Grid-Forming Static Power Generator with Coordinated Control of Two-Stage Converters

,
,
,
,
,
,
,
and
1
State Key Laboratory of Advanced Power Transmission Technology, China Electric Power Research Institute Company Ltd., Beijing 100192, China
2
College of Electrical Engineering, Zhejiang University, Hangzhou 310058, China
*
Author to whom correspondence should be addressed.

Abstract

Grid-forming (GFM) control is an important technical solution for addressing the declining voltage-support capability and inertia level of modern power systems. By integrating a high-voltage directly connected grid-side converter with supercapacitors, the grid-forming static power generator (GFM-SPG) can provide active- and reactive-power support to high-voltage power grids. This paper investigates a GFM-SPG with a two-stage converter topology and proposes a coordinated control strategy for the two-stage converters. The transient response characteristics of the GFM-SPG are classified into three operating regions, and the effects of key control parameters are analyzed to establish basic parameter design guidelines. To simultaneously enhance grid inertial support and transient voltage-support capability, a variable inertia time-constant control strategy is further proposed. Under normal operating conditions, a relatively large inertia time constant is adopted to provide inertial support, whereas a small inertia time constant is employed during voltage ride-through to enable rapid phase synchronization and prioritize reactive-power support. The proposed control strategy is validated through electromagnetic transient simulations and hardware-in-the-loop (HIL) experiments. The results demonstrate that the two-stage GFM-SPG can achieve stable DC-bus voltage regulation and provide effective inertia and transient voltage support under different grid operating conditions.

1. Introduction

With the implementation of carbon-reduction policies worldwide, renewable energy sources have increasingly replaced conventional synchronous generators and have been integrated into power systems on a large scale [1,2]. This transition fundamentally disrupts the long-established symmetry between generation and load dynamics, because the electromechanical response characteristics of synchronous machines, which inherently maintain rotational symmetry in frequency and voltage regulation, are progressively substituted by the fast-response yet low-inertia behavior of power-electronic interfaces [3,4]. In China, load centers are geographically separated from renewable-energy-rich regions by thousands of kilometers. Consequently, large amounts of power generated in the northwestern regions are transmitted to the central and eastern regions through high-voltage direct-current (HVDC) transmission systems [5]. At the sending end, the installed capacity of renewable energy has significantly exceeded that of thermal power generation, resulting in insufficient dynamic reactive power regulation capability and increasingly prominent transient overvoltage issues. At the receiving end, the dense infeed of HVDC systems has progressively displaced local thermal generating units, leading to reduced system inertia and insufficient dynamic voltage support. These challenges can be interpreted as a breakdown of the symmetrical balance between active-power generation and reactive-power regulation, as well as between fast electromagnetic transients and slow electromechanical dynamics [6,7]. Under severe disturbances, these conditions may result in successive commutation failures and even voltage collapse of regional power grids [8]. Therefore, enhancing the transient support capability of bulk power systems has become a prerequisite for the further large-scale development of renewable energy, and restoring the functional symmetry between power-electronics-dominated sources and the grid’s operational requirements is essential for achieving this goal.
Most conventional renewable energy generation systems employ grid-following (GFL) control and are connected to the grid as controlled current sources [9,10]. Their dynamic characteristics differ substantially from those of conventional synchronous generators, and they generally provide limited transient support to the power grid [10,11,12,13]. In contrast, power-electronic interfaces employing grid-forming (GFM) control exhibit external characteristics similar to those of a voltage source behind an impedance, resembling the electrical characteristics of synchronous generators [14,15,16,17,18]. Owing to their inherently grid-friendly characteristics, GFM technologies have attracted increasing attention for applications in bulk power systems [19,20,21]. The European Union introduced the concept of GFM technologies into bulk AC power-system applications through the MIGRATE project, with the objective of addressing power-system security and stability challenges under weak or absent synchronous-machine support [22].
One of the most representative applications of grid-forming control is the grid-forming retrofit of energy storage power stations, which is intended to ensure the safe and stable operation of energy storage systems under weak-grid conditions [21]. In large-scale energy storage plants, the outputs of multiple power conversion systems are aggregated and connected to the high-voltage grid through step-up transformers. Because the capacity of each individual converter is relatively small and its electrical distance from the high-voltage grid is relatively large, the dynamic reactive power support provided by such converters is mainly used to maintain the stable operation of the energy storage plant itself and nearby renewable energy units and to prevent them from disconnecting from the grid [21].
In recent years, with the decreasing proportion of synchronous generators in bulk power systems, high-voltage directly connected power-electronic support technologies have developed rapidly [20,21]. Hitachi and Siemens have proposed devices that combine supercapacitors with conventional dynamic reactive power compensation equipment, referred to as the Enhanced-STATCOM (E-STATCOM) and SVC PLUS, respectively [23,24,25,26]. E-STATCOM has already been deployed in wind farms in Saxony, Germany. Similarly, State Grid Corporation of China has proposed the concept of the grid-forming static power generator (GFM-SPG), which is based on supercapacitors and high-voltage directly connected converters. Compared with the conventional concept of a “VAR generator,” the GFM-SPG extends the functionality from reactive-power compensation to comprehensive active- and reactive-power support, thereby evolving toward a “power generator” [24,27]. In 2024, three GFM-SPG projects were commissioned in the Tibet power grid in China, improving the post-fault stability of the weakly interconnected power system.
At present, most existing studies focus primarily on grid-forming control and stability analysis, with their models generally assuming an ideal constant DC voltage source [28,29]. However, unlike battery energy storage systems, supercapacitors do not exhibit a nearly constant voltage characteristic [29]. First, for GFM-SPG control, sufficient consideration must be given to DC-bus voltage regulation and to the coordination between supercapacitor charging/discharging operation and grid-support functions, which is a prerequisite for the stable implementation of grid-forming control [28,29]. Second, the point of interconnection of a GFM-SPG is generally at the medium-voltage level or above, and the corresponding short-circuit ratio is typically higher than that of conventional GFM-BESS applications. Grid-forming control under relatively strong-grid conditions has received comparatively limited attention in existing studies [30,31]. Finally, few studies have investigated grid-support strategies based on a two-stage architecture combining supercapacitors with grid-connected converters. Such a configuration offers the advantage of DC-bus voltage stabilization, which provides a favorable basis for the implementation of grid-forming control.
Different from existing GFM converter studies that generally assume a stiff DC source, the GFM-SPG considered in this work employs supercapacitors whose terminal voltage varies significantly during charging and discharging. Therefore, the grid-forming control of the AC-side converter cannot be designed independently of the DC-side energy-storage dynamics [32,33]. In addition, existing studies on GFM-STATCOMs and energy-storage converters mainly focus on either grid-forming regulation, current limitation, or DC-link dynamics separately, whereas the coordinated operation of a two-stage supercapacitor-based GFM-SPG under both normal and fault conditions has received limited attention [34,35,36].
Accordingly, the main contributions of this paper are summarized as follows: First, a coordinated control framework for a two-stage GFM-SPG is developed, in which the SC-DC/DC converter regulates the DC-bus voltage while the grid-connected converter performs grid-forming control and coordinates supercapacitor charging/discharging according to the grid operating state. Second, the transient operating characteristics of the GFM-SPG are divided into rated, linear-response, and current-limited regions, and the effects of the main voltage-support parameters are analyzed to provide parameter-design guidelines. Third, a variable-inertia-time-constant strategy is proposed to reconcile the conflicting requirements of inertia support during normal operation and rapid phase resynchronization with reactive-power priority during voltage ride-through. The proposed strategy is verified through electromagnetic-transient simulations and controller hardware-in-the-loop experiments.
It should be noted that the analysis in this paper mainly considers symmetrical three-phase disturbances. A symmetrical three-phase fault preserves the phase symmetry while producing a severe change in voltage magnitude and phase angle [37]. The present work focuses on how the GFM-SPG maintains DC-side energy balance and provides positive-sequence voltage, active-power, and reactive-power support under such symmetrical grid disturbances. The extension to asymmetrical faults involving negative-sequence components is beyond the scope of this study and will be considered in future work. The remainder of this paper is organized as follows: Section 2 introduces the basic topology of the two-stage GFM-SPG. Section 3 presents the overall control strategy of the GFM-SPG, including the DC-side and AC-side control. Section 4 analyzes the response characteristics of the GFM-SPG and the influence of the associated control parameters. Section 5 and Section 6 validate the proposed method through electromagnetic transient simulations and hardware-in-the-loop experiments, respectively. Finally, Section 7 concludes the paper.

2. GFM-SPG Topological Structure

Figure 1 illustrates the overall topology of the grid-forming static power generator (GFM-SPG), which mainly consists of a transformerless DC/AC converter, an L filter, and supercapacitor DC/DC (SC-DC/DC) converters. The SC-DC/DC converters are connected to the DC bus through cascaded supercapacitor half-bridge submodules (SC-HBSMs), where multiple supercapacitor (SC) banks are connected to the DC side of each half-bridge submodule. Compared with conventional DC capacitors, supercapacitors have a higher energy density. However, the voltage rating of an individual SC cell is relatively low; therefore, hundreds of SC cells or tens of SC banks are typically connected in series on the DC side of each submodule. To increase the installed supercapacitor capacity, multiple SC-DC/DC branches can be connected in parallel.
Figure 1. Overall topology and control block diagram of the GFM-SPG.
The DC-bus-based GFM-SPG topology enables decoupled control of the AC- and DC-side voltages. The SC-DC/DC converters are dedicated to DC-bus voltage regulation, thereby providing a constant DC voltage source for the DC/AC converter. Consequently, during grid-fault transients, the DC/AC converter can focus on regulating the voltage at the point of common coupling (PCC) without being additionally constrained by DC-bus voltage stabilization. Moreover, this topology physically separates the DC/AC converter from the supercapacitor units, which facilitates optimized equipment layout and fire-protection design when the GFM-SPG is deployed in high-voltage substations.

3. Overall Control of the GFM-SPG

The control system of the GFM-SPG mainly consists of the control of the front-end grid-connected converter and that of the back-end SC-DC/DC converters.

3.1. Grid-Connected Converter Control

The detailed control block diagram of the grid-connected converter is shown in Figure 2. The grid-connected converter is primarily controlled using a virtual synchronous generator (VSG) scheme, which mainly consists of P − ω control for generating the phase angle of the reference voltage and Q − U control for determining its magnitude. The virtual internal-voltage phase angle generated by the P − ω control, and θs is given by Equation (1):
T j d ω s dt = P sc − P s − D ( ω s − ω g ) d θ s dt = ω s
where Tj is the inertia time constant, D is the damping coefficient, ωs is the virtual angular frequency generated by the GFM-SPG, θs is the corresponding virtual phase angle, and Ps is the active power delivered by the GFM-SPG to the grid. Psc denotes the active-power reference [27]. Equation (1) generates θs by simulating the second-order rotor motion equations of a synchronous generator. The presence of D and Tj endows the GFM-SPG with inertia and damping characteristics similar to those of a synchronous generator. It should be noted that the value of Tj should be matched to the capacity of the configured supercapacitor. During normal operation, P sc 0 generally needs to be adjusted in real time based on the supercapacitor’s voltage or charge. The specific expression is given in Equation (2).
P sc 0 = k sc ( U sc , ref − U sc )
where ksc is the proportional gain of the controller. Usc,ref and Usc represent the reference voltage and actual voltage of the supercapacitor, respectively.
Figure 2. Control block diagram of the grid-connected converter of the GFM-SPG.
For a configuration consisting of multiple SC-SMs, the average voltage of all SC-SMs is generally adopted, which can be expressed as Equation (3):
U sc = 1 N sc − max ∑ i = 1 N sc − max U sc , i
where Nsc denotes the total number of SC-SMs, and Usc,i represents the voltage of the i-th SC-SM, which is generally obtained by measuring the voltage at the module terminal.
In Q-U control, the amplitude E ref 0 of the internal potential generated by the GFM-SPG is given by Equation (4):
E ref 0 = E 0 + K u ( U ref − U g ) + K q s ( Q ref − Q s )
where Uref is the specified grid-voltage reference, Ug is the RMS value of the voltage at the point of common coupling (PCC), Qref is the reactive-power reference, and Qs is the reactive power delivered by the GFM-SPG to the grid. Ku is the voltage-regulation coefficient, and Kq is the integral gain of the reactive-power control loop.
Based on the generated θs and E ref 0 , the PCC voltage can then be regulated through the inner voltage–current (U–I) control loops. To accommodate variations in grid strength, virtual impedance is generally incorporated into the control system. In the dq reference frame where E ref 0 is aligned with the d-axis and the q-axis lags the d-axis by 90°, the relationship between E ref 0 and Ug can be expressed as Equation (5):
E ref 0 = U gd − X q I gq + R I gd 0 = U gq + X d I gd + R I gq
where Ugd and Ugq are the d- and q-axis components of the PCC voltage, respectively, and Igd and Igq are the corresponding d-axis and q-axis components of the grid-connected current. Xd and Xq denote the virtual reactances introduced along the d- and q-axes, respectively, and are generally set to the same value. R denotes the virtual resistance introduced in the control system, and bold symbols represent phasors.
Conventional cascaded PI controllers are employed in the inner U–I control loops to track the voltage and current references. To ensure that the output current of the GFM-SPG does not exceed its maximum allowable overload current Ilim, a circular current limiter is applied to the reference current idq,ref, as expressed by Equation (6):
i dq , ref = i dq , ref 0 , if i d , ref 0 2 + i q , ref 0 2 ≤ I lim i dq , ref 0 i d , ref 0 2 + i q , ref 0 2 I lim , otherwise
where idq,ref0 and idq,ref denote the dq-axis current reference vectors before and after current limiting, respectively.

3.2. SC-DC/DC Converter Control

The control block diagram of the SC-DC/DC converter is shown in Figure 3. The control objective of the SC-DC/DC converter is to maintain the DC-bus voltage, thereby providing a relatively constant DC voltage source for the GFM-SPG during grid-supporting operation. The overall control adopts a closed-loop DC voltage–current double PI control structure.
Figure 3. Control block diagram of the SC-DC/DC converter of the GFM-SPG.
Through the closed-loop control, the required number of SC-SMs connected to the DC bus, denoted as Nsc, is obtained and then sent to the nearest level modulation (NLM) algorithm, as shown in Figure 4. According to the voltage levels of all SC-SMs, the submodules are sorted in ascending or descending order. Then, depending on the charging or discharging state, Nsc SC-SMs with the lowest or highest capacitor voltages are selected for insertion, respectively. Finally, the corresponding modulation signals um−dc for the SC-SMs are generated.
Figure 4. Flowchart of the NLM algorithm for the DC-side SC-SMs.

3.3. Coordinated Control Design

Although the energy storage capacity of supercapacitors is significantly higher than that of conventional DC capacitors, supercapacitors do not exhibit a constant voltage plateau characteristic as batteries do. Therefore, during steady-state grid operation, the grid is expected to provide energy to charge the supercapacitors. Meanwhile, during grid faults, the supercapacitors should be capable of maintaining the operation of the GFM-SPG independently of the faulty grid.
Therefore, coordinated control of the supercapacitor system is required to achieve a smooth transition between normal grid operation and fault conditions. The binary logic function Th is introduced to indicate the grid fault status, which is defined as follows:
Th = 1 , 0.9   p . u . ≤ U g ≤ 1.1   p . u . 0 , otherwise
Generally, the normal operating range of the grid voltage is within 0.9 p.u. to 1.1 p.u. By detecting the magnitude of the PCC voltage |Ug|, the occurrence of a grid fault can be identified. Once the voltage falls outside this range, P sc 0 in Equation (2) is set to P sc = Th · P sc 0 . In this case, the GFM-SPG no longer actively absorbs energy from the grid and relies entirely on the energy previously stored in the supercapacitors to provide grid support.
As mentioned above, the grid voltage generally allows a normal operating deviation of ±0.1 p.u. However, in the Q-U control scheme, the grid voltage reference Uref is usually set to 1 p.u. This may cause the GFM-SPG to output excessive reactive power when the grid voltage slightly deviates from 1 p.u. During steady-state operation, grid operators typically expect the voltage and reactive power at each node to be determined by the automatic voltage control (AVC) system. Therefore, the steady-state reactive power output of the GFM-SPG should remain controllable and dispatchable.
To address this issue, a reactive-power integral term controlled by the binary function Th is introduced into the Q-U control loop, as shown in Equation (8). Under normal grid conditions, the AVC system can provide the reactive power command Qref to the GFM-SPG. Through the reactive power integral action, the reference internal voltage Eref is adjusted until the required reactive power is achieved. When a grid fault occurs, Th changes to zero, and Eref automatically exhibits voltage droop characteristics.
E ref = E 0 + K u ( U ref − U g ) + Th K q s ( Q ref − Q s )

4. Analysis of the GFM-SPG Response and the Influence of Parameters

4.1. Classification of Response Regions

According to the severity of grid voltage faults, the response characteristics of the GFM-SPG can be classified into three regions, as illustrated in Figure 5.
Figure 5. Three response regions.
(1)
Rated operating region
When the grid voltage operates within the range of (0.9,1.1) p.u., the GFM-SPG receives the reactive power command Qref from the grid operator and operates within the rated reactive power range. Therefore, this region is defined as the rated operating region.
(2)
Linear response region
When the grid voltage falls outside the range of (0.9,1.1) p.u., the GFM-SPG generates the internal voltage magnitude according to Equation (8). However, the output current has not yet reached the current limit. The output current can be expressed as
I g = 1 R + j X v ( E ref − U g )
In particular, X v = X d 2 + X q 2 . According to Equation (9), the amplitude Im of the GFM-SPG output current is
I m = I g = E ref − U g R 2 + X v 2
It can be observed from Equation (10) that, when parameters such as Ku and Xv are fixed, the output current magnitude exhibits a linear relationship with the grid voltage magnitude Ug. Therefore, this region is defined as the linear response region.
(3)
Current-limited region
When the grid voltage falls outside the range of (0.9,1.1) p.u. and the voltage sag becomes severe, the output current of the GFM-SPG reaches its maximum overload limit Imax due to the current-limiting function. Therefore, this region is defined as the current-limited region.

4.2. Influence of Parameters in the Linear Response Region

In the linear response region, the response characteristics mainly depend on the design of Eref and Xv. The selection of Xv and R is generally determined according to small-signal stability. According to the parameters listed in Table 1, the relationship between the dominant eigenvalues and X = Xd = Xq can be obtained, as shown in Figure 6. It can be observed that, within a certain range, increasing X shifts the dominant eigenvalues toward the left half of the s-plane, thereby significantly improving the damping characteristics. The influence of R can be neglected in the parameter design, since Xv/R is generally designed to satisfy Xv/R > 5.
Table 1. Simulation parameters.
Figure 6. Relationship between the dominant eigenvalues and Xd or Xq.
According to Equation (8), Eref in the linear response region is mainly determined by the selection of E0 and Ku.
(1)
Influence of Ku with E0 = 1 p.u.: Assuming E0 = 1 p.u. and neglecting the influence of R, the output current of the GFM-SPG in the linear response region can be expressed as Equation (11):
I m = 1 X v ( 1 + K u ) ( 1 − U g )
A special case occurs when Ku = 0, where Equation (12) becomes
I m = 1 X v ( 1 − U g )
By comparing Equations (11) and (12), it can be observed that the introduction of Ku enlarges the current response by a factor of (1 + Ku). Here, Ku plays a role similar to the excitation system of a synchronous generator.
(2)
Assuming that E0 = |Ug|, the output current of the GFM-SPG is expressed as
I m = K u X v ( 1 − U g )
Compared with Equation (11), the magnitude of Im is reduced by a factor of K u 1 + K u . In practical applications, selecting E0 = |Ug| has certain disadvantages because the calculation of |Ug| introduces an unavoidable delay. This delay may cause an adverse regulation effect on the grid. Therefore, E0 = 1 p.u. is selected in the following analysis.

4.3. Influence of the Inertia Time Constant Tj on the Response

A larger Tj can help reduce the rate of change of frequency (RoCoF) of the power grid. However, a large Tj does not necessarily provide an advantage during typical voltage ride-through events. Taking a three-phase short-circuit fault as an example, the fault inception is generally accompanied by a grid phase-angle jump, as illustrated in Figure 7. In this case, the PCC voltage phase lags behind the phase angle of the GFM-SPG. According to Equation (14), the output of the GFM-SPG contains both considerable active-power and reactive-power components. During a typical voltage ride-through event, however, the grid requires more reactive power to facilitate voltage recovery rather than active power. The clearing time of a three-phase short-circuit fault is generally on the order of hundreds of milliseconds. For a GFM-SPG with a large Tj, the fault may therefore be cleared before its phase angle has been sufficiently adjusted.
P s = U gd I gd + U gq I gq Q s = U gq I gd − U gd I gq
Figure 7. Phasor diagram at the instant of grid fault inception.
The phase relationship shown in Figure 8 represents the desired operating condition of the GFM-SPG during voltage ride-through. Following a voltage drop at the PCC, the GFM-SPG rapidly adjusts its phase angle such that the relevant voltage phasors become aligned. Under this condition, Ig = Igq, Igd = 0 and Ug.f = Ugd.f, Ugq.f = 0. According to Equation (14), the active power output Ps of the GFM-SPG becomes zero under this condition, allowing its current capability to be fully utilized for reactive-power support and thereby facilitating grid-voltage recovery.
Figure 8. Phasor diagram when Eref is in phase with Ug,f after the fault.
Therefore, a fixed Tj generally cannot simultaneously provide effective RoCoF suppression and strong transient voltage support. To address this issue, a variable-inertia-time-constant control strategy is proposed for voltage ride-through conditions, as expressed in Equation (15).
T j = T j 1 ,   when   Th = 1 T j 2 ,   when   Th = 0
Here, Tj1 and Tj2 are two inertia time constants satisfying Tj2 < Tj1. According to Equation (15), under normal grid conditions, Tj is set to the nominal design value Tj1 to help maintain an adequate level of system inertia. When a voltage ride-through event occurs, Tj is switched to the smaller value Tj2, enabling the GFM-SPG to rapidly adjust its phase angle and maximize its reactive-power injection or absorption capability, thereby facilitating grid-voltage recovery.
Specifically, the selection of Tj1 is determined based on the designed short-term energy-support capability. Tj1 is selected according to the required inertial active-power response and the available short-term active-power capability of the supercapacitor. For a GFM-SPG with a rated capacity of Sn, its maximum active power response ΔPmax at the maximum rate of change of frequency (RoCoF) in the power grid is
Δ P max ≈ − S n T j 1 f n RoCoF
Therefore, the discharge capability of the DC-side supercapacitor must be able to meet the requirements of ΔPmax under Tj1 parameters. As Tj decreases, the phase-angle correction becomes faster. However, an excessively small Tj increases the sensitivity of the frequency dynamics. Tj1 was therefore selected as the smallest tested value that achieved sufficiently fast synchronization without noticeable post-fault oscillation under the considered operating conditions. Tj1 should be as small as possible, at 0.1 s, which is the time for a typical circuit breaker to cut off faults.
It should be noted that the mutation of Tj does not introduce system discontinuity; it only changes the speed of ωs variation. The phase θs is integrated from the angular velocity, which maintains the continuity of the phase change.

5. Simulation Validation

5.1. Simulation Case

A grid-connected simulation model of the GFM-SPG was developed based on the main circuit configuration shown in Figure 9. The main parameters are listed in Table 1.
Figure 9. Main circuit diagram of the simulation model.

5.2. Basic Operating Characteristics

Figure 10 shows the response of the GFM-SPG to a 30 MVar reactive power command under normal grid operating conditions. At t = 6 s, a reactive power command is issued to the GFM-SPG. After approximately 100 ms, the reactive power output of the GFM-SPG reaches its steady-state value. During the transient process, the step change in reactive power causes a slight fluctuation in Ps; however, the active power flow direction remains from the grid to the GFM-SPG.
Figure 10. Response of the GFM-SPG under steady-state operating conditions.
Meanwhile, under the control of the SC-DC/DC converters, the DC-bus voltage rapidly returns to a stable value after a small transient deviation. Owing to the proportional control action, the stored energy of the supercapacitor does not recover to 1 p.u.; instead, it settles at a new equilibrium point after the transient process. In practice, the supercapacitor does not need to be maintained at a fully charged state. A certain energy margin should be reserved to accommodate transient charging from the grid and thereby prevent the supercapacitor voltage from exceeding its allowable limit. Such overvoltage may cause severe damage to the supercapacitor.
Figure 11 shows the power response of the GFM-SPG following a small disturbance in the grid voltage. At t = 6 s, the grid voltage undergoes a small disturbance and decreases to approximately 0.92 p.u., which remains within the normal operating voltage range of the grid. Immediately after the disturbance, the voltage regulation coefficient Ku introduces a deviation between Eref and Umag, causing the GFM-SPG to output reactive power. However, since the grid voltage is still identified as being within the normal operating range, the reactive-power integral control with Kq gradually adjusts Eref. After approximately 2 s, the reactive power output of the GFM-SPG returns to its commanded value of approximately zero.
Figure 11. Response of the GFM-SPG to Small Voltage Disturbances.
Similarly, at t = 9 s, when the grid voltage increases from 0.92 p.u. to 1 p.u., the GFM-SPG initially absorbs a small amount of reactive power. After approximately 2 s, its reactive power output returns to zero. Throughout the disturbance, the active power remains nearly unchanged. These simulation results verify that, within the normal grid voltage operating range, the reactive power output of the GFM-SPG remains controllable and can follow the dispatched reactive-power command.
Figure 12 illustrates the power response of the GFM-SPG following a major disturbance in the grid voltage. At t = 7.1 s, a three-phase short-circuit fault occurred in the grid, causing the grid voltage to drop to approximately 0.25 p.u. and remain at that level for 1 s. At the moment of the fault, the GFM-SPG injected current into the grid with near-zero delay and maintained the output current within the maximum overload multiple of 3 p.u. As can be seen from the power waveforms, after the fault, active power flows from the GFM-SPG to the grid, and the stored energy of the supercapacitor continuously decreases during the fault period. This demonstrates that during a grid fault, the GFM-SPG operates by relying on the energy discharged from the supercapacitor rather than absorbing energy from the grid. After the fault is cleared, the SPG begins to absorb active power from the grid; the stored energy is gradually restored after fault clearance, and the system gradually returns to equilibrium. As for the DC voltage, it exhibited slight fluctuations at the onset and termination of the fault but was stabilized by the DC-side control within a few milliseconds. This demonstrates that the two-stage GFM-SPG possesses independent DC voltage stabilization capabilities.
Figure 12. Response of the GFM-SPG under grid transient conditions.

5.3. Influence of Control Parameters

Figure 13 illustrates the influence of the virtual reactance Xv on the grid-connected stability of the GFM-SPG. Without the virtual reactance Xv, the GFM-SPG exhibits relatively poor grid-connected stability. Specifically, a change in its operating condition results in sustained power oscillations, as shown in Figure 13a. Although these oscillations are eventually damped, such a response is undesirable for power-system operation and control.
Figure 13. Influence of Xv on the grid-connected stability of the GFM-SPG.
Figure 13b,c demonstrate that increasing Xv can effectively improve the grid-connected stability of the GFM-SPG. When Xv = 0.424 p.u., the oscillations are suppressed within approximately one oscillation cycle. Therefore, Xv = 0.424 p.u. is adopted in the subsequent simulations.
Figure 14 illustrates the effect of the parameter Ku on the GFM-SPG’s response during transient conditions. Under the same three-phase short-circuit fault, the value of the parameter Ku is positively correlated with the GFM-SPG’s output current, provided that the system remains within the GFM-SPG’s linear response range.
Figure 14. Influence of Ku on the transient response.
Figure 15 shows the response of the GFM-SPG with Tj = 1 s under a three-phase short-circuit fault. At t = 8 s, a grid fault occurs, causing the grid voltage to drop to approximately 0.45 p.u., accompanied by a phase-angle jump. Owing to the relatively large inertia of the GFM-SPG, deviations in both the phase angle and angular frequency between the GFM-SPG and the grid still exist when the fault is cleared after 150 ms. Consequently, relatively long-lasting post-fault oscillations occur and require approximately 300 ms to substantially decay to the normal operating state.
Figure 15. Transient response of the GFM-SPG with Tj = 1 s under a three-phase short-circuit fault.
According to Section 4.3, the maximum and minimum inertia time constants are set to Tj,max = 6 s and Tj,min = 0.01 s, respectively. Figure 16 shows the response of the GFM-SPG when switching between these two inertia time constants. Under the same grid-voltage sag condition, the GFM-SPG operates with an inertia time constant of 0.01 s during the fault. Therefore, its phase angle and angular frequency rapidly resynchronize with those of the grid. During the fault, the active power output decreases to approximately zero, and the output current is predominantly reactive. This characteristic is beneficial for post-fault voltage recovery. After fault clearance, almost no noticeable oscillation is observed.
Figure 16. Transient response of the GFM-SPG with a variable Tj under a three-phase short-circuit fault.
Figure 17 further presents the response of the GFM-SPG to a grid-frequency variation. At t = 7 s, the grid frequency decreases to 47 Hz at a rate of 2 Hz/s. During the frequency decline, the GFM-SPG continuously injects active power to support grid-frequency recovery. Based on an inertia time constant of 6 s, the expected active power output is approximately 7.2 MW, which agrees well with the simulation results. Therefore, the results demonstrate that the proposed switching strategy for the inertia time constant does not compromise the frequency-support capability of the GFM-SPG.
Figure 17. Inertia response of the GFM-SPG with Tj = 6 s.

6. Experimental Validation

To validate the proposed control strategy, an actual GFM-SPG controller was developed based on a Texas Instruments (Dallas, TX, USA) TMS320C6657 and a Xilinx/AMD (Santa Clara, CA, USA) K7 FPGA XC7K325T-1FFG900. The controller was integrated with a real-time digital simulator (RTDS) from RTDS Technologies (Winnipeg, Manitoba, Canada) and a power amplifier from PONOVO (Beijing, China) to establish a hardware-in-the-loop (HIL) test platform, as shown in Figure 18. The RTDS was employed to emulate the power grid and the main electrical circuit of the GFM-SPG in real time, while the actual controller interacted with the RTDS through real-time signal exchange to form a closed-loop test system. In the test system, the GFM-SPG was connected to a 35 kV bus and interfaced with a 110 kV grid through a step-up transformer. Although it is different from the 220 kV grid used in Section 5.1, the grid-connected short-circuit ratio is 25. The sampling frequency of the HIL platform is 20 kHz, mainly used to validate the practical control performance of the proposed strategy under different steady-state and transient operating conditions.
Figure 18. Hardware-in-the-loop (HIL) test platform.
Figure 19 presents the experimental response of the GFM-SPG to a reactive power step from 0 to 1 p.u. The results demonstrate that the GFM-SPG is capable of effective steady-state reactive power regulation.
Figure 19. The test waveform of the GFM-SPG under steady-state operating conditions.
Figure 20 shows the response of the GFM-SPG to a 0.07 p.u. change in voltage reference. Immediately after the change in voltage reference, the GFM-SPG exhibits a small reactive power response. Subsequently, under the action of the reactive-power integral control, the reactive power gradually returns to its commanded value of zero.
Figure 20. The test waveform of the GFM-SPG to a change in voltage reference.
Figure 21 shows the condition where the voltage of the SCs is below the rated value before SPG startup. Before 0.5 s, the voltage of the SC was below 900 V, and it continued to discharge slowly. When the SPG starts at 0.5 s and charges the SCs from the grid side, the voltage of the SCs continues to slowly rise towards the set 1.1 kV. The entire process demonstrates the effectiveness of the charging strategy for SCs under steady-state conditions.
Figure 21. The test waveform of SCs charging after the startup of the GFM-SPG.
Figure 22 shows the response of SPG to phase jumps. At 0.5 s and 0.85 s, there were 30-degree phase jumps in the forward and reverse directions of the grid voltage, respectively. Due to the characteristic of maintaining the phase of the voltage, there is a phase difference between the SPG and the grid, resulting in two reverse active powers. The fluctuation of the two phase jumps lasted for about 200 ms, and finally the SPG stabilized.
Figure 22. The test waveform of the GFM-SPG under grid voltage phase jumps.
Figure 23 demonstrates the grid-support capability of the GFM-SPG during a three-phase short-circuit fault. During the fault, the output current of the GFM-SPG is predominantly reactive, while the active-current component remains nearly zero and exhibits only slight transient disturbances at fault inception and fault clearance. These experimental results are in good agreement with the simulation results shown in Figure 16.
Figure 23. The test waveform of the GFM-SPG under a three-phase short-circuit fault.

7. Conclusions

This paper investigates a GFM-SPG with a two-stage topology and proposes a coordinated control strategy that integrates supercapacitor charging/discharging management with grid-support functions. The main conclusions are summarized as follows:
(1)
A decoupled control scheme for the two-stage GFM-SPG is proposed. The DC-side converter regulates the DC-bus voltage, while the grid-connected converter coordinates the charging and discharging of the supercapacitor under steady-state and transient operating conditions through grid-fault detection.
(2)
Three response regions of the GFM-SPG are established. An AVC-following function is designed for the GFM-SPG in the rated operating region, while the influence of key control parameters in the linear response region is analyzed, and corresponding basic design guidelines are provided.
(3)
A variable-inertia-time-constant control strategy is proposed. A relatively large inertia time constant is adopted under normal operating conditions to maintain a high level of grid inertia, whereas the inertia time constant is switched to a small value during voltage ride-through to enable the GFM-SPG to respond with reactive-power priority. In this way, the GFM-SPG can simultaneously enhance system inertia and voltage-support capability.
The present study still has several limitations. First, the proposed control strategy and the corresponding validation mainly consider balanced three-phase operating conditions and symmetrical voltage disturbances; the effects of negative-sequence components and unbalanced faults have not yet been explicitly addressed. Second, the inertia time constants and the corresponding switching thresholds are selected according to the required dynamic response and supercapacitor capability, while a rigorous large-signal stability boundary for the parameter-switching process remains to be established. Third, the HIL tests focus on the operation of a single GFM-SPG, and the dynamic interactions among multiple GFM-SPGs have not been systematically investigated. Future work will therefore focus on asymmetrical-fault control, analytical stability assessment of the variable-inertia strategy, more detailed DC-side supercapacitor dynamics, and coordinated operation of multiple GFM-SPGs.

Author Contributions

Methodology, X.L., G.Q., Y.W., Y.C. and X.B.; Software, X.L., G.Q., Y.L., Y.C., Y.X. and Q.C.; Validation, X.L., Z.Y., G.Q. and Q.C.; Formal Analysis, X.L., G.Q., Y.W. and Z.Y.; Investigation, X.L., G.Q., Y.W., Z.Y., Y.C., Y.L. and Q.C.; Resources, X.L., G.Q. and Z.Y.; Data Curation, Y.W., Y.C., Y.L., X.B. and Q.C.; Writing—Original Draft, X.L., G.Q. and Y.W.; Supervision, X.L., G.Q. and Y.X.; Project Administration, X.L., G.Q., Y.X. and Z.Y.; Funding Acquisition, X.L., G.Q., Y.X. and Z.Y. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Science and Technology Project of State Grid Corporation of China (4000-202440367A-3-1-DG).

Data Availability Statement

The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.

Conflicts of Interest

Authors Xiaoming Luan, Guangyao Qiao, Yixuan Wang, Zhiyong Yu, Yundan Cheng, Yifeng Lin, Qi Chen, and Yunfei Xu were employed by the company State Grid Corporation of China. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest. The authors declare that this study received funding from the Science and Technology Project of State Grid Corporation of China (4000-202440367A-3-1-DG). The funder was not involved in the study design, collection, analysis, interpretation of data, the writing of this article, or the decision to submit it for publication.

References

  1. Li, H.; Bennett, M.; Wang, J.; Okhuegbe, S.N.; Ademola, A.A.; Alshuaibi, K.M.; Chen, C.; Jia, X.; Lin, M.; Albukhari, W.M.; et al. Modeling a Notional Carbon-Free Power Grid with 24-hour Dispatch and Power Flow. In Proceedings of the 2023 International Conference on Future Energy Solutions (FES), Vaasa, Finland, 12–14 June 2023; pp. 1–5. [Google Scholar] [CrossRef] [Scilit]
  2. Ulbig, A.; Borsche, T.S.; Andersson, G. Impact of Low Rotational Inertia on Power System Stability and Operation. IFAC Proc. Vol. 2014, 47, 7290–7297. [Google Scholar] [CrossRef] [Scilit]
  3. Jia, X.; Jiang, Z.; Yin, H.; Zhao, Y.; Liu, Y.; Tan, J.; Hoke, A.; Peng, J.; Koralewicz, P.; Mendiola, E.; et al. Real-Time Inertia Estimation Tool Implementation Based on Probing Signals. In Proceedings of the 14th International Renewable Energy Congress (IREC), Sousse, Tunisia, 16–18 December 2023; pp. 1–6. [Google Scholar] [CrossRef] [Scilit]
  4. Hatziargyriou, N.; Milanović, J.V.; Rahmann, C.; Ajjarapu, V.; Cañizares, C.A.; Erlich, I.; Hill, D.J.; Hiskens, I.; Kamwa, I.; Pal, B.C.; et al. Definition and Classification of Power System Stability—Revisited & Extended. IEEE Trans. Power Syst. 2021, 36, 3271–3281. [Google Scholar] [CrossRef] [Scilit]
  5. Wang, Y.; Zhu, J.; Li, Y.; Hu, J.; Ma, S.; Wang, T. Transient overvoltage suppression of LCC-HVDC sending-end system based on DC current control optimisation. IET Energy Syst. Integr. 2024, 6, 182–195. [Google Scholar] [CrossRef] [Scilit]
  6. Cao, Y.; Song, Y.; Liu, X.; Li, C. Parameter Identification of Synchronous Condenser and Its Excitation System Considering Multivariate Coupling and Symmetry Characteristic. Symmetry 2024, 16, 1596. [Google Scholar] [CrossRef] [Scilit]
  7. Zhang, J.; Wang, J.; Cao, Y.; Li, B.; Li, C. A Coordinated Control Strategy of Multi-Type Flexible Resources and Under-Frequency Load Shedding for Active Power Balance. Symmetry 2024, 16, 479. [Google Scholar] [CrossRef] [Scilit]
  8. Wang, Q.; Liu, K.; Wang, L. Suppression measures of commutation failure in MIDC transmission systems. J. Eng. 2019, 2019, 1328–1332. [Google Scholar] [CrossRef] [Scilit]
  9. Rocabert, J.; Luna, A.; Blaabjerg, F.; Rodríguez, P. Control of power converters in AC microgrids. IEEE Trans. Power Electron. 2012, 27, 4734–4749. [Google Scholar] [CrossRef] [Scilit]
  10. Rathnayake, D.B.; Akrami, M.; Phurailatpam, C.; Me, S.P.; Hadavi, S.; Jayasinghe, G.; Zabihi, S.; Bahrani, B. Grid forming inverter modeling, control, and applications. IEEE Access 2021, 9, 114781–114807. [Google Scholar] [CrossRef] [Scilit]
  11. Matevosyan, J.; Badrzadeh, B.; Prevost, T.; Quitmann, E.; Ramasubramanian, D.; Urdal, H.; Achilles, S.; MacDowell, J.; Huang, S.H.; Vital, V.; et al. Grid-forming inverters: Are they the key for high renewable penetration? IEEE Power Energy Mag. 2019, 17, 89–98. [Google Scholar] [CrossRef] [Scilit]
  12. Rosso, R.; Wang, X.; Liserre, M.; Lu, X.; Engelken, S. Grid-forming converters: Control approaches, grid-synchronization, and future trends—A review. IEEE Open J. Ind. Appl. 2021, 2, 93–109. [Google Scholar] [CrossRef] [Scilit]
  13. Zhao, Y.; Alshuaibi, K.M.; Jia, X.; Zhang, C.; Liu, Y.; Ramasubramanian, D.; Zhu, L.; Farantatos, E. Comparison of Wide-Area and Local Power Oscillation Damping Control Through Inverter-Based Resources. In Proceedings of the 2023 IEEE Power & Energy Society Innovative Smart Grid Technologies Conference (ISGT), Washington, DC, USA, 16–19 January 2023; pp. 1–5. [Google Scholar] [CrossRef] [Scilit]
  14. Arghir, C.; Jouini, T.; Dörfler, F. Grid-forming control for power converters based on matching of synchronous machines. Automatica 2018, 95, 273–282. [Google Scholar] [CrossRef] [Scilit]
  15. Beck, H.-P.; Hesse, R. Virtual synchronous machine. In Proceedings of the 9th International Conference on Electrical Power Quality and Utilisation (EPQU 2007), Barcelona, Spain, 9–11 October 2007; pp. 1–6. [Google Scholar] [CrossRef] [Scilit]
  16. Driesen, J.; Visscher, K. Virtual synchronous generators. In Proceedings of the 2008 IEEE Power and Energy Society General Meeting, Pittsburgh, PA, USA, 20–24 July 2008; pp. 1–3. [Google Scholar] [CrossRef] [Scilit]
  17. Zhong, Q.-C.; Weiss, G. Synchronverters: Inverters That Mimic Synchronous Generators. IEEE Trans. Ind. Electron. 2011, 58, 1259–1267. [Google Scholar] [CrossRef] [Scilit]
  18. D’Arco, S.; Suul, J.A. Virtual Synchronous Machines—Classification of Implementations and Analysis of Equivalence to Droop Controllers for Microgrids. In Proceedings of the 2013 IEEE Grenoble PowerTech, Grenoble, France, 16–20 June 2013; pp. 1–7. [Google Scholar] [CrossRef] [Scilit]
  19. Lin, Y.; Eto, J.H.; Johnson, B.B.; Flicker, J.; Lasseter, R.H.; Villegas Pico, H.N.; Seo, G.-S.; Pierre, B.J.; Ellis, A. Research Roadmap on Grid-Forming Inverters; Report No. NREL/TP-5D00-73476; National Renewable Energy Laboratory: Golden, CO, USA, 2020. [Google Scholar]
  20. North American Electric Reliability Corporation. Grid Forming Technology: Bulk Power System Reliability Considerations; NERC: Atlanta, GA, USA, 2021. [Google Scholar]
  21. Australian Energy Market Operator. Application of Advanced Grid-Scale Inverters in the NEM; AEMO: Melbourne, Australia, 2021. [Google Scholar]
  22. Denis, G.; Prevost, T.; Debry, M.-S.; Xavier, F.; Guillaud, X.; Menze, A. The MIGRATE project: The challenges of operating a transmission grid with only inverter-based generation. A grid-forming control improvement with transient current-limiting control. IET Renew. Power Gener. 2018, 12, 523–529. [Google Scholar] [CrossRef] [Scilit]
  23. Chivukula, A.B.; Maiti, S. Analysis and control of modular multilevel converter-based E-STATCOM to integrate large wind farms with the grid. IET Gener. Transm. Distrib. 2019, 13, 4604–4616. [Google Scholar] [CrossRef] [Scilit]
  24. Engelbrecht, T.; Isaacs, A.; Kynev, S.; Matevosyan, J.; Niemann, B.; Owens, A.J.; Singh, B.; Grondona, A. STATCOM technology evolution for tomorrow’s grid: E-STATCOM, STATCOM with supercapacitor-based active power capability. IEEE Power Energy Mag. 2023, 21, 30–39. [Google Scholar] [CrossRef] [Scilit]
  25. Frey, K.; Garg, M.; Morgenstern, R.; Platt, N.; Spahic, E. Provision of fast frequency response by SVC PLUS Frequency Stabilizer. In Proceedings of the 15th IET International Conference on AC and DC Power Transmission (ACDC 2019), Coventry, UK, 5–7 February 2019; pp. 1–6. [Google Scholar] [CrossRef] [Scilit]
  26. Heydari, R.; Hasler, J.-P.; Sundar, B.K.; Danielsson, C.; Zhang, H.; Owens, A.J. Stability Enhancement of Weak Grids with High Penetration of Renewables with Grid-Forming STATCOM/Enhanced-STATCOM. In Proceedings of the CIGRE Paris Session 2024, Paris, France, 25–30 August 2024. Paper B4-10518-2024. [Google Scholar]
  27. Wang, F.; Xu, J.; Li, G. A Variable Virtual Impedance Current Limitation Strategy of Grid-Forming Energy Storage-STATCOM. IEEE Trans. Power Deliv. 2024, 39, 3450–3461. [Google Scholar] [CrossRef] [Scilit]
  28. Kong, L.; Tang, H.; Wu, C.; Wang, J.; Wu, P.; Wang, Y.; Blaabjerg, F. Analysis and Damping of Sub-Synchronous Oscillations for Cascaded Grid-Forming Converters Considering DC-Link Dynamics. IEEE Trans. Power Electron. 2025, 40, 2284–2299. [Google Scholar] [CrossRef] [Scilit]
  29. Avdiaj, E.; Beerten, J. Control of MMC-Based Grid-Forming STATCOM with DC Supercapacitors for Energy Storage. In Proceedings of the 2023 IEEE Belgrade PowerTech, Belgrade, Serbia, 25–29 June 2023; pp. 1–6. [Google Scholar] [CrossRef] [Scilit]
  30. Zhao, F.; Wang, X.; Zhu, T. Power Dynamic Decoupling Control of Grid-Forming Converter in Stiff Grid. IEEE Trans. Power Electron. 2022, 37, 9073–9088. [Google Scholar] [CrossRef] [Scilit]
  31. Mitsugi, Y.; Baba, J. Phaser-Based Transfer Function Analysis of Power Synchronization Control Instability for a Grid Forming Inverter in a Stiff Grid. IEEE Access 2023, 11, 42146–42159. [Google Scholar] [CrossRef] [Scilit]
  32. Chen, M.; Zhou, D.; Blaabjerg, F. Enhanced Transient Angle Stability Control of Grid-Forming Converter Based on Virtual Synchronous Generator. IEEE Trans. Ind. Electron. 2022, 69, 9133–9144. [Google Scholar] [CrossRef] [Scilit]
  33. Yuan, L.; Hu, M.; Su, M.; Liu, Z.; Sun, Y.; Dong, Z.Y. PCH Theory-Based Energy Reshaping Control for Transient Stability Enhancement of Grid-Connected Grid-Forming Inverters. IEEE Trans. Ind. Electron. 2026. [Google Scholar] [CrossRef] [Scilit]
  34. Tozak, M.; Taskin, S.; Sengor, I.; Hayes, B.P. Modeling and Control of Grid Forming Converters: A Systematic Review. IEEE Access 2024, 12, 107818–107843. [Google Scholar] [CrossRef] [Scilit]
  35. Si, W.; Fang, J.; Chen, X.; Xu, T.; Goetz, S.M. Transient Angle and Voltage Stability of Grid-Forming Converters with Typical Reactive Power Control Schemes. IEEE J. Emerg. Sel. Top. Power Electron. 2025, 13, 2917–2927. [Google Scholar] [CrossRef] [Scilit]
  36. Fan, Y.; Han, M.; Wang, S.; Zhang, L.; Xie, W. Transient Stability Analysis of Grid-Forming Converter in Current Limiting Mode Based on Hamiltonian Theory. IEEE Trans. Power Deliv. 2025, 40, 1836–1846. [Google Scholar] [CrossRef] [Scilit]
  37. Sun, P.; Tian, Z.; Zha, X.; Huang, M.; Tao, Y.; Shao, C.; Ma, X. Hybrid Power Synchronization Based Transient Stability Enhanced Control for Grid-Forming Inverters Under Symmetrical Grid Fault. IEEE Trans. Power Electron. 2025, 40, 2780–2796. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.