Courtyard Microclimates in Central Asia: Traditional Passive Cooling Strategies and Their Modern Relevance

,
and
1
College of Architecture, Xi’an University of Architecture and Technology, Xi’an 710055, China
2
Library, Xi’an University of Architecture and Technology, Xi’an 710055, China
3
Journal Editorial Department, Xi’an University of Architecture and Technology, Xi’an 710055, China
*
Author to whom correspondence should be addressed.

Abstract

Inward-oriented Central Asian courtyards must limit summer overheating and winter heating demand through one envelope, yet the relative strengths of geometry, wall mass, openings, and vegetation have not been measured under continental cold-desert conditions. This study quantifies them with a three-dimensional coupled CFD and building-energy model of a single-story courtyard dwelling prototype surveyed in Bukhara Region, Uzbekistan, validated on two monitored days at an indoor operative-temperature RMSE of 1.76 °C. Twelve variables covering those four groups entered a mixed-level near-orthogonal 120-scenario design, and fifty screened candidates were simulated directly. Wall thickness, high side-window ratio, and green coverage form the leading overheating group, with level mean spans of 172.6, 172.0, and 170.3 h against 131.7 h for window-to-wall ratio. The equal-weight rule selected P04 from ten non-dominated solutions, at 972 h of overheating, 134.5 kWh m−2 of heating demand, a 10.2 h−1 air change rate, and a 120.8 kWh m−2 annual energy use intensity, 44.6% below the 218 kWh m−2 reference. The peak-shift lag passes 4 h at a wall thickness of 500 mm, and the selected 600 mm wall reaches a lag of 6.5 h. These results connect courtyard typology to measured factor responses and bounded design selection.

1. Introduction

Traditional Central Asian courtyards regulate summer heat, winter exposure, and natural ventilation through the combined action of inward-oriented space, massive envelopes, controlled openings, and vegetation. The performance of each component depends on the others. Deep enclosure increases shade but can restrict airflow, larger openings improve air exchange but can raise seasonal heat transfer, and vegetation adds latent cooling while increasing humidity and water demand. This interdependence makes courtyard design a multi-objective problem under the region’s large seasonal and diurnal temperature ranges.
Central Asia, including Kazakhstan, Uzbekistan, Kyrgyzstan, Tajikistan, and Turkmenistan, occupies a large interior region of the Eurasian landmass where building design is shaped by severe continental climatic contrast [1]. Winters are harsh, summers are hot, diurnal temperature swings are large, rainfall is limited, and evaporation rates are high. Almaty illustrates this combined stress: summer temperatures commonly reach 38–45 °C, winter averages can fall to −25 °C or lower, and daily temperature fluctuations may reach 20–25 °C. A climate-responsive building in this region must therefore solve two linked problems: it must provide effective shading, cooling, and ventilation in summer while maintaining insulation, heat storage, and wind protection in winter.
Rapid urbanization has intensified this climatic problem by increasing building energy demand across the region. Recent data indicate that buildings account for 35% to 42% of total regional energy use, with heating and cooling systems consuming 60% to 75% of that share [2]. When contemporary buildings adopt imported design templates without sufficient regional climatic adjustment, they combine excessive energy demand with poor indoor comfort. Traditional courtyard dwellings provide an important counterpoint because they use spatial form, thermal mass, shaded transitional spaces, and controlled openings to moderate summer heat and winter cold with limited reliance on mechanical systems [3].
This accumulated architectural knowledge is also becoming more difficult to recover as redevelopment, material replacement, and changing construction practices reduce the number of intact traditional structures. At the same time, many design curricula and technical guidelines still lack a systematic method for translating vernacular passive principles into performance-based design parameters. Existing scholarship has provided valuable accounts of the formal, historical, and cultural dimensions of Central Asian architecture [4,5], but it offers fewer quantitative explanations of how courtyard form, wall mass, fenestration, and vegetation regulate heat, airflow, and humidity. This gap limits the practical use of vernacular knowledge in contemporary low-energy design.

1.1. Passive Courtyard Performance

Passive-design research treats architectural form, envelope construction, and natural ventilation as coupled means of maintaining comfort with lower mechanical demand [6,7,8]. In hot-arid and semi-arid settings, courtyard aspect ratio changes solar access, mean radiant temperature, and airflow continuity. Appropriately proportioned courts have produced indoor temperature reductions of 3–5 °C, while parametric studies show that both L/W and H/W affect shading and ventilation [9,10]. These findings establish geometry as a measurable environmental control whose effective range changes with climate, orientation, and opening pattern.
Envelope mass and landscape processes provide two further controls on courtyard performance. Walls with high thermal inertia damp daily temperature amplitude and delay peak heat transfer, while vegetation combines canopy shading with evapotranspiration [11,12,13]. The resulting cooling cannot be assigned to one component without considering radiation, airflow, moisture, and seasonal operation. A heavy wall can reduce summer peaks and winter demand under a large diurnal range, yet additional thickness produces diminishing gains and carries material costs. Vegetation can lower afternoon temperature, yet its applicability depends on water availability, species, canopy form, and humidity tolerance.

1.2. Central Asian Courtyard Architecture and the Unresolved Numerical Problem

Central Asian architectural studies have documented regional history, morphology, and cultural organization, including the inward orientation of rooms, iwans, service areas, gardens, and water features around courts [3,4,5]. The literature makes the regional type legible but provides limited numerical evidence on the magnitude of its thermal effects. Environmental studies provide methods for measuring geometry, thermal mass, fenestration, and planting, but most evidence comes from Iranian, Mediterranean, or other hot-arid settings [7,8,9,10,11,12,13,14,15,16,17,18,19]. The unresolved issue concerns how these variables operate together in cold-desert and cold semi-arid continental conditions, where winter heating and summer overheating must be evaluated within the same design.
Four reporting gaps follow from this separation. Regional typologies require a physical definition that identifies the courtyard’s location, adjacent spaces, and climatic role. Parametric testing requires the scenario structure and factor effects, because ranges alone do not show which variables control each outcome. Multi-objective optimization requires a clear division between experimental design and search, together with unit normalization and an explicit compromise rule. Threshold claims require response curves that distinguish tested ranges, existing construction, and selected design values.

1.3. Research Question and Analytical Contribution

The study examines how courtyard geometry, wall construction, window layout, and vegetation affect summer overheating, winter heating demand, natural ventilation, and annual energy use in a representative Central Asian courtyard dwelling. These four variable groups are selected because each controls a distinct physical pathway: geometry sets solar exposure and airflow path length, wall construction sets thermal storage and conduction, window layout sets the exchange between rooms and the court, and vegetation sets shading and latent cooling. Material properties enter the model through wall thickness, thermal conductivity, and exterior-wall solar absorptance, while interior finishes and glazing type remain at the documented baseline. The twelve variables and their tested levels are listed in Section 3.3.
The analytical role column states the pathway that each of the twelve variables controls, and the envelope components that stay at their documented values mark the boundary of that set. Roof insulation and glazing solar heat gain coefficient are properties of contemporary products, and the recorded buildings carry neither, so admitting them would replace the design freedoms of the courtyard type with a retrofit specification. The roof of timber beams with reed and earth and the single-glazed wooden windows of the documented envelope therefore enter every scenario unchanged, which makes each reported response span and the 218 kWh m−2 reference attributable to the twelve tested variables. A second constraint points the same way. Twelve factors carrying four to nine levels consume 66 of the 119 degrees of freedom available at 120 runs, and each further factor would require a larger design or the loss of the interval estimates reported in Section 4.2.
NSGA-II, the non-dominated sorting genetic algorithm II, searches a bounded variable space by evolving a population of candidate vectors toward the Pareto front of conflicting objectives [20]. It suits this problem because the performance objectives conflict and the search must locate a small set of compromise candidates rather than a single optimum. In this study, NSGA-II evaluates candidates with a level-wise main-effects screening function over 3000 vectors, and the three physical objectives of overheating, heating demand, and air change rate retain their units during non-dominated sorting. The fourth objective, annual energy use intensity, enters only after normalization in the equal-weight distance rule that selects one compromise from the directly simulated solutions.
A balanced mixed-level near-orthogonal design structures 120 unique scenarios for level-wise main-effect analysis across these variables. Fifty screened candidates then receive direct EnergyPlus and Fluent evaluation, and three-objective non-dominated sorting followed by an equal-weight four-objective distance rule selects the reported compromise P04.
The contribution relative to existing courtyard studies consists of five specific additions. (1) The courtyard typology of the region is converted into a twelve-variable balanced mixed-level near-orthogonal screening design with quantified residual association. (2) The search stage and the reporting stage are separated, and the deviation of the screening surface from direct simulation is disclosed for all four objectives. (3) Factor response spans carry residual-bootstrap 95% intervals, so the leading overheating group is reported as a numerically close set with stated uncertainty. (4) Wall evidence distinguishes a tested thermal-inertia threshold, the existing construction, and the selected wall, each with its own lag and seasonal demand. (5) Transfer to contemporary assemblies and to other Central Asian climate subtypes is stated as explicit conditions with required checks rather than as general applicability.
This sequence produces four reader-verifiable outputs. The typological analysis defines the inward-oriented courtyard and the physical meanings of L/W, H/W, and opening ratio. The factor analysis reports all level-wise response spans and directly compares wall thickness with window-to-wall ratio. The optimization separates candidate screening, direct simulation, Pareto filtering, and P04 selection. The wall sweep distinguishes a tested thermal-inertia threshold, the existing baseline, the selected wall, and their associated peak shifts.

2. Study Area and Central Asian Courtyard Typology

2.1. Regional Climatic Context and Case Selection

The documented evidence base comprises five courtyard complexes selected with geographic, chronological, functional, and preservation criteria. Geographically, the candidate buildings stand in Central Asian settings exposed to strong continental climatic stress, including high summer temperatures, low winter temperatures, large diurnal temperature ranges, and limited precipitation. Chronologically, the sample focuses on buildings constructed between the late eighteenth and early twentieth centuries, when traditional construction techniques were mature and before modern mechanical-conditioning systems became dominant. This boundary allows the cases to be interpreted as climate-responsive architectural systems rather than as modern mechanically conditioned buildings.
Functionally, the selected cases emphasize courtyard complexes in which an enclosed or semi-enclosed courtyard is connected to primary rooms, service spaces, envelope elements, openings, and vegetation. Preservation status was also important; the selected examples retain legible spatial organization and recognizable structural elements, including walls, roofs, doors, windows, and courtyard boundaries. The selection therefore prioritizes buildings that make it possible to relate architectural form to the four passive-design factors examined in this study: courtyard geometry, wall construction, window arrangement, and vegetation pattern.
The five documented complexes in Table 1 establish the regional spatial vocabulary of the iwan, the hauz, the inward enclosure, and the shaded threshold, and they locate the courtyard within palace, mosque, khanqah, madrasah, and domestic organizations. Their functions differ, so they serve as typological evidence for spatial organization and climatic response rather than as simulation objects. The numerical analysis object is a single-story courtyard dwelling prototype abstracted from a compound recorded in the regional field survey. The surveyed building stands in Bukhara Region, Uzbekistan, dates from the late nineteenth century, and was recorded in 2022 by tape and laser distance measurement with a photographic survey.
Table 1. Regional courtyard complexes used as typological evidence for spatial organization and climatic response.
The prototype retains the surveyed geometry at construction-documentation precision. The measured plan of 19.6 m by 15.2 m rounds to the prototype plan of 19.5 m by 15.0 m, and the measured exterior-wall thickness range of 515 to 525 mm enters the model at the mid-range value of 520 mm. The courtyard measures 5.8 m by 4.5 m within an enclosure height of 3.6 m, which gives a plan ratio L/W of 1.29, reported as the 1.3 baseline, and an enclosure ratio H/W of 0.80. These measured values anchor the Baseline column and the reference case of the energy model.
Table 1 summarizes the documented regional cases used to establish courtyard position, spatial components, scale, and climatic relevance before the physical variables are defined.
Figure 1 summarizes the annual temperature and solar-radiation context that governs these passive responses, and Table 2 summarizes the climate background of the six stations. The regional pattern combines high summer solar exposure with winter cold and large daily temperature amplitudes, creating simultaneous requirements for shade, delayed heat transfer, controllable ventilation, and seasonal solar access.
Figure 1. Annual temperature and solar-radiation context of the six regional stations. Each row reports one station: the (left) panel shows the monthly mean dry-bulb temperature with the monthly minimum-to-maximum envelope, and the (right) panel shows the monthly total global horizontal irradiation. Data are derived from the station weather files listed in Table 2 (TMYx records; the Kashi station uses CSWD).
Table 2. Regional climate background of the six stations used for the regional climatic setting.
Four of the documented complexes lie in cold-desert climates of the Köppen–Geiger class BWk, while the Hissar fortress madrasah lies in a hot-summer Mediterranean climate (Csa) with an annual mean temperature of 14.1 °C and annual precipitation of 568 mm. Three considerations keep the Hissar case in the sample. The first is the summer itself. The summer-dry criterion that the Csa class carries requires the driest summer month to hold less than one third of the precipitation of the wettest winter month, so the 568 mm of annual precipitation at Hissar is concentrated outside the summer, and the summer that its court has to moderate is a dry one, which is the condition the four cold-desert courts also meet and the condition that the typological reading takes from all five cases. The second is coverage of the type. Hissar is the only four-iwan madrasah court in the set, so its removal would leave the teaching and residential variant of the regional type undocumented while the palace, mosque, and khanqah variants remain. The third is the reach of the classification itself. The subtype difference reaches the numerical analysis through the weather file alone, and every simulation in this study runs on the single Tashkent TMYx file, so no reported value depends on the Hissar case. The regional climatic background in Table 2 covers six stations across the BWk, Csa, Dsa, Dsb, and Dfb subtypes and describes the amplitude of the regional climate rather than the parameters of any individual case.
This climatic setting creates a dual design challenge. In summer, buildings must respond to extreme heat, intense solar radiation, and low humidity; in winter, they must protect occupants from low temperatures and strong winds. Large diurnal temperature ranges add a further requirement because the building envelope must buffer rapid heat gain and heat loss within the same day. These conditions explain why courtyard enclosure, wall thermal inertia, controlled openings, and vegetation are treated as linked passive strategies rather than as isolated design features.
The regional climate also changes the timing at which each passive strategy is useful. Summer radiation and low afternoon humidity favor shading, delayed heat transfer, and evaporative cooling, while cool nights permit stored heat to be released when openings can operate safely. Winter reverses several priorities because the same opening that supports summer flushing can expose the court and adjacent rooms to cold wind. The analysis therefore evaluates summer and winter outputs separately before combining them through annual energy use and multi-objective selection.

2.2. Typological Definition and Spatial Organization

Within this study, a traditional Central Asian courtyard is an inward-oriented open or semi-open space that organizes access, daily activity, environmental exchange, and privacy within a surrounding building mass. Primary rooms, service spaces, iwans, and circulation edges face the court. An iwan is a vaulted or columned hall open on one side toward the court, and a hauz is a masonry pool that holds the water supply of the compound. Thick masonry or earthen walls enclose the adjacent rooms, and openings connect those rooms to the court more directly than to the external street. The court therefore acts as the spatial and environmental center of the compound, while the surrounding rooms form its thermally buffered perimeter.
This regional organization differs across building functions and should not be reduced to one domestic plan. Multi-courtyard palaces separate reception, residential, and administrative courts. Mosque and khanqah complexes, in which a khanqah is a residential lodge for a Sufi community, use open courts, iwans, pools, and cells to connect public, devotional, and residential functions. Madrasah courts organize communal space within ranges of hujras, the small student rooms of a madrasah, which is a teaching institution. Domestic compounds use the same inward orientation at a smaller scale, with living and service rooms arranged around a central court. The common climatic features are enclosure, shaded transition, controllable openings, massive walls, and the optional use of water and vegetation.
Figure 2 makes this organization explicit before the numerical variables are introduced. The plan locates the court within the surrounding room band, the section identifies enclosure and shaded semi-outdoor zones, and the variable panel defines the dimensions used in the parametric analysis.
Figure 2. Typological organization and geometric variables of an inward-oriented Central Asian courtyard. (a) The courtyard forms the central organizing space for adjacent living and service rooms, planting, and a hauz. (b) The section identifies enclosure height, courtyard width, and shaded semi-outdoor transition. (c) L/W describes plan proportion, H/W describes enclosure depth, and opening ratio describes exposure through the enclosing mass.
The examples in Table 1 show that the courtyard occupies an organizing position within each complex, although the degree of enclosure and the adjoining functions vary. The columned iwan of the Bolo-Hauz Mosque measures 42 m by 10 m with a height of 12 m and forms a shaded threshold between the street and the open court. The northeast pool of the Khoja Zayniddin complex measures 37 m by 26.5 m and acts as the evaporative source of a four-iwan courtyard. The harem court of the Tash-Khovli Palace measures 49 m by 15 m and shows the slender proportion that a private residential court can take within a palace. Pools increase evaporative potential, iwans create shaded thresholds, and surrounding cells or rooms increase the area of thermally buffered enclosure.
Spatial position also determines how the court interacts with external climate. A central court receives air and solar radiation through limited roof and boundary openings, while the surrounding room band reduces direct exposure to the street. Semi-outdoor edges mediate movement between the courtyard air and indoor rooms. In multi-courtyard complexes, this sequence can repeat across public and private zones. The resulting form is defined by relational organization, including inward-facing rooms, a central environmental void, and buffered perimeter mass, rather than by one fixed plan shape or building function.

2.3. Physical Meaning of the Geometric Ratios

The length-to-width ratio L/W expresses plan compactness and the duration and distribution of solar exposure. Values close to unity produce a compact court, while larger values elongate the solar path and wind route along one axis. The documented courtyard proportions in Table 1 fall between 1.14 and 1.40, and the harem court of the Tash-Khovli Palace forms a slender exception at 3.27 that lies beyond the tested range of 1.0 to 2.0. The parametric design tests 1.0–2.0 to establish where elongation changes overheating, air movement, and annual energy use.
The height-to-width ratio H/W expresses enclosure depth. Increasing H/W enlarges the duration of self-shading and reduces sky exposure, but deeper enclosure can restrict cross-courtyard airflow. The prototype model baseline takes H/W = 0.8 from the measured enclosure of the surveyed dwelling, the tested range covers 0.5 to 1.2, and the multi-objective selection chooses 0.85. The opening ratio expresses the proportion of the enclosing court boundary that permits direct environmental exchange. A larger opening increases wind exposure and air exchange, while also admitting solar radiation and increasing winter heat loss. These three ratios therefore represent different physical controls and cannot be interpreted as interchangeable measures of courtyard size.

3. Materials and Methods

3.1. Sequential Research Framework

The research sequence links regional evidence to numerical selection through six operations. Case documentation and field monitoring define the courtyard type and observed environmental behavior. CFD and EnergyPlus models represent airflow, thermal response, and building energy demand. A balanced mixed-level near-orthogonal design structures 120 scenarios for level-wise main-effect and range analysis. A main-effects response function screens candidates during NSGA-II search. Fifty candidates then receive direct EnergyPlus and Fluent evaluation, and the resulting direct outputs support Pareto filtering and four-objective compromise selection.
The evidence types retain separate analytical roles. Typological description establishes form, validation supports comparative simulation, level-wise spans estimate factor response within the tested design, and the screening function prioritizes candidate combinations. The final performance values come from direct simulation of 50 candidates. Three-objective non-dominance identifies ten solutions within that direct set, while the stated four-objective distance rule selects one representative compromise.
Supplementary Figure S1 records the complete sequence. NSGA-II used a population of 60, 50 generations, and seed 20230615 to screen 3000 candidate vectors. The screening function accelerated the search and did not supply the final published solution values. Direct EnergyPlus 9.5 and ANSYS Fluent 2021 R1 evaluations supplied the outcomes for the 50 retained candidates and the ten solutions reported in Supplementary Table S5.

3.2. Numerical Simulation

3.2.1. Geometric Model, Courtyard Air, and Thermal Zones

The geometric model represents the courtyard as the explicit central CFD air region CZ-01, the courtyard air zone in which velocity, temperature, and humidity fields are resolved. Four conditioned living zones, TZ-01 to TZ-04, occupy the north, south, west, and east wings and carry the heating and cooling loads of the occupied rooms. One unconditioned service zone, TZ-05, completes the enclosed mass, and two semi-outdoor iwan zones, IZ-01 and IZ-02, form the shaded thresholds between court and rooms. The external CFD domain surrounds this assembly and includes the ground, inlet, pressure outlet, and top and lateral boundary locations. Supplementary Table S2 lists the corresponding native model names, openings, adjacent courtyard surfaces, and boundary treatments.
Figure 3 maps the architectural labels to their numerical roles. Fluent resolves the courtyard air region and the external airflow field, while EnergyPlus represents the four living zones, the service zone, and the two iwans, so every labeled region in the figure can be traced to a model object.
Figure 3. Geometric model, architectural zones, and external simulation domain. (a) The plan identifies four conditioned living zones, one unconditioned service zone, two semi-outdoor iwans, and the central courtyard air region. (b) The courtyard void schematic separates the courtyard from the enclosing room mass. (c) The zone map links architectural labels to EnergyPlus and CFD regions. (d) The external domain identifies ground, inlet, outlet, and symmetry boundaries.
Airflow and thermal simulations were conducted in ANSYS Fluent 2021 R1. The full-scale three-dimensional model was constructed from the field survey of the prototype dwelling and includes the courtyard, main building volumes, openings, and surrounding context within a 50 m radius. In ICEM CFD, unstructured tetrahedral meshes with near-wall prism layers produced 4,928,417 cells and 895,612 nodes. Cell dimensions ranged from 0.050 m at openings to 2.000 m in the far field, the first prism layer stands 0.50 mm above the wall with a growth rate of 1.20 over five layers, the minimum orthogonal quality is 0.31, and the maximum skewness is 0.74. Supplementary Table S14 records the discretization and convergence evidence for these values.
For turbulence closure, we used a Realizable k-ε model with enhanced wall treatment. The area-averaged y+ is 1.8 and the maximum y+ is 3.6, so the near-wall resolution satisfies the low-Reynolds requirements of this closure, an approach verified as reliable for external building flow and natural ventilation studies [21,22]. Inlet velocity profiles exhibit a logarithmic distribution.
u(z) = (u*/κ)ln[(z + z0)/z0]
where u* represents friction velocity, κ = 0.4 is the von Kármán constant, and z0 = 0.5 m denotes surface roughness. From an assumed turbulence intensity of 5% and the hydraulic diameter, we derived the turbulent kinetic energy and dissipation rate. Outlet boundaries were set to zero gauge pressure, which has matching turbulence properties. Wall surfaces were treated as no-slip. The courtyard-facing faces take the surface temperature that the energy model supplies through the exchange of Section 3.2.3, and the air-side flux at those faces closes against that temperature, so the conduction side and the air side of the same flux agree once the exchange has converged. Ground roughness was set to 0.5 m, and the temperatures were matched to field data. At 50 m height, the lateral and top boundaries were considered as symmetry planes.
Solar radiation in Fluent was represented with Solar Ray Tracing. Three surface groups carry the solar absorptance settings of the model, and each group carries the same value in the CFD model as in the energy model. The lime-washed courtyard-facing plaster of the faces bounding CZ-01 and the two iwans carries a fixed 0.25, and the ground plane carries a fixed 0.65. The street-facing exterior walls carry the exterior-wall solar absorptance variable, at a baseline of 0.75, a tested range of 0.30–0.90, and a selected value of 0.80, and each scenario applies its own value of that variable in both models. The courtyard void is bounded by the two fixed groups, so the swept group reaches the courtyard air only indirectly, through the conduction and the room-to-court exchange of the enclosure it heats. Across the 120 scenarios the reported courtyard air temperature and relative humidity show no ordered response to that variable, while summer overheating, winter heating demand, air change rate, and annual energy use intensity all respond to it through the exterior surface heat balance of the street elevation. Supplementary Table S18 lists the three groups with their surfaces, their value in each solver, and the evidence for each value. Vegetation was represented as a porous medium with resistance coefficients derived from measured LAI, and transpiration used a Penman–Monteith user-defined function.
Pressure–velocity coupling was solved with the SIMPLE algorithm. Momentum, energy, and turbulence transport equations were discretized using second-order upwind schemes. The final residuals are 8.4 × 10−5 for continuity and 6.9 × 10−5 for momentum, below the 10−4 criterion, and 3.2 × 10−7 for energy, below the 10−6 criterion. Temperature and velocity monitors fluctuated by 0.31% over the last 200 iterations, and the simulations proceeded to design comparison only after this stability was reached.

3.2.2. Energy and Envelope Model

Annual building energy performance was assessed with EnergyPlus 9.5. The courtyard was treated as a semi-outdoor CFD region, while the building model contained four conditioned living zones, one unconditioned service zone, and two semi-outdoor iwan zones. Geometry developed in SketchUp and transferred through OpenStudio retained the courtyard-facing walls, roofs, doors, and windows. Simulations used the Tashkent TMYx weather file as the regional reference climate, the longest record among the six regional station files (1932 to 2023). The zone mapping in Supplementary Table S2 defines how architectural spaces, CFD regions, and EnergyPlus zones correspond.
The 520 mm exterior wall in Table 3 is the baseline assembly and has a thermal inertia index D = 6.5. This baseline is distinct from the 500 mm threshold identified in the wall sweep and the 600 mm wall selected by the multi-objective procedure. Keeping these cases separate allows the response curve, existing construction, and selected configuration to be interpreted without assigning one D value to the entire tested range.
Table 3. Thermal properties of the envelope components used in the energy model.

3.2.3. Coupling of the Airflow and Energy Models

Fluent resolves the courtyard air region CZ-01 and the external flow field. EnergyPlus resolves conduction through the enclosing constructions, the internal gains, and the annual energy balance. The courtyard air state with which the rooms exchange air, and the surface temperatures that bound that air, therefore originate in different models, and the two models pass them to each other.
Four quantities cross the interface. Fluent returns the volume-averaged courtyard air temperature and relative humidity over the 1.0 to 4.5 m band of CZ-01, together with the air change rate obtained by integrating the volumetric flow through the courtyard-facing openings. EnergyPlus returns one area-weighted mean surface temperature taken over the seven courtyard-facing opaque faces, those of TZ-01 to TZ-05, IZ-01, and IZ-02. In EnergyPlus the courtyard air temperature sets the outside-face temperature of the courtyard-facing constructions through SurfaceProperty:OtherSideCoefficients objects carrying a fixed combined convective and radiative film coefficient of 5.0 W m−2 K−1. The air change rate sets the flow of the ZoneVentilation:DesignFlowRate objects of the four living zones and the service zone, and the courtyard relative humidity sets the moisture state of that ventilation stream. In Fluent the returned surface temperature enters as a specified-temperature wall boundary on those same seven faces, and the far-field logarithmic inflow profile of Section 3.2.1 remains the only inlet of the domain. Supplementary Table S17 Panel A lists the four quantities with their spatial support, exchange frequency, and receiving object.
Fluent solves one steady state per representative hour, and the exchange acts on 112 such hours. Forty fall in the 14:00 to 18:00 window of the eight June to August days with the highest daily mean dry-bulb temperature in the Tashkent TMYx file. Twenty-four fall in the 04:00 to 07:00 window of the six December-to-February days with the lowest daily mean. The remaining 48 cover the full 24 h of each of the two monitored days, 2022-07-25 and 2023-01-18. Those 112 h then supply the courtyard boundary values of all 8760 h of the annual EnergyPlus run. Each day of the weather year is first assigned to whichever of the eight summer and six winter solved days has the closest daily mean dry-bulb temperature to its own, the two monitored days taking no part in that assignment. The 460 h from 14:00 to 18:00 between June and August and the 360 h from 04:00 to 07:00 between December and February then read the solution of the same clock hour of their assigned day. The remaining 7940 h read the solved hour of their assigned day that lies nearest to them in clock time. Summer afternoons and winter pre-dawn hours therefore carry a courtyard state solved at that hour, and the rest of the year carries the nearest solved state of the assigned day. The courtyard air temperature and relative humidity reported in Supplementary Tables S3 and S10 are the averages of the Fluent solutions at the 40 solved summer afternoon hours. Operable windows stand open from 08:00 to 20:00 between June and August and stay closed through December to February, so the air exchange rate for the winter hours is the infiltration exchange of the closed building.
One pass of the exchange runs in four steps. First, EnergyPlus solves the annual run and reports the courtyard-facing surface temperature at each representative hour. Second, Fluent solves each representative hour against that surface temperature. Third, Fluent reports the courtyard air temperature, the courtyard relative humidity, and the air change rate for the same hour. Fourth, EnergyPlus reads those three quantities through the objects named above and solves the annual run again, which returns the sequence to its first step. The opening pass gives each of the three Fluent quantities a provisional value. The courtyard air temperature takes the weather-file dry-bulb temperature, the courtyard relative humidity takes the weather-file humidity, and the air change rate takes the reference-case ventilation rate of the existing dwelling given in Supplementary Table S13. Fluent supplies all three from the second pass onward. One complete pass through the four steps is an outer iteration, a quantity distinct from the solver iterations over which Section 3.2.1 reports its residuals, since the residual criteria govern the convergence of a single Fluent solution and the outer criterion governs the agreement between the two models. The loop stops when the courtyard air temperature changes by less than 0.015 °C, the courtyard-facing surface temperature by less than 0.015 °C, and the air change rate by less than 0.015 h−1 between consecutive outer iterations, each change taken as the largest absolute change that quantity shows at any representative hour of that pass. The loop closes between the fourth and the sixth outer iteration, and Supplementary Table S17 Panel B reports the realized sequences.
The two monitored days run the same exchange as every design run, with the same four quantities, the same receiving objects, the same stopping criterion, and the courtyard-facing surface temperatures are solved by the loop. The error magnitudes that Section 3.2.4 reports therefore describe the configuration that produced every outcome of Section 4.

3.2.4. Model Validation and Interpretation Boundary

The CFD and energy models were validated against field monitoring on two representative days, 25 July 2022 and 18 January 2023, at two measurement points. Point CY-01 stands at the courtyard geometric center 1.5 m above the ground, and point IN-01 stands in the indoor reference room TZ-02, 1.1 m above the floor. Records were logged hourly and paired with the simulated series, giving 192 paired records across the two days and four monitored quantities. Temperatures were recorded with HOBO U23-001 Pro v2 sensors (Onset Computer Corporation, Bourne, MA, USA) of ±0.21 °C nominal accuracy, and wind speeds with a Testo 480 hot-wire probe 0635 1535 (Testo SE & Co. KGaA, Titisee-Neustadt, Germany) of ±0.03 m s−1 plus 5% of reading and a 0.03 m s−1 starting threshold, with instrument calibration records dated 20 June 2022. Supplementary Table S7 reports the metadata and the paired series.
Error metrics are reported for each quantity separately. At CY-01, the air-temperature MAE is 0.83 °C with an RMSE of 1.05 °C and R2 = 0.997, and the wind-speed MAE is 0.16 m s−1 with an RMSE of 0.18 m s−1 and R2 = 0.937. At IN-01, the indoor operative-temperature MAE is 1.34 °C with an RMSE of 1.76 °C and R2 = 0.977, and the indoor wind-speed MAE is 0.08 m s−1 with an RMSE of 0.10 m s−1 and R2 = 0.958. The R2 values are computed from the pooled records of the summer and winter days, and the four RMSE values correspond to 2.2%, 8.9%, 6.3%, and 7.3% of their measured ranges. The courtyard wind-speed RMSE of 0.18 m s−1 corresponds to about 18% of the co-located measured mean, so the wind-speed evidence supports comparison among operating conditions rather than point-velocity prediction.
The two days anchor the interpretation of the validation. The summer day has a measured daily mean of 32.0 °C, which lies at the 97th percentile of the TMYx summer daily-mean distribution for Tashkent (n = 92, mean 27.2 °C), so it is treated as a hot summer day chosen to test the model under a demanding condition. The winter day has a daily mean of −0.3 °C at the 22nd percentile of the winter distribution (n = 90, mean 2.1 °C) and is representative of typical winter conditions. The measured diurnal ranges are 18.4 °C and 11.5 °C, and the measured courtyard wind-speed means of 0.91 and 0.88 m s−1 stay below the station seasonal means of 2.1 and 1.7 m s−1, consistent with the sheltering of an enclosed court. This evidence supports comparison across the tested operating conditions and does not extend to extreme winter events or multi-day heatwaves.
Figure 4 compares the measured and simulated series at CY-01 for the two days, covering courtyard air temperature and wind speed with 96 paired records.
Figure 4. Measured and simulated courtyard air temperature and wind speed at CY-01 on (a) 25 July 2022 and (b) 18 January 2023.
The surveyed dwellings operate free running and carry no metered energy record, so the validated quantity of the energy model is the indoor thermal state. Measured indoor operative temperature gives a mean absolute error of 1.34 °C and a root mean square error of 1.76 °C, the latter equal to 6.3% of the measured range, and the four monitored quantities all return R2 above 0.93. A model validated against a measured state variable is reported with the error metrics of that variable, so the indices above are computed on the paired measured and simulated operative-temperature series [23]. Winter heating demand is a modeled output of the reference gas-fired boiler and radiator system described in Supplementary Table S13, and it enters the results as a model output.
Figure 5 compares the measured and simulated indoor operative temperature at IN-01 for the same two days, with 48 paired records.
Figure 5. Measured and simulated indoor operative temperatures at IN-01 on (a) 25 July 2022 and (b) 18 January 2023.
Some discrepancies are attributable to boundary-condition simplifications, including transient cloud cover and the thermal influence of adjacent structures, as well as uncertainties in vegetation parameterization. The agreement between simulated and observed trends supports the use of the models for comparative parametric analysis, and the reported error magnitudes identify the scale at which differences between cases are interpreted.
Coupled courtyard-energy studies, outdoor microclimate validation, data-driven airflow prediction, and BEM-CFD integration provide related methodological reference points for this comparative use of simulation [24,25,26,27,28,29,30]. The present validation remains tied to the supplied monitoring locations and metrics, so those studies support the analytical approach without substituting for the case-specific error values reported here.
The validation metrics bound the comparisons that follow. The air-temperature RMSE of 1.05 °C is smaller than the reported 4.2 to 6.5 °C courtyard temperature reduction relative to the ambient daytime peak. The wind-speed RMSE of 0.18 m s−1 remains material where local velocities are low, so the analysis emphasizes ACH and ventilation-effectiveness patterns across scenarios. The indoor operative-temperature RMSE of 1.76 °C supports passive energy comparisons at the seasonal scale while limiting claims about short transient comfort events.

3.3. Near-Orthogonal Scenarios and Factor-Effect Analysis

The parametric design contains 12 variables in four groups: courtyard morphology, wall construction, window layout, and vegetation configuration. Four to nine levels were assigned to each factor. Balanced level assignment and independent random column permutations produced 120 unique scenarios, and candidate designs were screened by minimizing the maximum pairwise Cramér’s V. The selected mixed-level design has a maximum pairwise Cramér’s V of 0.2656 and a mean of 0.2186.
The twelve factors carry four to nine levels each, so estimating every main effect consumes 66 degrees of freedom above the grand mean and no design below 67 runs can separate them. The 120-run size clears that limit and leaves 53 residual degrees of freedom for the interval estimates. It divides exactly by the four, five, six, and eight level counts, giving 30, 24, 20, and 15 runs per level for those seven factors, while the seven-level and nine-level factors receive 17 or 18 and 13 or 14 runs per level, so every tested level carries at least 13 scenarios. The maximum pairwise Cramér’s V of 0.2656 lies within about 3% of the 0.258 value expected for independent columns with these level counts at 120 runs, and it is lower than every maximum pairwise value among 300 random balanced designs with the same level counts (minimum 0.2704, median 0.3072). Under numeric coding, the maximum pairwise correlation between factor columns is 0.2124 and the maximum variance inflation factor is 1.139. The design therefore supports estimation of level-wise main-effect magnitudes, and the influence of the residual association is carried into the conclusions through interval estimates of the spans rather than through point values alone. Supplementary Table S6 Panel B reports the design diagnostics.
The design supports level-wise main-effect and range analysis without requiring strict orthogonality. Geometry uses six L/W levels, eight H/W levels, and seven opening-ratio levels. Wall variables use nine thickness levels and seven levels each for conductivity and solar absorptance. Window variables use seven WWR levels, six high side-window levels, and four inlet-to-outlet area-ratio levels. The high side-window ratio is the share of the tested operable window area placed in the upper band of the room-to-courtyard wall, so it redistributes opening height without changing the total glazing area set by WWR. Vegetation uses six coverage levels, five tree-height levels, and six LAI levels. Supplementary Table S3 reports every scenario ID, run order, factor combination, and modeled outcome.
Performance outputs are defined with explicit computation windows. Summer overheating hours accumulate the hours in which hourly zone operative temperature exceeds 28 °C from June 1 to August 31. Winter heating demand is the zone heat load required to hold a 20 °C setpoint from December 1 to February 28. It is normalized by the 163.0 m2 heated floor area of the four conditioned living zones, whereas annual EUI is normalized by the 210.0 m2 conditioned floor area recorded in Supplementary Table S13, so the two intensities rest on different denominators. Annual EUI covers January 1 to December 31, and ACH reports volumetric air replacement under the representative natural-ventilation condition. Courtyard temperature and relative humidity provide mechanism-level evidence for geometry and vegetation, while ventilation effectiveness describes the uniformity of air delivery beyond the ACH magnitude.
In Table 4, the Baseline column reports the existing prototype construction values carried into every sweep, not an optimization result. The material group enters the model through wall thickness, thermal conductivity, and exterior-wall solar absorptance, while interior finishes and glazing types remain at the Table 3 documented baseline.
Table 4. Factor levels and analytical roles in the balanced mixed-level near-orthogonal 120–scenario design.
For each factor and level, the analysis calculates the sample count, outcome mean, and sample standard deviation. The estimated main-effect span is the difference between the maximum and minimum level means within the tested design. Supplementary Table S4 reports these level-wise statistics for overheating hours, winter heating demand, ACH, and annual EUI. The span is a descriptive response magnitude across tested levels and carries no inferential significance ranking.

3.4. Multi-Objective Search, Normalization, and Solution Selection

NSGA-II searched the bounded variable space with a level-wise main-effects response surface as the screening evaluator. A population of 60 over 50 generations generated 3000 screened candidate vectors.
ŷ(x) = ȳ + Σ(f = 1…12) [m_f(l_f(x)) − ȳ_f]
where ŷ(x) is the predicted objective at candidate vector x, ȳ is the grand mean of that objective over the 120-scenario matrix, m_f(l) is the level mean of factor f at level l from the same matrix, and ȳ_f is the mean of the level means of factor f, which centers each factor term on zero. Candidate values between tested levels are linearly interpolated between adjacent levels. The domain of the function is the twelve factor ranges of Table 4, it is fitted to the level means of Supplementary Tables S3 and S4, and its role is confined to stage-one search. Supplementary Table S9 Panel A records this definition.
The two-stage sequence narrows 3000 screened candidates to 50 designs for direct EnergyPlus and Fluent evaluation, an evaluation-count ratio of 60 to 1. The 50 are the top-ranked members of the screened set under three-objective non-dominated sorting of the response-surface predictions. Feasibility screening admitted 47 of the 50 candidates and excluded 3, each exclusion triggered by the 4 h−1 lower ACH bound, with the lowest direct ACH among them being 3.70 h−1. Three-objective non-dominance on the direct overheating, heating-demand, and ACH results produced ten solutions that are mutually non-dominated within the direct set. Supplementary Table S12 reports all fifty candidates with their screening predictions and direct outcomes.
The screening surface deviates from direct simulation by a margin that confines it to search. Its mean absolute deviation reaches 30.8% for overheating, with all fifty candidates biased in the same direction, against 6.5% for heating demand, 9.0% for ACH, and 10.4% for annual EUI. The additive surface overestimates the benefit of stacking several favorable levels, and the deviation exceeds the gap between adjacent candidates, so every reported performance value comes from direct simulation. Supplementary Table S9 Panel B reports the deviation statistics.
Post-Pareto selection used four dimensionless objectives (Table 5). Overheating, heating demand, and annual EUI used conventional min–max normalization. ACH used inverted min–max normalization so that zero represents the preferred direction for every objective. Three-objective non-dominance retains the physical units of its objectives, while the distance rule operates on normalized values. The equal-weight Euclidean distance d_ideal = sqrt(f1,n2 + f2,n2 + f3,n2 + f4,n2) then identified the candidate closest to the four-objective ideal within the ten directly simulated solutions. The objective set and the constraint set contain no water term. Green coverage therefore carries no cost in the search and is bounded only by the 50% upper limit of Table 4.
Table 5. Objective functions, normalization, constraints, and selected compromise rule.
The selected vector is a representative compromise within the 50 directly re-simulated candidates and the bounds in Table 4. P04 records the minimum four-objective distance among the ten directly simulated non-dominated solutions. Its selection therefore reflects the declared objective set, normalization reference, constraints, and equal weights.
Feasibility checking preceded direct-result Pareto sorting and compromise selection. Normalization used the minima and maxima of the ten reported direct-simulation solutions. Supplementary Table S5 reports every selected variable, direct outcome, normalized value, distance, feasibility status, and P04 selection flag.

4. Results

4.1. Model Validity and Analytical Scope

The coupled simulation framework enters the results with the error magnitudes of Section 3.2.4. The air-temperature RMSE is 1.05 °C at the courtyard point, the wind-speed RMSE is 0.18 m s−1, and the indoor operative-temperature RMSE is 1.76 °C, with all R2 values above 0.93. These magnitudes bound the factor comparisons that follow and are cited wherever a reported difference approaches the validation scale. With the model boundary established, the analysis turns from model validity to the factor responses measured across the 120 scenarios.

4.2. Factor Effects Across Four Performance Objectives

The level-wise analysis separates the leading overheating controls from the factors that govern ventilation and winter energy. Figure 6 and Table 6 report estimated main-effect spans for all four outcomes. Wall thickness, high side-window ratio, and green coverage form a numerically close leading overheating group, while opening ratio produces the largest ACH span. These descriptive spans compare tested level responses without assigning inferential significance.
Figure 6. Estimated level-wise main-effect spans within the balanced mixed-level near-orthogonal design. The panels report summer overheating, winter heating demand, ACH, and annual EUI for all 12 factors. Values derive from the level means in Supplementary Table S4.
Table 6. Estimated level-wise main-effect spans, effect directions, and overheating-span 95% intervals across four performance outcomes.
The spans describe response magnitude across tested factor levels. Direction and physical interpretation are discussed in the text with reference to the underlying level means.
Wall thickness produced an overheating span of 172.6 h, compared with 131.7 h for WWR, a difference of 40.9 h. The wall response reflects delayed heat transfer across the tested thickness levels, while the WWR response combines solar and conductive exchange across the glazing levels. The numerical comparison directly establishes their relative response ranges within the 120-scenario design.
These span comparisons carry uncertainty intervals from a residual bootstrap with 5000 resamples on a fixed design matrix. The 40.9 h difference between the wall-thickness and WWR overheating spans has a 95% interval of 16.4 to 65.3 h, which excludes zero. The pairwise span differences within the leading group are 0.6, 2.3, and 1.7 h for wall thickness, high side-window ratio, and green coverage, and all three intervals include zero, so the leading group is reported as one numerically close set rather than as an ordered ranking. Supplementary Table S6 Panel A and Figure 6 report the intervals.
High side-window ratio and green coverage produced overheating spans of 172.0 and 170.3 h. Together with wall thickness, these values define the leading group, whose pairwise differences are indistinguishable from zero by the bootstrap intervals. Elevated openings alter buoyancy-supported exchange, while vegetation changes shading and evapotranspiration. H/W and opening ratio followed with spans of 158.7 and 148.9 h, showing that enclosure and exposure remain material controls below the leading group.
Opening ratio produced the largest ACH span at 1.6 h−1. High side-window ratio, H/W, and solar absorptance each produced 1.2 h−1 spans, while WWR produced 1.0 h−1. Solar absorptance showed an overheating span of 79.0 h across the tested 0.30–0.90 range. The selected value of 0.80 belongs to the joint P04 compromise and carries no standalone cooling attribution.
Winter heating demand was most responsive to wall thickness at 18.9 kWh m−2, thermal conductivity at 17.3 kWh m−2, opening ratio at 16.5 kWh m−2, and WWR at 16.3 kWh m−2. These spans place storage, conduction, and controllable exposure at the center of the winter response.
Annual EUI produced its largest span for wall thickness at 15.7 kWh m−2, followed by WWR at 14.5 kWh m−2. Opening ratio and thermal conductivity each produced 11.9 kWh m−2, and solar absorptance produced 10.8 kWh m−2. Annual EUI therefore enters the post-Pareto selection as a fourth decision dimension that captures the combined seasonal energy response.

4.3. Non-Dominated Solutions and Selected Parameter Set

Direct EnergyPlus and Fluent evaluation of 50 screened candidates produced ten solutions that were non-dominated for overheating, heating demand, and ACH within that direct set. Figure 7a displays their direct outcomes and marks P04. Figure 7b shows the four normalized P04 objectives used in compromise selection. Supplementary Table S12 reports the complete fifty-candidate set, and the reported Figure 7 and Supplementary Table S5 values contain no screening-function predictions.
Figure 7. Directly simulated candidate trade-offs and P04 selection. (a) Ten solutions that are non-dominated among 50 candidates re-evaluated with EnergyPlus and Fluent; color represents direct-simulation ACH and the star marks P04. (b) P04 normalized overheating, heating demand, inverted ACH, and annual EUI values used to calculate d_ideal = 0.7987.
P04 retained compact courtyard geometry with L/W = 1.4, H/W = 0.85, and a 10% courtyard opening ratio. Its envelope used a 600 mm wall, conductivity of 0.60 W m−1 K−1, and exterior-wall solar absorptance of 0.80. The 10% WWR remained at the reference value, while all tested operable window area was assigned to the high side and the inlet-to-outlet area ratio remained 1:1.
The vegetation variables in P04 were 50% green coverage, 7.5 m tree height, and LAI = 5.0. These values complete the 12-variable vector and describe the selected compromise under the stated objectives and bounds. Table 7 reports their reference and tested ranges, while Supplementary Table S5 links the vector to direct outcomes and normalized values. Green coverage lies between 41 and 50% in all ten non-dominated solutions, six of them at the 50% tested maximum and the other four between 41 and 49%. The whole set therefore falls in the top fifth of the tested 0 to 50% range. No objective penalizes higher coverage and no constraint limits it, so nothing in the search pushes the variable down, and the 50% of P04 is the highest level the search can reach while irrigation carries no price.
Table 7. Baseline, tested range, and P04 value for the 12 design variables.
P04 yielded 972 h of overheating, 134.5 kWh m−2 winter heating demand, 10.2 h−1 ACH, and 120.8 kWh m−2 annual EUI, with d_ideal = 0.7987. The four normalized components are 0.4857, 0.2049, 0.6000, and 0.0000, obtained by min–max normalization over the extremes of the ten direct solutions with ACH inverted, and the distance is the square root of the sum of their squares. P08 and P09 followed at 0.8409 and 0.8747. An independent rerun of P04 reproduced the four outcomes within 0.23%, 0.45%, 0.98%, and 0.58%.
The reference annual EUI of 218 kWh m−2 is the modeled total of the existing prototype dwelling with its documented envelope and systems, itemized in Supplementary Table S13. P04 reduces this value to 120.8 kWh m−2, corresponding to 44.6%. This percentage describes the complete selected vector relative to the stated reference and is separate from any single-factor span or wall-only comparison.

4.4. Wall-Thickness Threshold and Thermal-Inertia Response

The wall sweep separates a tested threshold, the existing assembly, and the selected design. The thermal inertia index D is a periodic thermal-storage indicator of the complete assembly. Every D value in this study comes from the same computational procedure as the wall-thickness sweep, so the values are directly comparable across assemblies, and Supplementary Table S15 records that procedure as a layer-sum definition, together with the layer inputs of every assembly evaluated. At 500 mm, thermal lag = 4.2 h, making it the first tested thickness with a lag above 4 h, and D = 6.2. The 520 mm baseline has D = 6.5, lag = 5.1 h, overheating = 965 h, and heating demand = 159 kWh m−2. The 600 mm P04 wall has D = 7.9, lag = 6.5 h, overheating = 902 h, and heating demand = 147 kWh m−2.
Across the sweep, overheating fell from 1252 h at 300 mm to 988 h at 500 mm, 965 h at 520 mm, 938 h at 550 mm, and 902 h at 600 mm. Heating demand changed from 228 to 162, 159, 158, and 147 kWh m−2 at the same thicknesses. The 520–600 mm wall comparison therefore yields reductions of 63 overheating hours and 12 kWh m−2 heating demand. These values describe the wall sweep and remain separate from the integrated P04 effect.
Figure 8d compares the outdoor dry-bulb maximum of 41.2 °C at 14:00 with the 520 mm indoor operative-temperature maximum of 37.7 °C at 18:00, producing an approximately 4 h peak shift. The tested 500–550 mm band has lags of 4.2–5.7 h and supports the broader approximate 4–6 h design interpretation. The selected 600 mm wall is reported separately at 6.5 h.
Figure 8. Wall-thickness and thermal-inertia evidence. (a) Thermal inertia index across 300–700 mm. (b) Thermal lag and the tested threshold. (c) Summer overheating and winter heating demand. (d) Representative-day outdoor, 300 mm indoor, and 520 mm indoor temperatures. The outdoor maximum is 41.2 °C at 14:00 and the 520 mm indoor maximum is 37.7 °C at 18:00, giving a 4 h shift. (e) Heating-demand reduction relative to 300 mm. (f) The 20 + 480 + 20 mm baseline and 20 + 560 + 20 mm selected assemblies.

4.5. Fenestration, Ventilation, and Vegetation

The ventilation and vegetation responses in this section come from dedicated single-factor sweeps in which the remaining eleven factors stay at their Table 4 baseline values, reported in Supplementary Tables S8 and S10. This scope differs from the marginal means of the 120-scenario design, which average over the other eleven factors and therefore produce smaller amplitudes, so the two sets of magnitudes are not interchangeable.
Moving the tested operable area to the high side raises ACH from 6.0 h−1 in the single-sided baseline to 11.7 h−1 at a 100% high side-window ratio, while ventilation effectiveness rises from 0.45 to 0.75. The relative gain of 66.7%, approximately 67%, is accompanied by an ensemble range of 55% to 77% across eight summer representative-day cases and a conservative ensemble mean of about 65%. Ventilation effectiveness is the air change efficiency ηa = τn/(2 × mean age of air), for which fully mixed flow gives 0.5 and plug flow gives 1.0 [31], and the single-sided baseline value of 0.45 lies below the fully mixed value in the pattern of short-circuit flow. This benefit applies when windows are open and the high-level openings can use buoyancy and pressure differences, and seasonal closure is required to control winter losses.
Vegetation produces a graded response relative to the 0% unplanted case across the tested 0–50% coverage range. At 30% coverage, courtyard air temperature falls by approximately 2.4 °C and relative humidity rises by 5.8 percentage points. At 40% coverage the reduction reaches about 3.0 °C, and at the 50% bound it reaches approximately 3.5 °C with a humidity rise of 8.1 percentage points. Courtyard temperature and humidity are volume-averaged over the courtyard air volume between 1.0 and 4.5 m above ground and time-averaged over 14:00 to 18:00 from June to August. The same sweep fixes the cost of a water-constrained design. Moving from 50% to 30% coverage returns two fifths of the planted area and adds 69 overheating hours, from 896 to 965 h, while the courtyard air temperature reduction falls from 3.5 to 2.4 °C.
Tree height and leaf area index refine this coverage effect. A 7.5 m canopy provides additional shade for the single-story courtyard, while LAI = 5.0 increases latent heat flux with diminishing returns above approximately 5. These gains are conditional on afternoon water availability and plant maintenance. Morning humidity effects are smaller, and water scarcity limits transfer of the 50% coverage case to every site. Irrigation scales with the planted area on the same courtyard plan of 26.1 m2. The 50% coverage of P04 carries a seasonal irrigation demand of 8.81 m3 over June to August, about 96 L per day, against 7.05 m3 at 40% and 5.28 m3 at 30%, and Supplementary Table S19 derives these volumes from the reference evapotranspiration of the Tashkent record.

4.6. Integrated Courtyard Performance

Across the studied configurations, courtyard form, envelope mass, controlled openings, and vegetation affect different spatial and seasonal outcomes. The factor analysis identifies their response spans, while the directly simulated P04 vector integrates the selected values. P04 combines limited glazing and opening exposure with thermal mass, high-level operable windows, and vegetation, producing 972 overheating hours, 134.5 kWh m−2 heating demand, 10.2 h−1 ACH, and 120.8 kWh m−2 annual EUI.
Indoor and courtyard outcomes also operate at different spatial scales. Courtyard temperature reflects shade, exposed surfaces, air exchange, and latent cooling within the central void. Indoor temperature amplitude reflects delayed transfer through the enclosing mass and exchange through room openings. Annual EUI integrates these local effects with winter heating and the weather-year schedule. The agreement in performance direction across these scales supports the integrated interpretation, while their different denominators prevent direct numerical addition.
The combined results answer the research question through a hierarchy of controls and a verified compromise. Wall thickness, high side-window ratio, and green coverage lead the overheating response. Opening ratio controls the largest ACH span and remains constrained by seasonal thermal exposure. The P04 vector reduces annual EUI by 44.6% relative to the 218 kWh m−2 reference within the tested design and direct candidate set.

5. Discussion

5.1. Thermal Mass Under Large Diurnal Temperature Ranges

Massive envelopes work under continental conditions because the phase delay they impose separates the outdoor temperature peak from the indoor heat load. Heat stored in the wall during the afternoon reaches the interior after the outdoor maximum has passed, which shortens the coincidence of high indoor temperature with high outdoor temperature. In the tested sweep this mechanism becomes available at 500 mm, the first thickness with a lag above 4 h, and it strengthens toward 6.5 h lag at the selected 600 mm wall. The direction and magnitude agree with experimental and simulation evidence that high-inertia envelopes damp diurnal amplitude and delay peak transfer in comparable climates [11,12].
The distinction between threshold, existing construction, and selected wall carries the design content. The existing 520 mm assembly already lies above the threshold at 5.1 h lag, with D = 6.5, and the step to 600 mm buys 63 overheating hours and 12 kWh m−2 heating demand relative to it. The response flattens toward the upper tested range, so contemporary assemblies should target the required storage and delay rather than maximize thickness, and the flattening also bounds what any further thickness increase can contribute [11,12].

5.2. Courtyard Proportion and the Shading-Ventilation Trade-Off

L/W and H/W control different physical pathways, which is why the geometry response cannot be reduced to one size measure. L/W sets the length of the solar path and the wind route across the court, so elongation lengthens morning and afternoon exposure along one axis. H/W sets enclosure depth, sky view, and the resistance of cross-courtyard flow, so deeper courts shade more but exchange less. The selected values of L/W 1.4 and H/W 0.85 remain close to the documented regional proportions of 1.14 to 1.40 because the compact inward-oriented form already balances these pathways.
The shading-ventilation conflict concentrates in H/W and opening ratio. Raising exposure raises the ACH span to 1.6 h−1 while also raising overheating, heating demand, and annual EUI, and the same opposition appears in hot-arid courtyard studies where continuously open courts trade airflow against solar gain [7,9,10,14,15,16,17,18,19]. Continental winters break the tie toward operability, because the opening that supports summer flushing must close airtightly in winter. The selected 10% opening ratio with seasonally closable elements represents this controlled exchange.

5.3. Fenestration as a Controllable Airflow System

High and low openings drive different branches of the airflow path. Wind-driven pressure differences dominate at low level, the temperature difference between the court and rooms drives buoyancy at high level, and the two branches compound when inlets and exhausts are vertically separated. Assigning the tested operable area entirely to the high side raises ACH from 6.0 to 11.7 h−1 without adding glazing, because WWR stays at 10% and only the vertical distribution changes. The gain requires open windows and a pressure path established by geometry, so seasonal closure remains necessary to control winter losses.

5.4. Vegetation, Evaporative Cooling, and Resource Boundaries

Vegetation cools the courtyard through two fluxes with different resource costs. Canopy shading intercepts radiation before it reaches ground and wall surfaces, and evapotranspiration converts sensible heat into latent heat at a rate set by the water supply. The coverage response of approximately 2.4 to 3.5 °C with a humidity rise of 5.8 to 8.1 percentage points follows this dual mechanism, and the diminishing returns approximately above the LAI 5 mark the saturation of the interception and transpiration fluxes. The water boundary is therefore part of the strategy, because irrigation demand, species tolerance, and maintenance capacity determine where the 50% coverage case can be implemented [13,16,17,18]. The four objectives of Table 5 carry no water term, so irrigation demand shaped neither the search nor the compromise rule. Pricing irrigation as a fifth objective, or capping coverage at a locally supportable value, would both penalize the upper end of the tested range and move the distance rule toward a lower-coverage member of the ten directly simulated solutions. The coverage of a built design should therefore follow the local water budget, and the 50% of P04 stands as the highest level the tested range allows.

5.5. Regional Typology, Numerical Values, and Literature Position

The selected parameter set retains the climatic logic of the documented courtyards while adjusting several values for the stated objectives. Inward orientation, compact proportion, massive enclosure, limited glazing, high-level openings, and vegetation remain continuous with the regional examples. The precise values of 1.4 for L/W, 0.85 for H/W, 600 mm for wall thickness, and 50% for green coverage arise from the tested model and should not be treated as historical averages.
This distinction supports performance-based translation. Typological evidence identifies spatial relationships and feasible material practices. Level-wise analysis estimates factor responses across the 120 scenarios. NSGA-II screening prioritizes candidate combinations, direct simulation supplies the reported outcomes, and the normalized distance rule identifies P04 within the verified set. Each stage therefore contributes a distinct part of the design argument.
Cross-study comparison at the direction level supports the leading-group pattern. A survey of ten courtyard houses in Kerman reports plan ratios of 1.14 to 1.99 with shading performance improving as the ratio decreases [10], which matches the direction of the L/W response here. A parametric study of Hotan (also romanized Khotan) earth dwellings finds interior wall thickness to be the largest single-parameter contributor to indoor temperature change at 1.30 °C [14], consistent with wall thickness leading the overheating spans in Table 6. Baghdad simulations classify courts by height-to-width ratios from 0.1 to above 1.0 and identify courtyard width as the controlling variable for night ventilation [16], which parallels the H/W trade-off in this study. Water spray cases lower courtyard air temperature by 2.06 °C with a 4.29 percentage-point humidity rise under single-sided ventilation [18], the same cooling-humidification pairing as the vegetation response. The four studies measure different quantities with different models and boundaries, so the comparison is restricted to direction and carries no magnitude claim, with the cell-level sources recorded in Supplementary Table S11.
The same distinction clarifies where contemporary technology enters the design. Sensors and controls can schedule high-level openings, irrigation, or shading in response to weather and occupancy, but they do not create the thermal storage or pressure paths reported here. Materials can reproduce the time-lag function of thick masonry with a different assembly, but equivalence requires testing the D value, moisture response, and durability. Modern translation therefore begins from the measured function of each regional strategy and evaluates alternative means within local construction and resource constraints.

5.6. Transferability and Limitations

Transfer to contemporary construction depends on reproducing thermal storage rather than appearance. Three contemporary assemblies, evaluated with the same procedure as the wall sweep—a 200 mm reinforced concrete wall with 50 mm insulation, the same concrete with 100 mm insulation, and a 200 mm concrete-block wall with 100 mm insulation—reach D values of 2.3, 2.8, and 2.8, all below the 6.2 of the 500 mm threshold wall and the 6.5 of the existing 520 mm assembly. Equivalent performance therefore requires composite construction or added effective storage, and any candidate assembly must pass checks on thermal inertia, moisture transfer, durability, and constructability before the lag-based conclusions carry over. Supplementary Table S15 reports the assembly data.
Transfer across Central Asian climate subtypes changes specific mechanisms rather than the factor set. At stations with warmer nights, stored heat releases less effectively and the lag benefit shrinks. Where winters are colder or windier, the same opening exposure admits larger losses and requires lower opening ratios. Where humidity is higher, the evaporative component of the vegetation response weakens. Each condition requires repeating the workflow with the local weather file, and the geographic distance between the prototype in Bukhara Region and the Tashkent reference station belongs to this weather-file dependence.
The evidence supports a staged application with explicit checks. Early massing uses L/W and H/W to protect shade and airflow paths. Envelope design tests whether a proposed assembly reaches the target lag with acceptable heating demand. Opening design keeps total glazing limited and places operable exhausts high in the room-to-court connection. Landscape design starts from 30% coverage and increases planting only after irrigation, humidity, and maintenance constraints are checked. Supplementary Table S16 lists the twelve factors by design stage with their supported ranges and required transfer checks. The 69 overheating hours between 30% and 50% coverage set the performance price of that check.
The conclusions remain bounded by the supplied case geometry, monitoring basis, weather files, schedules, and factor ranges. The 120-scenario design estimates level-wise main effects under the residual association quantified in Section 3.3; higher-order interactions require a dedicated design, and the direct results cover the 50 re-simulated candidates with alternative objective weights able to select a different member of the verified set. CFD validation supports comparative airflow tendencies, and indoor-temperature validation supports passive comparisons without substituting for metered-energy checks in mechanically conditioned buildings. Multi-story courts alter both H/W and buoyancy paths beyond the single-story prototype. Roof insulation and glazing solar heat gain coefficient held the documented values of Table 3 throughout, so the results carry no estimate of how either would change overheating hours, heating demand, air change rate, or annual energy use intensity. The courtyard boundary values of the annual run resolve the summer afternoon and winter pre-dawn hours at the hour and carry the nearest solved state of the assigned representative day elsewhere, so the annual heating demand and energy use intensity inherit the time resolution of that mapping.

6. Conclusions and Future Work

This study quantified how inward-oriented courtyard form, envelope construction, window layout, and vegetation regulate performance under Central Asian continental climates. The balanced mixed-level near-orthogonal design showed a 172.6 h overheating span for wall thickness, 172.0 h for high side-window ratio, 170.3 h for green coverage, and 131.7 h for the WWR. Wall thickness therefore exceeded the WWR span by 40.9 h, while opening ratio produced the largest ACH span at 1.6 h−1.
The two-stage optimization separated rapid search from reported performance. A level-wise main-effects function screened 3000 NSGA-II candidates, 50 candidates received direct EnergyPlus and Fluent evaluation, and ten were non-dominated among that direct set. Four-objective normalization selected P04 at d_ideal = 0.7987. Its 12-variable vector combined L/W = 1.4, H/W = 0.85, 10% courtyard opening, 600 mm wall, conductivity 0.60 W m−1 K−1, solar absorptance 0.80, WWR 10%, high side-window ratio 100%, inlet-to-outlet area ratio 1:1, green coverage 50%, tree height 7.5 m, and LAI = 5.0.
The wall evidence assigns distinct roles to three thicknesses. The 500 mm point is the first tested thickness with a lag above 4 h, at D = 6.2. The existing 520 mm wall has D = 6.5 and lag = 5.1 h, while the selected 600 mm wall has D = 7.9 and lag = 6.5 h. The representative-day outdoor-to-520 mm indoor peak shift is 4 h, and the 500–550 mm lag band of 4.2–5.7 h supports an approximate 4–6 h design range. These lag values transfer only where the local assembly reaches a comparable thermal inertia index, which contemporary constructions must verify by testing.
P04 produced 972 overheating hours, 134.5 kWh m−2 heating demand, 10.2 h−1 ACH, and an annual EUI of 120.8 kWh m−2. The annual value is 44.6% below the 218 kWh m−2 reference. These outcomes apply to the stated geometry, weather, operation, factor bounds, and 50 directly evaluated candidates. The 50% green coverage of that vector is the highest tested level, reached under an objective set that carries no water cost.
Future work can test the selected combination in occupied buildings, extend monitoring across Central Asian subregions, and add interaction, economic, and life-cycle objectives. Repeating the direct-evaluation stage under local weather, construction, water, and operating conditions would show how the selected compromise changes across projects.

Supplementary Materials

The following supporting information can be downloaded at https://www.mdpi.com/article/10.3390/buildings16203999/s1. The separate Supplementary Material provides the complete evidence chain of the study. Figure S1 records the two-stage workflow. Table S1 summarizes the wall threshold and representative-day peak shift. Table S2 maps architectural, CFD, and EnergyPlus zones. Table S3 reports all 120 scenarios. Table S4 reports level-wise means and dispersions. Table S5 reports the ten non-dominated solutions and P04 selection. Table S6 reports factor-span intervals and design diagnostics. Table S7 reports the monitoring metadata and paired series. Table S8 reports the ventilation and opening sweep. Table S9 reports the screening-function definition and deviation statistics. Table S10 reports the vegetation coverage and LAI sweep. Table S11 reports the literature comparison. Table S12 reports the fifty directly evaluated candidates. Table S13 reports the reference-case energy baseline. Table S14 reports the CFD discretization and convergence record. Table S15 reports the contemporary assembly comparison. Table S16 reports the staged design guidance. Table S17 reports the coupling protocol of Section 3.2.3 and the convergence record of its outer loop. Table S18 reports the solar absorptance carried by each surface group in each solver. Table S19 reports the seasonal irrigation demand of the tested coverage levels. Table S20 reports the wall-thickness sweep with its layer inputs, thermal resistance, thermal inertia index, and thermal lag. Supplementary Figure S1. Two-stage candidate screening, direct EnergyPlus and Fluent verification, three-objective Pareto filtering, and four-objective P04 compromise selection. Supplementary Table S1. Wall-threshold states and representative-day peak timing Supplementary Tables S2–S20 are provided in the separate Supplementary Material file.

Author Contributions

L.Y.: Writing—Original Draft, Writing—Review and Editing, Data, Formal Analysis, Software; Y.X.: Methodology; Z.Y.: Methodology, Review, Analysis. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Innovative Construction of Central Asian Library and Information Service System in Xi’an under the Belt and Road Initiative, grant number 25YZ20; the Construction and Access of Central Asian Urban Architectural and Cultural Documentation Resources, grant number 2024KTP-28; Shaanxi Province Social Science Foundation Project “Research on the Multicultural Historical Value of Shaanxi Great Wall Fortress Architecture”, grant number 2022J051; and Shaanxi Provincial Department of Education General Special Project “Research on the Rise and Fall of Hancheng Fortress Architecture and Its Multicultural Historical and Cultural Value”, grant number 22JK0107.

Institutional Review Board Statement

Not applicable.

Data Availability Statement

The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.

Acknowledgments

The authors sincerely thank the University of Architecture and Technology in Xi’an for its support. We also appreciate the research team members who contributed to CFD model development and field data collection. AI-assisted language polishing was used to improve clarity and readability during manuscript preparation. The authors reviewed and approved all revised text and remain fully responsible for the research design, data collection, data analysis, scientific interpretation, and manuscript content.

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

ACHAir change rate per hour
AEAir change efficiency
BEMBuilding energy modeling
BWkCold desert (Köppen–Geiger)
CFDComputational fluid dynamics
CsaHot-summer Mediterranean (Köppen–Geiger)
DThermal inertia index
DfbHumid continental, warm summer (Köppen–Geiger)
DsaContinental, hot dry summer (Köppen–Geiger)
DsbContinental, warm dry summer (Köppen–Geiger)
EUIAnnual energy use intensity
GHIGlobal horizontal irradiation
H/WEnclosure height-to-courtyard-width ratio
HDWinter heating demand
L/WCourtyard plan length-to-width ratio
LAILeaf area index
MAEMean absolute error
NSGA-IINon-dominated sorting genetic algorithm II
OHSummer overheating hours
RHRelative humidity
RMSERoot mean square error
SBXSimulated binary crossover
TMYTypical meteorological year
TMYxTypical meteorological year (expanded reference period)
WWRWindow-to-wall ratio
y+Dimensionless wall distance in the log-law region

References

  1. Lioubimtseva, E.; Henebry, G.M. Climate and environmental change in arid Central Asia. J. Arid. Environ. 2009, 73, 963–977. [Google Scholar] [CrossRef] [Scilit]
  2. International Energy Agency. Energy Statistics for Central Asia; IEA: Paris, France, 2021. [Google Scholar]
  3. Ganiyeva, A. Traditions of house building in Kazakhstan: Archaeological perspective on the evolution of dwellings. Gumilyov J. Hist. 2025, 152, 48–67. [Google Scholar] [CrossRef] [Scilit]
  4. Knobloch, E. The Archaeology and Architecture of Afghanistan; Tempus Publishing: Stroud, UK, 2001. [Google Scholar]
  5. Pugachenkova, G.A. Architecture of Central Asia in the Middle Ages; Academy of Sciences USSR: Tashkent, Uzbekistan, 1958. [Google Scholar]
  6. Lechner, N. Heating, Cooling, Lighting: Sustainable Design Methods for Architects, 4th ed.; John Wiley & Sons: Hoboken, NJ, USA, 2015. [Google Scholar]
  7. Liu, S.; Sailor, D.J.; Fang, X.S.; Wu, R.Z. The role of outdoor courtyard design variables in microclimate performance: A review. Archit. Sci. Rev. 2024, 68, 224–239. [Google Scholar] [CrossRef] [Scilit]
  8. Nyasha, B.; Bertug, O. Bibliometric review of passive cooling design strategies and global thermal comfort assessment: Theories, methods and tools. Sustainability 2024, 16, 9629. [Google Scholar] [CrossRef] [Scilit]
  9. Tablada, A.; De Troyer, F.; Blocken, B.; Carmeliet, J.; Verschure, H. On natural ventilation and thermal comfort in compact urban environments. Build. Environ. 2009, 44, 1943–1958. [Google Scholar] [CrossRef] [Scilit]
  10. Soflaei, F.; Shokouhian, M.; Abraveshdar, H.; Alipour, A. The impact of courtyard design variants on shading performance in hot-arid climates of Iran. Energy Build. 2017, 143, 71–83. [Google Scholar] [CrossRef] [Scilit]
  11. Stazi, F.; Mastrucci, A.; di Perna, C. The behaviour of solar walls in residential buildings with different insulation levels: An experimental and numerical study. Energy Build. 2012, 47, 217–229. [Google Scholar] [CrossRef] [Scilit]
  12. Zhai, Z.; Previtali, J.M. Ancient vernacular architecture: Characteristics categorization and energy performance evaluation. Energy Build. 2010, 42, 357–365. [Google Scholar] [CrossRef] [Scilit]
  13. Shashua-Bar, L.; Hoffman, M.E. Vegetation as a climatic component in the design of an urban street: An empirical model for predicting the cooling effect of urban green areas with trees. Energy Build. 2000, 31, 221–235. [Google Scholar] [CrossRef] [Scilit]
  14. Li, M.; Yang, L.; Liu, Y.; Qiao, Y.; Zhu, X.; Cao, Q. Passive design patterns for Hotan earth buildings under hot-arid climatic conditions of the Taklamakan Desert. Energy Build. 2025, 349, 116546. [Google Scholar] [CrossRef] [Scilit]
  15. El Bat, A.M.; Romani, Z.; Bozonnet, E.; Draoui, A.; Allard, F. Optimizing urban courtyard form through the coupling of outdoor zonal approach and building energy modeling. Energy 2023, 264, 126176. [Google Scholar] [CrossRef] [Scilit]
  16. Khan, H.M.; Lane-Serff, G.F.; Dewsbury, J. Optimizing the design of courtyard houses for passive cooling in hot, dry regions. J. Build. Perform. Simul. 2023, 16, 231–247. [Google Scholar] [CrossRef] [Scilit]
  17. Darvish, A.; Eghbali, G.; Eghbali, S.R. Tree-configuration and species effects on the indoor and outdoor thermal condition and energy performance of courtyard buildings. Urban Clim. 2021, 37, 100861. [Google Scholar] [CrossRef] [Scilit]
  18. Sun, H.; Zhong, H.; Dik, A.; Ding, K.; Jimenez-Bescos, C.; Calautit, J.K. Numerical investigation of evaporative cooling strategies on the aero-thermal performance of courtyard buildings in hot-dry climates. Build. Environ. 2024, 258, 111588. [Google Scholar] [CrossRef] [Scilit]
  19. Zamani, Z.; Heidari, S.; Hanachi, P. Reviewing the thermal and microclimatic function of courtyards. Renew. Sustain. Energy Rev. 2018, 93, 580–595. [Google Scholar] [CrossRef] [Scilit]
  20. Deb, K.; Pratap, A.; Agarwal, S.; Meyarivan, T. A fast and elitist multiobjective genetic algorithm: NSGA-II. IEEE Trans. Evol. Comput. 2002, 6, 182–197. [Google Scholar] [CrossRef] [Scilit]
  21. Blocken, B.; Stathopoulos, T.; Carmeliet, J. CFD simulation of the atmospheric boundary layer: Wall function problems. Atmos. Environ. 2007, 41, 238–252. [Google Scholar] [CrossRef] [Scilit]
  22. Blocken, B. 50 years of Computational Wind Engineering: Past, present and future. J. Wind Eng. Ind. Aerodyn. 2015, 129, 69–102. [Google Scholar] [CrossRef] [Scilit]
  23. Ruiz, G.R.; Fernández Bandera, C. Validation of calibrated energy models: Common errors. Energies 2017, 10, 1587. [Google Scholar] [CrossRef] [Scilit]
  24. Erell, E.; Pearlmutter, D.; Williamson, T. Urban Microclimate: Designing the Spaces Between Buildings; Earthscan: London, UK, 2011. [Google Scholar]
  25. Jiang, L.; Yi, Y.H.; Akdeniz, N. Energy-saving cooling strategies in tunnel-ventilated dairy buildings: Computational fluid dynamics (CFD) simulations and validation. Smart Agric. Technol. 2024, 9, 100576. [Google Scholar] [CrossRef] [Scilit]
  26. Moediartianto, A.; Montazeri, H.; Blocken, B. On the use of UAV-thermal imaging for CFD validation of urban thermal microclimate. Sustain. Cities Soc. 2025, 136, 106968. [Google Scholar] [CrossRef] [Scilit]
  27. Prataviera, E.; De Carli, M. A review on outdoor urban environment modelling. J. Phys. Conf. Ser. 2024, 2893, 012024. [Google Scholar] [CrossRef] [Scilit]
  28. Quang, T.V.; Doan, D.T.; Phuong, N.L.; Yun, G.Y. Data-driven prediction of indoor airflow distribution in naturally ventilated residential buildings using combined CFD simulation and machine learning (ML) approach. J. Build. Phys. 2024, 47, 439–471. [Google Scholar] [CrossRef] [Scilit]
  29. Huang, W.H.; Xu, Q.F.; Zhao, B.L.; Lv, Q.; Wang, G.Y. Urban multi-scale building energy modeling (BEM) and computational fluid dynamics (CFD) integration: Tools, strategies and accuracy for energy microclimate analysis. J. Build. Eng. 2025, 103, 112041. [Google Scholar] [CrossRef] [Scilit]
  30. Hao, S. Multidimensional Analysis of Courtyard Building Environmental Performance Using Computational Fluid Dynamics. Ph.D. Thesis, University of Nottingham, Nottingham, UK, 2024. [Google Scholar]
  31. Sandberg, M. What is ventilation efficiency? Build. Environ. 1981, 16, 123–135. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.