Fuzzy Adaptive Steering Elite Optimization for Per-Phase Reactive Power Compensation in Unbalanced Radial Distribution Systems

Water Technologies Innovation Institute & Research Advancement (WTIIRA), Saudi Water Authority (SWA), Al-Jubail 31951, Saudi Arabia
This article belongs to the Section F2: Distributed Energy System

Abstract

This paper couples a Fuzzy Adaptive Steering Elite Optimization (FASEO) engine to a phase-decoupled three-phase backward/forward sweep in which each phase conductor is solved independently and the neutral is eliminated by Kron reduction. Single-phase equivalents are blind to inter-phase voltage asymmetry, and a weighting that drifts between generations makes the reported cost depend on when it was evaluated. Every compensation hub therefore carries three independent reactive injections bounded by a per-phase capacity ceiling, and three fuzzy memberships—active loss, voltage unbalance factor and voltage deviation—are combined with fixed weights under hard voltage and unbalance limits. The framework is validated on the IEEE 33-bus and 69-bus feeders under balanced, 40/25/35 and 45/45/10 load splits, with 30 independent runs per case against five benchmark algorithms, 1080 runs in total. All six cases satisfy V min ≥ 0.95 p.u. and VUF ≤ 2 % . FASEO attains the lowest active loss in the severe 33-bus case, by a margin smaller than the run-to-run spread and best described as a tie, and ranks second of six on the objective actually minimized (mean rank 2.00) and third on loss (Friedman 2.408). Of its 180 runs, 179 satisfy every limit, against 180 for PSO and DE.

1. Introduction

The rapid structural and architectural evolution of contemporary electrical distribution grids, driven by the aggressive integration of localized active distribution automation assets and highly asymmetric decentralized consumer load profiles, has necessitated a fundamental paradigm shift in active Volt-VAR Optimization (VVO) and multi-phase reactive power planning framework engineering [1,2]. Historically, secondary distribution networks were operated as passive, radial links designed to transport bulk power unidirectionally from high-voltage transmission substations down to localized low-voltage consumer intersections [3]. Under these conventional design philosophies, utility planning engineers typically mitigated tail-end voltage sags by over-dimensioning primary substation transformers, modifying mechanical online tap changers, or deploying fixed, three-phase symmetric shunt capacitor banks based on the fundamental assumption of structural phase symmetry [4]. However, modern distribution infrastructure faces escalating operational stress profiles characterized by highly volatile spatial consumer allocations, uncoordinated single-phase electric vehicle charging station clustering, and non-uniform residential load configurations [5,6]. These highly localized load extractions travel through mutually coupled phase conductors, driving conventional radial systems far out of their balanced operating boundaries and rendering classical single-phase equivalents mathematically invalid [7].
When severe consumer load imbalance occurs across a radial distribution network, the complex line currents traveling through the individual phase conductors drift significantly in both magnitude and phase angle displacement [8]. This structural phase asymmetry triggers highly elevated technical distribution losses and introduces severe, non-uniform longitudinal thermal stresses that accelerate the dielectric insulation degradation of underground cables and overhead conductors [9]. Phase current disparity also displaces the neutral point of a four-wire feeder, an effect reported as neutral-point voltage displacement [10]. Reproducing it requires neutral impedance and grounding data that the standard benchmark feeders do not supply, so the model adopted here retains the phase-wise asymmetry of the load but does not represent the neutral conductor; Section 2 states that assumption explicitly. This displacement severely distorts the terminal phase-to-neutral voltage profiles, subjecting consumer electronics on lightly loaded phases to damaging over-voltage swells, while heavily loaded adjacent phases experience deep, localized voltage sags [11,12]. To mitigate these localized distortions, optimize overall efficiency, and protect industrial utility asset insulation margins, the strategic allocation of multi-phase reactive compensation assets must be executed precisely at the terminal end nodes of long radial feeders.
To navigate the highly non-linear, multi-dimensional coordination challenges associated with decentralized reactive asset dispatch, the modern power systems literature has shifted from classical mathematical programming techniques toward advanced metaheuristic optimization frameworks and intelligent actor–critic schemes [13,14]. Classical optimization techniques, including mixed-integer linear programming, non-linear programming, and interior-point methods, frequently suffer from matrix ill-conditioning, severe truncation errors, or computational stalling when scaling into phase-separated multi-phase parameters due to the non-convex, non-differentiable nature of the underlying three-phase power flow injection equations [15,16]. Nature-inspired metaheuristic search engines have demonstrated exceptional performance in navigating complex, high-dimensional search terrains because they operate as gradient-free, stochastic global search algorithms capable of evading local optimum traps [17,18].
Numerous metaheuristic variants have been systematically adjusted to optimize power grid parameters. Genetic Algorithms and Particle Swarm Optimization established the foundational paradigms for heuristic parameter search in electrical distribution layouts, demonstrating competence in tracking discrete step changes in capacitor bank configurations and multi-node coordination [19,20]. Differential Evolution significantly advanced global convergence stability by introducing vector-differential mutation operators [21,22]. Advanced biological and physics-inspired variants have been introduced to solve complex grid automation loops, including Grey Wolf Optimizer [18,23,24], Pelican Optimization Algorithm [25], and Artificial Rabbit Optimization [26]. The Ant Lion Optimizer has been recognized for its capacity to extract non-dominated fronts in multi-objective engineering designs [12,27]. Parallel developments in machine intelligence have introduced model-free Deep Reinforcement Learning algorithms, such as Deep Deterministic Policy Gradient layers for continuous state coordination [28,29]. When extended into multi-conductor planning, these variants are typically structured to handle decentralized power quality by treating individual phase compensation bounds as independent parameters within candidate population strings or actor matrices [30].
Despite the widespread implementation of metaheuristic optimization variants and reinforcement learning schemes in active distribution networks, a systematic evaluation of the current literature reveals critical technical gaps:
  • Simplification-Driven Blindness to Mutual Coupling: A prominent majority of state-of-the-art studies continue to operate under single-line balanced assumptions or assume completely decoupled line segments where inter-phase physical parameters are ignored [9]. Real-world overhead lines and underground distribution cables feature highly asymmetric geometric layouts on their supporting physical cross-arms, introducing significant mutual electromagnetic and electrostatic coupling parameters ( z a b , z b c , z a c ) between adjacent conductors. By neglecting these mutual terms, conventional optimization models remain mathematically blind to the fact that an aggressive reactive power injection intended to mitigate a localized voltage sag on Phase A physically shifts the voltage magnitude and amplifies technical losses on Phase B and Phase C [31].
  • Rigid Multi-Objective Compromise Functions: The aggregation of highly conflicting grid operational targets—specifically active line loss shaving, voltage unbalance factor suppression, and cumulative voltage deviation minimization—is typically executed using fixed, static weighting matrices or simple minimum intersection compromise functions [32,33]. These static profiles lack the capacity to adjust priority focus across the generational timeline. If an algorithm prioritizes active loss shaving from the early stages of the search loop, it will aggressively over-compensate the network nodes, triggering severe over-compensation power loss loops and destructive localized voltage swells that violate utility asset safety margins [15]. Recent advances in multi-objective optimization have demonstrated the effectiveness of hybrid approaches combining analytic hierarchy processes with improved metaheuristic algorithms [24,34].
  • Discontinuous Penalty Barriers and Numerical Stagnation: To enforce strict utility voltage boundaries, conventional metaheuristic frameworks deploy hard, discontinuous step penalty constraints. A cliff of that kind destroys the gradient information a population search uses to approach the boundary, and it is the mechanism that most often produces premature stagnation in this literature. The framework here uses a single gate for candidates that violate a limit, scores every candidate inside the limit by a continuous cost, and adds a quadratic term on the normalized violation that grows from zero at the boundary [16,35]. When a candidate search particle steps even slightly outside the permissible operating envelope ( 0.95 ≤ V k ϕ ≤ 1.05 p . u . ) , these step functions apply an instantaneous, massive cost inflation. This mathematical cliff creates severe discontinuities across the fitness landscape, destroying vital gradient-like tracking information and causing search swarms to suffer from premature convergence or severe numerical stagnation inside sub-optimal local basins [30].
To systematically overcome these technical limitations and deliver a reproducible solution, this study introduces a comprehensive, multi-objective optimization framework that bridges the gap between metaheuristic search algorithms and multi-conductor grid physics. The major contributions of this research are the following:
  • Development of a Single Three-Phase Power-Flow Core: A phase-decoupled backward/forward sweep formulation is adopted in which each phase conductor is solved separately, with mutual coupling between phases set to zero. Mutual coupling is set to zero for both feeders. This is the Kron reduction implicit in the published line data of these benchmarks, and it is applied identically to every algorithm, so every comparison rests on one power-flow model rather than on a per-method one [36].
  • Introduction of the FASEO Engine with Dynamic Steering Operators: The Fuzzy Adaptive Steering Elite Optimization engine is proposed, which integrates piecewise continuous search operators. The engine combines a Master Elite Fine-Tuning mechanism driven by Gaussian normal distributions with an Elite Directed Vector Steering operator and an Exponential Satisfaction Cooling Operator to dynamically balance exploration and exploitation [14,37].
  • Formulation of a Fixed-Weight Objective Composition: The three fuzzy memberships are combined with fixed weights, so the priority given to loss, unbalance and voltage deviation does not drift between generations. This is a deliberate departure from time-varying weighting, which makes the reported cost of a solution depend on when it was evaluated and prevents a like-for-like comparison between algorithms. This framework is paired with a Continuous Symmetrical Quadratic Penalty function featuring adaptive constraint coefficients that smooth out the fitness landscape [31,32].
  • Comprehensive Validation on Multiple Test Systems: The proposed framework is rigorously validated through extensive numerical simulations on both the standard IEEE 33-bus and IEEE 69-bus distribution test systems across three distinct operational scenarios. The compensation hubs for the IEEE 69-bus system are selected by ranking the loss sensitivity factor at every bus and then checking that ranking against the placements reported for the same feeder in the capacitor-placement literature [15], so the selection rests on two sources rather than on the factor alone. The FASEO engine is benchmarked against five state-of-the-art metaheuristic algorithms [23,30,34].
To contextualize the contributions of this research against the existing literature, four capabilities separate the present framework from the metaheuristics reviewed above. First, the optimization is per phase: every compensation hub carries three independent reactive injections, so the search space scales with the number of phases instead of collapsing to a balanced equivalent. Second, the objective combines three fuzzy memberships with fixed weights of 0.40 for loss, 0.20 for voltage unbalance and 0.40 for voltage deviation, applied identically to every algorithm, and the loss membership is bounded so that a candidate cannot trade an unbounded loss increase for a marginal voltage gain. Third, the voltage and unbalance limits are evaluated by the same power flow that produces the objective, and a candidate that violates any of them receives a fixed large fitness plus a depth term rather than a finite cost, so an infeasible solution can never outrank a feasible one. Fourth, the engine is assessed with a statistical protocol—30 independent runs, Wilcoxon rank-sum tests, Cliff’s delta and Friedman ranking—rather than a single best result, which is what allows the claims in Section 4 and Section 5 to be made at all. Section 3.4 lists the settings needed to reproduce the study. While recent studies have made significant strides in mitigating unbalance and optimizing active distribution networks, the majority of these approaches remain constrained by simplified physical models or rigid algorithmic mechanics. Unlike previous methodologies that rely on single-phase approximations, neglect inter-phase mutual electromagnetic coupling, or employ discontinuous penalty barriers, the proposed framework uniquely couples a single three-phase power-flow core to the fuzzy multi-objective optimizer to simultaneously address all identified technical gaps.
Fuzzy membership aggregation is the established route to multi-objective capacitor and DG placement in distribution networks [12,33], and the adaptive variants couple that aggregation to time-varying weights or to adaptive penalty coefficients [31,32,35]. What separates the present formulation is not a new aggregation rule but three choices taken together: the weights are fixed before any comparative run and applied identically to every algorithm, so a reported cost does not depend on the generation at which it was evaluated; the injection is per phase rather than a balanced equivalent; and the constraint gate admits no infeasible candidate above a feasible one. Each of the three is defensible on its own, and the ablation of Section 6 measures what removing the adaptive components of the search costs.
The remainder of this manuscript is organized as follows. Section 2 establishes the phase-separated multi-conductor network topology, formulates the power flow core as a phase-decoupled backward/forward sweep, and defines the multi-objective problem formulation with fixed fuzzy weighting. Section 3 gives the mathematical framework of the FASEO engine and Algorithm 1. Section 4 presents the results for the IEEE 33-bus system and Section 5 those for the IEEE 69-bus system. Section 6 collects the diagnostic comparison and states the limitations, and Section 7 concludes the paper and sets out future work.

2. Problem Formulation and System Modeling

This section establishes the mathematical foundation for the proposed optimization framework. The phase-separated three-phase network topology is first described, followed by the formulation of the multi-conductor power flow equations using a phase-decoupled backward/forward sweep. The multi-objective problem formulation is then defined, incorporating the three conflicting operational objectives and their associated constraints. Finally, the fuzzy multi-objective balancing approach is presented to reconcile the disparate objective functions into a unified scalar cost. Figure 1 and Figure 2 show the single-line diagrams of the two test feeders used throughout.
Figure 1. Single-line diagram, IEEE 33-bus system.
Figure 2. Single-line diagram, IEEE 69-bus system.

2.1. Three-Phase Radial System Configuration

Compensation hubs were selected in two stages. The loss sensitivity factor was first evaluated at every bus, as it ranks each node by the reactive injection that most reduces active loss at that point; the factor is plotted for both feeders in Figure 3 and Figure 4, and the ranked candidates for both feeders appear in Table 1. The hub set itself follows the placements reported for the same feeders in the capacitor-placement literature [15], and the factor ranking was used as a cross-check on that set rather than as the selector. The two do not agree at every bus: the factor is highest at interior nodes of the heavily loaded main line, while the reported placements sit at the tails of the laterals, which is where sustained phase unbalance and the voltage floor bind together. Where they disagreed, the reported placement was kept, because the factor alone does not carry the unbalance condition that makes a hub worth installing, and Table 1 lists the factor at every candidate bus, including the ones the factor would have chosen, so the disagreement is visible rather than asserted. Four hubs were retained for the 33-bus feeder and seven for the 69-bus feeder, the counts following the number of distinct lateral tails rather than the ranking itself. Table 2 lists the 33-bus specifications and Table 3 the 69-bus ones; both are read from the same frozen dataset. Table 4 defines the load splits used throughout.
Figure 3. Loss sensitivity factor at every bus, IEEE 33-bus system.
Figure 4. Loss sensitivity factor at every bus, IEEE 69-bus system.
Table 1. Loss sensitivity factor and selected hubs.
Table 2. Specifications, IEEE 33-bus system.
Table 3. Specifications, IEEE 69-bus system.
Table 4. Load-split scenarios.

2.1.1. Visual Grid Architecture

To validate the structural and operational robustness of the proposed optimization framework under realistic conditions, a standardized testing environment must be established. In conventional single-phase distribution automation models, systems are generally represented using a simplified single line diagram which collapses the active network branches into a single phase equivalent structure. While such models are common in the single-objective literature, they are structurally blind to per-phase conductor loading and to the neutral-point displacement that asymmetrical loading produces; the model adopted here resolves the first and, lacking neutral impedance and grounding data, declares the second rather than estimating it [7].
To address these limitations while maintaining high visual clarity, this study adopts the topology of the standard IEEE 33-bus radial power distribution network as its baseline architecture. The compensation hubs for this system are established at Buses 6, 13, 24 and 30. Figure 1 presents the single line diagram of the IEEE 33-bus system. The primary base parameters are set at a system voltage of 12.66 kV and a total single-phase power base of 1.0 MVA per phase. The total connected nominal active and reactive consumer demands across the entire feeder layout stand at 3715 kW and 2300 kVAR , respectively [38]. These parameters are consistent with standard distribution system benchmarks used extensively in the literature, ensuring comparability with previous studies.
To demonstrate the scalability and generalizability of the proposed framework, the IEEE 69-bus radial distribution system is employed as a larger test case. The compensation hubs for this system are selected at Buses 12, 17, 21, 50, 61, 64 and 65 based on the loss sensitivity factor methodology [15]. The selection of seven compensation hubs provides enhanced spatial coverage and improved voltage support across the extended radial feeder. Figure 2 illustrates the single line diagram of the IEEE 69-bus system with the selected compensation hubs. The IEEE 69-bus system comprises 69 buses, 68 branches, a total active power demand of 3802.19 kW, and a total reactive power demand of 2694.60 kVAR [39]. This larger system presents more severe voltage drop characteristics and higher losses, providing a more challenging test for the optimization framework.
While the physical load intersections remain topologically identical to the standard baseline configurations, the internal model used by the core calculation engine is completely phase-separated. The 33-bus system is modeled as a 99 × 99 complex admittance matrix array spanning 33 discrete buses across 3 distinct conductors. The 69-bus system is modeled as a 207 × 207 complex admittance matrix array spanning 69 discrete buses. Each phase conductor is solved as an independent radial circuit. Mutual coupling between phases is set to zero, the Kron-reduced assumption implicit in the standard benchmark data, and the same assumption is applied to every algorithm so that all comparisons rest on identical power-flow results.

2.1.2. Core Physical Setup Description

The line model uses the series impedance and shunt susceptance of the standard feeder data, applied separately to each phase conductor. In standard single-line calculations, line sections are treated as isotropic, balanced impedances where transposition is assumed to eliminate cross-phase variance. However, real-world utility distribution assets feature geometric spacing asymmetries on the supporting cross-arms, which introduces significant mutual electromagnetic coupling between Phase A, Phase B, and Phase C [9]. These mutual coupling effects are particularly pronounced in underground cable installations where conductor spacing is constrained by physical cable geometries.
The physical line setup for each radial branch section is modeled using comprehensive primitive impedance submatrices. For any given branch connecting bus k to bus m, the physical traits are mathematically structured as a 3 × 3 complex matrix block:
Z k m = z a a z a b z a c z b a z b b z b c z c a z c b z c c
where the diagonal terms ( z a a , z b b , z c c ) represent the self-impedance values of the phase conductors, incorporating the line resistance and self-inductance. The off-diagonal terms ( z a b , z b c , z a c ) represent the mutual complex impedances mapping the electromagnetic coupling between the phases [40]. These mutual impedances are functions of conductor geometry, spacing, and soil resistivity, and must be accurately represented to capture the true behavior of unbalanced systems.
Single-phase equivalent reductions are not used: each phase is solved explicitly, so the effect of the uncompensated load split on every conductor is represented rather than averaged away. Mutual coupling between phases is set to zero throughout, which is the Kron reduction implicit in the published line data of these benchmarks; the model therefore does not represent how an injection on one phase shifts the voltage on the other two through mutual terms, and the residual phase spread that this leaves is reported as a limitation in Section 6. What is represented, phase by phase, is each conductor’s own voltage and current under the load split it carries, which is what the compensation limits are evaluated against.

2.1.3. Phase-Decoupled Power Flow Formulation

The mathematical coupling between the multi-conductor branch impedances and the non-linear, phase-isolated consumer load demands dictates that the network state vector cannot be solved using standard single-phase approximations. The physical inter-phase dependencies necessitate the simultaneous solution of a large system of non-linear algebraic equations [1]. The framework therefore carries one solver for every case: a phase-decoupled backward/forward sweep, in which each phase conductor is treated as an independent radial circuit and the phase currents are obtained by recursive branch summation. Mutual coupling between phases is set to zero, so the branch impedance matrix is diagonal; this is the standard Kron-reduced assumption for these benchmark feeders, and it reproduces their published uncompensated losses. The same solver is applied to both feeders and to all three load splits, so no result depends on an architecture having been selected for it. The phase-isolated complex power injections at any node k are as follows:
P k ϕ = V k ϕ ∑ m = 1 N ∑ γ ∈ { a , b , c } V m γ G k m ϕ γ cos ( θ k ϕ − θ m γ ) + B k m ϕ γ sin ( θ k ϕ − θ m γ )
Q k ϕ = V k ϕ ∑ m = 1 N ∑ γ ∈ { a , b , c } V m γ G k m ϕ γ sin ( θ k ϕ − θ m γ ) − B k m ϕ γ cos ( θ k ϕ − θ m γ )
where N is the number of buses, and V k ϕ and θ k ϕ represent the voltage magnitude and phase angle of phase ϕ at bus k. The terms G k m ϕ γ and B k m ϕ γ denote the real conductances and imaginary susceptances extracted from the phase-separated ( 3 N × 3 N ) complex bus admittance matrix ( Y bus ) . The backward/forward sweep solves these equations without a Jacobian matrix: it alternates a backward branch-current summation with a forward voltage update and stops when the largest nodal power mismatch falls below a specified tolerance (typically 10 − 6 p.u.). Because mutual coupling is set to zero, the inter-phase blocks of Y bus vanish, and G k m ϕ γ = B k m ϕ γ = 0 for γ ≠ ϕ , so each phase is solved against its own admittance submatrix and the sums in (2)–(3) run over γ = ϕ only. The sweep is therefore three independent single-phase sweeps over a common load model, which is the phase-decoupled formulation referred to throughout.

2.2. Multi-Objective Problem Formulation

The load splits that every later scenario refers to are defined first, so that the objective can be stated against a fixed set of operating conditions.
The coordinated allocation of decentralized multi-phase reactive power assets constitutes a non-linear, highly constrained multi-objective optimization problem. The objective is to determine the optimal phase-isolated reactive power injection vectors that simultaneously mitigate active power losses, suppress voltage unbalance distortions, and minimize nodal voltage deviations [12,30]. The problem is formalized below. The multi-objective nature of the problem arises from the inherent conflict between these objectives: minimizing losses may require aggressive reactive power injection that exacerbates voltage unbalance, while strictly enforcing voltage quality constraints may prevent optimal loss reduction. This fundamental trade-off necessitates the use of a multi-objective optimization approach capable of identifying best-compromise solutions.

2.2.1. Objective 1 ( f 1 ) : Active Power Loss Shaving

The first objective function ( f 1 ) is the cumulative summation of ohmic losses across all physical network branches and phases. Active power losses represent the primary economic cost in distribution system operation, as they directly translate to increased energy procurement costs and reduced system efficiency. Minimizing these losses is therefore a primary driver for distribution automation. For the IEEE 33-bus system:
f 1 33 = P loss , total 33 = ∑ j = 1 32 ∑ ϕ ∈ { a , b , c } | I j ϕ | 2 · R j ϕ
For the IEEE 69-bus system:
f 1 69 = P loss , total 69 = ∑ j = 1 68 ∑ ϕ ∈ { a , b , c } | I j ϕ | 2 · R j ϕ
where I j ϕ and R j ϕ represent the complex line current magnitude and line resistance [16]. Only the three phase conductors carry current in this model: the neutral is eliminated by Kron reduction, no neutral conductor or neutral current is represented, and the reported loss is the sum of the three per-phase branch losses in both the uncompensated and the compensated cases.

2.2.2. Objective 2 ( f 2 ) : Voltage Unbalance Factor Mitigation

The second objective function ( f 2 ) is defined as the maximum true voltage unbalance factor observed across all critical pilot buses. Voltage unbalance is a critical power quality concern in distribution systems, as it can cause adverse effects such as reduced motor efficiency, increased transformer losses, and tripping of protective devices. Using Fortescue’s symmetrical component transformation:
V k , zero V k , pos V k , neg = 1 3 1 1 1 1 a a 2 1 a 2 a V k a V k b V k c
where a = 1 ∠ 120 ∘ = − 0.5 + j 0.866 [30]. The VUF is then:
f 2 = V U F max = max k ∈ { 1 , … , N } | V k , neg | | V k , pos | × 100 %
The use of symmetrical components allows for the isolation of negative-sequence components, which are directly responsible for unbalance-related equipment issues. By minimizing the maximum VUF across all buses, the optimization ensures that even the most unbalanced bus in the system remains within acceptable limits.

2.2.3. Objective 3 ( f 3 ) : Voltage Deviation Minimization

The third objective function ( f 3 ) targets the minimization of cumulative voltage deviation ( V D ) [11,33]:
f 3 = V D = ∑ k = 1 N ∑ ϕ ∈ { a , b , c } | V k ϕ − V nominal |
where V nominal is the ideal reference profile calibrated to 1.0 p . u . Voltage deviation minimization is important for ensuring that all loads receive power at acceptable voltage levels, preventing equipment damage and ensuring proper operation of sensitive electronics. This objective incentivizes the optimization to maintain voltages close to nominal levels across all phases.

2.3. Operational Constraints

The optimization problem is subject to operational constraints [16,35] that ensure physical feasibility and utility compliance:
  • Power Balance Equalities: These constraints ensure that power flow is conserved at every node:
    P sub , k ϕ − P load , k ϕ − P inj , k ϕ = 0
    Q sub , k ϕ − Q load , k ϕ + Q comp , k ϕ − Q inj , k ϕ = 0
    The power balance constraints ensure that the power flow equations are satisfied, guaranteeing that the optimization solution corresponds to a physically feasible operating point.
  • Voltage Magnitude Limits: Nodal steady-state voltage magnitudes must remain within standard inequality limits:
    0.95 ≤ V k ϕ ≤ 1.05 , ∀ k ∈ [ 1 , N ] , ∀ ϕ ∈ { a , b , c }
    The same mandatory 0.95 p.u. floor applies to every scenario, including Scenario C; no relaxation to 0.90 p.u. is applied. The 0.95–1.05 p.u. band is Range A of ANSI C84.1 [41].
  • Voltage Unbalance Factor Limit: The VUF at each terminal node must not violate the maximum asymmetry constraint:
    V U F k ≤ 2.0 % , ∀ k ∈ [ 1 , N ]
    This constraint is particularly important for motor loads, which are sensitive to negative-sequence voltage components.
    Branch currents are therefore not constrained in the optimization. The standard IEEE 33-bus and 69-bus datasets provide no conductor ampacity ratings, and thermal limits are not imposed in the capacitor-placement literature this work compares against. The solutions are therefore thermally unverified, and the branch-current behavior is not used as evidence anywhere in this work.
  • Reactive Power Compensation Bounds: Compensation values are limited to the installed per-phase compensator capacity:
    0.0 ≤ Q comp , c , 33 ϕ ≤ 600.0 kVAR , ∀ c ∈ { 6 , 13 , 24 , 30 }
    0.0 ≤ Q comp , c , 69 ϕ ≤ 700.0 kVAR , ∀ c ∈ { 12 , 17 , 21 , 50 , 61 , 64 , 65 }
    Equation (13) gives the bound for the 33-bus feeder and Equation (14) the bound for the 69-bus feeder; both follow the installed per-phase capacity of utility-grade capacitor banks.

2.4. Fuzzy Multi-Objective Balancing

2.4.1. Clamped Membership Boundaries

Because the three objective functions possess disparate physical dimensions, a fuzzy optimization approach maps each objective onto a normalized satisfaction scale [12,33]. This approach has been widely adopted in power system optimization due to its ability to handle conflicting objectives without requiring a priori weighting information. The membership function for each objective is defined as follows:
μ i = 1.0 , f i ≤ f i , min f i , max − f i f i , max − f i , min , f i , min < f i < f i , max 0.0 , f i ≥ f i , max
where f i , max is the uncompensated baseline and f i , min is the single-objective lower bound. The loss bound is therefore taken from the uncompensated solution of the case being solved: 202.19, 211.70 and 265.80 kW for the three 33-bus scenarios and 224.65, 235.75 and 298.47 kW for the three 69-bus scenarios, with lower bounds of 130 and 200 kW, respectively. The unbalance membership spans 0 to 2.5%, just beyond the 2% operating limit, and the voltage-deviation membership 0.45 to 1.20 p.u. All four spans are fixed before any comparative run and are identical for every algorithm. When the uncompensated baseline has zero unbalance the denominator of μ 2 vanishes; in that case, μ 2 is defined as unity at every bus, so a balanced case contributes a perfect unbalance score rather than an undefined one. This formulation ensures that each objective is mapped to a value between 0 (worst) and 1 (best), enabling meaningful comparison across objectives.

2.4.2. Fuzzy Weighting and Global Cost

The three fuzzy memberships are combined with fixed weights, and the same weights are applied to every algorithm and every generation:
w loss = 0.40 , w vuf = 0.20 , w vd = 0.40
The weights follow the priorities of the problem rather than a tuning search. Loss reduction is what the compensation is installed to deliver, and voltage deviation is what binds first at the tail of a lateral, so those two carry equal weight; unbalance carries half as much, because the unbalance limit is enforced separately as a hard constraint and a membership that is already constrained at 2% needs less of the scalar budget. A fixed weighted sum is the standard aggregation for capacitor and DG placement with these objectives [33], and the ordering matches the trade-offs reported for unbalance and voltage-deviation compensation on the same feeders [31].
Holding the weights constant has two consequences that matter for the comparisons in Section 4 and Section 5. First, the cost of a solution does not depend on the generation at which it was evaluated. Second, every algorithm is scored by the same function, so the reported costs are comparable across methods and across cases. A generation-dependent schedule was implemented and tested and is not used, because a weight that changes with g makes costs from different generations, and therefore from different algorithms, incomparable.
Constraints enter the fitness in two stages. A candidate that violates any limit is not scored by the fuzzy cost at all: it receives a fixed fitness of 10 9 plus 10 6 times a normalized violation depth,
D = max ( 0 , 0.95 − min k V k ) 0.95 + max ( 0 , max k V k − 1.05 ) 1.05 + max ( 0 , VUF − 2.0 ) 2.0 ,
so every infeasible candidate ranks below every feasible one while infeasible candidates are still ordered among themselves. A feasible candidate is scored by
F = 1.0 − w loss μ 1 + w vuf μ 2 + w vd μ 3 + P ( x ) ,
where
P ( x ) = 100 ∑ k = 1 N ∑ ϕ ∈ { a , b , c } max ( 0 , 0.95 − V k ϕ ) 2 0.95 2 + 100 ∑ k = 1 N ∑ ϕ ∈ { a , b , c } max ( 0 , V k ϕ − 1.05 ) 2 1.05 2 + 100 ∑ k = 1 N max ( 0 , VUF k − 2.0 ) 2 2.0 2 + 10 − 3 max ( 0 , f 1 − f 1 , max ) 2 .
The three limit terms carry a coefficient of 100 and the excess-loss term a coefficient of 10 − 3 , so the penalty is deliberately asymmetric: it is dominated by constraint violation where a candidate breaches a limit, and by the excess-loss term where it does not. For a feasible candidate the three limit terms are zero by construction, so the term that is active in practice is the last one: it applies to feasible solutions whose loss exceeds the upper end of the loss membership, f 1 , max , which is the uncompensated baseline of the case being solved, and it removes the drive toward over-injection that a saturating loss membership would otherwise leave open [35]. The gate in (17) is what keeps infeasible solutions out of the population. This formulation ensures that the optimization minimizes a single scalar cost that encompasses all three objectives while maintaining feasibility.

3. Proposed FASEO Optimization Engine

3.1. Swarm Initialization Matrices

The effectiveness of population-based metaheuristic algorithms depends significantly on the quality and diversity of the initial population, as a well-distributed initial swarm facilitates comprehensive exploration of the search space and reduces the likelihood of premature convergence to sub-optimal solutions. In the proposed FASEO framework, candidate solutions are structured as an operational matrix that systematically organizes the decision variables representing the reactive power compensation values at the designated hubs. For a population size of N p = 30 individuals and a problem dimensionality D—which varies depending on the network configuration and operational scenario (12 for the 33-bus system, four compensation hubs across three phases, and 21 for the 69-bus system, seven hubs across three phases; the balanced scenario uses the same 12 variables, because each phase is optimized independently rather than replicated)—the search coordinates are arranged in the following matrix format as specified in the following matrix:
T agent ( g ) = x 1 , 1 ( g ) x 1 , 2 ( g ) … x 1 , D ( g ) x 2 , 1 ( g ) x 2 , 2 ( g ) … x 2 , D ( g ) ⋮ ⋮ ⋱ ⋮ x N p , 1 ( g ) x N p , 2 ( g ) … x N p , D ( g )
where x i , j ( g ) denotes the reactive power injection value (kVAR) assigned to the j-th decision variable by the i-th search agent at generation g.
The initialization process employs a uniform random sampling strategy within the feasible bounds [ x min , x max ] , where x min = 0 kVAR and x max = 600 kVAR per phase per hub. This approach ensures that the initial population is uniformly distributed across the entire search space, providing broad coverage of the feasible region and maximizing the probability of identifying promising regions early in the optimization process. The diversity of the initial population is critical for effective global exploration, as it prevents the algorithm from being biased toward any particular region of the search space. Furthermore, the adaptive dimensionality D allows the framework to seamlessly transition between balanced and unbalanced operational conditions without requiring structural modifications to the algorithm, thereby enhancing its practical applicability across diverse distribution system configurations.

3.2. Master Elite Fine-Tuning

Premature convergence to sub-optimal local minima represents a fundamental challenge in population-based metaheuristic optimization, particularly when addressing highly non-convex problems such as the multi-objective reactive power optimization considered in this study. To systematically mitigate this risk without compromising search efficiency, the proposed FASEO engine incorporates a Master Elite Fine-Tuning operator that is applied exclusively to the single best-performing individual within the population matrix during each discrete generation [37]. This operator is inspired by the concept of exploitation in metaheuristic optimization, where the best-known solution is refined through localized search to improve its quality while maintaining the diversity of the remaining population. The exclusive application of this operator to the elite individual is a deliberate design choice that enables precise refinement of the optimal solution without disrupting the exploration capabilities of the broader population, thereby preserving the algorithm’s ability to continue searching for potentially superior solutions.
The complete state transition is formulated as a piecewise continuous mapping function that distinguishes between the elite individual and all other population members:
x i ( g + 1 ) = χ tune ( g ) , if i = arg min k F ( x k ( g ) ) χ steer ( g ) , otherwise
where the leader fine-tuning equation χ tune ( g ) tracks the localized exploration footprint around the moving optimum reference line:
χ tune ( g ) = x i ( g ) + β · N ( 0 , 1 ) · ( x max − x min ) · max 1 − 0.7 · g g max , 0.05
where β = 0.08 is the fine-tuning step size, and  N ( 0 , 1 ) is a stochastic vector generated from a standard normal distribution. The damping factor max ( 1 − 0.7 · g / g max , 0.05 ) ensures that the fine-tuning perturbation gradually decreases as the optimization progresses, transitioning from broader exploratory refinements in early generations to highly localized, precise adjustments near the optimum in later generations. The lower bound of 0.05 prevents the perturbation from becoming excessively small, maintaining a minimal level of stochastic variation to facilitate escape from any potential local minima. This operator is applied exclusively to the elite individual to enhance exploitation without disrupting the exploration of the rest of the population, ensuring that the algorithm maintains both solution quality and population diversity throughout the optimization process.

3.3. Elite Directed Vector Steering

While the Master Elite Fine-Tuning operator enhances local exploitation, maintaining sufficient exploration is equally critical for global search capability. The Elite Directed Vector Steering operator serves as the primary exploration mechanism in the FASEO engine, enabling the population to systematically explore promising regions of the search space while maintaining the diversity necessary to avoid premature convergence. This operator calculates trajectory updates for all non-elite searching particles relative to the location of the master elite individual, effectively steering the population toward the current best-known solution while incorporating stochastic perturbations to maintain exploration capability.
The steering operator is mathematically integrated into the secondary block of the piecewise state function and is expressed as follows:
χ steer ( g ) = x elite ( g ) + α scale ( g ) · U ( 0 , 1 ) · [ η ( g ) · ( x elite ( g ) − x i ( g ) ) + ( 1 − η ( g ) ) · ( x rand , ϕ ( g ) − x i ( g ) ) ]
where x elite ( g ) represents the spatial coordinate row vector extracted from the elite leader at generation g, U ( 0 , 1 ) is a uniformly distributed random array, and  x rand , ϕ ( g ) is the position vector of an independent candidate agent chosen at random from the population matrix. This formulation combines two complementary search components: an elite-guided term η ( g ) · ( x elite ( g ) − x i ( g ) ) that steers particles toward the best-known solution, and a random exploratory term ( 1 − η ( g ) ) · ( x rand , ϕ ( g ) − x i ( g ) ) that maintains population diversity by encouraging particles to explore regions associated with other promising individuals.
The spatial step size of this steering process is controlled by the non-linear operator α scale ( g ) , which functions as the Exponential Satisfaction Cooling Operator for the system:
α scale ( g ) = 3.0 · exp − ζ · g g max , ζ = 1.5
This exponential cooling function provides a smooth, non-linear reduction in step size as generations progress, enabling the algorithm to transition from broad exploration in early generations to refined exploitation near the optimum. The cooling rate ζ = 1.5 is set so that the steering amplitude falls to half its initial value at about 46% of the generation budget: a larger rate collapses exploration before the elite trajectory has formed, and a smaller one leaves the search diffuse at generation 50. The value is a design choice, not a fitted parameter, and its effect is measured in the ablation of Section 6.
An influence factor η ( g ) decays from 0.75 to 0.30 over the run. Because  η weights the elite term, a small η transfers influence to the peer term, so the schedule moves the population from elite-directed movement toward peer-driven exploration:
η ( g ) = 0.75 − 0.45 · g g max
This factor controls the balance between elite-guided search and random exploration, starting with a strong elite influence (0.75) in early generations to rapidly guide the population toward promising regions, and gradually reducing it to 0.30 in later generations to allow for more diverse exploration and refinement. The linear decay of η ( g ) provides a smooth transition from exploration to exploitation. Whether the schedule earns its place is measured rather than asserted: the ablation in Section 6 removes it and finds no case changed by more than 3%, so it is presented here as a design choice.

3.4. Algorithm Parameter Settings

The settings that all six algorithms share, and the ones specific to FASEO, are collected in one place before the results are read.
The performance of any metaheuristic optimization algorithm is critically dependent on the appropriate selection of its control parameters, which govern the balance between exploration and exploitation, convergence speed, and solution quality. Table 5 gives the common budget shared by all six algorithms and the control parameters specific to the proposed engine; each benchmark uses the values reported in its source publication within that budget. The parameter values were selected based on an extensive review of the literature, following the recommendations of the original algorithm proponents and subsequent studies that have demonstrated their effectiveness in power system optimization applications [18,19,21,25,26]. For the benchmark algorithms, standard parameter configurations were adopted to ensure a fair and equitable comparison, with population size and maximum generations held constant across all algorithms to isolate the effects of the algorithmic search mechanisms. The comparison is not budget-matched in tuning: FASEO’s parameters were chosen for this problem, the benchmarks use the values published for their source problems, so any tuning advantage sits with FASEO. It holds such an advantage and still ranks third of six on active loss, which is the honest reading; a per-algorithm tuning study on a disjoint seed set is left to future work.
Table 5. Simulation parameters.
The parameter selection process involved a systematic sensitivity analysis to identify the most effective configurations for the distribution system optimization problem. For the FASEO engine, the cooling operator parameters α 0 = 3.0 and ζ = 1.5 are design choices rather than fitted parameters: they are set so that the steering amplitude halves at about 46% of the generation budget, which leaves exploration active while the elite trajectory forms and allows refinement before generation 50. The fine-tuning step size β = 0.08 was selected to provide sufficient local search capability without causing premature convergence, while the population restart mechanism—applied every four generations to replace 25% of the worst individuals—was designed to maintain population diversity and prevent stagnation at sub-optimal local minima. These parameter settings were further validated through statistical analysis of multiple independent runs, confirming their robustness and effectiveness across the three operational scenarios investigated in this study.

3.5. Algorithmic Implementation

The complete implementation of the FASEO engine is presented in Algorithm 1 and illustrated in Figure 5, which provides a comprehensive overview of the optimization procedure from initialization through convergence. The algorithm begins by initializing a population of N p = 30 candidate solutions uniformly distributed within the feasible search space, ensuring broad initial coverage of the solution domain. At each generation, the algorithm evaluates each candidate solution by performing a three-phase power flow calculation and computing the associated Global Fuzzy Cost F ( x i ) , which incorporates both the multi-objective performance and any constraint violations. The elite solution, defined as the individual with the lowest fuzzy cost, is then identified to guide the search process through the Elite Directed Vector Steering mechanism, while the Master Elite Fine-Tuning operator is applied exclusively to this elite individual to enhance local exploitation.
Algorithm 1 Fuzzy Adaptive Steering Elite Optimization (FASEO)
  1:
Initialize population T agent ( 0 ) with N p agents
  2:
Set g = 0 , g max = 50
  3:
while  g < g max   do
  4:
for  i = 1 to N p  do
  5:
Run 3-phase load flow with x i ( g )
  6:
Compute fuzzy membership μ 1 , μ 2 , μ 3
  7:
Calculate Global Fuzzy Cost F ( x i )
  8:
end for
  9:
Find elite leader x elite = arg min F ( x i )
10:
Update α scale ( g ) = 3.0 exp ( − ζ g / g max ) , ζ = 1.5
11:
Update η ( g ) = 0.75 − 0.45 · g / g max
12:
Update damping = max ( 1 − 0.7 · g / g max , 0.05 )
13:
for  i = 1 to N p  do
14:
if  i = elite_index then
15:
x i ( g + 1 ) = x i ( g ) + 0.08 · N ( 0 , 1 ) · ( x max − x min ) · max ( 1 − 0.7 · g / g max , 0.05 )
16:
else
17:
x i ( g + 1 ) = x elite + α scale ( g ) · U ( 0 , 1 ) · [ η ( g ) · ( x elite − x i ( g ) ) + ( 1 − η ( g ) ) · ( x rand − x i ( g ) ) ]
18:
end if
19:
Clip x i ( g + 1 ) to [ x min , x max ]
20:
Accept the candidate only if it improves its parent (greedy)
21:
end for
22:
if  g > 0 and g mod 4 = 0  then
23:
Replace worst 25% of population with random solutions
24:
Re-evaluate elite position
25:
end if
26:
Reject the candidate if it does not improve its parent
27:
g = g + 1
28:
end while
29:
return optimal solution x elite
Figure 5. Flowchart of the FASEO engine.
The exponential operator described above reduces the search step size as generations progress, and the population restart mechanism, applied every four generations to replace 25% of the worst-performing individuals, maintains diversity and prevents the population from converging to sub-optimal local minima [14,16]. This periodic restart, combined with the adaptive steering mechanism, ensures that the algorithm maintains sufficient exploration capability throughout the optimization process while progressively refining the best solutions. The termination criterion is set to a maximum of 50 generations, which was determined through convergence analysis to be sufficient for all algorithms to reach stable solutions.

4. IEEE 33-Bus System Results and Discussion

This section presents a comprehensive evaluation of the proposed FASEO engine on the IEEE 33-bus radial distribution system. The evaluation encompasses three distinct operational scenarios representing increasing levels of phase loading asymmetry. The results are benchmarked against five state-of-the-art metaheuristic algorithms: Differential Evolution (DE) [21], Grey Wolf Optimizer (GWO) [18,24], Pelican Optimization Algorithm (POA) [25], Particle Swarm Optimization (PSO) [19], and Artificial Rabbit Optimization (ARO) [26]. All simulations used a population of 30 for 50 generations, with statistical analysis performed over 30 independent runs for every case.
The IEEE 33-bus system specifications are given in Table 2. The system has a base voltage of 12.66 kV and a total connected load of 3715 kW and 2300 kVAR. Compensation hubs at Buses 6, 13, 24 and 30 each have a capacity of 600 kVAR per phase. Table 6 collects the objective values and Table 7 the uncompensated baselines for all six cases.
Table 6. Objective values, IEEE 33-bus system (mean ± standard deviation).
Table 7. Uncompensated baselines.

4.1. Scenario A: Symmetrical Balanced Network Configuration

Figure 6, Figure 7, Figure 8 and Figure 9 report the voltage, angle and branch-loss profiles for this case, and Table 6 and Table 8, Table 9 and Table 10 give the corresponding metrics.
Figure 6. Nodal voltage envelopes, IEEE 33-bus system, Scenario A. The grey dashed lines mark the 0.95 and 1.05 p.u. voltage limits.
Figure 7. Voltage angle deviation, IEEE 33-bus system, Scenario A.
Figure 8. Branch active power loss, IEEE 33-bus system, Scenario A.
Figure 9. Branch reactive power loss, IEEE 33-bus system, Scenario A.
Table 8. Active loss, IEEE 33-bus system (kW, median); dashes mark infeasible cases.
Table 9. Unbalance and voltage deviation, IEEE 33-bus system.
Table 10. Voltage bounds, IEEE 33-bus system (p.u.).
Scenario A represents the baseline case where the network operates under perfectly balanced conditions with load evenly distributed across all three phases (Phase A: 1/3, Phase B: 1/3, Phase C: 1/3). This scenario serves as a reference case to validate the optimization framework’s performance in the absence of phase asymmetry. Table 7 gives the uncompensated baseline for this case: 202.19 kW of active loss, a minimum voltage of 0.9135 p.u. and zero unbalance by symmetry. The published single-phase value for this feeder is 202.67 kW; the 0.48 kW difference is the phase-decoupled model and load representation, not a tolerance. FASEO reduces the median loss to 143.29 kW, 29.1% below the uncompensated value, and lifts the minimum voltage to 0.9514 p.u. GWO attains the lowest median loss at 142.0 kW with PSO at 142.4 kW, so FASEO is 0.9% behind the best. Its VUF of 0.0863% is second only to PSO’s 0.0609% and ahead of GWO’s 0.1183%. Figure 6, Figure 7, Figure 8 and Figure 9 illustrate the voltage profile improvement, phase angle behavior, and loss reduction achieved by FASEO.

4.2. Scenario B: Moderately Unbalanced Feeder Distribution

Figure 10, Figure 11, Figure 12 and Figure 13 report the voltage, angle and branch-loss profiles for this case, and Table 6 gives the corresponding metrics.
Figure 10. Nodal voltage envelopes, IEEE 33-bus system, Scenario B. The grey dashed lines mark the 0.95 and 1.05 p.u. voltage limits.
Figure 11. Voltage angle deviation, IEEE 33-bus system, Scenario B.
Figure 12. Branch active power loss, IEEE 33-bus system, Scenario B.
Figure 13. Branch reactive power loss, IEEE 33-bus system, Scenario B.
Scenario B introduces realistic phase loading asymmetry (Phase A: 0.40, Phase B: 0.25, Phase C: 0.35). This scenario is representative of practical distribution systems where single-phase loads, such as residential customers and EV chargers, create significant phase unbalance. The search expands to twelve variables, three per hub across the four hubs, so each phase is compensated independently. Table 8, Table 9 and Table 10 give the medians: FASEO reduces the loss from the uncompensated 211.70 kW to 167.17 kW, a 21.0% reduction, with a VUF of 0.4730% against the 1.358% baseline and a minimum voltage of 0.9500 p.u. GWO and PSO tie for the lowest median loss at 166.6 kW, so FASEO is 0.3% behind the best. The convergence traces show FASEO reaching 95% of its total improvement after about 33 generations, against 28 for PSO and 32 for GWO.

4.3. Scenario C: Severely Unbalanced Network Configuration

Figure 14, Figure 15, Figure 16 and Figure 17 report the voltage, angle and branch-loss profiles for this case, and Table 8, Table 9 and Table 10 give the corresponding metrics; Figure 18 isolates the per-phase spread, and Table 11 gives the injection at each hub.
Figure 14. Nodal voltage envelopes, IEEE 33-bus system, Scenario C. The grey dashed lines mark the 0.95 and 1.05 p.u. voltage limits.
Figure 15. Voltage angle deviation, IEEE 33-bus system, Scenario C.
Figure 16. Branch active power loss, IEEE 33-bus system, Scenario C.
Figure 17. Branch reactive power loss, IEEE 33-bus system, Scenario C.
Figure 18. Per-phase voltage envelope, IEEE 33-bus system, Scenario C. The grey dashed lines mark the 0.95 and 1.05 p.u. voltage limits.
Table 11. Reactive injection per hub and phase, IEEE 33-bus system (kVAR).
Scenario C represents the most extreme operational stress case with severe phase-wise load asymmetry (Phase A: 0.45, Phase B: 0.45, Phase C: 0.10). This scenario simulates conditions where Phase C is critically lightly loaded compared to Phases A and B, creating extreme phase current disparities on the phase conductors. FASEO attains the lowest median loss of the six in this case, 291.54 kW against 291.6 kW for GWO, a margin of 0.06 kW that is no greater than the run-to-run spread, with a VUF of 1.9969% against the 3.529% baseline, a 43.4% reduction, and a minimum voltage of 0.9501 p.u. The loss is higher than the uncompensated 265.80 kW: under a 45/45/10 split the voltage floor binds before the loss objective, so every algorithm injects reactive power that raises loss, and FASEO raises it least. GWO returns a lower VUF (1.9853% against 1.9969%) but a higher voltage deviation (0.6916 against 0.6591 p.u.), so the two trade one objective for the other. The constraint gate of Section 2.4 applies unchanged in every scenario.

4.4. Statistical Analysis

To evaluate robustness and statistical significance, 30 independent runs were conducted for each algorithm under Scenario B. The statistical analysis in Figure 19 shows that the six algorithms are not equally good, but it also shows that the leading three are not separable. FASEO’s Friedman mean rank is 2.408, inside the leading group with GWO (1.944) and PSO (2.078) (the test ranks the per-run active loss, and an infeasible run counts as the worst outcome), and the Nemenyi critical difference at N = 180 blocks is 0.562, which exceeds the GWO–PSO (0.133), PSO–FASEO (0.330) and GWO–FASEO (0.464) gaps inside the leading group, while DE (4.078), ARO (4.867) and POA (5.625) all lie beyond it. A Wilcoxon rank-sum test over the six case pairs places FASEO and GWO within the same band: GWO leads in four of the six pairs and FASEO in none at the 95% level, which is what “inseparable” means here. What distinguishes FASEO is not the median loss but the shape of its distribution. Across 180 runs, 179 of its solutions satisfy every limit, a 99.4% rate that only PSO and DE improve on (180 of 180), against 96.1% for GWO and 85.0% for ARO. Its mean-rank standard deviation of 0.229 is narrower than GWO’s 0.620, DE’s 0.729 and POA’s 0.365, although PSO (0.166) and ARO (0.169) are tighter still. The convergence traces in Figure 20 show where that case-by-case stability stops being an advantage: FASEO reaches 95% of its total improvement after 33 generations, within 5 generations of PSO (28) and GWO (32), so all three settle at a comparable pace. The best costs are effectively tied: PSO 0.4189, FASEO 0.4210 and GWO 0.4249, differences within the run-to-run spread. What FASEO does hold in Table 9 is a close second on unbalance, 0.4730% against PSO’s 0.4575%, at within 0.3% of the lowest active loss: the fixed equal weights on loss and voltage deviation keep a solution from buying loss with voltage quality, which is the trade this comparison is meant to expose. That is the same picture the Wilcoxon and Friedman results above give, and it is why the leading three are described as not separable.
Figure 19. Cliff’s δ against each benchmark; positive values favor FASEO ( p < 0.001 as ***, p < 0.01 as **, p < 0.05 as *).
Figure 20. Convergence of the six algorithms, IEEE 33-bus system, Scenario B.

4.5. Convergence Characteristics

Figure 20 and Figure 21 show the convergence traces and the run-to-run spread.
Figure 21. Final-loss distribution over 30 runs, IEEE 33-bus system, Scenario B.
Figure 20 presents convergence characteristics of all six algorithms. FASEO demonstrates rapid initial convergence, reducing the fuzzy cost from approximately 0.58 to 0.50 within the first 10 generations. This rapid improvement is attributed to the Elite Directed Vector Steering operator, which effectively guides the population toward promising regions of the search space. The Exponential Satisfaction Cooling Operator, α scale ( g ) = 3.0 · exp ( − 1.5 · g / g max ) , ensures smooth transition from exploration to exploitation, enabling precise fine-tuning around promising solutions. The population restart mechanism, applied every 4 generations to replace 25% of the worst individuals, maintains population diversity, preventing premature convergence. In contrast, POA and ARO exhibit slower convergence, achieving similar fitness only after 30–40 generations.

4.6. Multi-Objective Trade-Off Analysis

Figure 22 plots loss against unbalance for every feasible run.
Figure 22. Loss against voltage unbalance factor, IEEE 33-bus system.
The best-solution trade-off in Figure 22 plots every feasible run. FASEO holds neither extreme in this scenario: GWO and PSO tie for the lowest loss at 166.6 kW against FASEO’s 167.17 kW, and PSO has the lowest VUF at 0.4575% against FASEO’s 0.4730%. Its position is close to the knee of the set rather than at either end, which is the outcome the fixed weights are designed to produce, as with loss and voltage deviation carrying equal shares, and unbalance half of each, a solution cannot buy a small loss reduction with a large voltage-deviation penalty, which is what keeps the feasible set concentrated where both are acceptable. The excess-loss term in the penalty removes the remaining gain from over-injection once the loss passes this scenario’s uncompensated baseline of 211.70 kW. In contrast, DE and PSO show a wider spread of solutions, indicating less focused exploration of the trade-off frontier.

5. IEEE 69-Bus System Results and Discussion

To demonstrate the scalability and generalizability of the proposed framework, extensive simulations were conducted on the larger IEEE 69-bus radial distribution system [39]. The same three operational scenarios were applied. The compensation hubs (Buses 12, 17, 21, 50, 61, 64, 65) were selected by ranking the loss sensitivity factor at every bus and checking that ranking against the placements reported for the same feeder in the literature [15]; the set follows the reported placements, and the factor was used as a cross-check (Section 2.1). The same backward/forward sweep core was used in all three scenarios. This section demonstrates that the FASEO framework scales effectively to larger systems while maintaining performance.
Table 3 presents the IEEE 69-bus system specifications. The system has a base voltage of 12.66 kV and a total connected load of 3802.19 kW and 2694.60 kVAR. The seven compensation hubs each have a capacity of 700 kVAR, so the installed reactive capability is 14,700 kVAR.

5.1. Scenario A: Symmetrical Balanced Network Configuration (69-Bus System)

Figure 23, Figure 24, Figure 25 and Figure 26 report the voltage, angle and branch-loss profiles for this case, and Table 12, Table 13, Table 14, Table 15 and Table 16 give the corresponding metrics.
Figure 23. Nodal voltage envelopes, IEEE 69-bus system, Scenario A. The grey dashed lines mark the 0.95 and 1.05 p.u. voltage limits.
Figure 24. Voltage angle deviation, IEEE 69-bus system, Scenario A.
Figure 25. Branch active power loss, IEEE 69-bus system, Scenario A.
Figure 26. Branch reactive power loss, IEEE 69-bus system, Scenario A.
Table 12. Objective values, IEEE 69-bus system (mean ± standard deviation).
Table 13. Active loss, IEEE 69-bus system (kW, median); dashes mark infeasible cases.
Table 14. Unbalance and voltage deviation, IEEE 69-bus system.
Table 15. Voltage bounds, IEEE 69-bus system (p.u.).
Table 16. Reactive injection per hub and phase, IEEE 69-bus system (kVAR).
Under balanced conditions the 69-bus feeder returns little on loss, and the paper reports that rather than dressing it up. The uncompensated loss is 224.65 kW, close to the 225 kW usually quoted for this feeder, and FASEO’s median is 227.20 kW, 1.1% above it. GWO reaches 211.8 kW, so FASEO is 7.3% behind on this case: with the voltage floor slack, the loss objective dominates and FASEO’s fixed weights do not chase it as hard as a loss-led search does. The VUF is 0.5526% (the balanced baseline is zero by symmetry, so any per-phase asymmetry appears here) and the minimum voltage rises from 0.9093 p.u. to 0.9500 p.u. The backward/forward sweep maintains exact inter-phase compliance across all ( 207 × 207 ) admittance matrix entries. The voltage profile in Figure 23 shows substantial improvement, with a smoother gradient indicating more uniform reactive power support.
Table 12 presents the multi-objective performance comparison. GWO returns the lowest objective in Scenarios A and B (0.566 and 2.674) and PSO in Scenario C (333.5); FASEO returns 0.767, 4.758 and 340.9, second in the severe case within 2.2% of PSO and 1.6% ahead of GWO. Where feasible runs carry the excess-loss penalty, the standard deviation of the objective exceeds its mean, which is the skew the objective is designed to create. The larger feeder rewards a loss-led search; FASEO holds voltage and unbalance inside their limits, and its active loss is 227.20, 292.40 and 871.21 kW in the three scenarios.
Table 13 presents the power loss comparison. FASEO returns 227.20, 292.40 and 871.21 kW, within 7.28%, 5.31% and 1.81% of the lowest value in Scenarios A, B and C, so the gap narrows as the constraint tightens. The comparison is reported in full rather than omitted because the 69-bus results carry the reliability argument developed in Section 6. In Scenario B, DE returns 366.32 kW against FASEO’s 292.40 kW, and its objective value is correspondingly higher, so FASEO dominates it in that case rather than trading loss for voltage quality.
Table 14 gives the voltage quality metrics. FASEO reaches a VUF of 0.5526% in Scenario A, 1.9250% in B and 1.9952% in C, and its minimum voltage is 0.9501, 0.9500 and 0.9500 p.u., the floor the constraint imposes. The unbalance limit is satisfied in every case. GWO returns a lower VUF (0.4400%, 1.8780% and 1.9842%), and ARO in Scenario B (1.3886%), so on this feeder FASEO’s margin is carried by the voltage floor and the loss rather than by the unbalance.

5.2. Scenario B: Moderately Unbalanced Feeder Distribution (69-Bus System)

Figure 27, Figure 28, Figure 29 and Figure 30 report the voltage, angle and branch-loss profiles for this case; Table 12 gives the corresponding metrics.
Figure 27. Nodal voltage envelopes, IEEE 69-bus system, Scenario B. The grey dashed lines mark the 0.95 and 1.05 p.u. voltage limits.
Figure 28. Voltage angle deviation, IEEE 69-bus system, Scenario B.
Figure 29. Branch active power loss, IEEE 69-bus system, Scenario B.
Figure 30. Branch reactive power loss, IEEE 69-bus system, Scenario B.
Under moderately unbalanced conditions (Phase A: 0.40, Phase B: 0.25, Phase C: 0.35), the same phase-decoupled backward/forward sweep is used as in the balanced case. No solver transition takes place, and none is needed: the sweep forms no Jacobian matrix that phase asymmetry could render ill-conditioned. FASEO returns a median loss of 292.40 kW against an uncompensated 235.75 kW, 24.0% higher: the 40/25/35 split drives one phase below the floor and the injection needed to lift it costs more active power than it saves. GWO’s 277.7 kW is the lowest of the six. FASEO’s VUF is 1.9250% against the 1.468% baseline, worse because the compensation concentrates on the loaded phase, and the minimum voltage rises from 0.8889 p.u. to 0.9500 p.u. The voltage profile in Figure 27 shows significant improvement, with inter-phase voltage variation decreasing from 3.2% to under 1.5%. The sweep’s recursive branch-current summation mechanism maintains numerical stability while delivering superior optimization performance.

5.3. Scenario C: Severely Unbalanced Network Configuration (69-Bus System)

Figure 31, Figure 32, Figure 33 and Figure 34 report the voltage, angle and branch-loss profiles for this case; Table 13 gives the corresponding metrics; Figure 35 isolates the per-phase spread.
Figure 31. Nodal voltage envelopes, IEEE 69-bus system, Scenario C. The grey dashed lines mark the 0.95 and 1.05 p.u. voltage limits.
Figure 32. Voltage angle deviation, IEEE 69-bus system, Scenario C.
Figure 33. Branch active power loss, IEEE 69-bus system, Scenario C.
Figure 34. Branch reactive power loss, IEEE 69-bus system, Scenario C.
Figure 35. Per-phase voltage envelope, IEEE 69-bus system, Scenario C. The grey dashed lines mark the 0.95 and 1.05 p.u. voltage limits.
Under severely unbalanced conditions (Phase A: 0.45, Phase B: 0.45, Phase C: 0.10), the same phase-decoupled backward/forward sweep is used throughout the optimization. This scenario presents the greatest challenge because of the extreme phase current disparities it creates. FASEO returns a median loss of 871.21 kW, 2.92 times the uncompensated 298.47 kW, with PSO’s 855.7 kW the lowest of the six. The VUF is 1.995% against the 3.811% baseline, and the minimum voltage rises from 0.8729 p.u. to 0.9500 p.u. The severe scenario is where the per-phase compensation model is actually exercised. With 45% of the load on phases a and b and only 10% on phase c, the phase currents differ by a factor of four, and a balanced shunt would over-compensate phase c while leaving a and b short. The per-phase injection absorbs that asymmetry, and Figure 31 shows the three phase envelopes converging on a common corridor. The resulting loss of 871.21 kW is 2.92 times the uncompensated baseline, which is a property of the case rather than a shortcoming of the optimizer: under a 45/45/10 split the voltage constraint binds before the loss objective, and any solution satisfying V min ≥ 0.95 p.u. must inject reactive power of that order. The sweep’s ability to handle deeply radial networks with asymmetric phase loading profiles is demonstrated by stable convergence to a feasible solution despite the extreme loading profile.

5.4. Statistical Analysis (69-Bus System)

To evaluate robustness on the 69-bus system, 30 independent runs were conducted under Scenario B. Table 17 places FASEO’s mean rank at 2.408, inside the leading group, with a rank standard deviation of 0.229. The test ranks the per-run active loss and places every infeasible run below every feasible one. Unlike the earlier parameterization, the composite cost no longer saturates: its standard deviation over the 30 runs is 4.37 × 10 − 2 , so the ordering is carried by the cost itself rather than by a tie-break. Loss across the 30 runs has a coefficient of variation of 6.2% in this case against 1.0% in 33-A.
Table 17. Friedman ranks and Nemenyi critical difference ( N = 180 ).

5.5. Convergence Characteristics (69-Bus System)

Figure 36 and Figure 37 show the convergence traces and the run-to-run spread.
Figure 36. Convergence of the six algorithms, IEEE 69-bus system, Scenario B.
Figure 37. Final-loss distribution over 30 runs, IEEE 69-bus system, Scenario B.
Figure 36 traces the six algorithms over the 50-generation budget of Section 3.4 and Figure 37 shows the distribution of final loss across the 30 runs. The behavior is the same in kind as on the 33-bus system: the fuzzy cost falls steeply while the step size is large and flattens once the cooling operator has reduced it, so the last third of the budget refines rather than explores. What differs is the margin. FASEO’s loss on this feeder is 227.20 kW in Scenario A, GWO reaches 211.8 kW and DE 266.4 kW, so the 7.3% gap to GWO is visible in the medians and the boxplot shows the run-to-run spread around them.

5.6. Multi-Objective Trade-Off Analysis (69-Bus System)

Figure 38 plots loss against unbalance for every feasible run.
Figure 38. Loss against voltage unbalance factor, IEEE 69-bus system.
The best-solution trade-off in Figure 38 illustrates a highly complex trade-off landscape driven by the system’s extended dimensionality and spatial asymmetry. On this feeder GWO returns 277.7 kW and PSO 284.3 kW, ahead of FASEO’s 292.40 kW, while FASEO’s unbalance of 1.9250% is lower than PSO’s 1.9902%; the two objectives trade and neither algorithm dominates the other. What the fixed weighting does is hold the search inside the constraint boundary instead of pushing to the lowest achievable loss. FASEO’s fixed weighting keeps the search inside that boundary, because the excess-loss term removes any gain from over-injection, which avoids the over-compensation traps observed in rigid single-objective strategies.

6. Discussion and Limitations

The diagnostic results are collected here. The remaining figures report the per-bus unbalance (Figure 39 and Figure 40), the injection per hub and phase (Figure 41 and Figure 42, with Table 11 and Table 16 carrying the same quantities as numbers), the comparison with published results (Table 18), the component ablation (Table 19), the constraint compliance (Figure 43 and Figure 44) and the 69-bus convergence (Figure 36 and Figure 37). Figure 45 gives the excess cost of each algorithm in every case, Figure 46 its mean rank by case, Figure 47 the number of feasible runs and Figure 48 runtime and evaluation counts; Table 20 collects the same four columns as numbers. Figure 45 plots, for each case, how far the mean cost of each algorithm lies above the best in that case, on one logarithmic scale. The 33-bus panels separate least; the 69-bus panels separate most, with a factor of three between the best algorithm and the rest in 69-B, and the whole field within about 2% of PSO in 69-C once the penalty dominates. Figure 46 reduces the same comparison to a mean rank per case: on cost the order is PSO 1.83, FASEO 2.00 and GWO 2.17, then DE 4.50, ARO 4.83 and POA 5.67, while on loss it is GWO 1.67, PSO 1.83, FASEO 2.50, DE 4.17, ARO 4.83 and POA 6.00, so FASEO gains a place when the objective rather than the loss is ranked. Figure 47 shows where that ordering comes from: PSO and DE are feasible in all 180 runs, FASEO in 179, GWO in 173, ARO in 153 and POA in 120, with ARO down to 23 of 30 in 33-C and POA to none in 69-C. Figure 48 reports what each run costs: the median is 62.9 s for ARO, 67.8 s for FASEO, 70.6 s for POA, 70.8 s for PSO, 88.8 s for GWO and 112.0 s for DE, and the evaluation counts differ only through the cache discussed next. Table 20 places the four columns side by side.
Figure 39. Voltage unbalance factor at every bus, IEEE 33-bus system, Scenario C. The grey dashed line marks the 2% unbalance limit.
Figure 40. Voltage unbalance factor at every bus, IEEE 69-bus system, Scenario C. The grey dashed line marks the 2% unbalance limit.
Figure 41. Reactive injection per hub and phase, IEEE 33-bus system, Scenario C.
Figure 42. Reactive injection per hub and phase, IEEE 69-bus system, Scenario C.
Table 18. Comparison with published results.
Table 19. Component ablation.
Figure 43. Minimum voltage against voltage unbalance, IEEE 33-bus system. The grey dashed line marks the 0.95 p.u. lower voltage limit.
Figure 44. Minimum voltage against voltage unbalance, IEEE 69-bus system. The grey dashed line marks the 0.95 p.u. lower voltage limit.
Figure 45. Excess cost over the best algorithm in each case (logarithmic scale).
Figure 46. Mean rank by case on cost (left) and loss (right).
Figure 47. Feasible runs out of 30, by algorithm and case.
Figure 48. Median runtime (a) and median evaluations (b) per algorithm.
Table 20. Comparison summary.
The evaluation counts in Figure 48b differ between algorithms although every run performs the same 50 generations of 30 candidates. The cause is the fitness cache: a candidate vector is memorized to four decimal places, so a trial that repeats an earlier point is served from the cache and does not increment the counter. The median of 1614 for FASEO against 1530 for the alternatives therefore measures how often each search revisits a point, not a larger budget, and the lowest count, POA’s 1145, is the signature of an update rule that proposes the incumbent itself whenever the selected individual is the current elite. The comparison is budget-equal in generations and population size, not in distinct evaluations, and the runtime figures in Section 6 should be read with that in mind. The residual spread between phases is a property of the decoupled model rather than of the optimizer: because the phases are solved independently, driving the loaded phase to 0.95 p.u. leaves the lightly loaded phase above 1.0 p.u., and the largest difference between phases at a bus is about 4.5% of nominal, and it is visible in Figure 18. Reducing it further would require a coupled impedance model, which the available feeder data do not support. All simulations were implemented in Python 3.7 using NumPy and SciPy, with a custom phase-decoupled backward/forward sweep solver; the feeder data follow the standard IEEE 33-bus and 69-bus test cases and the complete configuration and per-run results are held in the accompanying data files. One property of the objective limits how much can be read into the ranking: the penalty of (19) grows with the square of the excess loss, so the objective’s scale spans three orders of magnitude, from 0.34–0.44 in the balanced 33-bus cases to about 340 on 69-C. The Friedman order therefore rests on within-case ranks rather than on the absolute values, and should be read as a grouping rather than a strict ordering.
Full-FASEO reproduces the main comparison to 0.00 kW in all six cases, so the ablation and the comparison measure the same algorithm. Read on the objective the optimizer minimizes, the complete configuration is the only variant that is never worse than second on any of the three measures the study reports: it holds the best objective rank (2.67, level with the constant- η arm), the second-highest feasibility (179 of 180) and the second-lowest mean objective. No other variant achieves that. Each removal buys something on one measure and pays for it on another. Dropping the cooling schedule is the only change that degrades every case, from 0.342 to 0.383 on 33-A and from 4.758 to 7.760 on 69-B, and it is the worst variant on both the objective and the loss ranking. Dropping elite tuning costs 39% on 33-C and 19% on 69-C; dropping the restart costs 6.7% on 33-C. The two mechanisms that trade rather than degrade are steering and the η schedule: removing steering improves 33-C (1.381 against 1.601) and 69-C (333.4 against 340.9) but costs the mild cases and three feasible runs, so its aggregate rank falls from 2.67 to 2.83, while removing the η schedule leaves the rank unchanged and raises the mean objective. The ablation therefore supports the engine as a configuration whose components protect different cases, not a single operator as indispensable.
The compensation hubs at buses 64 and 65 of the 69-bus feeder are electrically adjacent, which invites the objection that a single device would suffice. Under the stated ceiling they do not substitute for one another: a hub is limited to 700 kVAR per phase, and the optimizer loads both nodes in every scenario, with 1168 and 462 kVAR total in the balanced case and 1601 and 1565 kVAR in the severe case (Table 16), so neither is idle. The adjacent placement is therefore the configuration the installed capacity admits rather than an artifact of the selection rule.
FASEO’s advantages are therefore specific and reproducible rather than uniform. It attains the lowest active loss of the six algorithms in the severe 33-bus case (291.54 kW against 291.6 kW for GWO, a margin of 0.06 kW that is within the run-to-run spread) and remains within 0.9% of the best in the two remaining 33-bus scenarios. Among the algorithms competitive on loss, FASEO is the second most reliable: 179 of its 180 runs satisfy every constraint, against 173 for GWO and 153 for ARO, and only PSO returns 180. Its rank dispersion (0.229) is narrower than GWO’s, DE’s and POA’s, and its median runtime across the 180 runs is 67.8 s, against 88.8 s for GWO, 70.8 s for PSO and 112.0 s for DE, with only ARO (62.9 s) quicker, even though it uses 5.5% more power-flow evaluations than the 1530 run by four of the benchmarks. The generality of the loss advantage is bounded: on the 69-bus feeder its median loss lies within 1.8–7.3% of the lowest of the six, and the Friedman test places it third of six, inside the critical difference that keeps the leading three together.

6.1. Uncertainty of the Reported Medians

Every median in Section 4 and Section 5 is a point estimate from 30 runs, so it is reported here with a 95% confidence interval obtained by bootstrap resampling of the feasible runs of each cell (10,000 resamples, percentile method); Table 21 gives the 33-bus intervals and Table 22 the 69-bus ones. The intervals bound how much of the ordering between algorithms can be read from the medians. In the severe 33-bus case FASEO’s median of 291.54 kW carries an interval of 285.68–298.69 kW, which is far wider than the 0.06 kW by which it precedes GWO, so the case is a tie between the two and is described as one. On the severe 69-bus case the interval spans 844.05–915.79 kW, so the differences of a few per cent that separate the six algorithms there are not resolvable from 30 runs, and no ordering is claimed on that case. Where the intervals do separate algorithms they support the ranking reported in Section 6, and where they overlap the text reports a tie rather than a winner.
Table 21. Median active loss with 95% bootstrap confidence intervals, IEEE 33-bus. The interval resamples the feasible runs of each cell 10,000 times and reports the percentile bounds.
Table 22. Median active loss with 95% bootstrap confidence intervals, IEEE 69-bus. The interval resamples the feasible runs of each cell 10,000 times and reports the percentile bounds.

6.2. Scope and Limitations

Four limits bound what the results establish, and each is stated here rather than left to inference. First, no formal convergence guarantee is claimed. FASEO is a stochastic population search, and no global-convergence result is available for this class of method. What can be argued is weaker and verifiable: the elite individual is copied unchanged into the next generation, so the best-so-far objective is non-increasing by construction, and Table 19 and the convergence traces of Figure 20 and Figure 36 show the 30 runs of every case settling in the second half of the 50-generation budget. The known failure mode is the one the severe cases exhibit: when the voltage floor binds before the loss objective, the population can spend generations in the infeasible region before the gate of (17) admits a feasible candidate. That behavior is visible in the feasibility counts of Section 6 and is the reason the feasibility column is reported alongside every objective value.
Second, the study uses synthetic IEEE test feeders. No measured field data were available, so the load splits, the per-phase injections and the compensation siting are evaluated on standard benchmark models rather than on a recorded feeder. The results therefore establish behavior under stated and repeatable conditions, not field performance, and no field-readiness is claimed.
Third, distributed generation is not modeled. The feeders carry passive loads and capacitor-type compensation only, so the interaction between DG injection and per-phase compensation is outside the scope of both the model and the runs. DG placement is solved with the same metaheuristic family used here [22,23], and extending the per-phase formulation to co-optimize DG and compensation is left as future work rather than implied by these results.
Fourth, the sensitivity study is not reported. A load-factor sweep was run under an earlier objective formulation and was never re-run under the bounds frozen for this study, so its numbers would describe different solutions and are withheld instead of ported. Weight and operator sensitivity is addressed instead by the seven-variant ablation of Table 19, which removes each component in turn and scores the result on the same objective.

7. Conclusions

7.1. Core Research Takeaways

This study has successfully demonstrated a comprehensive multi-objective optimization framework for managing severe operational unbalance in radial distribution networks. A single phase-decoupled backward/forward sweep serves every case, so no result depends on which solver architecture was selected. The FASEO engine’s unique operators—Master Elite Fine-Tuning with β = 0.08 , Elite Directed Vector Steering with adaptive influence factor η ( g ) = 0.75 − 0.45 · g / g max , and Exponential Satisfaction Cooling Operator with α 0 = 3.0 and ζ = 1.5 —are described in Section 3. The ablation in Section 6 finds that only the cooling schedule degrades every case when removed; the elite-tuning, restart and influence-schedule components are reported there as design choices with case-dependent effects rather than as uniform gains.
Extensive validation on the IEEE 33-bus system gives objective values of 0.342, 0.421 and 1.601 for the balanced, moderately and severely unbalanced scenarios, with median losses of 143.29, 167.17 and 291.54 kW against uncompensated values of 202.19, 211.70 and 265.80 kW. The two milder cases see a 21–29% loss reduction; in the severe case the voltage floor binds and the compensated loss exceeds the uncompensated one for every algorithm, FASEO least so. On the IEEE 69-bus system with seven hubs, the objective values are 0.767, 4.758 and 340.9, with median losses of 227.20, 292.40 and 871.21 kW. None of the three reaches the uncompensated loss of 224.65 kW; the two unbalanced cases cost active power because the voltage floor binds, and that is reported here rather than presented as a saving. The VUF falls from 3.529% to 1.997% in the severe 33-bus case and from 3.811% to 1.995% in the severe 69-bus case, and the minimum voltage reaches 0.9500 p.u. in every case. Statistical analysis places FASEO third of six by Friedman rank (2.408), within the Nemenyi critical difference of GWO and PSO, and second of six on the composite cost by mean rank (2.00).

7.2. Future Strategic Roadmap

Future work will extend the framework to larger test systems, including IEEE 118-bus networks and real-world feeder data [29]. The framework will be expanded to optimize microgrids with high PV penetrations and battery energy storage systems. Integration of model-predictive control layers will enable real-time adaptive optimization [14]. Future iterations will incorporate intelligent machine learning for short-term load forecasting, advanced state-space modeling for variable-speed renewable generation [42], and modified metaheuristics for real-time classification of power quality disturbances.

Funding

This research received no external funding.

Data Availability Statement

The per-run results underlying every table and figure are held in the project dataset (1080 runs: six algorithms across six cases with 30 seeds) and are available from the corresponding author on reasonable request.

Acknowledgments

The author thanks the Water Technologies Innovation Institute & Research Advancement (WTIIRA) at the Saudi Water Authority (SWA) for its support.

Conflicts of Interest

The author declares no conflicts of interest.

Abbreviations

The following abbreviations are used in this manuscript:
AROArtificial Rabbit Optimization
BFSBackward/Forward Sweep
DEDifferential Evolution
FASEOFuzzy Adaptive Steering Elite Optimization
GWOGrey Wolf Optimizer
POAPelican Optimization Algorithm
PSOParticle Swarm Optimization
VDVoltage Deviation
VUFVoltage Unbalance Factor
VVOVolt-VAR Optimization

References

  1. Teng, J.H. A direct approach for distribution system load flow solutions. IEEE Trans. Power Del. 2003, 18, 882–887. [Google Scholar] [CrossRef] [Scilit]
  2. Bassi, H.; Rawa, M.; Abusorrah, A.; Al-Turki, Y.; Sindi, H.; Mostafa, M.H. Efficient energy management framework for enhancing the techno-economic-environmental performance of grid-connected microgrids under uncertain conditions. Ain Shams Eng. J. 2024, 15, 102336. [Google Scholar] [CrossRef] [Scilit]
  3. Gonen, T. Electric Power Distribution System Engineering, 3rd ed.; CRC Press: Boca Raton, FL, USA, 2014. [Google Scholar]
  4. Iba, K. Reactive power optimization by genetic algorithm. IEEE Trans. Power Syst. 1994, 9, 685–692. [Google Scholar] [CrossRef] [Scilit]
  5. Acharya, N.; Mahat, P.; Mithulananthan, N. An analytical approach for DG allocation in a radial distribution system. Int. J. Electr. Power Energy Syst. 2006, 28, 669–675. [Google Scholar] [CrossRef] [Scilit]
  6. Chakravorty, M.; Das, D. Voltage stability analysis of radial distribution networks. Int. J. Electr. Power Energy Syst. 2001, 23, 129–135. [Google Scholar] [CrossRef] [Scilit]
  7. Kersting, W.H. Radial distribution test feeders. IEEE Trans. Power Syst. 1991, 6, 975–985. [Google Scholar] [CrossRef] [Scilit]
  8. Maataoui, Y.; Dankir, S.; Chekenbah, H.; Puig, V.; Lasri, R. A model predictive control approach solved via modified mixed-variable PSO for voltage unbalance mitigation in an unbalanced distribution system with high photovoltaic penetration. Electr. Eng. 2026, 108, 122. [Google Scholar] [CrossRef] [Scilit]
  9. Gil-Gonzalez, W.; Montoya, O.D.; Rajagopalan, A.; Grisales-Noreña, L.F.; Hernández, J.C. Optimal selection and location of fixed-step capacitor banks in distribution networks using a discrete version of the vortex search algorithm. Energies 2020, 13, 4914. [Google Scholar] [CrossRef] [Scilit]
  10. Wang, Y.; Xu, R.; Zhou, F.; Shi, T. Mesh-Based Planning for Distribution Networks Considering the Risk of Voltage Imbalance. In Proceedings of the 2025 5th International Conference on New Energy and Power Engineering (ICNEPE), Guangzhou, China, 14–16 November 2025. [Google Scholar]
  11. Liu, Y.; Zhang, Y.; Li, X. A Multi-Time Scale Reactive Power Optimization Model Considering Network Reconfiguration. IEEE Trans. Ind. Appl. 2026, 62, 328–340. [Google Scholar] [CrossRef] [Scilit]
  12. Soesanti, I.; Syahputra, R. Multiobjective ant lion optimization for performance improvement of modern distribution network. IEEE Access 2022, 10, 12096–12114. [Google Scholar] [CrossRef] [Scilit]
  13. Hlalele, T.S. Optimization of Power Flow in Renewable-Rich Distribution Networks Using Fibonacci Search and Heuristic Scheduling Algorithms. Int. Trans. Electr. Energy Syst. 2026, 2026, 8516574. [Google Scholar] [CrossRef] [Scilit]
  14. Sultan, H.M.; Diab, A.; Menesy, A.S.; Kassas, M. Enhancing optimal power flow in power systems: A comparative analysis of recent metaheuristic optimization techniques. Energy Rep. 2025, 13, 3957–3999. [Google Scholar] [CrossRef] [Scilit]
  15. Salem, A.; Flah, A.; Aboraya, A. A new optimization algorithm integrated with power flow analysis for efficient shunt capacitor bank allocation in radial distribution networks. IEEE Access 2026, 14, 1–18. [Google Scholar] [CrossRef] [Scilit]
  16. El-Rifaie, A.M.; Shaheen, A.M.; Tolba, M.A.; Smaili, I.H.; Moustafa, G.; Ginidi, A.R.; Elshahed, M.A. Modified gradient-based algorithm for distributed generation and capacitors integration in radial distribution networks. IEEE Access 2023, 11, 120899–120917. [Google Scholar] [CrossRef] [Scilit]
  17. Kunya, A.B.; Ibrahim, A.A.; Hamid, S.B.A. Metaheuristic optimization algorithms for multi-area economic dispatch of power systems: Part I—A comprehensive survey. Artif. Intell. Rev. 2025, 58, 98. [Google Scholar] [CrossRef] [Scilit]
  18. Mirjalili, S.; Mirjalili, S.M.; Lewis, A. Grey wolf optimizer. Adv. Eng. Softw. 2014, 69, 46–61. [Google Scholar] [CrossRef] [Scilit]
  19. Kennedy, J.; Eberhart, R. Particle swarm optimization. Proc. IEEE Int. Conf. Neural Netw. 1995, 4, 1942–1948. [Google Scholar]
  20. Moradi, M.H.; Abedini, M. A combination of genetic algorithm and particle swarm optimization for optimal DG location and sizing in distribution systems. Int. J. Electr. Power Energy Syst. 2012, 34, 66–74. [Google Scholar] [CrossRef] [Scilit]
  21. Storn, R.; Price, K. Differential evolution—A simple and efficient heuristic for global optimization over continuous spaces. J. Glob. Optim. 1997, 11, 341–359. [Google Scholar] [CrossRef] [Scilit]
  22. El-Fergany, A. Optimal allocation of multi-type distributed generators using backtracking search optimization algorithm. Int. J. Electr. Power Energy Syst. 2015, 64, 1197–1205. [Google Scholar] [CrossRef] [Scilit]
  23. Sanjay, R.; Jayabarathi, T.; Raghunathan, T.; Ramesh, V.; Mithulananthan, N. Optimal allocation of distributed generation using hybrid grey wolf optimizer. IEEE Access 2017, 5, 14807–14818. [Google Scholar] [CrossRef] [Scilit]
  24. Rawa, M.; Abusorrah, A.; Bassi, H.; Mekhilef, S.; Ali, Z.M.; Aleem, S.H.A.; Hasanien, H.M.; Omar, A.I. Economical-technical-environmental operation of power networks with wind-solar-hydropower generation using analytic hierarchy process and improved grey wolf algorithm. Ain Shams Eng. J. 2021, 12, 2717–2734. [Google Scholar] [CrossRef] [Scilit]
  25. Trojovsky, P.; Dehghani, M. Pelican optimization algorithm: A novel nature-inspired algorithm for engineering applications. Sensors 2022, 22, 855. [Google Scholar] [CrossRef] [Scilit]
  26. Wang, L.; Cao, Q.; Zhang, Z.; Mirjalili, S.; Zhao, W. Artificial rabbits optimization: A new bio-inspired meta-heuristic algorithm for solving engineering optimization problems. Eng. Appl. Artif. Intell. 2022, 114, 105082. [Google Scholar] [CrossRef] [Scilit]
  27. Mirjalili, S. The ant lion optimizer. Adv. Eng. Softw. 2015, 83, 80–98. [Google Scholar] [CrossRef] [Scilit]
  28. Lillicrap, T.P.; Hunt, J.J.; Pritzel, A.; Heess, N.; Erez, T.; Tassa, Y.; Silver, D.; Wierstra, D. Continuous control with deep reinforcement learning. arXiv 2015, arXiv:1509.02971. [Google Scholar]
  29. Liao, J.; Lin, J. A distributed deep reinforcement learning approach for reactive power optimization of distribution networks. IEEE Access 2024, 12, 114281–114296. [Google Scholar] [CrossRef] [Scilit]
  30. Alanazi, M.; Alanazi, A.; Almadhor, A.; Memon, Z.A. Multiobjective reconfiguration of unbalanced distribution networks using improved transient search optimization algorithm considering power quality and reliability metrics. Sci. Rep. 2022, 12, 13686. [Google Scholar] [CrossRef] [Scilit]
  31. Zolfaghari, M.; Jalilian, A. A two-stage approach for reducing unbalance and voltage deviation in active distribution networks considering load pattern and correlated uncertainties. IET Gener. Transm. Distrib. 2025, 19, e70187. [Google Scholar] [CrossRef] [Scilit]
  32. Li, Y.; Zhang, Z.; Liu, J. Optimum Operation of Low-Voltage AC/DC Distribution Areas with Embedded DC Interconnections under Three-Phase Unbalanced Compensation Conditions. Electr. Power Syst. Res. 2026, 123, 1. [Google Scholar] [CrossRef] [Scilit]
  33. Selim, A.; Kamel, S.; Alghamdi, A.S.; Jurado, F. Optimal placement of DGs in distribution system using an improved Harris Hawks optimizer based on single- and multi-objective approaches. IEEE Access 2020, 8, 52847–52865. [Google Scholar] [CrossRef] [Scilit]
  34. Refaat, M.M.; Al-Gahtani, S.F.; Bassi, H.; Ali, Z.M.; Aleem, S.H.A. Optimizing power network expansion with pumped hydro energy storage using a multi-objective enhanced spider wasp optimizer approach. Sci. Rep. 2025, 15, 13409. [Google Scholar] [CrossRef] [Scilit]
  35. Biswal, S.R.; Shankar, G.; Elavarasan, R.M.; Mihet-Popa, L. Optimal allocation/sizing of DGs/capacitors in reconfigured radial distribution system using quasi-reflected slime mould algorithm. IEEE Access 2021, 9, 125658–125677. [Google Scholar] [CrossRef] [Scilit]
  36. Bassi, H.; Siddique, M.D.; Seyedmahmoudian, M.; Mekhilef, S.; Alghamdi, A.S.; Mahmoud, A.M.; Albutuwaybh, H.H.; Stojcevski, A. Power Quality Improvement Using Phase Transposition for Multi-Motor System with Variable Speed Drives Using Diode-Bridge Rectifier. In Proceedings of the 2025 IEEE Conference on Power Electronics and Renewable Energy (CPERE), Aswan, Egypt, 28–30 September 2025; pp. 1–5. [Google Scholar]
  37. Qais, M.H.; Hasanien, H.M.; Alghuwainem, S. Transient search optimization: A new meta-heuristic optimization algorithm. Appl. Intell. 2020, 50, 3926–3941. [Google Scholar] [CrossRef] [Scilit]
  38. Baran, M.E.; Wu, F.F. Network reconfiguration in distribution systems for loss reduction and load balancing. IEEE Trans. Power Del. 1989, 4, 1401–1407. [Google Scholar] [CrossRef] [Scilit]
  39. Baran, M.E.; Wu, F.F. Optimal sizing of capacitors placed on a radial distribution system. IEEE Trans. Power Del. 1989, 4, 735–743. [Google Scholar] [CrossRef] [Scilit]
  40. Das, D.; Kothari, D.P.; Kalam, A. Simple and efficient method for load flow solution of radial distribution networks. Int. J. Electr. Power Energy Syst. 1995, 17, 335–342. [Google Scholar] [CrossRef] [Scilit]
  41. ANSI C84.1-2020; American National Standard for Electric Power Systems and Equipment—Voltage Ratings (60 Hz). National Electrical Manufacturers Association: Arlington, VA, USA, 2020.
  42. Bassi, H.; Mobarak, Y.A. State-space modeling and performance analysis of variable-speed wind turbine based on a model predictive control approach. Eng. Technol. Appl. Sci. Res. 2017, 7, 1436–1443. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.