21,22,23].
Previous studies have shown that the thermal and energy-saving performance of PCM varies significantly from one climate to another, even when similar building configurations are considered [18,19]. For example, the reported saving potential reached up to 80% in northwestern China, while it was only about 10% in southeastern China under different climatic conditions [18]. Similarly, for the same model, the energy-saving potential was reported to be around 8.8% in Manaus and approximately 13.5% in Tokyo, further confirming the influence of climate on PCM effectiveness [19]. This variation is mainly associated with the relationship between the outdoor temperature profile and the PCM melting range, since the average ambient temperature and daily thermal swing govern the charging and discharging behavior of the material [17,20]. Accordingly, several studies have emphasized that the optimum PCM melting temperature should be selected in relation to the local outdoor conditions rather than using a universal value [17,20]. For instance, the optimum melting point was reported as 26 °C for Singapore [19], 26 °C for Lleida [21,23], and 29 °C for Putrajaya due to the higher average outdoor temperature in that tropical climate [22]. These findings confirm that PCM optimization is inherently climate dependent and that the suitability of a given PCM cannot be generalized across different regions [19,20,21,22,23].
In addition to climatic conditions, the thermal performance of PCM in building envelopes is influenced by several design parameters, including wall orientation, PCM layer position, and PCM thickness [24,25,26,27,28]. Wall orientation affects the amount and timing of solar heat gain, thereby altering the charging period of the PCM and its ability to interact effectively with external thermal loads [24]. For example, an experimental test room study in Iraq showed that the maximum PCM absorption occurred in the southern wall orientation [24]. PCM thickness also influences the amount of latent storage available; however, previous studies have shown that the thermal benefit does not increase linearly with thickness and may exhibit diminishing returns beyond certain values [25,26]. Ascione and Lei reported that the absorption rate decreased from approximately 3%/mm to 2%/mm when thickness increased from 3 mm to 20 mm [25,26]. The position of the PCM layer within the wall assembly is another important parameter, yet the literature remains inconclusive regarding the most effective placement. A numerical study in Baltimore concluded that placing PCM near the outermost wall layer was more effective than locating it near the innermost layer [27], whereas Ascione et al. reported for Madrid that the inner-layer position provided more than double the effect of the outermost placement [28]. These contrasting findings indicate that PCM performance results from the combined interaction of climate conditions and wall configuration, rather than from any single design variable considered in isolation [24,25,26,27,28].
Previous investigations have also assessed PCM effectiveness using different performance indicators, such as cooling-energy saving, heat absorbed by the PCM, reduction in indoor temperature, decrease in overheating time, and improvement in thermal comfort hours [20,25,29,30]. Zhou and Alam investigated the effect of PCM on indoor temperature under conditioned and unconditioned cases and reported a temperature reduction of about 0.44 °C for the conditioned case and around 2 °C for the unconditioned case [20,29]. Ascione and Bianco examined the effect of PCM on overheating time under different climate conditions and found a reduction of approximately 11–15% [25]. In another study conducted in Portland, moving PCM to the interior wall surface increased thermal comfort hours by about 46 h, whereas removing PCM entirely increased overheated hours by about 220 h [30]. This diversity in evaluation criteria highlights the complexity of PCM assessment, since the preferred configuration may vary depending on the selected performance measure [20,25,29,30]. Nevertheless, the literature consistently indicates that the optimum PCM characteristics are strongly linked to climate type [31,32,33,34,35,36,37,38,39].
Research on PCM-integrated building envelopes has also received increasing attention under Egyptian climatic conditions. Kamel et al. [40] investigated the incorporation of different PCM types into a conventional wall in Cairo using a finite-volume numerical model, demonstrating the influence of melting temperature and installation position on cooling-related heat transfer. Bolteya et al. [41] employed DesignBuilder to evaluate PCM integration in an educational building in Cairo, examining the effects of PCM thickness on cooling-energy consumption and associated environmental performance. Hassan et al. [42] investigated the optimization of PCM integration into opaque building envelopes in Egypt using a multi-objective approach aimed at improving building energy performance. More recently, Azimi et al. [43] evaluated several PCM melting temperatures, including 21–29 °C, in a building located in Ismailia, Egypt, considering thermal performance, PCM distribution, and economic feasibility. Collectively, these investigations demonstrate the applicability of PCM-based envelope modifications under Egyptian climatic conditions while highlighting the importance of material selection, installation strategy, and the adopted performance criterion.
Further investigations have examined PCM-integrated building envelopes under the climatic conditions of Upper Egypt and North Africa. Anter et al. [44] investigated the thermal performance of building walls incorporating different PCM types, thicknesses, and installation positions under the hot summer conditions of Aswan, Egypt, demonstrating the importance of PCM configuration in regulating wall heat transfer. Similarly, Guermat et al. [45] examined the integration of a bio-based PCM at different positions within building walls under the summer climatic conditions of several Algerian cities, emphasizing the influence of material placement and local environmental conditions on thermal performance. In a related experimental and numerical investigation conducted in Morocco, Ait Laasri et al. [46] examined PCM-integrated building envelopes under semi-arid climatic conditions, highlighting the effects of hysteresis and subcooling on predicted thermal behavior and the importance of accurately characterizing phase-change processes. Collectively, these investigations demonstrate that PCM effectiveness depends on the interaction between climatic exposure, material characteristics, and installation configuration. They also highlight the importance of distinguishing the observed thermal response of PCM-integrated walls from the underlying phase-change mechanisms, which require additional transient characterization for direct verification.
Reported optimum melting temperatures differ among various climate categories. For example, the optimum melting point was reported as 25 °C for Seoul under a hot-summer continental climate [31,33,34], while for Beijing it was around 27 °C [32,33,34]. In warm-summer continental climates, previous optimization studies reported an optimum melting point of approximately 23 °C [35,36]. For tropical rainforest climates, optimization studies for Putrajaya and Singapore indicated an optimum melting point of around 29 °C [22,26,35]. In warm-summer Mediterranean climates such as Ankara and Coimbra, the optimum melting points were reported as 24 °C and 29 °C, respectively, while the optimum thickness for both cases was nearly 4 cm [25,38,47]. In humid subtropical climates, Ascione et al. reported an optimum melting point of 23 °C and thickness of 2 cm for Termoli [39], whereas Gaspar et al. found an optimum melting point of 24 °C and thickness of 4 cm for Milan [37,38]. These differences further demonstrate that PCM selection must be treated as a climate-responsive design problem, in which both material properties and wall arrangement should be matched carefully with the local thermal environment [31,32,33,34,35,36,37,38,39].
Although previous investigations have demonstrated the potential of PCM integration under Egyptian and North African climatic conditions, direct comparison of reported findings remains challenging because of differences in building constructions, material specifications, operating conditions, and thermal-performance indicators. Existing studies have investigated PCM melting temperature, thickness, installation position, and building-energy performance; however, further assessment is warranted to establish a consistent basis for evaluating their combined influence on seasonal wall heat-transfer behavior under the same climatic and operating assumptions. In particular, distinguishing warm-season inward heat-gain attenuation from signed cool-season wall energy transfer is important for identifying orientation-dependent performance trade-offs that may be overlooked when configurations are evaluated primarily through cooling-season reductions. Furthermore, relating these seasonal thermal indicators to material expenditure provides an additional basis for distinguishing maximum thermal performance from material-level cost-effectiveness. Accordingly, the present investigation addresses these considerations through a systematic comparative assessment of BioPCM configurations under the investigated Cairo conditions.

Parametric Assessment Approach and Novelty of the Study

Previous investigations have established the potential of phase change materials to improve building envelope thermal performance and have demonstrated the influence of material properties, installation position, and climatic conditions on their effectiveness. Nevertheless, the assessment of PCM-integrated walls remains challenging because the relative performance of different configurations depends not only on the magnitude of heat-transfer attenuation but also on its seasonal variation, direction, and associated material requirements. While existing studies have addressed PCM-based building energy performance and configuration-dependent thermal behavior [15,27], further investigation is warranted to establish a consistent basis for comparing the combined effects of PCM design parameters under the climatic and operating conditions of hot desert regions. In this context, the present study conducts a comprehensive numerical assessment of 240 BioPCM-integrated wall configurations, systematically examining five phase-change temperature grades, four-layer thicknesses, three installation positions, and four wall orientations under identical climatic and operating assumptions. Beyond evaluating individual parameter effects, the investigation adopts a seasonally differentiated approach that distinguishes accumulated warm-season inward heat gain from signed cool-season wall energy transfer and combines these contributions into a comparative thermal-performance indicator. This framework enables the identification of orientation-dependent performance trade-offs that may be overlooked when PCM configurations are assessed solely on the basis of summer heat-gain reduction. Furthermore, the thermal analysis is complemented by a material-level cost-performance assessment, allowing the configuration delivering the greatest thermal improvement to be distinguished from that providing the highest thermal benefit relative to material expenditure. The principal contribution therefore lies in establishing an integrated, climate-responsive assessment framework that relates PCM configuration, seasonal wall thermal behavior, and material cost, providing a more comprehensive basis for selecting PCM-integrated wall arrangements under the investigated Cairo conditions.

2. Materials and Methods

The present study adopts a structured numerical methodology to evaluate the thermal performance of BioPCM integrated into a typical Egyptian wall under Cairo climatic conditions and to identify the most suitable PCM configuration for Tropical/Subtropical Desert climates. The methodology consists of a sequence of interconnected stages, beginning with the definition of the building-energy simulation model and the specification of Cairo climatic boundary conditions, followed by the characterization of the reference building envelope and the validation of the simulation model against a published benchmark. Subsequently, the thermophysical properties of the selected BioPCM materials are implemented, and a parametric evaluation is carried out to investigate the influence of wall orientation, PCM position, melting range, and layer thickness on thermal performance. Ultimately, the candidate configurations are assessed from both thermal and economic perspectives in order to determine the preferred PCM arrangement. The overall methodological framework adopted in this study is illustrated in Figure 1.
Figure 1. Methodological framework for climate responsive PCM assessment.

3. Model Description

The numerical model is developed as a dynamic building-energy simulation using DesignBuilder v7.02 with EnergyPlus v9.4 as the underlying simulation engine. As illustrated in Figure 2, the investigated wall forms part of a complete building model in which the conditioned space interacts thermally with both the outdoor environment and the surrounding indoor spaces. The building geometry, wall orientations, adjacent spaces, and climatic exposure are therefore represented within the simulation environment. However, since the objective of the present study is to evaluate the influence of PCM integration on the building envelope, the analysis and reported results are specifically focused on the thermal energy exchanged through the selected external wall. The PCM layer is introduced at different locations within this wall assembly, while its melting range, thickness, and wall orientation are varied systematically to quantify their effects on the external-wall thermal response.
Figure 2. Simulation boundary conditions and investigated PCM-integrated wall configurations.
Heat exchange through surfaces shared with adjacent rooms is retained as part of the overall building simulation and contributes to the thermal balance of the conditioned zone. Nevertheless, these internal exchanges are not treated as the primary performance indicators of the present study, since the comparative assessment is based specifically on the thermal response of the PCM-integrated external wall. The external wall investigated in the present study is constructed from materials commonly used in Egyptian building practice, namely cement plaster and conventional brick. Since heat transfer through the building envelope constitutes a significant contributor to cooling demand in buildings [48,49], this wall assembly is adopted as the reference external-wall configuration for the parametric assessment. The analysis is designed to isolate and quantify the influence of PCM integration on the thermal response of this wall while maintaining the remaining building-model conditions unchanged.

3.1. Numerical Simulation Engine

The present numerical model is implemented using DesignBuilder software, with EnergyPlus adopted as the underlying simulation engine. EnergyPlus is an integrated building-energy simulation tool capable of modeling transient heat-transfer behavior under dynamic climatic conditions. In this study, EnergyPlus is employed to simulate the dynamic thermal response of the building and to quantify the thermal energy exchanged through the investigated external wall under Cairo climatic conditions. The simulation incorporates the selected climatic weather file together with the building geometry, external-wall construction, PCM thermophysical properties, surrounding-space conditions, and indoor temperature setpoint. The numerical calculations are performed iteratively until the prescribed convergence criteria are achieved. The general workflow of the numerical modeling procedure, including the main inputs, simulation engine, output variables, and performance-evaluation stage, is presented in Figure 3.
Figure 3. Numerical modeling and evaluation workflow for BioPCM assessment using DesignBuilder.

3.2. Indoor and Outdoor Boundary Conditions

The indoor boundary conditions were defined to represent a cooling-controlled environment, with a cooling temperature setpoint of 24 °C and a nominal relative humidity of 50%. The selected cooling setpoint was based on its suitability as a representative operating temperature for air-conditioned occupied buildings and its consistency with indoor thermal conditions that may satisfy the comfort criteria established by ANSI/ASHRAE Standard 55-2023 [50], depending on clothing insulation, metabolic activity, mean radiant temperature, and air velocity. The adopted temperature was therefore considered a reasonable reference condition for the present investigation rather than a universally prescribed thermal comfort requirement.
The adoption of a cooling-only operating strategy was motivated by the climatic characteristics and energy-conservation considerations associated with Egyptian buildings. Cairo experiences prolonged warm conditions and comparatively mild winters, resulting in a building-energy demand profile predominantly influenced by cooling requirements. Previous investigations have also indicated that space heating is less commonly employed in Egyptian buildings than mechanical cooling, while national electricity-conservation initiatives emphasize reducing unnecessary energy consumption. Accordingly, space heating was disabled throughout the simulations to represent an energy-conscious operating scenario relevant to cooling-dominated buildings in Egypt. Under these conditions, indoor air temperatures were allowed to vary when cooling was not required, rather than being maintained at a constant temperature throughout the year. The same operating assumptions were applied to all reference and PCM-integrated configurations to ensure consistent comparison of their thermal performance.
The investigated external wall is subjected to time-dependent outdoor climatic conditions governed by the local climate. These dynamic conditions include variations in outdoor dry-bulb temperature and incident solar radiation throughout the day and over the year. The outdoor temperature follows a transient profile, as illustrated in Figure 4, while the incident solar radiation varies with both time and wall orientation. The variation in solar exposure for different wall orientations is presented in Figure 5, highlighting its influence on the external thermal load applied to the wall.
Figure 4. Outside dry-bulb temperature.
Figure 5. Incident solar radiation for different wall orientations.
In addition to ambient temperature and solar radiation, heat transfer through the investigated wall is governed by the coupled conductive, convective, and radiative processes occurring at its boundaries. At the indoor surface, convective heat exchange takes place between the wall and the conditioned indoor air, with the corresponding heat-transfer rate depending on the surface-to-air temperature difference and the applicable convective heat-transfer coefficient. The prescribed cooling setpoint of 24 °C provides a consistent thermal operating condition, while the surface heat-transfer processes are evaluated according to the numerical formulations implemented in EnergyPlus. At the outdoor surface, the wall exchanges heat with the surrounding air through convection and with the external environment through longwave radiation, while simultaneously absorbing incident shortwave solar radiation. The absorbed solar energy depends on the incident radiation intensity, wall orientation, and optical properties of the exposed exterior surface. These coupled surface heat-balance processes govern the transient conduction of thermal energy through the wall assembly, which is subsequently evaluated using the wall heat-transfer indicators.
The transient outdoor climatic boundary conditions were defined using the Egyptian Typical Meteorological Year (ETMY) dataset available within DesignBuilder, corresponding to the weather file “EGY_AL QAHIRAH_CAIRO INTL AIRPORT_ETMY”. The dataset represents Cairo International Airport (WMO station 623660), located at approximately 30.13° N latitude and 31.40° E longitude, at an elevation of 74 m above sea level. The meteorological data are provided in EnergyPlus Weather (EPW) format and comprise hourly climatic variables, including dry-bulb temperature, relative humidity, solar radiation, wind speed, and wind direction. These inputs enable the transient thermal response of the building envelope to be evaluated under representative diurnal and seasonal variations. The use of a typical meteorological year provides a consistent climatic basis for the parametric assessment, avoiding the influence of differences between individual weather years. All reference and PCM-integrated wall configurations were evaluated using the same weather dataset to ensure comparability. Nevertheless, the adopted dataset represents a typical climatic year rather than an extreme weather event or a future climate scenario; therefore, the findings should be interpreted within the climatic conditions represented by the selected dataset.

3.3. Wall Heat-Transfer Assessment and Performance Indicators

The thermal performance of the investigated PCM-integrated walls was evaluated based on the transient conductive heat transfer through the selected external wall, having a surface area of 16 m2. The assessment focused on wall-level thermal-energy exchange rather than the total heating or cooling demand of the building. For each investigated configuration, the simulated wall heat-transfer results were integrated over specified time intervals to quantify daily, seasonal, and annual thermal responses. All PCM-integrated configurations were evaluated against their corresponding conventional reference walls under identical geometric, climatic, and indoor operating conditions.
A consistent heat-flow sign convention was adopted throughout the analysis. Heat transfer directed toward the conditioned indoor environment was considered positive, whereas heat transfer directed outward was considered negative. Accordingly, positive accumulated wall energy values represent net inward heat transfer, while negative values indicate net outward transfer. This distinction is particularly important under Cairo’s climatic conditions, where the prevailing direction of wall heat transfer can change between seasons and may also reverse during individual daily cycles.
The instantaneous conductive heat-transfer rate through the investigated wall was determined from the corresponding wall heat flux and surface area using Equation (1).
Q ˙ i = A q i
where Q ˙ i is the instantaneous conductive heat-transfer rate (W), qi is the signed conductive wall heat flux (W/m2), and A is the investigated wall area (m2). The heat-flux sign was interpreted consistently with the adopted inward-positive convention for all reference and PCM-integrated configurations.
The accumulated signed thermal energy transferred through the wall over a specified assessment period was calculated by integrating the instantaneous heat-transfer rate with respect to time. For discrete simulation intervals, the accumulated net energy is expressed as in Equation (2).
E net = 1 1000 ∑ i = 1 N Q ˙ i ∆ t i
where Enet is the accumulated signed wall energy transfer (kWh), ∆ti is the simulation time interval (h), and N is the number of intervals within the investigated period. This procedure was applied consistently when determining daily, seasonal, and annual wall energy transfer.
Since the algebraic summation of heat transfer in opposing directions may conceal the actual magnitudes of inward and outward energy exchange, these contributions were also distinguished separately. The accumulated inward conductive heat gain was defined as in Equation (3).
E in = 1 1000 ∑ i = 1 N max Q ˙ i ,   0 ∆ t i
Similarly, the accumulated outward conductive heat loss was determined as in Equation (4).
E out = 1 1000 ∑ i = 1 N max − Q ˙ i ,   0 ∆ t i
Both quantities are expressed as positive energy magnitudes in kWh. Consequently, the signed net wall energy transfer can be expressed as in Equation (5).
E net = E in − E out
This distinction ensures that a reduction in net wall energy transfer is not automatically interpreted as an equivalent reduction in inward heat gain or outward heat loss.
To investigate the influence of seasonal climatic conditions, the representative meteorological year was divided into two assessment periods: a warm season extending from 1 April to 31 October and a cool season extending from 1 November to 31 March. These periods were adopted to reflect the prolonged warm conditions characteristic of Cairo while accounting for changes in thermal excitation and prevailing wall heat-transfer direction during cooler months. The seasonal classification does not imply that heat transfer remains exclusively inward or outward throughout either period. For the warm-season assessment, the relative reduction in accumulated inward heat gain associated with PCM integration was calculated as in Equation (6).
R S = E in , S , ref − E in , S , PCM E in , S , ref × 100 %
where RS is the warm-season inward heat-gain reduction (%), while the subscripts S, ref, and PCM denote the warm season, conventional reference wall, and PCM-integrated wall, respectively. For the cool-season assessment, the relative reduction in accumulated outward conductive heat loss, when applicable, was determined as in Equation (7).
R C = E out , C , ref − E out , C , PCM E out , C , ref × 100 %
where RC is the cool-season outward heat-loss reduction (%). Positive values indicate reduced outward heat loss, whereas negative values indicate increased outward heat loss relative to the reference wall. This percentage indicator is applicable when the reference configuration exhibits a non-zero accumulated outward heat-loss magnitude.
In addition to these individual performance indicators, a combined seasonal thermal benefit was introduced to evaluate the balance between warm-season heat-gain attenuation and changes in cool-season thermal transfer. The combined benefit was calculated as in Equation (8).
B = ( E S , ref − E S , PCM ) ⏟ Warm − season   contribution + ( E C , PCM − E C , ref ) ⏟ Cool − season   contribution
where B is the combined seasonal thermal benefit (kWh), ES is the accumulated warm-season wall energy indicator, and EC is the accumulated signed cool-season wall energy transfer. The warm-season term represents the reduction in inward thermal transfer relative to the reference wall, whereas the cool-season term accounts for the effect of PCM integration on the corresponding signed energy exchange. This formulation retains the direction of heat transfer in the cool-season calculation, allowing the indicator to accommodate orientations exhibiting either net inward or net outward thermal transfer. It should be noted that the combined seasonal thermal benefit is intended as a comparative wall-level performance indicator under the adopted cooling-only operating conditions. Since space heating was not considered, the cool-season contribution reflects changes in conductive heat transfer through the wall rather than actual heating-energy consumption.
Under the adopted convention, a positive combined seasonal benefit indicates that the favorable contributions of PCM integration exceed the corresponding adverse seasonal effects, while a negative value indicates an unfavorable combined response. For configurations in which PCM integration increases outward heat transfer during the cool season, the resulting negative contribution offsets part of the warm-season benefit. Conversely, a reduction in outward heat transfer contributes positively to the combined indicator. The formulation therefore provides a consistent basis for comparing PCM configurations across wall orientations without assuming that every cool-season result represents outward heat loss.
The heat-transfer directions and calculation procedure adopted for the seasonal assessment are summarized schematically in Figure 6. The same methodology was applied to all investigated PCM grades, thicknesses, installation positions, and wall orientations. For each orientation, the corresponding conventional reference wall was used to establish the baseline conditions, ensuring that differences in solar exposure and wall thermal response were considered consistently.
Figure 6. Wall heat-transfer assessment methodology: (a) heat-flow sign convention, (b) seasonal energy indicators, and (c) combined seasonal thermal benefit.
It is important to distinguish the combined seasonal thermal benefit from the annual reduction in gross wall energy exchange. The former is derived from the selected warm- and cool-season indicators, whereas annual gross exchange is obtained by accumulating the absolute magnitudes of inward and outward conductive heat transfer over the complete year. These measures describe different aspects of wall thermal performance and should not be used interchangeably. Furthermore, the reported wall energy reductions cannot be directly equated with reductions in whole-building HVAC energy consumption, since the latter also depends on system efficiency, operating schedules, internal loads, and interactions with other building components.
The adopted methodology therefore provides a consistent basis for interpreting the seasonal behavior of the investigated PCM-integrated wall configurations. By evaluating inward heat gain, signed cool-season transfer, and their combined effect, the assessment enables both the thermal benefits and potential seasonal penalties associated with PCM integration to be identified. The resulting indicators are used in the parametric comparisons presented in Section 6.3 and Section 6.4, while the detailed transient surface-temperature analysis provides complementary information on the thermal response of selected configurations.

3.4. Parametric Assessment and Configuration Selection

The preferred PCM configuration was identified through a comprehensive parametric assessment considering four principal design variables: wall orientation, PCM layer position, melting temperature, and layer thickness. Four wall orientations (North, East, South, and West), three PCM positions (innermost, middle, and outermost), five nominal melting temperatures (Q21, Q23, Q25, Q27, and Q29), and four commercially available thicknesses (M27, M51, M91, and M182) were investigated. The full combination of these parameters resulted in 240 simulated PCM configurations, comprising 60 cases for each wall orientation. The overall assessment and selection procedure are illustrated in Figure 7.
Figure 7. Parametric assessment and selection procedure for the 240 investigated PCM-integrated wall configurations.
All configurations were evaluated under identical indoor operating assumptions and using the same Cairo meteorological dataset. For each orientation, the PCM-integrated configurations were compared against the corresponding conventional reference wall to assess the influence of the investigated parameters on thermal performance. Unlike a sequential screening approach, the complete set of parameter combinations was evaluated, allowing the relative performance of different PCM arrangements to be compared without excluding potentially favorable combinations at an intermediate selection stage.
The assessment was based on the wall heat-transfer indicators described in Section 3.3, with particular emphasis on the influence of melting temperature, thickness, layer position, and orientation on the seasonal thermal response. The results were subsequently compared to identify the configurations offering the greatest thermal benefit, while material-level cost-performance characteristics were considered separately to distinguish the thermally preferred arrangement from the economically favorable alternative.
Although the complete parameter combinations were investigated, the procedure represents a comparative parametric assessment rather than a formal statistical optimization. Accordingly, differences in performance were interpreted through direct comparisons between simulated configurations, without calculating statistical interaction coefficients or developing a predictive response-surface model. The identified configurations therefore represent the most favorable alternatives within the investigated design space and adopted boundary conditions.

4. Material Selection

The PCM adopted in this study is an organic phase change material with suitable additives, commercially known as BioPCM. The selection of this material is based on its applicability to building envelope systems and its favorable implementation characteristics within the studied temperature range. Unlike conventional paraffin-based PCM, BioPCM undergoes a phase transition from a solid state to a gel-like state, which helps mitigate leakage concerns during operation and facilitates its integration into building components [51]. In addition, its compatibility with plastic-based applications supports its practical use in wall assemblies [51]. Although paraffin-based PCM has been extensively investigated in building thermal-energy-storage applications, issues related to leakage control, implementation safety, and material compatibility remain relevant in material selection [52,53]. Nevertheless, paraffin materials are generally less expensive than BioPCM, and this economic aspect is considered in the present study [54]. In the numerical model, BioPCM was characterized using a density of 235 kg/m3, thermal conductivity of 0.2 W/m·K, and specific heat capacity of 1970 J/kg.K [51]. Its phase-change behavior was further defined through the enthalpy–temperature (h–T) relationship presented in Figure 8.
Figure 8. Enthalpy–temperature (h–T) curve of BioPCM.
BioPCM materials are characterized by a narrow phase-change temperature range of approximately 2 °C, and they are commercially coded based on their average melting temperature. For example, the designation Q21 corresponds to a phase-change interval ranging from 20 °C to 22 °C, as illustrated in Figure 8. In addition to the melting range classification, BioPCM products are also categorized according to their nominal thickness, which directly influences their thermal storage capacity. In the present study, four commercially available thicknesses are considered: 1.12 cm, 2.08 cm, 3.71 cm, and 7.42 cm, corresponding to the codes M27, M51, M91, and M182, respectively. These standardized classifications enable a systematic parametric evaluation of PCM performance under different thermal and geometric configurations.
The thermophysical properties adopted in the present numerical model were based on the nominal characteristics of the selected commercial BioPCM series available within the DesignBuilder database. The specified density, thermal conductivity, and specific heat capacity are consistent with values previously employed in numerical investigations of BioPCM-integrated building envelopes, including the study by Markarian and Fazelpour [55], which considered the same material grades and nominal thicknesses. This agreement with established numerical applications provides a literature-supported basis for the adopted material parameters, although it does not constitute independent experimental verification of their exact values. Furthermore, the use of a consistent thermophysical property set and numerical modeling procedure across all 240 configurations ensures that the comparative assessment is conducted on a common material basis. This consistency is particularly important when examining the relative influence of melting temperature, layer thickness, and placement within the wall assembly.
Nevertheless, the predicted thermal response remains subject to uncertainties associated with the nominal material properties. Variations in thermal conductivity directly affect the conductive resistance of the PCM layer, while deviations in density and specific heat capacity influence its sensible thermal storage capacity. Similarly, uncertainties in the enthalpy–temperature relationship may alter the temperature interval over which latent heat is absorbed or released, particularly when the local PCM temperature approaches its phase-transition range. These effects may influence the magnitude of the predicted thermal-energy reduction and the relative performance of configurations exhibiting small differences. Although the consistent application of nominal material properties supports the internal comparability of the simulated cases, it does not eliminate uncertainty in their absolute thermal performance. Since independent experimental characterization and formal material-property sensitivity analyses were not conducted, the reported results are interpreted as numerical predictions for the specified BioPCM properties and operating conditions. Accordingly, the identified preferred configurations represent the most favorable alternatives within the investigated parameter space, while their performance under variations in actual material properties warrants further experimental assessment.

5. Benchmark-Based Numerical Model Assessment

To assess the reliability of the numerical approach adopted in the present investigation, a benchmark comparison was performed against the published numerical study of Kishore et al. [27], which investigated the thermal performance of conventional and PCM-integrated building walls under different climatic conditions. The comparison was intended to examine the consistency of the baseline wall heat-transfer predictions obtained using the DesignBuilder/EnergyPlus simulation framework before applying the model to the parametric investigation of PCM-integrated walls under Cairo climatic conditions.
The benchmark case was based on the reference wall considered by Kishore et al. [27] for Baltimore, Maryland, USA. The wall assembly comprised expanded polystyrene, wood, oriented strand board, and gypsum, with the corresponding thermophysical properties summarized in Table 1. The reference configuration was represented within the DesignBuilder/EnergyPlus environment using the adopted benchmark material properties and climatic conditions. The comparison focused on the cumulative thermal energy transferred through the conventional wall during June and July, thereby providing an assessment of the model’s ability to reproduce the overall conductive thermal response under seasonally varying boundary conditions.
Table 1. Thermophysical properties of the wall materials adopted for the Baltimore benchmark case.
Figure 9 compares the monthly cumulative wall heat-transfer energy obtained from the present simulation with the corresponding published benchmark results. Both approaches exhibited a similar variation between the investigated months, with the cumulative thermal energy transferred through the wall being higher in July than in June.
Figure 9. Comparison of monthly cumulative wall heat-transfer energy obtained from the present DesignBuilder/EnergyPlus simulation and the published Baltimore numerical benchmark by Kishore et al. [27] for June and July.
For a quantitative assessment of the agreement, the relative percentage deviation between the present simulation and the published benchmark was defined as in Equation (9).
ε m = E present , m − E benchmark , m E benchmark , m × 100 %
where εm is the relative percentage deviation for month m, while Epresent,m and Ebenchmark,m represent the corresponding monthly cumulative wall heat-transfer energies (kWh) obtained from the present DesignBuilder simulation and the published benchmark, respectively.
The comparison presented in Figure 9 indicates reasonable agreement between the present DesignBuilder/EnergyPlus simulation and the published numerical benchmark of Kishore et al. [27]. The relative deviations were approximately 7.7% in June and 1.2% in July, corresponding to a mean absolute percentage deviation of approximately 4.5% across the two investigated months. These results support the consistency of the baseline wall heat-transfer predictions. Nevertheless, the comparison is limited to cumulative monthly thermal-energy transfer and does not independently validate the transient melting and solidification behavior of the PCM.
The subsequent parametric investigation therefore employs the established DesignBuilder/EnergyPlus simulation framework together with the specified BioPCM enthalpy–temperature relationships and consistent numerical assumptions across all investigated configurations. The resulting performance predictions are interpreted within the limitations of the adopted material properties, climatic conditions, and numerical representation of phase-change behavior. Further comparison with experimentally measured transient PCM temperatures, heat-flux histories, and phase-change progression would provide additional validation of the PCM thermal-storage response.

6. Results and Discussion

6.1. Influence of PCM Melting Temperature and Layer Position on Wall Heat Transfer Integration

The combined influence of PCM melting temperature and its position within the wall assembly on the daily net thermal energy transferred through the investigated external wall is presented in Figure 10. The comparison includes the conventional reference wall and five BioPCM grades (Q21, Q23, Q25, Q27, and Q29), each incorporated at the innermost, middle, and outermost positions using a constant thickness of M182 (7.42 cm). This comparative assessment enables the influence of PCM placement to be evaluated across different melting ranges under identical geometric and operating conditions. Positive daily net-energy values indicate predominant heat transfer toward the indoor environment, whereas negative values represent a net outward transfer of thermal energy.
Figure 10. Daily net heat transferred through the reference and PCM-integrated walls at different layer positions (inner, middle, and outer) for M182 thickness (7.42 cm): (a) Q21, (b) Q23, (c) Q25, (d) Q27, and (e) Q29. Positive and negative values indicate net inward and outward heat transfer, respectively.
As illustrated in Figure 10a–e, PCM integration substantially modifies the daily thermal response of the wall throughout the investigated year, with the most pronounced differences occurring during the cooling-dominated period. The conventional wall exhibits considerable fluctuations in daily net heat transfer, with positive values reaching approximately 8 kWh during periods of elevated thermal loading. In comparison, the PCM-integrated configurations generally exhibit lower positive daily net-energy values, indicating attenuation of inward thermal-energy transfer through the wall. The extent of this attenuation depends primarily on the position of the PCM layer, while differences associated with the investigated melting temperatures are comparatively smaller.
Across all five PCM grades, the outermost arrangement consistently exhibits the lowest positive daily net-energy values during the warmer months, followed generally by the middle and innermost configurations. The superior performance of the outermost arrangement is associated with its proximity to the external thermal excitation, where variations in ambient temperature and absorbed solar radiation produce substantial transient temperature gradients across the wall. Positioning the PCM near the exterior boundary modifies the thermal response before the imposed temperature fluctuations propagate through the remaining wall layers. During periods when the PCM temperature passes through its phase-transition range, part of the transferred energy can be temporarily stored through latent heat absorption, in addition to sensible energy storage within the wall assembly. The subsequent release of stored energy alters the timing and magnitude of the heat transferred toward the indoor environment, thereby contributing to the attenuation of daily net thermal-energy transfer.
The influence of layer position is particularly evident when comparing the three PCM arrangements within each subplot. Although the material properties and thickness remain unchanged, the thermal response differs because the PCM experiences different temperature histories depending on its location within the wall. For a given PCM grade, relocating the material changes its interaction with the transient thermal boundary conditions without modifying its nominal conductive thermal resistance. This observation highlights the importance of PCM positioning in determining the effectiveness of the temperature-dependent thermal-storage mechanism. The relatively close responses of the innermost and middle configurations, compared with the more pronounced attenuation achieved by the outermost arrangement, further indicate that the thermal benefit is not governed solely by the presence or quantity of PCM, but also by its location within the wall construction.
The comparison between PCM grades reveals generally similar seasonal trends across Q21, Q23, Q25, Q27, and Q29. This similarity is expected because the investigated grades were assigned identical nominal thermal conductivity, density, sensible specific heat capacity, and thickness, while their enthalpy–temperature relationships differ according to their phase-transition ranges. Consequently, variations in the predicted transient responses between grades at equivalent positions are associated with differences in their temperature-dependent thermal-storage characteristics. The relatively limited differences between the curves indicate that PCM placement exerts a more pronounced influence on the investigated daily net-energy response than changes in nominal melting temperature within the considered range. Nevertheless, these differences remain relevant to the selection of the preferred PCM grade, which is assessed further using the cumulative thermal-energy indicators presented in Section 6.3.
During the cooler months, the thermal response changes as the prevailing temperature gradient across the wall reverses, resulting in negative daily net-energy values. Under these conditions, a reduction in the magnitude of negative energy values indicates lower net outward heat transfer, whereas more negative values indicate greater outward transfer. Figure 10 shows that the relative advantage of the outermost arrangement becomes less pronounced during this period, with its net outward energy transfer frequently exceeding that of the middle and innermost PCM placements. This behavior can be related to the position-dependent redistribution of thermal energy within the wall and the changing interaction between the PCM layer and the external environment. Accordingly, the configuration providing the greatest attenuation of inward heat transfer during summer does not necessarily provide the most favorable thermal response during winter.
Overall, Figure 10 demonstrates that PCM-integrated wall performance is governed by the combined effects of melting temperature, layer position, and seasonal thermal excitation. The outermost arrangement provides the strongest attenuation of positive daily net-energy transfer during the cooling-dominated period across the five investigated PCM grades, while the relative performance of the different placements’ changes under cooler conditions. These findings establish PCM location as a major design parameter and emphasize the importance of evaluating thermal performance over the complete seasonal cycle rather than relying exclusively on individual high-load days. Since the presented results represent signed daily net wall energy transfer, the observed reductions should be interpreted as changes in the thermal response of the investigated wall rather than as direct reductions in whole-building HVAC energy consumption.

6.2. Influence of PCM Integration on Wall Surface Temperatures

The influence of PCM integration on the thermal response of the external and internal wall surfaces is examined in Figure 11 for five BioPCM grades (Q21, Q23, Q25, Q27, and Q29), considering innermost, middle, and outermost layer positions at a constant thickness of M182 (7.42 cm). The comparison provides a comprehensive assessment of surface-temperature variations throughout the representative meteorological year and allows the relative influence of melting temperature and PCM placement to be investigated under identical operating conditions. While the preceding section examined the resulting daily net energy transferred through the wall, the present analysis focuses on the temperature response of both wall boundaries and the attenuation of temperature fluctuations associated with PCM integration.
Figure 11. Daily variation in external (a,c,e,g,i) and internal (b,d,f,h,j) wall surface temperatures for the reference and PCM-integrated configurations at inner, middle, and outer placement positions, considering M182 thickness (7.42 cm): Q21 (a,b), Q23 (c,d), Q25 (e,f), Q27 (g,h), and Q29 (i,j).
The East-facing wall was selected as a representative configuration for illustrating the influence of PCM integration on wall surface temperatures, owing to its distinct diurnal solar exposure and associated transient thermal response. Considering a single orientation provides a consistent basis for examining the effects of PCM melting temperature and layer position without introducing additional variations associated with orientation-dependent solar radiation. This approach allows the thermal influence of PCM integration to be demonstrated through direct comparisons with the conventional reference wall, while the comprehensive assessment of all four orientations is presented separately in Section 6.4.
As illustrated in Figure 11a,c,e,g,i, the external surface temperatures exhibit pronounced seasonal variations, with the highest values occurring during the warmer months. The conventional reference wall experiences considerable temperature fluctuations in response to changes in the external thermal environment. Incorporating PCM at the outermost position produces the most noticeable modification of the external surface-temperature profile, particularly during periods of elevated thermal loading. In comparison, the middle and innermost configurations generally exhibit temperatures closer to those of the reference wall. This behavior demonstrates that the position of the PCM layer influences the temperature distribution within the wall assembly, even when the material properties and layer thickness remain unchanged.
The pronounced temperature reduction associated with outermost placement can be explained through the interaction between transient heat conduction and temperature-dependent energy storage. Solar radiation absorbed at the exposed exterior surface, together with variations in outdoor air temperature, establishes a time-dependent thermal excitation that propagates through the wall. When the PCM is positioned near this boundary, the resulting temperature variations interact more directly with its thermal-storage characteristics. As the local PCM temperature approaches the phase-transition interval, the effective heat-storage capacity increases, allowing part of the transferred energy to be temporarily absorbed and subsequently released as the temperature changes. This process, combined with the additional conductive resistance and sensible thermal storage of the PCM layer, modifies the transient temperature distribution and moderates the external surface response.
The corresponding internal surface-temperature variations are presented in Figure 11b,d,f,h,j. Compared with the external surfaces, the internal surfaces exhibit considerably smaller temperature fluctuations, reflecting the attenuation of external thermal excitation as heat propagates through the multilayer wall construction. Nevertheless, differences between the reference and PCM-integrated configurations remain evident, particularly during the warmer months. The outermost arrangement generally exhibits lower internal surface-temperature peaks and a smoother seasonal profile, whereas the innermost and middle arrangements tend to remain closer to the reference-wall response. These findings indicate that placing the PCM near the exterior boundary can influence the temperature response at the indoor side of the wall, despite the intervening construction layers.
Comparison of the five PCM grades reveals broadly similar temperature profiles, particularly for configurations having the same layer position. This similarity is consistent with their identical nominal thermal conductivity, density, sensible specific heat capacity, and thickness. Differences between the grades arise from their respective enthalpy–temperature relationships, which determine the temperature intervals over which latent heat absorption and release occur. Within the investigated range, the influence of layer position on surface-temperature attenuation is generally more pronounced than the differences associated with nominal melting temperature. However, the relatively small variations in surface temperature between PCM grades should not be interpreted as evidence of identical thermal-energy performance, since accumulated wall energy transfer also depends on the temporal evolution and direction of heat flux.
During the cooler months, the temperature differences between the investigated configurations generally become less pronounced, particularly at the internal wall surface. The seasonal variation in the PCM response is associated with changes in outdoor thermal excitation and the prevailing direction of heat transfer. Under these conditions, lower surface temperatures do not necessarily indicate improved thermal performance, since the corresponding effect on heat loss depends on the temperature gradient and transient energy balance across the wall. Accordingly, the surface-temperature results should be interpreted alongside the daily net wall energy profiles presented in Section 6.1 rather than as independent indicators of heating or cooling demand.
Overall, Figure 11 demonstrates that PCM integration modifies the thermal response of both wall surfaces, with the greatest visible influence associated with outermost placement during the warmer months. The results further indicate that PCM location has a substantial effect on surface-temperature attenuation, whereas differences between the investigated melting grades are comparatively limited. These findings complement the preceding energy-transfer analysis by demonstrating how PCM placement and temperature-dependent storage characteristics influence the thermal response of the wall assembly under seasonal climatic variations.

6.3. Combined Effects of PCM Melting Temperature, Thickness, and Layer Position

The combined influence of PCM melting temperature, layer thickness, and installation position on the seasonal thermal response of the East-facing wall is presented in Figure 12. The assessment includes five BioPCM grades (Q21–Q29), four thicknesses (M27–M182), and three installation positions, resulting in 60 configurations. The comparison considers accumulated warm-season inward heat gain, signed cool-season wall energy transfer, and the combined seasonal thermal benefit.
Figure 12. Seasonal thermal performance of the East-facing wall: (a) warm-season inward heat gain, (b) signed cool-season wall energy transfer, and (c) combined seasonal thermal benefit for different PCM grades, thicknesses, and layer positions.
As illustrated in Figure 12a, increasing PCM thickness generally decreases warm-season inward heat gain, particularly when the PCM is installed at the outermost position. For Q21 M182, the accumulated heat gain decreased from 633.35 kWh for the reference wall to 100.47 kWh, corresponding to an 84.1% reduction. However, Figure 12b shows that this configuration increased the magnitude of cool-season outward heat transfer from 418.13 to 463.05 kWh. Accounting for both seasonal contributions, the combined thermal benefit reached 487.95 kWh, as shown in Figure 12c. The highest combined benefit for the East-facing wall was obtained with Q21 M182 at the outermost position, although its improvement over Q23 was marginal.
To quantify the contribution of conductive thermal resistance, the overall thermal transmittance of the reference and PCM-integrated walls was examined using the corresponding DesignBuilder results. The conventional reference wall exhibited a U-value of 2.000 W/m2·K, whereas incorporation of the M182 PCM layer (7.42 cm) reduced the U-value to 1.148 W/m2·K. This represents a 42.6% reduction in steady-state thermal transmittance, corresponding to an increase in total wall thermal resistance from 0.500 to approximately 0.871 m2·K/W. The resulting additional resistance of approximately 0.371 m2·K/W is consistent with the theoretical conductive resistance of the M182 layer, calculated using the adopted PCM thickness and thermal conductivity (0.371 m2·K/W). This agreement confirms that the additional thermal resistance introduced by the PCM layer contributes to the improved wall performance independently of the material’s latent heat-storage properties.
The influence of PCM melting temperature is also evident in Figure 12, although the differences between the investigated grades are generally smaller than those associated with thickness and placement. Q21 exhibited favorable thermal performance within the investigated temperature range, supporting its selection as a candidate material for the considered climatic conditions. However, the relatively small differences between several PCM grades indicate that the preferred melting temperature should be interpreted in relation to the selected performance indicator and the specific wall configuration. Since the investigated grades were modeled using the same nominal density, thermal conductivity, and specific heat capacity, differences between grades at equivalent thickness and placement are associated with their prescribed enthalpy–temperature characteristics and resulting transient thermal responses.
From a thermodynamic perspective, the thermal performance of a PCM-integrated wall is governed by the transient conservation of energy, in which the conductive heat flux is coupled to the rate of internal energy storage within the wall layers. Unlike conventional insulation, whose primary function is to increase thermal resistance, PCM can additionally modify the transient heat-transfer response through temperature-dependent enthalpy storage. When the local material temperature passes through its phase-transition interval, the effective heat-storage capacity increases, moderating temperature variations and altering the magnitude and timing of heat flux reaching the indoor surface. The stored energy may subsequently be released as the material cools; therefore, PCM performance depends on the relationship between its phase-transition range and the imposed thermal cycle rather than on latent heat capacity alone.
In the present investigation, all five BioPCM grades were modeled with identical thermal conductivity, density, sensible specific heat capacity, and geometric properties at equivalent thickness and placement. Consequently, their conductive thermal resistances and steady-state U-values are identical, while their enthalpy–temperature relationships differ according to the nominal phase-change temperature. Under identical boundary conditions, any differences in their predicted transient thermal responses therefore originate from these temperature-dependent enthalpy characteristics. This provides a thermodynamic basis for comparing the suitability of the investigated melting grades without separately quantifying the latent contribution to the total heat-transfer reduction. Furthermore, the configuration selection is based on the accumulated heat transferred through the complete wall assembly, which inherently accounts for the combined effects of conduction and thermal energy storage. Accordingly, separating these contributions would provide additional insight into the underlying mechanisms but would not change the ranking obtained from the existing simulations of the actual PCM configurations. The integrated thermodynamic assessment therefore provides a reliable basis for identifying the most favorable PCM configuration, as it inherently accounts for the combined influence of conductive resistance, sensible heat storage, and latent heat exchange under the investigated operating conditions. Further investigation of the individual contributions of these mechanisms would provide additional insight into the thermal behavior of PCM-integrated walls and support a more comprehensive understanding of their energy-saving potential.

6.4. Influence of Wall Orientation on Seasonal Thermal Performance

Wall orientation plays an important role in determining the effectiveness of PCM integration, primarily because it influences the intensity and temporal distribution of solar radiation incident on the external wall. To examine this effect, the parametric assessment was extended to the West-, North-, and South-facing walls, as presented in Figure 13, Figure 14 and Figure 15, respectively. Together with the East-facing results discussed in Section 6.3, these figures provide a comprehensive comparison of the investigated PCM configurations under different orientations.
Figure 13. Seasonal thermal performance of the West-facing wall: (a) warm-season inward heat gain, (b) signed cool-season wall energy transfer, and (c) combined seasonal thermal benefit for different PCM grades, thicknesses, and layer positions.
Figure 14. Seasonal thermal performance of the North-facing wall: (a) warm-season inward heat gain, (b) signed cool-season wall energy transfer, and (c) combined seasonal thermal benefit for different PCM grades, thicknesses, and layer positions.
Figure 15. Seasonal thermal performance of the South-facing wall: (a) warm-season inward heat gain, (b) signed cool-season wall energy transfer, and (c) combined seasonal thermal benefit for different PCM grades, thicknesses, and layer positions.
The results demonstrate considerable differences in the thermal response of the conventional reference walls. During the warm season, the West-facing wall exhibited the highest accumulated inward heat gain, followed by the East-facing, South-facing, and North-facing orientations. These variations reflect the different solar exposure conditions experienced by each wall throughout the investigated period. Although PCM integration generally reduced warm-season inward heat gain, the magnitude of the improvement and the corresponding cool-season response depended on both wall orientation and PCM configuration.
For the West-facing wall, Figure 13a demonstrates that outermost PCM placement substantially reduced warm-season heat gain across the investigated melting temperatures and thicknesses. The Q21 M182 configuration decreased accumulated inward heat gain from 764.74 kWh for the reference wall to 111.38 kWh, corresponding to an 85.4% reduction. However, Figure 13b shows that the same configuration increased cool-season outward heat transfer from 320.73 to 455.97 kWh. Consequently, part of the warm-season benefit was offset by the increased outward transfer during the cooler period. Despite this seasonal penalty, the combined thermal benefit remained substantial, reaching 518.12 kWh for Q21 M182. As illustrated in Figure 13c, Q21 M182 with outermost placement provided a substantial combined seasonal thermal benefit, with only marginal differences among the most closely performing melting grades, supporting its selection as the preferred representative configuration.
The North-facing wall exhibited a different seasonal response, as shown in Figure 14. Although its reference warm-season heat gain was considerably lower than that of the West- and East-facing walls, outermost PCM placement remained effective in attenuating inward heat transfer. For Q21 M182, accumulated warm-season heat gain decreased from 372.04 to 77.14 kWh. Unlike the corresponding West-facing configuration, the cool-season signed energy transfer became less negative, changing from −604.31 kWh for the reference wall to −480.01 kWh for the PCM-integrated wall. This represents a reduction in the magnitude of net outward heat transfer, providing an additional favorable contribution to the combined seasonal indicator. The resulting benefit reached 419.19 kWh for Q21 M182, while Q23 M182 achieved a slightly higher value of 419.48 kWh. These findings indicate that, for the North-facing orientation, sufficiently thick outermost PCM layers can improve both the warm-season and cool-season components of the adopted performance indicator.
A distinctly different response was observed for the South-facing wall, as presented in Figure 15. During the warm season, outermost PCM placement produced substantial reductions in inward heat gain, particularly at greater thicknesses. For Q21 M182, the accumulated inward heat gain decreased from 542.62 kWh for the conventional wall to 90.78 kWh. However, the corresponding cool-season response differed markedly from those of the other orientations. The conventional South-facing wall exhibited a small positive signed cool-season energy transfer of 8.08 kWh, whereas the Q21 M182 outermost configuration produced a negative value of approximately −420.24 kWh. This change indicates a reversal in the net direction of heat transfer, substantially offsetting the favorable warm-season contribution.
Consequently, the combined seasonal benefit of Q21 M182 with outermost placement was limited to 23.52 kWh. For several thinner outermost configurations, the adverse cool-season contribution exceeded the warm-season improvement, producing negative combined benefits. In contrast, inner-layer PCM placement provided substantially more favorable results under the adopted seasonal criterion. The highest combined benefit for the South-facing wall was obtained with Q25 M182 at the innermost position, reaching approximately 199.54 kWh. This result demonstrates that the preferred PCM installation position cannot be generalized across wall orientations and that outermost placement, although effective in reducing summer heat gain, does not necessarily provide the most favorable combined seasonal performance.
Table 2 summarizes the seasonal thermal performance of the selected PCM configurations across the four investigated orientations. The results confirm that the West-facing wall provides the greatest absolute combined seasonal thermal benefit under the adopted assessment criterion, followed by the East- and North-facing walls. For these orientations, Q21 M182 with outermost placement provides substantial attenuation of warm-season inward heat gain, although its cool-season response differs depending on orientation. In particular, the increased outward transfer observed for the West- and East-facing walls partially offsets their warm-season improvements, whereas the North-facing configuration exhibits a reduction in the magnitude of cool-season outward transfer. The South-facing wall demonstrates a different response, with Q25 M182 at the innermost position providing a greater combined seasonal benefit than the corresponding outermost configurations. These results confirm that the preferred PCM arrangement depends on wall orientation and the combined influence of seasonal heat-transfer conditions, rather than solely on the reduction in warm-season inward heat gain.
Table 2. Comparison of warm-season inward heat gain, signed cool-season wall energy transfer, and combined seasonal thermal benefit for the selected PCM configurations across the four wall orientations.
Overall, the results demonstrate that evaluating PCM performance solely on the basis of warm-season heat-gain reduction may overlook unfavorable changes during cooler periods. Outermost installation generally provided the greatest attenuation of summer inward heat gain, but its effect on the cool-season thermal response varied considerably among orientations. Under the investigated climatic conditions and adopted combined seasonal indicator, the West-facing wall offered the greatest absolute thermal benefit. Accordingly, this orientation was selected for the detailed hourly surface-temperature analysis presented in Section 6.5. The identified rankings apply to the investigated wall-level thermal indicators and should not be interpreted as direct reductions in whole-building HVAC energy consumption.

6.5. Detailed Seasonal Thermal Response of the West-Facing Wall

Following the comparative assessment of wall orientations in Section 6.4, the West-facing wall was selected for detailed investigation because it exhibited the greatest combined seasonal thermal benefit among the investigated orientations. The analysis considered the conventional reference wall and five BioPCM grades (Q21, Q23, Q25, Q27, and Q29), with the PCM positioned at the outermost layer and maintained at the maximum investigated thickness (M182, 7.42 cm). Hourly internal and external surface temperatures were obtained over a complete representative meteorological year, comprising 8760 observations for each surface and configuration. July, October, and January were selected to represent warm, transitional, and cool conditions, respectively. For each month, the temperature at a given hour was averaged across all days of that month to obtain a representative 24 h temperature profile. The resulting variations are presented in Figure 16, allowing the influence of PCM melting temperature on the transient surface response to be examined under identical geometric and climatic conditions.
Figure 16. Average hourly external (a–c) and internal (d–f) wall surface temperatures during July, October, and January for the reference wall and five BioPCM grades (Q21–Q29), considering West orientation, outermost PCM placement, and M182 thickness (7.42 cm).
During July, the conventional West-facing wall exhibited substantial diurnal fluctuations at its external surface, with the average hourly temperature increasing from approximately 25.0 °C during the early morning to 51.24 °C at 17:00 (Figure 16a). This pronounced afternoon increase reflects the elevated solar exposure experienced by the West-facing surface. In comparison, the PCM-integrated configurations exhibited considerably lower external surface-temperature peaks, ranging from 33.52 °C for Q29 to 35.12 °C for Q21. These values correspond to reductions of approximately 16.1–17.7 °C relative to the peak of the reference-wall average hourly profile. The higher-melting PCM grades generally exhibited smaller afternoon temperature peaks, although differences between individual grades remained considerably smaller than those between the PCM-integrated and conventional walls.
The corresponding internal surface-temperature profiles (Figure 16d) reveal a more pronounced attenuation of diurnal fluctuations following PCM integration. The reference wall exhibited a maximum-to-minimum variation of approximately 3.61 °C in its average hourly profile, compared with 0.22–0.62 °C for the different PCM configurations. Furthermore, the monthly mean internal surface temperature decreased from 26.98 °C for the conventional wall to approximately 24.02–24.05 °C for the PCM-integrated configurations. Despite the relatively small differences in mean internal temperature between PCM grades, their diurnal temperature amplitudes differed, with Q21 exhibiting a variation of approximately 0.62 °C compared with 0.22 °C for Q29. This indicates that the nominal melting temperature influences the temporal surface-temperature response, even when the resulting monthly mean temperatures are nearly identical.
During October, the overall temperature levels decreased, while the attenuation of diurnal fluctuations remained evident. As illustrated in Figure 16b, the external surface of the conventional wall reached a maximum average hourly temperature of 45.88 °C, compared with 29.36–30.22 °C for the PCM-integrated configurations. At the internal surface (Figure 16e), the temperature variation across the average hourly profile decreased from approximately 3.13 °C for the reference wall to 0.22–0.34 °C for the PCM configurations. The corresponding monthly mean internal surface temperatures ranged from 21.66 to 21.88 °C, compared with 23.95 °C for the conventional wall. These results demonstrate that the modified wall assemblies continued to moderate surface-temperature variations during the transitional period. Nevertheless, the relatively small differences between the PCM grades indicate that their influence on the mean internal surface temperature remained limited under these conditions.
The thermal response during January differed from that observed during the warmer months. As shown in Figure 16c, the external surface-temperature profiles of the five PCM grades were almost identical, with maximum average hourly temperatures of approximately 18.3 °C, compared with 28.35 °C for the conventional wall. A similar trend was observed at the internal surface (Figure 16f), where the PCM configurations exhibited nearly overlapping profiles, with monthly mean temperatures of approximately 13.38–13.39 °C, compared with 15.39 °C for the reference wall. The corresponding temperature variation across the average hourly profiles decreased from approximately 2.29 °C for the conventional wall to 0.37–0.38 °C for the PCM-integrated configurations. These observations indicate that the influence of nominal PCM melting temperature on the investigated surface-temperature indicators became negligible during the cooler period.
The lower internal surface temperatures observed during January are consistent with the adopted cooling-only operating strategy. Since space heating was disabled, the indoor environment was not maintained at a prescribed heating temperature during the cooler months. Consequently, the wall surfaces were exposed to lower indoor temperatures governed by the simulated building thermal balance. These results should therefore be interpreted as the thermal response of an unheated building during the cool season rather than as an indication of improved or reduced heating-system performance. The corresponding changes in wall energy transfer are discussed in Section 6.4.
An important observation from Figure 16 is that the relative performance of the PCM grades depends on the thermal indicator considered. During July, the higher-melting grades generally exhibited lower afternoon external surface-temperature peaks and smaller internal temperature fluctuations than Q21. However, the monthly mean internal surface temperatures of all PCM configurations remained nearly identical. This distinction demonstrates that the configuration exhibiting the smallest diurnal temperature variation does not necessarily provide the greatest reduction in accumulated conductive energy transfer. Accordingly, the selection of Q21 as a preferred PCM grade is primarily supported by its favorable warm-season wall energy performance, rather than by consistently achieving the lowest surface temperatures or the greatest attenuation of diurnal temperature fluctuations.
Overall, the hourly analysis demonstrates that PCM integration substantially modifies the surface-temperature response of the investigated wall, with the magnitude of the improvement and differences between melting grades varying across seasons. The observed behavior reflects the combined effects of the thermal resistance, sensible heat capacity, and phase-change characteristics of the modified wall assembly. Nevertheless, the presented temperatures correspond to the external and internal surfaces of the complete wall construction rather than to locations within the PCM layer. Consequently, the temperature profiles do not independently establish the extent of PCM melting, solidification, or nighttime restoration of latent storage capacity. The present assessment therefore provides additional quantitative evidence of diurnal surface-temperature attenuation and melting-grade sensitivity, complementing the preceding wall energy analysis without attributing the observed improvements exclusively to latent heat storage.

6.6. Material-Level Cost–Performance Assessment

Although increasing PCM thickness generally improves the thermal performance of the investigated wall, its practical applicability also depends on the additional material expenditure required to achieve the corresponding benefit. Therefore, a comparative material-level cost–performance assessment was conducted to distinguish the configuration providing the greatest thermal improvement from that offering the highest benefit relative to material cost. The analysis focused on the four investigated Q21 thicknesses (M27, M51, M91, and M182), considering outermost PCM placement in the West-facing wall. This configuration was selected based on its favorable warm-season performance and combined seasonal thermal response, as discussed in the preceding sections.
The economic assessment considered the investigated wall area of 16 m2 and the nominal PCM density of 235 kg/m3 adopted in the numerical simulations. Material expenditure was estimated using the thickness-dependent wholesale prices reported by Kośny et al. [54] in a technical report prepared for the National Renewable Energy Laboratory (NREL). These prices were applied on a unit-area basis to provide a consistent comparison among the investigated configurations. Since the published values represent historical commercial data for related PCM products rather than current supplier quotations for Q21 in Egypt, they were treated as reference prices rather than actual project procurement costs.
The nominal PCM mass, initial material expenditure, and thermal cost-effectiveness were determined using Equations (10)–(12), respectively:
m i = ρ A t i
C i = A p i
Ψ i = B i C i
where mi is the nominal PCM mass (kg), ρ is the material density (kg/m3), A is the investigated wall area (m2), ti is the PCM layer thickness (m), pi is the material price per unit area (USD/m2), and Ci is the corresponding PCM expenditure (USD). The term Bi represents the combined seasonal thermal benefit (kWh), calculated using Equation (8), while Ψi expresses the thermal benefit per unit initial material cost (kWh/USD). This indicator provides a comparative measure of material-level cost-effectiveness and should not be interpreted as a direct estimate of electricity savings or financial return.
Figure 17 illustrates the relationship between combined seasonal thermal benefit, material expenditure, and thermal cost-effectiveness for the investigated PCM thicknesses. The results indicate that increasing PCM thickness produces progressively greater absolute thermal benefits, with the M182 configuration achieving the strongest overall thermal improvement. However, the corresponding increase in material expenditure is more pronounced than the proportional improvement in thermal performance. Consequently, the thermal benefit obtained per unit material cost decreases as PCM thickness increases, with M27 exhibiting the highest cost-effectiveness under the adopted reference-price assumptions.
Figure 17. Comparison of combined seasonal thermal benefit, estimated PCM cost, and thermal cost-effectiveness for the West-facing wall with outermost Q21 BioPCM at different thicknesses.
From a thermodynamic perspective, the diminishing material-specific benefit associated with increasing PCM thickness reflects the interaction between transient heat conduction and thermal energy storage within the wall assembly. Although thicker PCM layers provide greater conductive resistance and increased sensible and latent storage capacity, their effective contribution depends on the local temperature distribution and the extent to which the material experiences temperatures within its phase-transition interval. Consequently, adding PCM thickness does not necessarily produce a proportional increase in thermal benefit, particularly when the additional material is not fully utilized during the imposed thermal cycles.
The economic ranking is also influenced by the relationship between material thickness and the corresponding unit-area price. Under the adopted reference-price scenario, the additional expenditure associated with thicker PCM layers exceeds the proportional increase in their combined seasonal thermal benefit. This explains the greater material-level cost-effectiveness of M27, despite its lower absolute thermal performance. Accordingly, the selection of PCM thickness involves a trade-off between maximizing thermal improvement and minimizing the initial material expenditure required to achieve that improvement.
It should be emphasized that the present assessment represents a comparative material-level evaluation rather than a comprehensive life-cycle cost analysis. The adopted historical prices do not account for transportation, installation, maintenance, replacement, or other project-specific expenditures [56]. Furthermore, the absence of active space heating in the simulated operating scenario means that changes in cool-season outward heat transfer do not directly correspond to additional heating-energy expenditure. Establishing financial savings, a payback period, or a return on investment would require additional information concerning HVAC operation, equipment efficiency, energy tariffs, and long-term system performance.
Overall, the results demonstrate that the thermally preferred PCM thickness does not necessarily represent the most economically favorable alternative. While Q21 M182 with outermost placement provides the greatest combined seasonal thermal benefit among the investigated Q21 thicknesses, Q21 M27 offers the highest thermal benefit per unit initial material cost under the adopted assumptions. Consequently, increasing PCM thickness does not necessarily produce a proportional improvement in thermal performance, as the effective contribution of additional material depends on the transient temperature distribution and its interaction with the prescribed phase-transition range.

7. Conclusions

This study investigated the thermal performance of BioPCM-integrated external walls under Cairo’s hot desert climate through a comprehensive numerical assessment of 240 configurations. The combined effects of PCM melting temperature, layer thickness, installation position, and wall orientation were examined using DesignBuilder/EnergyPlus. The results demonstrated that PCM integration can substantially modify heat transfer through building envelopes, although its effectiveness depends on the interaction between material properties, wall configuration, and seasonal climatic conditions.
The results revealed that PCM thickness and installation position exerted a more pronounced influence on wall thermal performance than the relatively small differences among the investigated melting grades. Increasing PCM thickness generally enhanced the attenuation of warm-season inward heat gain, with outermost placement consistently providing the greatest reduction. The M182 configuration reduced the overall wall thermal transmittance by 42.6%, confirming the contribution of additional conductive resistance to the observed improvement. Among the investigated melting grades, Q21 exhibited favorable thermal performance and was selected as the preferred practical option, while the differences between closely performing grades remained limited. In particular, Q21 M182 with outermost placement in the West-facing wall was identified as the preferred configuration for achieving substantial warm-season thermal attenuation.
The seasonal assessment further demonstrated that improvements during the warm period do not necessarily translate into favorable performance throughout the year. Although outermost PCM placement generally reduced summer heat gain, its influence on cool-season wall energy transfer varied with orientation. The West-facing wall provided the greatest absolute combined seasonal thermal benefit among the investigated orientations, followed by the East- and North-facing walls. In contrast, the South-facing wall exhibited a distinctly different response, with inner-layer placement offering a more favorable combined seasonal performance than outermost integration. These findings highlight the importance of considering seasonal heat-transfer behavior and wall orientation when selecting PCM configurations rather than relying exclusively on summer performance.
The detailed hourly analysis of the West-facing wall confirmed that PCM integration considerably attenuated external surface-temperature peaks and internal surface-temperature fluctuations. However, the relative performance of the investigated melting grades depended on the selected thermal indicator, demonstrating that lower surface temperatures do not necessarily correspond to the greatest reduction in accumulated wall energy transfer. Furthermore, the observed improvements reflect the combined influence of conductive resistance, sensible heat storage, and temperature-dependent enthalpy characteristics, without establishing the individual contribution of latent heat storage.
The material-level economic assessment revealed a trade-off between maximizing thermal improvement and minimizing the associated material expenditure. Although Q21 M182 provided the greatest absolute combined seasonal thermal benefit among the investigated Q21 thicknesses, Q21 M27 exhibited the highest thermal benefit per unit material cost under the adopted reference-price assumptions. Accordingly, the preferred PCM thickness depends on whether the primary design objective is maximum thermal attenuation or material-level cost-effectiveness.
Overall, the findings demonstrate the potential of BioPCM integration to improve wall-level thermal performance under hot desert climatic conditions, while emphasizing the importance of considering seasonal heat-transfer behavior, wall orientation, material configuration, and cost in the selection process. Nevertheless, the applicability of the identified configurations is subject to several limitations. The investigation was restricted to a representative plaster–brick wall assembly exposed to Cairo’s typical meteorological conditions, using a commercial BioPCM product series and a cooling-controlled operating strategy with a 24 °C setpoint. Consequently, the relative performance and preferred configuration cannot be directly generalized to other wall constructions, climatic conditions, intermittently conditioned or naturally ventilated buildings, or operating scenarios involving winter heating. Furthermore, the reported thermal benefits are confined to the investigated wall energy indicators and do not establish equivalent reductions in whole-building HVAC consumption or economic payback. Future investigations should extend the analysis to alternative wall assemblies and operating schedules, incorporate experimentally characterized PCM properties and transient phase-change validation, and assess whole-building heating and cooling requirements alongside life-cycle economic performance to establish the broader practical applicability of the proposed configurations.

Author Contributions

Conceptualization, M.A.H., N.A.M., W.M.E.-M. and A.A.H.; methodology, M.A.H., N.A.M., M.M.I. and A.A.H.; software, M.A.H. and M.M.I.; validation, A.M.E., W.M.E.-M. and A.A.H.; formal analysis, N.A.M., A.M.E. and W.M.E.-M.; investigation, M.A.H., N.A.M. and A.A.H.; data curation, A.M.E.; writing—original draft preparation, M.A.H., N.A.M. and M.M.I.; writing—review and editing, A.M.E., W.M.E.-M. and A.A.H. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.

Conflicts of Interest

The authors declare no conflicts of interest.

Nomenclature

The following nomenclatures are used in this manuscript:
AArea, m2
BCombined seasonal thermal benefit, kWh
CiInitial PCM cost for configuration i, USD
CpSpecific heat capacity at constant pressure, J kg−1 K−1
EAccumulated wall thermal energy, kWh
EinAccumulated inward conductive heat gain, kWh
EoutAccumulated outward conductive heat loss, kWh
EnetAccumulated signed net wall energy transfer, kWh
hSpecific enthalpy, kJ kg−1
piPCM price per unit wall area, USD m−2
UOverall wall thermal transmittance, W m−2 k

Abbreviations

The following abbreviations are used in this manuscript:
ASHRAEAmerican society for heating, refrigeration and air conditioning engineers
BioPCMBio-based phase change material
EPWEnergyPlus Weather
ETMYEgyptian Typical Meteorological Year
HVACHeating, ventilation, and air conditioning
NRELNational Renewable Energy Laboratory
PCMPhase change material
TMYTypical Meteorological Year

References

  1. Elmnifi, M.; Aleksandrovna, D.T.; Fadiel, A.F.A.; Shehata, A.I.; Moharram, N.A.; Taha, A.A. Unlocking hybrid solar efficiency: Experimental integration of aluminum foam fins and nanofluids in PVT collectors. Results Eng. 2026, 29, 108751. [Google Scholar] [CrossRef] [Scilit]
  2. Hamied, M.A.; Atta, M.; García-Regodeseves, P.; Ríos-Fernández, J.C. A novel sequential approach through structural enhancements for designing a new serrated helical heat exchanger. Case Stud. Therm. Eng. 2025, 69, 106006. [Google Scholar] [CrossRef] [Scilit]
  3. El-Maghlany, W.M.; Attia, M.E.H.; Kabeel, A.E.; Elazab, M.A.; Hidouri, A.; Moharram, N.A. Comparative experimental study on the performance of single-slope, hemispherical, and conical solar stills. Arch. Thermodyn. 2025, 46, 187–197. [Google Scholar] [CrossRef] [Scilit]
  4. International Energy Agency (IEA). World Energy Outlook 2025; IEA: Paris, France, 2025; Available online: https://www.iea.org/reports/world-energy-outlook-2025 (accessed on 24 August 2026).
  5. International Energy Agency (IEA). The Future of Electricity in the Middle East and North Africa; IEA: Paris, France, 2025; Available online: https://www.iea.org/reports/the-future-of-electricity-in-the-middle-east-and-north-africa (accessed on 20 November 2026).
  6. United Nations Environment Programme (UNEP). Global Alliance for Buildings and Construction, 2020 Global Status Report for Buildings and Construction: Towards a Zero-Emission, Efficient and Resilient Buildings and Construction Sector; UNEP: Nairobi, Kenya, 2020; Available online: https://wedocs.unep.org/handle/20.500.11822/49782 (accessed on 20 November 2026).
  7. Ibrahim, M.M.; William, M.A.; Hanafy, A.A.; Moussa, M.F.; Suárez-López, M.J. Boosting energy efficiency in educational buildings: The role of electrochromic glazing and ASHRAE standard integration. AIP Conf. Proc. 2025, 3395, 060002. [Google Scholar] [CrossRef] [Scilit]
  8. International Energy Agency (IEA). Transition to Sustainable Buildings: Strategies and Opportunities to 2050; IEA: Paris, France, 2013. [Google Scholar] [CrossRef] [Scilit]
  9. Colliver, D.G.; Jarnagin, R.E. Advanced Energy Design Guide for Small Office Buildings. ASHRAE J. 2005, 47, 22–27. [Google Scholar]
  10. Ibrahim, M.M.; William, M.A.; Elharidi, A.M.; Hanafy, A.A.; Suárez-López, M.J. Techno-Economic and Environmental Evaluation of Building Retrofit Strategies Toward NZEB Targets in Hot Climatic Contexts. Sustainability 2026, 18, 1991. [Google Scholar] [CrossRef] [Scilit]
  11. Hamied, M.A.; Saad, M.A.; García-Regodeseves, P.; Ríos-Fernández, J.C. A novel integrated approach to heat transfer enhancement using baffles and inner fins in helical coil heat exchangers. Case Stud. Therm. Eng. 2026, 77, 107529. [Google Scholar] [CrossRef] [Scilit]
  12. Egyptian Electricity Holding Company (EEHC). Annual Report 2023/2024; EEHC: Cairo, Egypt, 2024. Available online: https://www.eehc.gov.eg/CMSEehc/Files/AnnualReport2024En.pdf (accessed on 20 November 2026).
  13. ASHRAE. 2017 ASHRAE Handbook—Fundamentals (SI Edition); American Society of Heating, Refrigerating and Air-Conditioning Engineers: Atlanta, GA, USA, 2017; ISBN 978-1-939200-58-7. [Google Scholar]
  14. Oropeza-Perez, I.; Østergaard, P.A. Active and passive cooling methods for dwellings: A review. Renew. Sustain. Energy Rev. 2018, 82, 531–544. [Google Scholar] [CrossRef] [Scilit]
  15. Hamied, M.A.; El-Haridi, A.M.; El-Maghlany, W.M.; Hanafy, A.A. Improving Office Building Energy Performance Using Phase Change Material in Building Envelope. In The 11th International Conference on Informatics, Environment, Energy and Applications; ACM: New York, NY, USA; pp. 52–55. [Google Scholar] [CrossRef] [Scilit]
  16. Prieto, A.; Knaack, U.; Auer, T.; Klein, T. Passive cooling & climate responsive façade design exploring the limits of passive cooling strategies to improve the performance of commercial buildings in warm climates. Energy Build. 2018, 175, 30–47. [Google Scholar] [CrossRef] [Scilit]
  17. Kośny, J. PCM-Enhanced Building Components; Springer: Berlin/Heidelberg, Germany, 2015. [Google Scholar] [CrossRef] [Scilit]
  18. Osterman, E.; Tyagi, V.V.; Butala, V.; Rahim, N.A.; Stritih, U. Review of PCM based cooling technologies for buildings. Energy Build. 2012, 49, 37–49. [Google Scholar] [CrossRef] [Scilit]
  19. Saffari, M.; de Gracia, A.; Fernández, C.; Cabeza, L.F. Simulation-based optimization of PCM melting temperature to improve the energy performance in buildings. Appl. Energy 2017, 202, 420–434. [Google Scholar] [CrossRef] [Scilit]
  20. Alam, M.; Sanjayan, J.; Zou, P.X.W.; Ramakrishnan, S.; Wilson, J. Evaluating the passive and free cooling application methods of phase change materials in residential buildings: A comparative study. Energy Build. 2017, 148, 238–256. [Google Scholar] [CrossRef] [Scilit]
  21. Cabeza, L.F.; Castellón, C.; Nogués, M.; Medrano, M.; Leppers, R.; Zubillaga, O. Use of microencapsulated PCM in concrete walls for energy savings. Energy Build. 2007, 39, 113–119. [Google Scholar] [CrossRef] [Scilit]
  22. Nazi, W.I.W.M.; Wang, Y.; Chen, H.; Zhang, X.; Roskilly, A.P. Passive Cooling Using Phase Change Material and Insulation for High-rise Office Building in Tropical Climate. Energy Procedia 2017, 142, 2295–2302. [Google Scholar] [CrossRef] [Scilit]
  23. Meteoblue, Climate Lleida—Meteoblue. Available online: https://www.meteoblue.com/ (accessed on 10 March 2026).
  24. Hasan, M.I.; Basher, H.O.; Shdhan, A.O. Experimental investigation of phase change materials for insulation of residential buildings. Sustain. Cities Soc. 2018, 36, 42–58. [Google Scholar] [CrossRef] [Scilit]
  25. Ascione, F.; Bianco, N.; De Masi, R.F.; de’ Rossi, F.; Vanoli, G.P. Energy refurbishment of existing buildings through the use of phase change materials: Energy savings and indoor comfort in the cooling season. Appl. Energy 2014, 113, 990–1007. [Google Scholar] [CrossRef] [Scilit]
  26. Lei, J.; Yang, J.; Yang, E.H. Energy performance of building envelopes integrated with phase change materials for cooling load reduction in tropical Singapore. Appl. Energy 2016, 162, 207–217. [Google Scholar] [CrossRef] [Scilit]
  27. Kishore, R.A.; Bianchi, M.V.A.; Booten, C.; Vidal, J.; Jackson, R. Optimizing PCM-integrated walls for potential energy savings in U.S. Buildings. Energy Build. 2020, 226, 110355. [Google Scholar] [CrossRef] [Scilit]
  28. Ascione, F.; De Masi, R.F.; de Rossi, F.; Ruggiero, S.; Vanoli, G.P. Optimization of building envelope design for nZEBs in Mediterranean climate: Performance analysis of residential case study. Appl. Energy 2016, 183, 938–957. [Google Scholar] [CrossRef] [Scilit]
  29. Zhou, G.; Yang, Y.; Wang, X.; Zhou, S. Numerical analysis of effect of shape-stabilized phase change material plates in a building combined with night ventilation. Appl. Energy 2009, 86, 52–59. [Google Scholar] [CrossRef] [Scilit]
  30. Sailor, D.J. Evaluation of phase change materials for improving thermal comfort in a super-insulated residential building. Energy Build. 2014, 79, 32–40. [Google Scholar] [CrossRef] [Scilit]
  31. Abdullah, A.; Gassar, A.; Yun, G.Y. Energy Saving Potential of PCMs in Buildings under Future Climate Conditions. Appl. Sci. 2017, 7, 1219. [Google Scholar] [CrossRef] [Scilit]
  32. Xiao, W.; Wang, X.; Zhang, Y. Analytical optimization of interior PCM for energy storage in a lightweight passive solar room. Appl. Energy 2009, 86, 2013–2018. [Google Scholar] [CrossRef] [Scilit]
  33. World Meteorological Organization (WMO). World Weather Information Service: Beijing, China. Available online: https://worldweather.wmo.int/en/city.html?cityId=237 (accessed on 2 September 2026).
  34. Chen, D.; Chen, H.W. Using the Köppen classification to quantify climate variation and change: An example for 1901–2010. Environ. Dev. 2013, 6, 69–79. [Google Scholar] [CrossRef] [Scilit]
  35. World Meteorological Organization (WMO). World Weather Information Service: Murmansk, Russian Federation. Available online: https://worldweather.wmo.int/en/city.html?cityId=967 (accessed on 2 September 2026).
  36. Kenzhekhanov, S.; Memon, S.A.; Adilkhanova, I. Quantitative evaluation of thermal performance and energy saving potential of the building integrated with PCM in a subarctic climate. Energy 2020, 192, 116607. [Google Scholar] [CrossRef] [Scilit]
  37. World Meteorological Organization (WMO). World Weather Information Service: Milan (Milano), Italy. Available online: https://worldweather.wmo.int/en/city.html?cityId=603 (accessed on 2 September 2026).
  38. Soares, N.; Gaspar, A.R.; Santos, P.; Costa, J.J. Multi-dimensional optimization of the incorporation of PCM-drywalls in lightweight steel-framed residential buildings in different climates. Energy Build. 2014, 70, 411–421. [Google Scholar] [CrossRef] [Scilit]
  39. Ascione, F.; Bianco, N.; De Masi, R.F.; Mastellone, M.; Vanoli, G.P. Phase Change Materials for Reducing Cooling Energy Demand and Improving Indoor Comfort: A Step-by-Step Retrofit of a Mediterranean Educational Building. Energies 2019, 12, 3661. [Google Scholar] [CrossRef] [Scilit]
  40. Kamel, J.A.; Mina, E.M.; Elsabbagh, A.M. Implementation of phase change material for cooling load reduction: A case study for Cairo, Egypt. Int. J. Air-Cond. Refrig. 2022, 30, 13. [Google Scholar] [CrossRef] [Scilit]
  41. Bolteya, A.M.; Elsayad, M.A.; El Monayeri, O.D.; Belal, A.M. Impact of Phase Change Materials on Cooling Demand of an Educational Facility in Cairo, Egypt. Sustainability 2022, 14, 15956. [Google Scholar] [CrossRef] [Scilit]
  42. Hassan, M.; Dewidar, K.; Ismail, M.; Nessim, A.; Abdelalim, A. Optimizing Phase Change Material on Opaque Building Envelope to Reach nZEB. Civ. Eng. Archit. 2023, 11, 3667–3680. [Google Scholar] [CrossRef] [Scilit]
  43. Azimi, M.; Mahdavinejad, M.; Yeganeh, M. Economic optimization of PCM use for enhanced energy efficiency in passive buildings: A case study in Egypt. Sol. Energy 2025, 300, 113876. [Google Scholar] [CrossRef] [Scilit]
  44. Anter, A.G.; Sultan, A.A.; Hegazi, A.A.; El Bouz, M.A. Thermal performance and energy saving using phase change materials (PCM) integrated in building walls. J. Energy Storage 2023, 67, 107568. [Google Scholar] [CrossRef] [Scilit]
  45. Guermat, Z.; Kabar, Y.; Kuznik, F.; Boukelia, T.E. Numerical investigation of the integration of new bio-based PCM in building envelopes during the summer in Algerian cities. J. Energy Storage 2024, 79, 110111. [Google Scholar] [CrossRef] [Scilit]
  46. Ait Laasri, I.; Charai, M.; Es-sakali, N.; Mghazli, M.O.; Outzourhit, A. Evaluating passive PCM performance in building envelopes for semi-arid climate: Experimental and numerical insights on hysteresis, sub-cooling, and energy savings. J. Build. Eng. 2024, 98, 111161. [Google Scholar] [CrossRef] [Scilit]
  47. World Meteorological Organization (WMO). World Weather Information Service: Ankara, Türkiye. Available online: https://worldweather.wmo.int/en/city.html?cityId=48 (accessed on 2 September 2026).
  48. Kwan, Y.; Guan, L. Design a Zero Energy House in Brisbane, Australia. Procedia Eng. 2015, 121, 604–611. [Google Scholar] [CrossRef] [Scilit]
  49. Bhatia, A. HVAC Made Easy: A Guide to Heating & Cooling Load Estimation. PDH Online Course M196; PDH Online: Orlando, FL, USA, 2026. Available online: https://www.pdhonline.com/courses/m196/m196content.pdf (accessed on 6 September 2026).
  50. ASHRAE. ANSI/ASHRAE Standard 55-2023; Thermal Environmental Conditions for Human Occupancy. American Society of Heating, Refrigerating and Air-Conditioning Engineers: Atlanta, GA, USA, 2023. Available online: https://www.ashrae.org/technical-resources/bookstore/standard-55-thermal-environmental-conditions-for-human-occupancy (accessed on 10 September 2026).
  51. Phase Change Solutions, BioPCM: Bio-Based Phase Change Materials, Product Information. Available online: https://phasechange.com/biopcm/ (accessed on 19 July 2026).
  52. Cabeza, L.F.; Castell, A.; Barreneche, C.; De Gracia, A.; Fernández, A.I. Materials used as PCM in thermal energy storage in buildings: A review. Renew. Sustain. Energy Rev. 2011, 15, 1675–1695. [Google Scholar] [CrossRef] [Scilit]
  53. Mehling, H.; Cabeza, L.F. Heat and Cold Storage with PCM: An up to Date Introduction into Basics and Applications; Springer: Berlin/Heidelberg, Germany, 2008. [Google Scholar] [CrossRef] [Scilit]
  54. Kośny, J.; Shukla, N.; Fallahi, A. Cost Analysis of Simple Phase Change Material-Enhanced Building Envelopes in Southern U.S. Climates; Technical Report NREL/SR-5500-55553; National Renewable Energy Laboratory (NREL): Golden, CO, USA, 2013. Available online: https://www.osti.gov/biblio/1067934 (accessed on 24 August 2026). [CrossRef] [Scilit]
  55. Markarian, E.; Fazelpour, F. Multi-objective optimization of energy performance of a building considering different configurations and types of PCM. Sol. Energy 2019, 191, 481–496. [Google Scholar] [CrossRef] [Scilit]
  56. Ibrahim, M.M.; Moharram, N.A.; Hamied, M.A.; Elharidi, A.M.; Shehata, A.S.; Hanafy, A.A. HVAC exhaust-air-assisted thermal management of rooftop photovoltaics for energy retrofitting toward nearly zero-energy buildings. Appl. Therm. Eng. 2026, 308, 133660. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Article metric data becomes available approximately 24 hours after publication online.