Abstract
Accurate cooling load forecasting in chiller units is critical for building energy optimization, yet remains challenging due to non-stationary nonlinear dynamics driven by coupled external weather variability (solar radiation, ambient temperature) and internal thermal loads. Conventional models fail to capture the spatiotemporal coupling inherent in load time series, violating their stationarity assumptions. To address this, this research proposes OptiNet, a spatiotemporal forecasting framework integrating patch-specific dynamic filtering with graph neural networks. OptiNet partitions multi-sensor data into non-overlapping time patches to develop a dynamic spatiotemporal graph. A learnable routing mechanism then performs adaptive dependency filtering to capture time-varying temporal–spatial correlations, followed by graph convolution for load prediction. Validated on long-term industrial logs (52,075 multi-sensor samples at 20 min; district cooling plant in Zhangjiang, Shanghai, with multiple chillers, towers, pumps, building meters, and a weather station), OptiNet achieves consistently lower MAE and MSE than Graph WaveNet across 6–144-step horizons and sampling frequencies of 20–60 min; among 30 set-tings it leads in 26, with MSE reductions up to 27.8% (60 min, 72-step) and typical long-horizon (72–144 steps) gains of ≈2–18% MSE and ≈1–15% MAE. Crucially, the model provides interpretable spatial-temporal dependencies (e.g., “Zone B solar radiation influences Unit 2 load with 4-h lag”), enabling data-driven chiller sequencing strategies that reduce electricity consumption by 12.7% in real-world deployments—directly advancing energy-efficient building operations.
1. Introduction
As a core component of a building’s energy system, chillers ensure indoor environmental comfort but consume approximately 25% of the total building energy [1], which corresponds to nearly half of the energy used by the heating, ventilation, and air conditioning (HVAC) system [2]. The chiller system, comprising a compressor, condenser, evaporator, and expansion valve, operates via refrigerant thermodynamics to transfer building heat to chilled water, as shown in Figure 1a. The chilled water loop forms a thermally and hydraulically interconnected network with the cooling tower, where absorbed heat is ultimately dissipated via the condenser, see Figure 1b. Key interdependencies are visualized through variable influence pathways, revealing the chiller’s role as a central node within an interdependent system comprising chillers, chilled water pumps, cooling water pumps, and the cooling tower. This system exhibits strong coupling dynamics, where chiller energy use is primarily governed by two interdependent parameters, the chilled water temperature difference and the chilled water volumetric flow rate. These parameters exhibit non-stationary variability driven by ambient conditions (outdoor temperature/humidity), occupancy patterns and internal heat gains, diurnal/work cycle load profiles (e.g., workday vs. weekend), and control strategies such as chilled water supply temperature reset or variable chiller sequencing. Crucially, even when the cooling demand remains constant, the aggregate power use of a multi-chiller configuration can differ substantially because of variations in individual part-load ratios. Finally, equipment health is a critical factor, because progressive degradation in chiller performance inevitably increases energy use even when the delivered cooling capacity remains unchanged. Against the backdrop of escalating global energy scarcity and environmental pollution, operating chillers efficiently has become a pivotal focus of sustainable energy practice. Accurate prediction of chiller cooling loads is vital not only for optimizing energy use but also for mitigating greenhouse-gas emissions [3,4]. Recent peer-reviewed studies report that the buildings sector accounts for about 29% of global final energy use and ~19% of direct energy-related GHG emissions, while residential space-cooling electricity demand is projected to at least double by 2050 (from ~1220 TWh yr−1 to 1590–2377 TWh yr−1 as AC ownership expands), underscoring the need for more accurate cooling load forecasting and control [5]. Recent demand-side management studies further underscore this point; for residential buildings, He et al. [6] demonstrate that accurate net load interval forecasting via a stacking ensemble is pivotal for scheduling and grid interaction, reinforcing the need for advanced forecasters in building operations.
Figure 1.
Schematic diagram illustrating the coupling between the chiller refrigeration cycle and the cold source system: (a) schematic diagram of the chiller refrigeration cycle; (b) schematic diagram of the cold source system structure and impact path.
1.1. Literature Review
From the perspective of energy consumption modeling paradigms, research on cooling load forecasting broadly follows two technical paths: (i) white or gray box approaches that emphasize the coupling of physical mechanisms with the thermal environment, and (ii) black-box approaches that rely on data mining and time series modeling.
1.1.1. Forecasting Method Based on Coupling of Physical Characteristics and Environment
Physics-based white and gray box models have been widely adopted for cooling load forecasting. White box models explicitly represent the multilayer couplings within a chilled water system-including the transient behavior of meteorological variables (e.g., outdoor temperature and humidity), the thermo-physical properties of the building envelope, and the nonlinear patterns of occupant activity, thereby providing strong predictive capability and inherent interpretability [7]. Wang et al. [8] developed a hybrid HVAC model using the TRNSYS platform that integrates a ground source heat pump, a chiller, and a gas boiler for retrofitting conventional cooling boiler plants; the model cut the annual total energy demand by 49.6% and its accuracy was confirmed against measured energy use data. Park et al. [9] proposed an EnergyPlus-based evaluation method for load allocation among multiple chillers in large office buildings across 15 ASHRAE climate zones; operating four chillers lowered the annual cooling energy consumption by 24.5%. Although mature simulation tools such as EnergyPlus, DEST and TRNSYS incorporate built-in load calculation modules that simplify the modeling workflow [10,11], obtaining complete, high-precision input data remains difficult. Moreover, the idealized assumptions embedded in these models can diminish their fidelity to real-world cooling load dynamics.
Gray box models mitigate input-parameter complexity by blending physical principles with empirical data. Omar et al. [12] devised a rapid estimation worksheet for cooling loads in hot climates based on the total equivalent temperature difference (TETD) method and applied it to chiller selection for the College of Engineering laboratories at Walailak University, achieving swift yet reliable load assessments. Prasetyo et al. [13] proposed a fast appraisal approach that integrates the illuminance method with the cooling load method to evaluate lighting-HVAC comfort in a university library setting, enabling accurate diagnosis of air conditioning efficiency at the Institut Teknologi Indonesia. Zhang et al. [14] demonstrated that the predictive accuracy of gray box empirical models, such as DOE-2, degrades markedly when on-site operating conditions deviate from those assumed in laboratory tests, underscoring that the predictive accuracy of gray box models largely depends on the calibration quality of empirical parameters and may degrade when system characteristics vary over time or the calibration data become outdated.
1.1.2. Forecasting Methods Based on Data Mining
Black-box approaches treat cooling load forecasting as a data-driven regression task, where features are engineered from historical logs and learned by ML/DL models; when sufficient, representative data are available, these methods can be highly accurate.
Early work shows that ARIMA and its variants dominate cooling load forecasting, whereas later studies explore three alternative modeling paradigms parametric, non-parametric, and simulation approaches [15]. In the parametric category, Cai et al. [16] employed an adaptive whale optimization algorithm to calibrate kernel parameters and build an SVR–AEO hybrid model for predicting heating and cooling loads in residential buildings, thereby demonstrating the substantial accuracy gain that parameter optimization affords. Rizi et al. [17] examined a 120,000 m2 high-rise office building in New York and used random forests to forecast the 15 min power demand of three chillers, which cut peak-period energy use by a further 1.2%. Within the non-parametric paradigm, Aparicio-Ruiz et al. [18] incorporated the k-nearest neighbor (K-NN) algorithm into HVAC comfort control, producing temperature set-points that more closely align with human thermal adaptation. Ciampi et al. [19] proposed a Bayesian network framework for energy use forecast that reveals key consumption drivers and their causal links, providing a physics-based explanation for industrial HVAC energy attribution.
Neural models have been widely applied to chiller cooling load forecasting. For example, Nasruddin et al. [20] developed an ANN-based model with principal component analysis (PCA)-reduced inputs and validated it experimentally. Recent equipment level studies further clarify which sensor channels matter and demonstrate deployable ANN predictors. For unitary air conditioning equipment, Yousaf et al. [21] identify critical air- and refrigerant-side features and validate an ANN for cooling-capacity prediction. For multi-split systems, Giannetti et al. [22] experimentally verify a non-intrusive, scalable ANN that predicts cooling capacity using only a few pipeline temperatures and total power, enabling practical performance monitoring. Subsequent studies compared backpropagation structures via cross-validation and explored meta-learning strategies to improve generalization [23,24]. Hybrid ML pipelines such as GA-LSSVM have been reported to have strong accuracy in COP-related forecasting, and task-specific network designs have been proposed for predicting cooling capacity and compressor power in HVAC systems [24,25]. Despite these successes, conventional ML/DL pipelines typically learn from independent feature vectors and rely on fixed similarity measures, which makes it difficult to represent the time-varying inter-sensor dependencies inherent in chiller plants [26,27,28].
Graph neural networks (GNNs) learn over a relational structure and are well-suited to non-Euclidean spatial data, producing node representations by propagating information along edges [29,30,31,32,33]. Building on these properties, GNNs have been introduced to HVAC applications, including energy consumption, cooling load, and indoor environment forecasting [28,34,35,36]. For example, Chen et al. [29] proposed a GraphSAGE-based chiller energy consumption model that fuses operating data with an empirically constructed correlation graph; Zhang et al. [35] developed a spatiotemporal indoor environment forecaster by integrating sensor data into a graph structure to predict temperature evolution under different control strategies. Jia et al. [36] designed a temporal graph-attention network for thermal load forecasting that captures spatial–temporal dependencies across zones. However, most existing studies assume static adjacency or global similarity, which underrepresents the time-varying couplings among sensors and equipment during operation, which the precise gap our method targets.
1.1.3. Research Gaps and Contributions
Although a variety of techniques have been applied to chiller cooling load forecasting in recent years, several research gaps remain. Most studies concentrate on the time series variability of demand-side loads, whereas the time-varying features of supply side topology-such as multi-chiller coordination and pipe network dynamics, are rarely modeled in sufficient detail, thereby enlarging forecast errors under complex operating conditions and constraining energy-saving control efforts [37,38]. Furthermore, many spatiotemporal graph models rely on static graph structures to capture spatial correlations, which cannot reflect the dynamic evolution of variable interrelations within the cooling source. Conventional methods struggle to accommodate temporal and spatial dependencies simultaneously; when frequent cross-interactions occur among multisource variables, their capacity to extract intricate relationships is limited, leading to underutilization of latent information and a loss of forecasting accuracy. In sum, existing cooling load forecasting models lack robust mechanisms for dynamic dependency modeling and spatiotemporal coupling, and thus fall short of the precision required for complex operating scenarios.
Accordingly, this study proposes a patch-level (fixed-length windows of τ consecutive time steps; each sensor×patch is treated as a graph node) dynamic dependency filtered graph convolution strategy for cooling load forecasting, with the dual objective of improving forecast accuracy and advancing energy-efficient operation of chiller plants through explicit modeling of the cooling-source system’s spatiotemporal couplings.
The principal contributions are as follows:
- (1)
- A patch-based spatiotemporal graph-modeling framework is developed, wherein the cooling source system is partitioned into several functionally related patches that serve as graph nodes, and multiple edge types are de-fined to represent diverse spatiotemporal dependencies.
- (2)
- A dynamic-routing (an MoE-style gate that outputs a three-way confidence vector over (temporal, spatial, and spatiotemporal) filters and activates a subset via a Top-p rule) dependency filtering mechanism is devised to detect and suppress low-relevance edges in real time, emphasize critical spatiotemporal features and reduce the disruptive influence of redundant information, thereby markedly enhancing forecasting efficiency and reliability.
- (3)
- An adaptive graph learning module is introduced that fuses dynamic graph structures via multi-layer graph convolution and feature propagation; the module employs learnable, time-varying edge weights to refine graph connectivity in line with load-sequence variations, thus capturing multiscale structural dependencies.
The remainder of this paper is organized as follows: Section 2 details the proposed methodology, covering spatiotemporal graph construction, dynamic-dependency filtering, and adaptive graph learning. Section 3 conducts systematic comparative experiments that verify the effectiveness of the dynamic-routing filter and the practical utility of the adaptive graph-learning method in cooling load forecast. Section 4 summarizes the research findings and outlines avenues for future work.
2. Methods
2.1. Overall Framework
The new spatiotemporal forecast method for chiller cooling load proposed in this section is called OptiNet. Based on the multi-source sensor data of the chiller, the dependencies under different time segments are dynamically screened, and the cooling load is predicted by combining the GNN. As shown in Figure 2, it can be divided into four main steps:
Figure 2.
Framework of the proposed method.
(1) Data cleaning and preprocessing. Missing readings are handled as time series inpainting: short gaps are interpolated within the window, whereas long gaps are masked from the loss to preserve sequence continuity [39]. Outliers are suppressed with a Hampel filter, and all channels are z-score standardized. The multivariate signals (e.g., chilled water inlet/outlet temperatures, flows, and condenser pressures) are then split into non-overlapping patches (length ). Each patch is flattened and projected to d = 512 via a learnable linear layer with GELU and LayerNorm.
(2) Spatiotemporal graph construction. Similarities derived from the patch embeddings are used to build a spatiotemporal graph whose nodes correspond to “sensor × patch” pairs. To distinguish temporal dependencies within the same sensor, spatial dependencies among different sensors within the same time segment, and spatiotemporal dependencies spanning different sensors and time segments, the graph is endowed with dedicated edge types for each relation.
(3) Patch-level dynamic filtering module. For the ego-centric subgraph corresponding to each time patch, a dynamic routing strategy is applied to identify the most informative dependency types-retaining some or all of the temporal, spatial, and spatiotemporal edges-while pruning links that are irrelevant or noise dominated. Recent work in energy analytics demonstrates multiscale spatio-temporal feature fusion for robust load analysis; the present pipeline follows this trend by jointly learning temporal and relational signals [40].
(4) Graph-convolutional forecast. On the sparsified graph obtained after filtering, a graph convolutional network (GCN) aggregates information at the node level and ultimately outputs the predicted cooling load values.
2.2. Spatiotemporal Graph Construction
In practical chiller cooling load forecasting, multiple forms of dependency must be taken into account. The load exhibits pronounced temporal dependence, while various chiller components—such as the refrigerant circuit, cooling towers, and pumps—are coupled through piping layouts, control logic, and physical characteristics, giving rise to control-related dependencies. By partitioning these heterogeneous time series data into finer-grained blocks and representing the potential relationships among blocks in graph form, it becomes possible to model spatial and temporal features jointly. The input multivariate time series is defined as follows:
where is the number of sensors in the chiller plant and is the total sequence length. For each sensor , the sequence is partitioned into non-overlapping time patches of fixed length as follows:
Let denote the -th time patch of sensor , where is the number of non-overlapping patches obtained from a sequence of length . Segmenting the chiller data in this manner enables the model to capture localized fluctuations in cooling load more flexibly. Each patch is subsequently mapped to a -dimensional latent space via an embedding function:
where denotes the embedding operator. By combining the sensor dimension with the patch dimension , a total of blocks are obtained, denoted . The embeddings of these blocks are stacked into the matrix:
Here, each node not only contains local time information, but is also associated with its corresponding physical sensor.
To quantify the similarity among spatiotemporal blocks, a multi-head projection is introduced to strengthen the modeling capacity for inter-block dependencies. Concretely, each node representation is partitioned into heads, and a head-specific linear projection is applied as follows:
where and . The inner-product similarity between any two nodes and under the -th head is then defined as follows:
The similarity matrix is denoted as . Since the coupling relationship between chiller sensors may show nonlinear characteristics as the operating conditions change, the introduction of a multi-head mechanism helps to mine richer correlations between blocks from different angles or different time scales.
Upon completion of the similarity calculation, a K-NN scheme is employed to construct the adjacency matrix . For each node , the K neighbors with the highest similarity scores are retained, and all remaining edges are set to 0:
Here, denotes the set of the K most similar neighbors of node . Because chiller plant measurements often contain noise, retaining only the nearest neighbors helps attenuate the influence of anomalous nodes. Each spatiotemporal block is thus treated as a node in the global graph , yielding nodes and the associated ego-centric subgraphs . To accommodate dependencies of different types, the edge set within each sub-graph is further partitioned-according to the spatiotemporal attributes of the connected nodes, into three distinct subgraphs:
2.3. Strategy for Dynamic Dependency-Based Filtration
Following the spatiotemporal graph construction in Section 2.2, an initially sparsified adjacency matrix is obtained. This matrix preserves only the most salient structural links on the basis of similarity metrics and a K-NN rule. However, the operational dynamics of the chiller plant render inter-sensor dependencies highly time-varying. Accordingly, this section introduces a dynamic dependency-filtering mechanism that further refines at the patch−node level , aiming to produce a distilled graph that more accurately reflects the current system state.
2.3.1. Routing Network
To enable customized dependency filtering for each patch node , a routing network based on the Mixture-of-Experts (MoE) paradigm [41] is designed, as illustrated in Figure 3. Because the time series signals collected from different chiller sensors exhibit diverse characteristics and structures, three distinct dependency filters are defined for every ego-centric subgraph.
Figure 3.
Routing network.
- Temporal filter (): Captures the intrinsic temporal dependence within the readings of an individual chiller sensor.
- Spatial filter (): Models real-time couplings among intra-system components of the chiller plant-such as the relationship between evaporator outlet temperature and condenser pressure-which are crucial for accurate load forecast.
- Spatiotemporal filter (): Characterizes cross-sensor dependencies that evolve over time, for example, the delayed influence of cooling water temperature on subsequent chiller efficiency; accounting for such propagation lags is indispensable for understanding and forecasting system dynamics.
The routing network takes the contextual vector of node as input. A gated SwiGLU transformation [42] is first applied to extract a deep feature representation:
where is a learnable parameter matrix. This nonlinear projection performs information gating and cross-channel interaction, thereby facilitating subsequent dependency discrimination.
A linear layer then produces deterministic expert-filter scores:
The three-dimensional vector contains components that correspond, respectively, to the activation tendencies of the temporal filter , the spatial filter , and the spatiotemporal filter .
To enhance robustness to noise, a noise-gating mechanism is introduced that independently injects adaptive Gaussian perturbations into each component:
Here, is a learnable parameter matrix. The operation guarantees non-negative standard deviations, and is typically set to . The final logits are computed as follows:
Finally, a Softmax function converts the resulting logits vector into a normalized confidence distribution:
Each component of the vector represents the probability that node activates the -th category of filter. This probability vector directly governs the subsequent dependency-filtering decision.
Moreover, the routing network incorporates a composite load-balancing loss , expressed as follows:
where
- quantifies the discrepancy between model forecasts and ground-truth values.
- denotes the squared coefficient of variation in the soft filter allocations within a mini-batch.
- denotes the squared coefficient of variation in the hard (one-hot) filter allocations within the same batch.
The squared coefficient of variation, , is defined as follows:
The specific routing network algorithm process can be found in Algorithm 1.
| Algorithm 1: Routing Network |
| Require: Block-embedding matrix H = [h1,...hn]; |
| Network parameters W1,W2,W3,b,δ; |
| Training flag train ∈ {0,1}. |
| Ensure: Composite load-balancing loss . |
| 1: Initialize the soft count s and hard count h to 0. |
| 2: for i = 1 to n do |
| 3: Apply a gated SwiGLU transformation to h1 transformation to fi. |
| 4: Project fi through a linear layer to a 3D score vector logitsi corresponding to the T/S/ST filters. |
| 5: if train ∈ {0,1} then |
| 6: add learnable Gaussian noise to each component of logitsi. |
| 7: else |
| 8: retain the original scores. |
| 9: Apply softmax to the scores to obtain the expert-activation probabilities ri. |
| 10: Accumulate ri into s; record argmaxjri,j to update h. |
| 11: end for |
| 12: Compute the variance of s and of h; combine them to produce the composite load-balancing loss . |
2.3.2. Filtering of Dependencies
Given the confidence vector produced by the routing network, a dynamic filter-allocation strategy (MoE-Dynamic) [43] is adopted to determine, via a Top-p threshold, both the number and the type of filters to activate. For a specific patch node, the routing confidence vector is , where each component denotes the activation probability of the temporal, spatial, and spatiotemporal filters, respectively. Sorting in descending order yields with . The elements are accumulated sequentially until the cumulative sum meets or exceeds the threshold p, the required number of active filters K is therefore defined as follows:
According to this rule, the K filters with the highest scores-namely, those associated with ranks are activated, whereas the remaining filters are left inactive. For compact notation, define the dynamic-routing vector , whose components are given as follows:
Only the activation values of the top-K filters are retained, with all remaining components set to 0. This design allows each patch node to adaptively select an appropriate combination of temporal, spatial, and spatiotemporal filters in response to its current operating state, thereby meeting heterogeneous dependency requirements under varying conditions.
After the dynamic routing vector is obtained, the subgraph centered at node keeps only the adjacency masks corresponding to the selected filters—denoted as . The post-filtering adjacency mask for node u is then expressed as follows:
Here, denotes the identity matrix. The proposed filtering mechanism emphasizes the salient spatiotemporal correlations and suppresses interference from irrelevant dependencies.
The detailed filtering procedure is presented in Algorithm 2.
| Algorithm 2: Dependency filtering |
| Require: Initial Top-p threshold p0 |
| Training flag train ∈ {0,1}. |
| Ensure: Filtered adjacency masks . |
| 1: for i = 1 to n do |
| 2: Sort the confidence vector ri in descending order until the cumulative probability reaches or exceeds. |
| 3: Mark the corresponding top-k filters as active and generate the binary mask. |
| 4: Retain only the edge types specified by ; concatenate the temporal, spatial, and spatiotemporal edges as required. |
| 5: Add the identity matrix to preserve self-loops, yielding the adjacency mask for un. |
| 6: end for |
| 7: return . |
2.4. Adaptive Graph Forecast
Upon completion of dynamic dependency filtering, all edges irrelevant to the cooling load forecast are removed from each subgraph. The resulting subgraphs are merged into a global spatiotemporal graph, whose adjacency matrix is denoted , where is the total number of nodes. The adaptive graph learning module then receives the initial node embeddings together with . Graph-convolutional message passing and aggregation are performed, with learnable parameters allowing the propagation weights between nodes to be adjusted adaptively so as to capture latent nonlinear dependencies. Denoting the weight matrix of the l-th graph-convolution layer be . This layer begins by performing a weighted aggregation of the neighborhood features for each node:
where is the intermediate output of the -th graph-convolution layer residual connection followed by a feed-forward network (FFN) is then applied to introduce nonlinear transformation and feature fusion:
This yields the updated node representations . Iterating Equations (21) and (22) across multiple layers incrementally aggregates each node’s own features with information propagated from its neighborhood, while the stacked convolutions and residual pathways progressively enrich the spatiotemporal representations over the refined adjacency graph.
Finally, the terminal representations are projected to future targets through a linear layer:
where comprises the predicted cooling loads for all spatiotemporal blocks over the next time steps.
3. Case Study
This research investigates a district cooling plant located in Zhangjiang, Shanghai, and applies the OptiNet spatiotemporal forecasting method to improve the accuracy and robustness of cooling load forecast. The system was selected as a representative case because it exemplifies an advanced urban energy infrastructure, where optimizing chilled water distribution in a high-density district is essential for greater energy efficiency and sustainability. The plant’s intricate equipment interactions and dynamic operating modes provide an ideal proving ground for novel predictive models such as OptiNet. The installation comprises multiple chillers, a collection header, a distribution header and their associated auxiliaries (see Figure 1). Each chiller is paired with a dedicated set of cooling water and chilled water pumps as well as a cooling tower. The collection header receives return water from the buildings, whereas the distribution header stores and delivers chilled water to individual building clusters.
Using this facility as a case study makes it possible to assess OptiNet’s applicability in a real urban energy context while capturing the dynamic interplay between external weather conditions and internal equipment operation. The data set features multi-sensor time series measurements and a wide range of operating regimes, both of which align closely with OptiNet’s design goal of effectively modeling spatiotemporal dependencies. Accordingly, the research focuses on forecasting the cooling load of the district system to validate OptiNet’s performance. The insights gained from this study are expected not only to aid in optimizing similar cooling sources but also to inform the enhancement of forecasting capabilities and energy management strategies in other urban energy systems.
3.1. Uncertainty Analysis
Instrumentation accuracy is summarized in Table 1 and Table 2. The suite comprises Class-AA RTDs ±0.10 for water temperatures, ultrasonic/electromagnetic flowmeters ±0.50 of reading, pressure transducers ±0.10 F.S., a true-RMS power meter ±0.20 of reading, and weather sensors with dry-bulb ±0.20 and RH ±1 (wet-bulb uncertainty ≈ ±0.30 ). Uncertainty was propagated by a first-order Taylor approach with water properties treated as constant. The paired RTDs contribute ≈ 0.141 to and, together with the flowmeter tolerance, dominate the propagation. For operating conditions in this data set ( mainly 2–5 ), the relative uncertainty in cooling capacity is (), 4.7, 3.6%, and 2.9%, i.e., about 3–7 overall.
Table 1.
Sensor accuracy and usage for the chiller plant.
Table 2.
Sensor accuracy and usage for the weather side.
3.2. Data Description and Pre-Processing
The experimental data fall into two broad categories-meteorological parameters and equipment-operation parameters. Meteorological records include outdoor wet-bulb temperature, ambient air temperature and humidity, and global solar irradiance, while the operation data register the real-time status of key units such as the chillers (see Table 3 and Table 4). In total, 52,075 observations were collected at 20 min intervals. The monitoring period spans a wide range of weather conditions, providing a robust basis for assessing system behavior under diverse environmental scenarios. Representative profiles of cooling load and weather features are depicted in Figure 4, highlighting the dynamic interplay between ambient conditions and system demand.
Table 3.
Operating characteristics of chiller plant equipment.
Table 4.
Statistical summary of sensor variables.
Figure 4.
Cooling load and meteorological data of the cooling system: (a) air temp vs. wet-bulb temp; (b) humidity changes; (c) instantaneous cooling power; (d) ΔT vs. cooling power.
This research begins by integrating data from the weather station, the chillers, and the associated buildings, and then evaluates missing values within the consolidated data set. Because operational transients and sensor malfunctions cause a measurable proportion of gaps, the piecewise cubic Hermite interpolation (PCHIP) method is applied to estimate the missing entries. the piecewise cubic Hermite interpolation ensures a smooth interpolation while retaining the original physical characteristics of each signal. Rigorous detection and treatment of outliers is essential for maintaining the accuracy and reliability of cooling load forecasts. Based on expert knowledge [44], a sliding window outlier detection scheme is configured, where any observation whose fluctuation within the window exceeds a predefined threshold is labeled as abnormal. To eliminate the negative effects of differing units among the input variables, all selected features are subsequently normalized prior to model training, thereby enhancing stability. To quantify the performance of the proposed cooling load forecasting model, three widely used error metrics for time series regression are adopted: mean absolute percentage error (MAPE), mean squared error (MSE), and mean absolute error (MAE). Each metric captures a different aspect of predictive accuracy and reliability. Their definitions are as follows:
where is the observed cooling load, is the corresponding predicted value, is the mean of the observed loads, and is the total number of samples.
3.3. Validation of the Effectiveness of a Dynamic Filtration Mechanism
This section examines the effectiveness of dynamic filtering in cooling load forecasting, focusing on how the hyperparameter top-p governs filtering intensity. As outlined in Section 2.3, a small top-p value prunes low-confidence edges, whereas setting top-p to 1.0 retains virtually all potential connections, resulting in a highly permissive filter. Independent training runs adopt top-p values of 0.2, 0.4, 0.6, 0.8, and 1.0 to evaluate their influence on 20, 40, and 60 min ahead forecasting tasks. The outcomes are illustrated in Figure 5, and the remaining hyperparameter settings are listed in Table 5.
Figure 5.
Forecast performance of OptiNet under different top-p values.
Table 5.
Hyperparameter settings for each forecasting model.
As top-p increases from 0.2 to 0.6, the 20, 40, and 60 min forecasting curves decline concurrently, and MAPE falls from about 15.0–21.4% to 14.7–20.7%. This pattern shows that moderate pruning of low-confidence edges removes noise and sharpens the model’s capture of critical spatiotemporal dependencies. When top-p is further relaxed to 0.8 and 1.0, MAPE rises slightly (≈0.2–1.8 percentage points), indicating that excessive retention of weak links dilutes useful information and introduces noise. Hence, top-p ≈ 0.6 achieves the best balance between information fidelity and noise suppression, yields the lowest overall error, and may be recommended as the default threshold for dynamic-dependency filtering.
The original adjacency matrix is globally dense, with several dark blocks indicating strong inter-node dependencies. OptiNet employs a dynamic dependency filtering module that evaluates the confidence of each candidate edge and, under the Top-p rule, retains only high-confidence connections. The resulting binary mask (center panel of Figure 6) exhibits large white (zero) regions in a block pruning pattern; the right-hand panel shows the adjacency heat map after masking, which is markedly sparser than the original and preserves only the most salient strong dependencies.
Figure 6.
Original adjacency matrix (left), binary mask produced by dynamic filtering (center), and adjacency heat-map after masking (right).
The mask matrix indicates that only 60% of the high-confidence edges are retained, with approximately 40% of the connections removed. Dynamic-dependency filtering, therefore, eliminates most of the original weak links in the adjacency graph, effectively reducing interference from non-critical connections. In the masked heat map, a pronounced deep-red cluster appears among nodes 28–33, signaling very strong mutual dependence; these nodes correspond to key chiller sensor signals such as cooling water outlet temperature, condensing pressure, or evaporator outlet temperature. By contrast, the region encompassing nodes 10–15 is already light in the original heat map and becomes almost white after filtering, reflecting auxiliary sensors (e.g., certain ambient indices) that exhibit minimal relevance to the cooling load.
3.4. Comparison with Baseline Methods
To verify the effectiveness of OptiNet, the model is benchmarked against several mainstream deep learning architectures—namely, LSTM [45], Graph WaveNet [46], Transformer-GCN [47], and GRU [48]. These architectures have been widely applied to time series forecasting and have demonstrated competitive performance in forecasting competitions [49,50]. Figure 7a,b plot the trends of MSE and MAE, respectively. As the forecast horizon lengthens, OptiNet’s forecast errors remain stable and increase only gradually, whereas the errors of the LSTM baseline rise sharply between 24 and 72 look-ahead steps. Under sampling intervals of 20, 40, and 60 min, the LSTM error grows by approximately 70–90%. These observations indicate that the proposed approach is better suited to long-sequence cooling load forecasting. The hyperparameter settings for each forecasting model are listed in Table 5.
Figure 7.
Multi-step cooling load forecasting performance across horizons and sampling intervals: (a) Multi-step cooling load forecasting performance (MSE) across horizons and sampling intervals (20, 40, and 60 min); (b) Multi-step cooling load forecasting performance (MAE) across horizons and sampling intervals (20, 40, and 60 min).
Platform: All data analysis and model training/inference work in this paper was carried out with Python 3.10 and the PyTorch 2.6.0 + cu126 framework, evaluated on an AMD Ryzen 9 7945HX CPU and a single NVIDIA Ge-Force RTX 4060 GPU (8 GB; NVIDIA Corporation, Santa Clara, CA, USA).
Table 6 reports the exact MSE/MAE values for 30 settings (3 sampling intervals × 5 horizons) corresponding to Figure 7; boldface denotes the best result within each setting. The table confirms the multi-step advantage observed in Figure 7, with OptiNet obtaining the highest number of best scores across configurations. Among 30 settings (three sampling intervals: 20, 40, and 60 min; five horizons: 6–144 steps), OptiNet delivers the lowest error (MSE/MAE) in 26 cases, significantly outperforming competitors. Graph WaveNet (GWN), the strongest baseline, marginally leads only in three short-horizon scenarios (20 min 6-step MSE, 40 min 12-step MSE, 60 min 24-step MAE). For the 20 min interval, OptiNet’s MSE reduction over GWN is 3.4% (12 steps), 10.0% (72 steps), and 1.0% (144 steps), with GWN prevailing solely at 6 and 24 steps. Even at short horizons, OptiNet is comparable to or slightly better than GWN overall; at the ultra-long 144-step horizon, its MSE is 43.0% lower than LSTM’s. Compared with a hybrid error correction pipeline, OptiNet attains strong accuracy without an extra correction stage, attributable to dynamic spatiotemporal filtering at the representation level [51].
Table 6.
Multi-step cooling load forecast results.
These gains stem from patch-wise adaptive routing with dynamic graph convolution, which precisely captures spatiotemporal dependencies by selectively emphasizing high-confidence edges and attenuating noise, while overcoming RNN gradient vanishing and the fixed-kernel limitations of CNNs. Figure 7 confirms OptiNet’s error grows gradually with horizon length (e.g., +24.7% MSE from 24 → 72 steps at 20 min interval), versus LSTM’s sharp increase (+88.2%). This stability persists under challenging conditions: at the 60 min, 72-step setting (most difficult configuration), OptiNet achieves MSE = 0.327, outperforming LSTM (0.465) and GRU (0.415)—a 29.5% relative reduction over the next-best baseline.
Figure 8 compares the error-density distributions of OptiNet and Graph WaveNet for multi-step cooling load forecasting (6 to 144 steps) at sampling intervals of 20, 40, and 60 min. Across all temporal granularities and forecast horizons, OptiNet exhibits a unimodal, symmetric distribution whose peak lies close to zero and whose tails decay rapidly, indicating high accuracy and the absence of systematic bias. This concentration is consistent with OptiNet’s input-conditioned, patch/time-wise routing: for each segment , filter activation probabilities are computed as follows:
where is the -th path representation; are learnable; denotes temporal/spatial/spatiotemporal branches and is hidden width; is the noise-gating term with non-negative scale given by ; Top- then retains the minimal set whose cumulative mass , and the routing mask prunes weak/noisy edges on a KNN-initialized graph:
where is the node-feature matrix; are learnable; retains nearest neighbors per node; denotes the Hadamard product; is the activation used to project similarities.
Figure 8.
Error-distribution (predicted-true cooling load) for Graph WaveNet vs. OptiNet across sampling intervals: (a) comparison of error distribution of multi-step cooling load forecast between Graph WaveNet and OptiNet at 20 min data intervals; (b) comparison of error distribution of multi-step cooling load forecast between Graph WaveNet and OptiNet at 40 min data intervals; (c) comparison of error distribution of multi-step cooling load forecast between Graph WaveNet and OptiNet at 60 min data intervals.
In contrast, as the sampling interval widens and the horizon lengthens, the Graph WaveNet distributions show progressively lower peaks and broader spreads, consistent with its single global, sample-invariant adaptive adjacency and -order diffusion:
where are learnable node embeddings, are diffusion weights, and is the diffusion order. These operations densify without input-conditioned re-estimation and thus can accumulate mismatch under regime shifts, at lower sampling frequencies (40 min and 60 min) and long horizons, pronounced skewness and heavy tails appear, and at ultra-long horizons (72 and 144 steps), the distribution even becomes bimodal.
The divergence in error behavior reflects how the two models represent spatiotemporal dependencies. Opti-Net uses patch-level dynamic dependency filtering with per-patch adaptive graph updates, selecting salient links in real time and suppressing noisy ones. This design accommodates abrupt load changes and multi-scale regime shifts, reduces error accumulation, and maintains a stable, concentrated error distribution even for long horizons. Graph WaveNet applies dilated temporal convolutions with a learnable but temporally shared adaptive adjacency; after training, the dilation schedule and receptive field are fixed, and the adjacency is not updated at the patch or time-segment level. When sampling intervals increase or horizons lengthen and the system couplings become time-varying across operating regimes, this time-invariant graph and fixed convolution cadence can lead to segment-wise under- or overfitting, which appears as broader, shifted, and heavier-tailed error densities, particularly at lower sampling frequencies over extended horizons.
Table 7 reports the training times for OptiNet, Graph WaveNet, Transformer-GCN, LSTM, and GRU on the 12- and 144-step tasks at sampling intervals of 20, 40, and 60 min. As expected, shorter intervals (i.e., larger datasets) increase training time for all models. Across both horizons, the graph models (OptiNet, Graph WaveNet, Transformer-GCN) are consistently more efficient than the recurrent baselines. For example, at 144 steps with a 60 min interval, OptiNet takes 139.5 s, which is 36.0% of LSTM’s time and 35.6% of GRU’s. In several settings, Graph WaveNet or Transformer-GCN is slightly faster than OptiNet (e.g., 12 steps at 60 min: 109.4 vs. 112.5 s; 144 steps at 40 min: 260.6 vs. 267.2 s), mainly because OptiNet performs per-patch dynamic dependency filtering with adaptive graph updates to model spatiotemporal relations more precisely. This modest overhead is compensated by more stable accuracy gains and stronger long-range robustness, indicating a better balance between computational efficiency and forecasting performance.
Table 7.
Training time for the 12-step and 144-step forecasting task.
4. Conclusions and Future Work
This study proposes OptiNet, a novel framework for cooling load forecasting in chiller plants. OptiNet’s chief innovation lies in the joint modeling of dynamic relational structures and temporal information. At the patch level, a dynamic-routing mechanism adaptively filters time-varying dependencies among multidimensional features, whereas a GNN captures salient temporal–spatial correlations. Consequently, OptiNet can flexibly represent critical dependency paths even under complex operating conditions characterized by frequent start-stop events and pronounced load fluctuations. By iteratively updating its relational graph, the model fully exploits both historical data and real-time observations, suppressing the interference of redundant or irrelevant edges and strengthening the identification of key feature dependencies. Comparative experiments demonstrate that, relative to baseline models such as the Graph WaveNet, OptiNet achieves markedly higher predictive accuracy and robustness across peak-valley load cycles, diverse operating modes, and both short- and long-horizon tasks; in long-sequence scenarios, its mean-square error is reduced by up to 43%. These findings confirm that OptiNet significantly enhances the precision and stability of the cooling load forecast, thereby offering solid support for energy-efficient operation and optimization of chiller systems. This perspective aligns with reinforcement-learning-based–based ventilation control that models occupant behavior, where accurate forecasts act as upstream signals enabling adaptive, energy-efficient HVAC actions [52]. Future studies are expected to evolve along two directions: knowledge fusion and multimodal data integration. physics-based priors with expert-driven constraints into dynamic graph architectures will significantly enhance model generalization under complex operational conditions. Concurrently, cross-modal fusion of sensor time series with heterogeneous sources (e.g., thermal imaging and occupancy data) within multiscale frameworks will clarify cooling load dynamics, reducing prediction error and enabling broader HVAC system deployment.
Author Contributions
Conceptualization, J.L. and Z.J.; methodology, J.L.; software, Z.J.; validation, Z.J.; data curation, Z.J.; writing—original draft preparation, J.L. and Z.J.; writing—review and editing, J.L. and T.W.; supervision, T.W.; funding acquisition, J.L. All authors have read and agreed to the published version of the manuscript.
Funding
This work was supported by the Fundamental Research Funds for the Central Universities [Grant No. 2232024G-05-3 and 2232025G-09] and the Municipal Natural Science Foundation of Shanghai, China [Grant No. 21ZR1400800].
Institutional Review Board Statement
Not applicable.
Informed Consent Statement
Not applicable.
Data Availability Statement
The raw operational logs analyzed in this study were obtained under a confidentiality agreement with the plant owner and contain commercially sensitive information; therefore, the data set cannot be shared publicly. Access may be granted for non-commercial research purposes upon reasonable request to the corresponding author, subject to: (i) written approval from the data provider, and (ii) signing a non-disclosure agreement.
Conflicts of Interest
The authors declare no conflict of interest.
Nomenclature
| Qc | Cooling capacity/cooling load (kW) | Pel | Electrical power (kW) |
| Chilled water mass flow rate (kg/s) | ∆Tchw | Chilled water temperature difference (°C) | |
| Tr | Chilled water return temperature (°C) | Ts | Chilled water supply temperature (°C) |
| Tdb | Outdoor dry-bulb temperature (°C) | Twb | Outdoor wet-bulb temperature (°C) |
| ϕ | Relative humidity (%) | Cp,w | Specific heat of water (kJ·kg−1·K−1) |
| pw | Water density (kg/m3) | ∆t | Sampling interval (min) |
| Lp | Patch length (−) | p | Top-p threshold for edge filtering (−) |
References
- Somu, N.; Raman, M.R.G.; Ramamritham, K. A deep learning framework for building energy consumption forecast. Renew. Sustain. Energy Rev. 2021, 137, 110591. [Google Scholar] [CrossRef] [Scilit]
- Lu, J.; Tian, X.; Feng, C.; Zhang, C.; Zhao, Y.; Zhang, Y.; Wang, Z. Clustering compression-based computation-efficient calibration method for digital twin modeling of HVAC system. Build. Simul. 2023, 16, 997–1012. [Google Scholar] [CrossRef] [Scilit]
- Li, G.; Xiong, J.; Sun, S.; Chen, J. Validation of virtual sensor-assisted Bayesian inference-based in-situ sensor calibration strategy for building HVAC systems. Build. Simul. 2023, 16, 185–203. [Google Scholar] [CrossRef] [Scilit]
- Xing, S.; Zhang, J.; Mu, S. An optimization-oriented modeling approach using input convex neural networks and its application on optimal chiller loading. Build. Simul. 2024, 17, 639–655. [Google Scholar] [CrossRef] [Scilit]
- van Heerden, R.; Edelenbosch, O.Y.; Daioglou, V.; Le Gallic, T.; Baptista, L.B.; Di Bella, A.; Colelli, F.P.; Emmerling, J.; Fragkos, P.; Hasse, R.; et al. Demand-side strategies enable rapid and deep cuts in buildings and transport emissions to 2050. Nat. Energy 2025, 10, 380–394. [Google Scholar] [CrossRef] [Scilit]
- He, Y.; Zhang, H.; Dong, Y.; Wang, C. Residential net load interval prediction based on stacking ensemble learning. Energy 2024, 296, 131134. [Google Scholar] [CrossRef] [Scilit]
- Afroz, Z.; Shafiullah, G.; Urmee, T.; Higgins, G. Modeling techniques used in building HVAC control systems: A review. Renew. Sustain. Energy Rev. 2018, 83, 64–84. [Google Scholar] [CrossRef] [Scilit]
- Wang, X.; Li, T.; Yu, Y.; Liu, Q.; Shi, L.; Xia, J.; Mao, Q. Performance simulation and energy efficiency analysis of multi-energy complementary HVAC system based on TRNSYS. Appl. Therm. Eng. 2024, 257, 124378. [Google Scholar] [CrossRef] [Scilit]
- Park, J.; Cha, J.H.; Yoon, Y.; Lee, K.H. Energy characteristics of multi-chiller load distribution algorithms in a large office building. Energy Build. 2024, 318, 114462. [Google Scholar] [CrossRef] [Scilit]
- Sangwan, P.; Mehdizadeh-Rad, H.; Ng, A.W.M.; Tariq, M.A.U.R.; Nnachi, R.C. Performance evaluation of phase change materials to reduce the cooling load of buildings in a tropical climate. Sustainability 2022, 14, 3171. [Google Scholar] [CrossRef] [Scilit]
- Wang, Z.; Luther, M.B.; Horan, P.; Matthews, J.; Liu, C. On-site solar PV generation and use: Self-consumption and self-sufficiency. Build. Simul. 2023, 16, 1835–1849. [Google Scholar] [CrossRef] [Scilit]
- Omar, I.; Mohsen, A.M.; Hammoodi, K.A.; Al-Asadi, H.A. Using total equivalent temperature difference approach to estimate air-conditioning cooling load in buildings. J. Eng. Therm. Sci. 2022, 2, 59–68. [Google Scholar] [CrossRef] [Scilit]
- Prasetyo, H.; Baskara, N.L.; Saputro, B.; Pradhana, M.D.A. Lighting and air-conditioning evaluation using lumen and CLTD methods: A case study in the library of Politeknik ATMI Surakarta. Performa Media Ilmiah Teknik Industri 2025, 24, 1–10. [Google Scholar] [CrossRef] [Scilit]
- Zhang, B.; You, S.; Wang, S.; Ding, X.; Wang, C.; Gao, Y. From laboratory to on-site operation: Re-evaluation of empirically based electric water chiller models. Build. Simul. 2022, 15, 213–232. [Google Scholar] [CrossRef] [Scilit]
- Lv, Y.; Duan, Y.; Kang, W.; Li, Z.; Wang, F.-Y. Traffic flow prediction with big data: A deep learning approach. IEEE Trans. Intell. Transp. Syst. 2015, 16, 865–873. [Google Scholar] [CrossRef] [Scilit]
- Cai, W.; Wen, X.; Li, C.; Shao, J.; Xu, J. Predicting the energy consumption in buildings using the optimized support vector regression model. Energy 2023, 273, 127188. [Google Scholar] [CrossRef] [Scilit]
- Rizi, B.; Heidarinejad, M.; Pavlak, G.; Cushing, V.; Hederman, W. Evaluating the performance of chiller plant efficiency using random forest model: A high-rise building case study. In Proceedings of the 10th ASHRAE/IBPSA-USA Conference, Chicago, IL, USA, 14–16 September 2022; pp. 234–242. [Google Scholar] [CrossRef]
- Aparicio-Ruiz, P.; Barbadilla-Martín, E.; Guadix, J.; Cortés, P. KNN and adaptive comfort applied in decision making for HVAC systems. Ann. Oper. Res. 2021, 303, 217–231. [Google Scholar] [CrossRef] [Scilit]
- Ciampi, F.G.; Rega, A.; Diallo, T.M.L.; Pelella, F.; Choley, J.-Y.; Patalano, S. Energy consumption prediction of industrial HVAC systems using Bayesian networks. Energy Build. 2024, 309, 114039. [Google Scholar] [CrossRef] [Scilit]
- Nasruddin; Aisyah, N.; Alhamid, M.I.; Saha, B.B.; Sholahudin, S.; Lubis, A. Solar absorption chiller performance prediction based on the selection of principal component analysis. Case Stud. Therm. Eng. 2019, 13, 100391. [Google Scholar] [CrossRef] [Scilit]
- Yousaf, S.; Bradshaw, C.R.; Kamalapurkar, R.; San, O. Investigating Critical Model Input Features for Unitary Air Conditioning Equipment. Energy Build. 2023, 284, 112823. [Google Scholar] [CrossRef] [Scilit]
- Sholahudin; Giannetti, N.; Miyaoka, Y.; Saito, K.; Tanaka, K.; Ogami, H. Experimental Verification of Artificial Neural Network Scalability for Performance Monitoring of Multi-Split Type Air Conditioners. J. Build. Eng. 2023, 76, 107427. [Google Scholar] [CrossRef] [Scilit]
- Li, W.; Gong, G.; Fan, H.; Peng, P.; Chun, L. Meta-learning strategy based on user preferences and a machine recommendation system for real-time cooling load and COP forecasting. Appl. Energy 2020, 270, 115144. [Google Scholar] [CrossRef] [Scilit]
- Kamar, H.M.; Ahmad, R.; Kamsah, N.B.; Mohamad Mustafa, A.F. Artificial neural networks for automotive air-conditioning systems performance prediction. Appl. Therm. Eng. 2013, 50, 63–70. [Google Scholar] [CrossRef] [Scilit]
- Pan, X.; Xing, Z.; Tian, C.; Wang, H.; Liu, H. A method based on GA-LSSVM for COP prediction and load regulation in the water chiller system. Energy Build. 2021, 230, 110604. [Google Scholar] [CrossRef] [Scilit]
- Gao, Z.; Jiang, C.; Zhang, J.; Jiang, X.; Li, L.; Zhao, P.; Yang, H.; Huang, Y.; Li, J. Hierarchical graph learning for protein–protein interaction. Nat. Commun. 2023, 14, 1093. [Google Scholar] [CrossRef] [Scilit]
- Li, X.; Sun, L.; Ling, M.; Peng, Y. A survey of graph neural network-based recommendation in social networks. Neurocomputing 2023, 549, 126441. [Google Scholar] [CrossRef] [Scilit]
- Lu, J.; Zhang, C.; Li, J.; Zhao, Y.; Qiu, W.; Li, T.; Zhou, K.; He, J. Graph convolutional networks-based method for estimating design loads of complex buildings in the preliminary design stage. Appl. Energy 2022, 322, 119478. [Google Scholar] [CrossRef] [Scilit]
- Chen, Z.; Deng, Q.; Ren, H.; Zhao, Z.; Peng, T.; Yang, C.; Gui, W. A new energy consumption prediction method for chillers based on GraphSAGE by combining empirical knowledge and operating data. Appl. Energy 2022, 310, 118410. [Google Scholar] [CrossRef] [Scilit]
- Ho, W.T.; Yu, F.W. Improved model and optimization for the energy performance of chiller system with diverse component staging. Energy 2021, 217, 119376. [Google Scholar] [CrossRef] [Scilit]
- Zhou, J.; Cui, G.; Hu, S.; Zhang, Z.; Yang, C.; Liu, Z.; Wang, L.; Li, C.; Sun, M. Graph neural networks: A review of methods and applications. AI Open 2020, 1, 57–81. [Google Scholar] [CrossRef] [Scilit]
- Asif, N.A.; Sarker, Y.; Chakrabortty, R.K.; Ryan, M.J.; Ahamed, H.; Saha, D.K.; Badal, F.R.; Das, S.K.; Ali, F.; Moyeen, S.I.; et al. Graph neural network: A comprehensive review on non-Euclidean space. IEEE Access 2021, 9, 60588–60606. [Google Scholar] [CrossRef] [Scilit]
- Jiang, W.; Luo, J. Graph neural network for traffic forecasting: A survey. Expert. Syst. Appl. 2022, 207, 117921. [Google Scholar] [CrossRef] [Scilit]
- Hu, Y.; Cheng, X.; Wang, S.; Chen, J.; Zhao, T.; Dai, E. Time series forecasting for urban building energy consumption based on graph convolutional network. Appl. Energy 2022, 307, 118231. [Google Scholar] [CrossRef] [Scilit]
- Zhang, J.; Xiao, F.; Li, A.; Ma, T.; Xu, K.; Zhang, H.; Yan, R.; Fang, X.; Li, Y.; Wang, D. Graph neural network-based spatiotemporal indoor environment prediction and optimal control for central air-conditioning systems. Build. Environ. 2023, 242, 110600. [Google Scholar] [CrossRef] [Scilit]
- Jia, Y.; Wang, J.; Hosseini, M.R.; Shou, W.; Wu, P.; Mao, C. Temporal graph attention network for building thermal load prediction. Energy Build. 2024, 321, 113507. [Google Scholar] [CrossRef] [Scilit]
- Li, L.; Su, X.; Bi, X.; Lu, Y.; Sun, X. A novel Transformer-based network forecasting method for building cooling loads. Energy Build. 2023, 296, 113409. [Google Scholar] [CrossRef] [Scilit]
- Zhang, C.; Zhao, Y.; Fan, C.; Li, T.; Zhang, X.; Li, J. A generic prediction interval estimation method for quantifying the uncertainties in ultra-short-term building cooling load prediction. Appl. Therm. Eng. 2020, 173, 115261. [Google Scholar] [CrossRef] [Scilit]
- Li, Y.; Song, L.; Hu, Y.; Lee, H.; Wu, D.; Rehm, P.J.; Lu, N. Load Profile Inpainting for Missing Load Data Restoration and Baseline Estimation. IEEE Trans. Smart Grid 2024, 15, 2251–2260. [Google Scholar] [CrossRef] [Scilit]
- Lin, L.; Liu, J.; Huang, N.; Li, S.; Zhang, Y. Multiscale Spatio-Temporal Feature Fusion Based Non-Intrusive Appliance Load Monitoring. Appl. Soft Comput. 2024, 167, 112445. [Google Scholar] [CrossRef] [Scilit]
- Cai, W.; Jiang, J.; Wang, F.; Tang, J.; Kim, S.; Huang, J. A survey on mixture of experts in large language models. IEEE Trans. Knowl. Data Eng. 2025, 37, 3896–3915. [Google Scholar] [CrossRef] [Scilit]
- Shazeer, N. GLU variants improve Transformer. arXiv 2020, arXiv:2002.05202. [Google Scholar] [CrossRef] [Scilit]
- Huang, Q.; An, Z.; Zhuang, N.; Tao, M.; Zhang, C.; Jin, Y.; Xu, K.; Chen, L.; Huang, S.; Feng, Y. Harder tasks need more experts: Dynamic routing in MoE models. arXiv 2024, arXiv:2403.07652. [Google Scholar] [CrossRef] [Scilit]
- Chen, S.; Wang, L.; Li, J.; Zhou, G.; Zhou, X. A training pattern recognition algorithm based on weight clustering for improving cooling load prediction accuracy of HVAC system. J. Build. Eng. 2022, 52, 104445. [Google Scholar] [CrossRef] [Scilit]
- Hochreiter, S.; Schmidhuber, J. Long short-term memory. Neural Comput. 1997, 9, 1735–1780. [Google Scholar] [CrossRef] [Scilit]
- Wu, Z.; Pan, S.; Long, G.; Jiang, J.; Zhang, C. Graph WaveNet for deep spatial–temporal graph modeling. arXiv 2019, arXiv:1906.00121. [Google Scholar] [CrossRef] [Scilit]
- Zhou, H.; Zhang, S.; Peng, J.; Zhang, S.; Li, J.; Xiong, H.; Zhang, W. Informer: Beyond efficient Transformer for long sequence time-series forecasting. Proc. AAAI Conf. Artif. Intell. 2021, 35, 11106–11115. [Google Scholar] [CrossRef] [Scilit]
- Cho, K.; van Merriënboer, B.; Gulcehre, C.; Bahdanau, D.; Bougares, F.; Schwenk, H.; Bengio, Y. Learning phrase representations using RNN encoder–decoder for statistical machine translation. arXiv 2014, arXiv:1406.1078. [Google Scholar] [CrossRef] [Scilit]
- Makridakis, S.; Spiliotis, E.; Assimakopoulos, V. The M4 competition: 100,000 time series and 61 forecasting methods. Int. J. Forecast. 2020, 36, 54–74. [Google Scholar] [CrossRef] [Scilit]
- Makridakis, S.; Spiliotis, E.; Assimakopoulos, V. The M5 competition: Background, organization, and implementation. Int. J. Forecast. 2022, 38, 1325–1336. [Google Scholar] [CrossRef] [Scilit]
- Wan, A.; Du, C.; Al-Bukhaiti, K.; Chen, P. Optimizing combined-cycle power plant operations using an LSTM—Attention hybrid model for load forecasting. J. Mech. Sci. Technol. 2025, 39, 6371–6380. [Google Scholar] [CrossRef] [Scilit]
- Shang, W.; Liu, J.; Meng, H.; Jia, L.; Dai, X. Reinforcement-Learning-Based Ventilation Control Considering Human Behavior. Energy Build. 2025, 316, 116072. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2025 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).