Abstract

The accurate prediction of electric-field magnitude in high-voltage transmission lines under symmetrical power-system conditions is of great significance for transmission-line safety assessment. By quantifying the spatiotemporal distribution characteristics of the transmission-line electric field, it provides a scientific basis for evaluating system equipment reliability, operational stability, fault risks, and personnel safety. Traditional numerical methods face limitations in computational efficiency and real-time performance, while pure data-driven deep learning methods lack the guarantee of physical constraints. To address this issue, an Adaptive Physics-Informed Neural Network (APINN) framework is proposed. This framework adopts an independent dual-network architecture, decoupling the main prediction network from the physical sub-network to avoid the interface loss problem of traditional PINNs. Meanwhile, a 15-dimensional input feature system is constructed from query coordinates, known conductor geometry, and applied voltages, and a clustering-driven adaptive sampling strategy is proposed to handle the data imbalance in high-field regions. Furthermore, a three-stage adaptive weight scheduling mechanism is designed to achieve a dynamic balance between data fitting and physical constraints. To comprehensively evaluate the performance of the proposed surrogate model (APINN), a typical 500 kV transmission line tower–conductor system operating under symmetrical three-phase conditions was selected as the benchmark testing scenario. The results show that APINN exhibits reasonable performance in prediction accuracy and physical consistency, while maintaining high computational efficiency.

1. Introduction

Electric-field calculations support electrical-stress analysis in power systems [1]. Traveling-wave partial-discharge localization and temporary-overvoltage studies address related needs in insulation diagnosis and abnormal voltage assessment [2,3]. Around overhead AC lines, the conductor configuration influences the spatial field distribution [4]. This study focuses on predicting the three-dimensional electric-field magnitude around a tower–conductor system at a specified operating snapshot under balanced three-phase conditions.
Han and Chen [5] used a boundary element model to examine how conductor arrangement, height, and bundle spacing affect near-ground power-frequency fields. To calculate the field around a tower, El Dein [6] combined charge simulation with the method of images and explicitly represented charges induced on the tower. Fathy et al. [7] applied charge simulation to bipolar HVDC lines. In these charge-simulation models, accuracy depends on how well the equivalent charges reproduce the prescribed boundary conditions.
The finite element method (FEM) accommodates complex geometries and boundary conditions, although local mesh refinement increases the size of the discrete system [8]. It is used here to generate reference field values. For transient problems, explicit finite-difference time-domain schemes are subject to grid-dependent time-step limits [9], and Bérenger’s perfectly matched layer reduces reflections at truncated boundaries [10]. Where a surface integral formulation is available, the method of moments can limit discretization to surfaces but generally yields dense matrices [11]. An existing FEM solution can be reused for field-value extraction. The benefit of a surrogate therefore depends on its offline construction cost and subsequent query demand.
A trained neural network can approximate nonlinear mappings through forward evaluations [12,13]. Hamid et al. [14], for example, used a learned reduced-order model to support repeated evaluation of power-grid dynamics. A fit to numerical data alone leaves the governing equations unenforced [15]. Raissi et al. [16] addressed this by including differential-equation residuals in the training objective. The resulting physics-informed formulation depends on the governing problem and the constraints imposed during training [17].
Power-system applications illustrate how the prediction target shapes those constraints. Stiasny and Chatzivasileiadis [18] assessed accuracy and cost in predicting responses to load disturbances. Shen et al. [19] incorporated induction-machine dynamics into a learning model, while Ngo et al. [20] combined physical state estimation with a graph neural network. For spatial field prediction, the corresponding question is which electromagnetic variable can connect the governing equation to the desired output.
Brendel et al. [21] used magnetic vector potential to derive inductance and coupling for axisymmetric transformers, illustrating how a learned potential can be linked to a target quantity. Eddy-current analysis [22] and forward modeling of material discontinuities [23] require formulations suited to their respective physical regimes. When the interface location is unknown, Piao et al. [24] treated it as an inverse variable and included interface conditions in the loss. For the present transmission-line problem, the required link is between the electric potential and the scalar field magnitude.
Training performance also depends on sample placement and loss weighting. Jagtap and Karniadakis [25] used domain decomposition to allow different approximations across subdomains, while Gao et al. [26] added residual-guided collocation points in difficult regions. Here, the sampling question is how to cover high-field regions with a fixed number of labeled field samples. Xiang et al. [27] and Bischof and Kraus [28] developed adaptive loss-balancing methods, and Farhani et al. [29] examined differences in convergence between equation and initial or boundary losses. These studies motivate examining the role of the equation-residual weight during training.
Three issues follow for the present task. First, strong near-conductor field variation makes both geometric representation and high-field sample coverage important. Second, Gauss’s law constrains the electric-field vector, while the target is its scalar magnitude. Third, the equation-residual weight must be set alongside the data-fitting, magnitude-consistency, and boundary terms during joint training.
To address these issues, we propose an Adaptive Physics-Informed Neural Network (APINN) with separate networks for field magnitude and electric potential. The potential network is constrained by the Laplace equation in homogeneous, charge-free air and by prescribed boundary potentials. A differentiable loss matches the predicted field magnitude to the norm of the potential gradient at the same location. Geometry-enhanced inputs describe the locations of query points relative to the conductors, and cluster-based sampling improves high-field coverage within a fixed supervised-sample budget. The equation-residual weight is introduced gradually, adjusted according to the loss ratio, and then held fixed. We evaluate the framework on a 500 kV tower–conductor benchmark through model comparisons and controlled ablations. Additional configurations are evaluated with separately trained models. The main innovations and contributions of this study are as follows.
  • An Adaptive Physics-Informed Neural Network (APINN) with an independent dual-network architecture and differentiable soft coupling is developed to separate the main prediction task from the auxiliary physical-variable representation.
  • A 15-dimensional input feature system is constructed from query coordinates, known conductor geometry, and applied voltages, avoiding the use of target Maxwell-derived field quantities as model inputs.
  • Cluster-based sampling and a three-stage equation-residual weighting schedule are incorporated, and their contributions are evaluated through direct learning-method benchmarks and controlled ablation experiments.

2. Physics-Constrained Surrogate Model for Rapid Electric Field Prediction

2.1. Theoretical Framework for Ultra-Large-Scale Multi-Magnitude Problems

The studied electric-field prediction problem is defined by a fixed tower–conductor geometry and specified operating conditions, with the task of predicting the electric-field magnitude at arbitrary spatial query locations. Let E ( r ) denote the electric-field vector in the three-dimensional domain. Under the electroquasistatic approximation, Gauss’s law is
∇ · ϵ E = ρ f ,
where ϵ is the permittivity and ρ f is the free volume-charge density. In the homogeneous, charge-free air region used for the physical residual, ρ f = 0 and ϵ is treated as constant.

2.2. Numerical Stability Design of the Independent Dual-Network Architecture

Traditional PINNs couple data fitting and physical constraints in a single network, which can make multi-objective optimization difficult when the loss terms have different scales and convergence behaviors. To separate the engineering prediction task from the auxiliary physical-variable representation, the proposed APINN retains two networks and connects them through a differentiable soft-coupling objective. Figure 1 shows the overall dual-network architecture.
Figure 1. APINN network architecture diagram.
For the same spatial position r , the main prediction network f θ : R 15 → R receives the paired feature vector z ( r ) and predicts the scalar electric-field magnitude
S ^ θ ( r ) = f θ z ( r ) .
The physical sub-network g ϕ : R 3 → R receives only the spatial coordinates and predicts the electric potential
V ^ ϕ ( r ) = g ϕ ( r ) .
The electric-field magnitude associated with the physical branch is obtained by automatic differentiation as
E ^ ϕ ( r ) = ∇ r g ϕ ( r ) 2 .
Thus, the two branches are coupled at the same spatial positions through magnitude consistency rather than by directly comparing electric-field magnitude with electric potential.
Training uses the unified soft-penalty objective
L = L d + λ p ( t ) L p + λ c L c + λ b L b ,
where the data-fitting, physical-equation, magnitude-consistency, and prescribed-potential boundary losses are respectively defined as
L d = 1 N d ∑ i = 1 N d f θ ( z i ) − S i ref E * 2 ,
L p = 1 N p ∑ j = 1 N p L * 2 V * ∇ r 2 g ϕ ( r j ) 2 ,
L c = 1 N c ∑ j = 1 N c f θ ( z j ) − ∥ ∇ r g ϕ ( r j ) ∥ 2 E * 2 ,
L b = 1 N b ∑ k = 1 N b g ϕ ( r k ) − V b ( r k ) V * 2 .
Here, N d , N p , N c , and N b are the corresponding batch sizes, L * and V * are characteristic length and potential scales, and E * = V * / L * . Spatial derivatives are evaluated in physical coordinates, with coordinate-normalization factors handled through the chain rule. The data-loss weight is fixed at one, the normalized magnitude-consistency and boundary-loss weights are set to λ c = λ b = 1.0 , and λ p ( t ) follows the three-stage schedule described in Section 2.6. Any additional boundary or interface conditions used in the reference electromagnetic model must be represented by the corresponding boundary loss. Point-set sizes, sampling relationships, and batch settings are reported in Section 3.1.
The two networks are jointly optimized at every training step. The data term directly updates the main network, the physical and boundary terms directly update the potential network, and the coupling term propagates gradients to both networks. The potential gradient is therefore evaluated while retaining the computational graph for back-propagation. The training scheme changes the relative loss weights over stages but does not alternate the optimization of the two networks. No additional hard consistency constraint with a threshold δ is imposed.

2.3. Physical Residual Calculation Based on Gauss’s Law

The main prediction network outputs the scalar electric-field magnitude rather than the electric-field vector. For a real-valued electric field at the specified operating snapshot, the prediction target is
S ( r ) = ∥ E ( r ) ∥ 2 .
Gauss’s law constrains the vector field E and therefore cannot be constructed by summing the three spatial derivatives of the scalar magnitude. To impose a physically valid constraint while retaining scalar-magnitude prediction, the physical sub-network outputs electric potential. Under the electroquasistatic approximation, the electric field is given by
E ( r ) = − ∇ r V ( r ) .
Substituting this relation into Gauss’s law gives
∇ r · ϵ ∇ r V + ρ f = 0 .
In homogeneous air with no free volume charge ( ρ f = 0 ) and constant permittivity, this reduces to
∇ r 2 V = 0 ,
which is the governing relation used to construct L p . The main network and the physical sub-network are linked through the magnitude-consistency relation
f θ ( z ( r ) ) ≈ ∇ r g ϕ ( r ) 2 .
The physical residual is applied only in regions satisfying the homogeneous-air and charge-free assumptions. Conductor surfaces and other boundaries are treated through the boundary conditions corresponding to the reference electromagnetic model. Consequently, training controls both the potential-equation residual and the field-magnitude consistency error, rather than interpreting derivatives of a scalar magnitude as electric-field divergence.
Although physics-informed neural networks incorporate governing equations into neural-network training, previous studies show that multi-objective optimization can be affected by imbalanced contributions of different loss terms and different convergence behaviors, thereby increasing optimization difficulty [28,29]. Accordingly, this study does not assume a fixed loss of prediction accuracy for the standard PINN; instead, the standard PINN is used as a direct learning baseline and compared with APINN under the same data split, computational platform, and evaluation procedure.

2.4. Feature Engineering for Multi-Magnitude Numerical Stability

The main prediction network uses six base inputs and nine geometric features. The spatial coordinates locate the query point, and the three phase voltages specify the conductor boundary potentials at the selected operating snapshot. The geometric features comprise the distances to the three phase-conductor centerlines, their inverse squares, and the coordinate products x y , y z , and x z . For an ideal infinite line charge, the field magnitude scales with inverse distance, while its radial rate of change in magnitude scales with inverse squared distance. This motivates the inverse-square features used to emphasize near-conductor variation. The coordinate products represent pairwise spatial interactions. Table 1 lists the feature definitions.
Table 1. The 15 input features.

2.5. Clustering-Driven Intelligent Sampling Strategy

The reference data are first divided into a training candidate pool, a validation set, and a test set. Standardization, K-means clustering, and cluster-based sampling are performed only within the training candidate pool, while the validation and test sets remain fixed across comparisons. Samples are allocated to clusters according to the supervised-sample budget. If a cluster contains insufficient samples, the remaining budget is redistributed to other valid clusters to preserve the total sample count. Dataset sizes, split ratios, and sampling settings are reported in Section 3.1.
To intuitively demonstrate the performance differences of different sampling strategies, Figure 2 compares random, uniform, and clustering sampling over the same evaluation range.
Figure 2. Performance evolution of sampling strategies and optimal parameter analysis.
Clustering variables are Z-score standardized using only the means and standard deviations of the training candidate pool to reduce the influence of different units and numerical ranges on Euclidean distance. Candidate cluster numbers are compared using the trend of the sum of squared errors (SSE) and the silhouette coefficient. The selected cluster number remains fixed in subsequent related comparisons. Different sampling strategies use the same training candidate pool and supervised-sample budget.

2.6. Three-Stage Scheduling of the Physical-Loss Weight

The physical-equation loss weight follows three stages: warm-up, adaptive adjustment, and fixed weighting. These stages gradually introduce the physical constraint, adjust its weight using loss feedback, and hold the physical-loss coefficient fixed during late training. Stage boundaries are prescribed; only intermediate-stage updates depend on training losses. Here, λ ( t ) denotes the physical-equation loss coefficient, while the other loss weights retain the settings in Section 2.2.
During warm-up, epochs 1–15 use a logistic function to increase the physical-loss coefficient smoothly
λ ( t ) = λ max 1 + exp [ − k ( t − t 0 ) ] , 1 ≤ t ≤ 15 .
The parameters λ max = 1.0 , k = 0.5 , and t 0 = 7.5 control the upper limit, growth rate, and transition midpoint, respectively, increasing the coefficient from approximately 0.037 at epoch 1 to 0.977 at epoch 15. This setting is intended to avoid an abrupt increase in the physical term’s influence during early training.
The adaptive stage covers epochs 16–80. The weight used at epoch 16 is initialized to the final warm-up weight. For epochs 16–79, the losses from the current epoch are used in Equation (16) to compute the weight for the next epoch. Starting at epoch 81, the weight is fixed according to Equation (19).
λ ( t + 1 ) = min 2.0 , max 0.1 , λ ( t ) ( 1 + Δ ( t ) ) .
R ( t ) = L d ( t ) L p ( t ) .
Δ ( t ) = + 0.05 , R ( t ) > 2.0 , 0 , 0.5 ≤ R ( t ) ≤ 2.0 , − 0.05 , R ( t ) < 0.5 .
Here, L d and L p are the dimensionless losses defined in Section 2.2. The threshold interval reduces frequent adjustments, the 5% step limits each relative change, and the bounds restrict the coefficient’s range. This heuristic rule provides loss feedback rather than equalizing gradient contributions.
During epochs 81–120, the coefficient is fixed at its mean over epochs 71–80:
λ ( t ) = λ stable = 1 10 ∑ s = 71 80 λ ( s ) , 81 ≤ t ≤ 120 .
The mean weight over epochs 71–80 reduces the fixed coefficient’s dependence on single-epoch fluctuations. The final 40 epochs are reserved for continued optimization under a fixed equation-residual weight. Epoch 81 is a prescribed transition rather than one triggered by an automatic convergence criterion. Stage boundaries, ratio thresholds, and update step size are treated as preset training parameters in this study. The overall schedule is evaluated through the fixed-weight ablation in Section 3.3.

3. Experimental Design and Results Analysis

3.1. Experimental Setup and Benchmarks

Ansys Maxwell 3D Electrostatic is used to calculate the electroquasistatic electric field for the fixed 500 kV single-span tower–conductor configuration. The span is 200 m; the three phases are arranged horizontally with 12 m between adjacent conductor centerlines; the conductor-end center height is 15 m; the maximum sag is 4 m, giving a midspan conductor-center height of 11 m; and the conductor radius is 15 mm. Balanced three-phase potentials at one specified operating snapshot are applied to the conductors, while the ground plane and the simplified grounded gantries are assigned zero potential. The Laplace residual is imposed only in the homogeneous, charge-free air region and is not applied directly on conductor surfaces. Insulators and finite-conductivity soil are not explicitly modeled. Accordingly, the present model is limited to the electrostatic/electroquasistatic field associated with the specified geometry, excitation, and boundary conditions; corona space charge, streamer development, breakdown, and full-wave propagation effects are not considered.
The reference dataset generated by Ansys Maxwell contains 2,792,784 spatial samples; no experimental measurements are used. The training candidate pool, validation set, and test set contain 1,954,949, 418,918, and 418,917 samples, respectively, corresponding to approximately 70%, 15%, and 15% of the dataset. Candidate cluster numbers are 20, 30, …, 100, with 80 clusters selected and a nominal allocation of 1024 samples per cluster, yielding 81,920 supervised training samples. Insufficient cluster allocations are redistributed according to Section 2.5. The extension to 100 in Figure 2 represents the candidate search range.
A fixed set of 20,480 physics collocation points is independently sampled within the air region. Geometric filtering excludes conductor interiors and surfaces and ensures that the points satisfy the assumptions of the physical residual. The magnitude-consistency loss reuses these coordinates, with the main network’s input features constructed at the corresponding locations. These points require no Maxwell field labels and do not alter the validation or test split.
Known-potential boundaries use 8192 fixed points: 1536 on each phase-conductor surface, 2560 on the ground plane, and 1024 across the grounded gantry surfaces. Conductors are assigned their phase potentials at the specified operating snapshot, while the ground plane and grounded gantries are assigned zero potential. These boundary points are sampled separately from the interior physics collocation points.
Each epoch contains 64 parameter updates, using 1280 supervised points, 320 physics collocation points and their corresponding coupling points, and 128 known-potential boundary points per update. Each fixed point set is traversed once per epoch. The batch sizes for the data-fitting, physical-residual, magnitude-consistency, and boundary losses are therefore 1280, 320, 320, and 128, respectively. The additionally sampled collocation and boundary points are not included in the 2,792,784 Maxwell reference samples.
The benchmark is the fixed 500 kV tower–conductor system. The reference electric-field magnitude ranges approximately from 10 − 6 to 10 7 V/m, spanning about 13 orders of magnitude. Computational performance is evaluated using 100,000, 500,000, and 1,000,000 spatial query points. Query scale is reported separately from model-training and error-evaluation sample counts and is not equivalent to the full dataset size or finite-element mesh size.
The Maxwell/pyaedt reference workflow runs on a Windows 10 workstation with an Intel i9-13900K CPU, whereas APINN training and inference use an Ubuntu 22.04 platform with an NVIDIA RTX 4080 Super GPU. These platform differences are explicitly retained in the timing interpretation in Section 3.3.

3.2. Model Training Dynamics and Performance Across Configurations

Under the current fixed data split, five independent runs are used to characterize training randomness rather than five-fold cross-validation. Figure 3 presents the training and validation loss curves for these runs.
Figure 3. Training and validation loss curves from five independent trials.
As shown in Figure 3, under the current fixed data split, the training and validation losses of the five independent runs show similar convergence trends, and no clearly and persistently widening loss separation is observed in the later training stage. The final training and validation losses over the five independent runs are 0.087 ± 0.011 and 0.112 ± 0.016 , respectively (mean ± standard deviation). These results describe only the training and validation behavior under the current fixed configuration and data split and do not constitute rigorous evidence that overfitting is entirely absent.
To examine the applicability and robustness of the APINN framework across configurations, six transmission-line configurations were investigated, as summarized in Table 2. Maxwell reference data were generated independently for each configuration, and the model was retrained using the same network architecture and training procedure. Prediction errors and equation residuals remain within comparable ranges, supporting the framework’s applicability and consistent performance after retraining under the investigated conditions. These tests do not establish zero-shot generalization of a single trained model to unseen configurations.
Table 2. Quantitative comparison of APINN performance under different transmission-line configurations.

3.3. Computational Performance Analysis

Table 3 compares the Maxwell/pyaedt workflow and APINN under the stated computational configurations. For 1,000,000 spatial query points, the two execution times are 48 h and 65 s, respectively, and the APINN average relative error is 4.8%. This result reflects execution-time differences under different deployment configurations; it does not represent an algorithmic speedup under identical hardware and does not include the full cost of offline APINN construction. The APINN complete online times in Table 3 are the mean values of five independent repeated timings under the same conditions.
Table 3. Recorded performance of the Maxwell/pyaedt workflow and APINN inference under the specified computing configurations.
For a direct learning-method comparison, a conventional DNN, a standard PINN, and APINN are compared under the same data split, test positions, and computing platform, as shown in Table 4. The overall relative L 2 error and near-conductor MAE of APINN are 3.8% and 1406 V/m, respectively, both lower than those of the DNN and standard PINN. Its training time is 1457 s, and its complete online time for 1,000,000 query points is 65 s, showing an accuracy benefit over the DNN and time and accuracy benefits over the standard PINN under these conditions.
Table 4. Learning-method benchmark comparison under a common evaluation protocol.
To quantitatively analyze the roles of individual components, controlled ablation experiments are conducted under the same data split, training budget, hardware environment, and evaluation procedure. The compared models include a conventional DNN, a standard PINN, APINN without physics constraints, APINN without cluster-based sampling, fixed-loss-weight APINN, APINN without geometric feature augmentation, a control model without independent dual networks, an 18-input APINN variant, and the full APINN (Table 5). All models use the same training budget of 120 epochs, and their physical-consistency metrics are reported in Table 6. Cluster-based sampling and random sampling use the same training candidate pool and the same supervised-sample budget, while the validation and test sets remain fixed.
Table 5. Prediction performance and training efficiency of the compared models.
Table 6. Mean physical-consistency metrics of the compared models.
APINN without geometric feature augmentation retains the six base inputs—spatial coordinates and three-phase applied voltages—and removes the nine conductor-distance, inverse-squared-distance, and coordinate-cross-term features. The main network’s input layer is adjusted accordingly, while the remaining network settings, data split, supervised-sample budget, physical constraints, and training rules remain unchanged. This comparison evaluates geometric augmentation as a whole rather than the independent contribution of each feature group.
The six-input model retains only the spatial coordinates and phase voltages. The 18-input model adds the three inverse conductor distances to the full 15-input set. Increasing the input dimension from 6 to 15 reduced the overall relative L 2 error from 4.8% to 3.8% and the near-conductor MAE from 2051 to 1406 V/m. The 18-input model achieved the same reported overall error of 3.8% and reduced the near-conductor MAE to 1390 V/m, with a recorded training time of 1490 s compared with 1457 s for the 15-input model. This comparison supports retaining the 15-input configuration among the feature sets evaluated.
For the investigated 500 kV transmission-line configuration, the total computational cost of APINN comprises high-fidelity reference-data generation, data preprocessing, network training, model loading, and subsequent online prediction. The measured APINN training time is 1457 s, and the complete online inference time for one million spatial queries is 65 s. By contrast, the Maxwell/pyaedt timings reported in the computational comparison represent the recorded high-fidelity workflow rather than field-value extraction from a retained finite-element solution. Therefore, the reported timing ratio should not be interpreted as an algorithmic speedup under identical hardware or as a reduction in total computational cost. The break-even query count depends on the fixed construction costs and marginal query times of both workflows. Since the field-extraction time from a retained Maxwell solution was not measured separately, a reliable numerical break-even threshold cannot be determined from the available timing records. For modified geometries or operating conditions, the costs of generating configuration-specific reference data and retraining the surrogate model must also be included.

3.4. In-Depth Analysis of Prediction Accuracy

Figure 4 shows the reference electric-field magnitude from Ansys Maxwell and the APINN prediction-error distribution. The Maxwell solution is used as the reference benchmark rather than as a learning model with a separate prediction error.
Figure 4. (a) Spatial distribution cloud map of electric-field magnitude simulated by Ansys Maxwell. (b) Spatial heatmap of prediction error rates from the APINN model.
To avoid the influence of tail-sample trimming on the overall performance evaluation, final prediction performance is evaluated on all 418,917 independent test samples. Supplementary central-90% robust statistics (Table 7) and the near-conductor, intermediate, and background regional statistics are constructed from this same independent test set. The full-test MAE, RMSE, overall relative L 2 error, and Log-RMSE are 306 V/m, 1040 V/m, 3.8%, and 0.071, respectively.
Table 7. Central-90% robust statistics within the independent test set.
All prediction errors are calculated from denormalized electric-field magnitudes, with the reference electric-field magnitudes obtained from Ansys Maxwell used as the benchmark. For N test samples, the mean absolute error (MAE) and root-mean-square error (RMSE) are defined as
MAE = 1 N ∑ i = 1 N | S ^ i − S i | ,
RMSE = 1 N ∑ i = 1 N ( S ^ i − S i ) 2 .
Both MAE and RMSE are reported in V/m. The overall relative L 2 error is used to characterize the global relative deviation between the predicted and reference fields,
ε L 2 = ∑ i = 1 N ( S ^ i − S i ) 2 ∑ i = 1 N S i 2 × 100 % ,
while logarithmic error is used as a complementary metric for prediction performance across multiple orders of magnitude,
Log − RMSE = 1 N ∑ i = 1 N log 10 ( S ^ i + S 0 ) − log 10 ( S i + S 0 ) 2 .
All metrics are calculated on the same independent test set.
The negative-bias proportion is defined as the fraction of samples for which the predicted electric-field magnitude is lower than the reference value, whereas the positive-bias proportion is defined as the fraction of samples for which the predicted electric-field magnitude is higher than the reference value. These two quantities are used only to characterize the direction of prediction bias and do not imply physical shielding or electric-field enhancement.
The independent test set is further divided into near-conductor, intermediate, and background regions according to the distance from each spatial point to the nearest conductor surface. Table 8 reports the regional error statistics. The near-conductor MAE is 1406 V/m, which is higher in absolute terms than in the other regions, while its relative L 2 error is 3.5%, indicating that the model maintains good relative prediction accuracy in the high-field region. The background region has smaller absolute errors but larger relative errors because the reference field magnitude approaches zero; therefore, Log-RMSE is also reported as a complementary metric.
Table 8. Prediction errors by spatial region within the independent test set.
Regional prediction errors should be distinguished from engineering safety acceptance criteria. For near-conductor regions, absolute errors and deviations near prescribed electric-field limits are particularly important. Intermediate regions require joint consideration of absolute and relative errors, whereas background regions should be evaluated using absolute and logarithmic errors. For safety-related applications, acceptance criteria should be established using application-specific field limits and independently validated error bounds. Predictions close to the prescribed limits require further verification. Since such error bounds have not been established in this study, the regional errors in Table 8 should not be interpreted as validated engineering safety tolerances.

4. Discussion

Although the proposed Adaptive Physics-Informed Neural Network (APINN) framework has demonstrated substantial improvements in computational efficiency and prediction accuracy for ultra-large-scale electromagnetic field analysis, certain limitations remain that warrant further in-depth investigation. Primarily, the current mathematical formulation and physical feature engineering strategy are specifically tailored for quasi-static electromagnetic fields. In practical power system operations, transmission lines are frequently subjected to high-frequency transient events, such as lightning strikes and switching overvoltages. Additionally, the model currently operates under the assumption of decoupled physical fields, whereas real-world scenarios often involve complex multi-physics interactions, particularly thermal–electromagnetic coupling where localized Joule heating dynamically alters the surrounding dielectric properties and spatial conductivity. Therefore, extending the physical sub-network to incorporate time-varying Maxwell’s equations and multi-physics coupling mechanisms will be a critical direction for future research.
Furthermore, the APINN framework relies on high-quality numerical reference data for surrogate model construction. The additional configuration tests demonstrate that the same network architecture and training procedure can accommodate the investigated variations in conductor geometry and operating conditions after configuration-specific retraining. For comparable three-phase transmission-line configurations governed by the same electrostatic or electroquasistatic assumptions and adequately represented by the adopted geometric feature set, the framework may be extended by updating the geometric features, excitation conditions, and boundary constraints, followed by configuration-specific retraining and independent validation. However, direct generalization of a trained model to arbitrary unseen configurations without adaptation has not been established. More efficient adaptation strategies, including incremental learning, remain subjects for future investigation.
The current validation relies on Maxwell-generated reference data, including the additional configuration tests. Independent validation using other electromagnetic solvers or experimental electric-field measurements has not yet been performed. Therefore, the reported numerical results do not establish the reliability of APINN for direct engineering safety assessment.
Finally, to maximize the engineering utility of this physics-constrained surrogate model in real-time digital twin applications, future efforts will also be directed toward algorithmic and computational optimization. Developing automated hyperparameter optimization frameworks will reduce the manual tuning overhead and improve the model’s adaptability across various transmission line specifications. Concurrently, introducing model compression technologies, such as knowledge distillation and network pruning, will be essential for deploying these predictive models onto resource-constrained edge computing devices, such as smart sensors on transmission towers. These developments may facilitate the deployment of the proposed framework in practical transmission-line monitoring applications, although further implementation and validation are required.

5. Conclusions

An APINN electric-field magnitude surrogate model is constructed for the fixed 500 kV tower–conductor configuration. The reference field spans approximately 13 orders of magnitude, and computational performance is evaluated using 100,000 to 1,000,000 spatial query points. Model accuracy is reported using explicitly defined absolute, relative, and logarithmic error metrics. Computational-efficiency conclusions are limited to the stated hardware configurations and timing scope.

Author Contributions

Conceptualization, Z.Y. and L.H.; methodology, Z.Y. and F.L.; software, F.L. and Z.H.; validation, Z.H., Y.D. and L.H.; formal analysis, Z.Y. and F.L.; investigation, F.L.; resources, L.H.; data curation, Z.H.; writing—original draft preparation, Z.Y.; writing—review and editing, F.L. and L.H.; visualization, Y.D.; project administration, Z.Y.; funding acquisition, Z.Y. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Science and Technology Project of State Grid Sichuan Electric Power Company, grant number 52199923001M.

Data Availability Statement

Due to the data-management and confidentiality requirements of the engineering project, the raw data, processed data, and complete source code used in this study cannot currently be made publicly available. To support reproducibility, the manuscript provides detailed descriptions of the data-generation workflow, feature construction methods, model architecture, training parameters, and evaluation procedures.

Acknowledgments

We used an AI tool (DeepSeek-V4-Pro) for language polishing only. It was not involved in the core content revision, experimental design, or data analysis. The authors have reviewed and edited the output and take full responsibility for the content of this publication.

Conflicts of Interest

Authors Ziyang Ye, Fuchao Li, Lin Huang, Zihuan Huang and Yihui Ding were employed by the Marketing Service Center of State Grid Sichuan Electric Power Company. The authors declare that this study received funding from the Science and Technology Project of State Grid Sichuan Electric Power Company (Grant No. 52199923001M). The funder was not involved in the study design, collection, analysis, interpretation of data, the writing of this article or the decision to submit it for publication.

References

  1. Jackson, J.D. Classical Electrodynamics, 3rd ed.; Wiley: New York, NY, USA, 1999. [Google Scholar]
  2. Yan, Y.; Jin, L.; Chen, J.; Yang, Y.; Li, H. Robust Hierarchical Traveling-Wave Partial Discharge Localization for Efficient Insulation Defect Detection of Medium-Voltage Overhead Lines. IEEE Trans. Instrum. Meas. 2026, 75, 3507915. [Google Scholar] [CrossRef] [Scilit]
  3. Liu, X.; Huang, J.; Zheng, D.; Xin, H.; Bi, T. Analysis and Suppression for Temporary Overvoltage Considering Dynamic Interactions Between LCC-HVDC and Renewable Energy Plants. IEEE Trans. Sustain. Energy 2025, 16, 1849–1859. [Google Scholar] [CrossRef] [Scilit]
  4. Chen, S.; Guo, Y.; Lan, S.; Zhang, K.; Tan, L.; Zhang, D. Simulation Research on Distribution Characteristics of Electromagnetic Field of AC UHV Transmission Line. IOP Conf. Ser. Earth Environ. Sci. 2021, 632, 042050. [Google Scholar] [CrossRef] [Scilit]
  5. Han, C.; Chen, Y. Modeling and Simulation Analysis of Power Frequency Electric Field of UHV AC Transmission Line. Int. J. Adv. Comput. Sci. Appl. 2015, 6, 77–81. [Google Scholar] [CrossRef] [Scilit]
  6. El Dein, A.Z. Calculation of the Electric Field Around the Tower of the Overhead Transmission Lines. IEEE Trans. Power Deliv. 2014, 29, 899–907. [Google Scholar] [CrossRef] [Scilit]
  7. Fathy, A.M.; Al-Gabalawy, M.; Ismail, H.M. Numerical Simulation of Electromagnetic Fields in HVDC Transmission Lines: Realistic Case Studies of 500 kV and 800 kV Systems. Discov. Appl. Sci. 2025, 7, 1145. [Google Scholar] [CrossRef] [Scilit]
  8. Jin, J.M. The Finite Element Method in Electromagnetics, 3rd ed.; Wiley: Hoboken, NJ, USA, 2015. [Google Scholar]
  9. Taflove, A.; Hagness, S.C. Computational Electrodynamics: The Finite-Difference Time-Domain Method, 3rd ed.; Artech House: Boston, MA, USA, 2005. [Google Scholar]
  10. Berenger, J.P. A perfectly matched layer for the absorption of electromagnetic waves. J. Comput. Phys. 1994, 114, 185–200. [Google Scholar] [CrossRef] [Scilit]
  11. Gibson, W.C. The Method of Moments in Electromagnetics, 2nd ed.; CRC Press: Boca Raton, FL, USA, 2014. [Google Scholar]
  12. LeCun, Y.; Bengio, Y.; Hinton, G. Deep learning. Nature 2015, 521, 436–444. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  13. Goodfellow, I.; Bengio, Y.; Courville, A. Deep Learning; MIT Press: Cambridge, MA, USA, 2016. [Google Scholar]
  14. Hamid, A.; Rafiq, D.; Nahvi, S.A.; Bazaz, M.A. Deep Learning Assisted Surrogate Modeling of Large-Scale Power Grids. Sustain. Energy Grids Netw. 2023, 34, 101031. [Google Scholar] [CrossRef] [Scilit]
  15. Karpatne, A.; Atluri, G.; Faghmous, J.H.; Steinbach, M.; Banerjee, A.; Ganguly, A.; Shekhar, S.; Samatova, N.; Kumar, V. Theory-guided data science: A new paradigm for scientific discovery from Data. IEEE Trans. Knowl. Data Eng. 2017, 29, 2318–2331. [Google Scholar] [CrossRef] [Scilit]
  16. Raissi, M.; Perdikaris, P.; Karniadakis, G.E. Physics-informed neural networks: A deep learning framework for solving forward and inverse problems involving nonlinear partial differential equations. J. Comput. Phys. 2019, 378, 686–707. [Google Scholar] [CrossRef] [Scilit]
  17. Cuomo, S.; Di Cola, V.S.; Giampaolo, F.; Rozza, G.; Raissi, M.; Piccialli, F. Scientific machine learning through physics-informed neural networks: Where we are and what’s next. J. Sci. Comput. 2022, 92, 88. [Google Scholar] [CrossRef] [Scilit]
  18. Stiasny, J.; Chatzivasileiadis, S. Physics-Informed Neural Networks for Time-Domain Simulations: Accuracy, Computational Cost, and Flexibility. Electr. Power Syst. Res. 2023, 224, 109748. [Google Scholar] [CrossRef] [Scilit]
  19. Shen, Q.; Zhou, Y.; Zhang, P. Physics-Informed Induction Machine Modelling. arXiv 2023, arXiv:2309.16943. [Google Scholar]
  20. Ngo, Q.H.; Nguyen, B.L.H.; Vu, T.V.; Zhang, J.; Ngo, T. Physics-Informed Graphical Neural Network for Power System State Estimation. Appl. Energy 2024, 358, 122602. [Google Scholar] [CrossRef] [Scilit]
  21. Brendel, P.; Medvedev, V.; Rosskopf, A. Physics-Informed Neural Networks for Magnetostatic Problems on Axisymmetric Transformer Geometries. IEEE J. Emerg. Sel. Top. Ind. Electron. 2024, 5, 700–709. [Google Scholar] [CrossRef] [Scilit]
  22. Han, J.H.; Park, J.H.; Song, S.M.; Hong, S.K. Electromagnetic Field Analysis Using Physics Informed Neural Network Considering Eddy Current. In Proceedings of the 2024 IEEE 21st Biennial Conference on Electromagnetic Field Computation (CEFC), Jeju, Republic of Korea, 2–5 June 2024; pp. 1–2. [Google Scholar]
  23. Nohra, M.; Dufour, S. Physics-Informed Neural Networks for the Numerical Modeling of Steady-State and Transient Electromagnetic Problems with Discontinuous Media. In Proceedings of the 2024 21st International Multi-Conference on Systems, Signals & Devices (SSD), Sousse, Tunisia, 12–15 March 2024. [Google Scholar]
  24. Piao, S.; Gu, H.; Wang, A.; Qin, P. A Domain-Adaptive Physics-Informed Neural Network for Inverse Problems of Maxwell’s Equations in Heterogeneous Media. IEEE Antennas Wirel. Propag. Lett. 2024, 23, 2905–2909. [Google Scholar] [CrossRef] [Scilit]
  25. Jagtap, A.D.; Karniadakis, G.E. Extended Physics-Informed Neural Networks (XPINNs): A Generalized Space-Time Domain Decomposition Based Deep Learning Framework for Nonlinear Partial Differential Equations. Commun. Comput. Phys. 2020, 28, 2002–2041. [Google Scholar] [CrossRef] [Scilit]
  26. Gao, Z.; Yan, L.; Zhou, T. Failure-Informed Adaptive Sampling for PINNs. SIAM J. Sci. Comput. 2023, 45, A1971–A1994. [Google Scholar] [CrossRef] [Scilit]
  27. Xiang, Z.; Peng, W.; Liu, X.; Yao, W. Self-Adaptive Loss Balanced Physics-Informed Neural Networks. Neurocomputing 2022, 496, 11–34. [Google Scholar] [CrossRef] [Scilit]
  28. Bischof, R.; Kraus, M.A. Multi-Objective Loss Balancing for Physics-Informed Deep Learning. Comput. Methods Appl. Mech. Eng. 2025, 439, 117914. [Google Scholar] [CrossRef] [Scilit]
  29. Farhani, G.; Hosseini Dashtbayaz, N.; Kazachek, A.; Wang, B. A Simple Remedy for Failure Modes in Physics-Informed Neural Networks. Neural Netw. 2025, 183, 106963. [Google Scholar] [CrossRef] [Scilit] [PubMed]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Article metric data becomes available approximately 24 hours after publication online.