Abstract
Medium-voltage direct current (MVDC) converter stations integrate conventional power equipment and power-electronic components with distinct failure and degradation characteristics, making unified health assessment challenging. This study proposes a failure-mode-based health assessment method for major MVDC converter-station equipment. Major equipment is selected through risk priority number (RPN) analysis, while equipment health is independently evaluated using failure mode and effects analysis (FMEA), cross matrices, and condition indicators. The relationships between equipment failure modes and condition indicators are systematically established using FMEA and cross matrices. The selected indicators are classified into five condition grades using indicator-specific thresholds, and a folding function is applied to determine a representative health index (HI) by prioritizing the most severely degraded indicator. The proposed method is evaluated using 10 transformer cases derived from fault and condition assessment datasets and five submodule cases constructed from independent IGBT and capacitor accelerated degradation datasets. The transformer results generally exhibit assessment trends comparable to existing condition assessments, although differences are observed in certain cases. The submodule results demonstrate that degradation information from different components can be integrated into a representative HI under the constructed degradation scenarios. These findings demonstrate the applicability of the proposed framework to heterogeneous condition indicators and provide a basis for extending health assessment to other MVDC converter-station equipment.