TRNSYS-Based Assessment of DHW Preheating Storage in a Residential PVT–ASHP System: Energy Performance and Operational CO2 Emissions

,
,
and
1
Mechanical Engineering Faculty, University of Slavonski Brod, I. Gundulića 20A, 35000 Slavonski Brod, Croatia
2
Faculty of Mechanical Engineering and Naval Architecture, University of Zagreb, I. Lučića 5, 10000 Zagreb, Croatia
*
Author to whom correspondence should be addressed.

Abstract

This study evaluates how photovoltaic–thermal (PVT) domestic hot water (DHW) preheating tank configurations affect the energy performance and operational CO2 emissions of a residential air-source heat pump (ASHP) system in Croatia. A TRNSYS model compared a reference configuration without PVT (K0) with six PVT-assisted configurations (K1–K6) using 100–600 L tanks with regression-derived geometric and hydraulic parameters. Comparison of simulated annual gas consumption with six-year average space-heating consumption estimated from measured total gas consumption (2020–2025) yielded a −1.96% deviation. All configurations met the specified space-heating and DHW temperature criteria. PVT preheating increased the whole-system seasonal performance factor (SPF) from 2.352 to 2.521–2.623 and reduced annual thermal-system electricity consumption by 7.76–13.66%. Maximum useful PVT thermal output (1418.74 kWh/year), maximum SPF (2.623), and minimum electricity consumption (6429.64 kWh/year) occurred at 300, 400, and 600 L, respectively. Using an assumed grid emission factor of 0.116 kg CO2/kWh, the maximum operational emissions reduction was 118.02 kg CO2/year. PVT electricity self-consumption and exports were excluded from emissions accounting. Thus, the preferred tank configuration depends on the selected performance indicator, and the reported emissions reductions reflect thermal-system electricity savings only.

1. Introduction

Air-source heat pumps (ASHPs), particularly air-to-water systems, are used for space heating and domestic hot water (DHW) preparation in residential buildings. Their seasonal performance depends on outdoor air temperature, the required heating-water temperature, thermal load, and control strategy. Electricity consumption and associated operational CO2 emissions are therefore important performance indicators. Photovoltaic–thermal (PVT) collectors simultaneously generate electricity and recover useful heat, although the benefits of their integration with heat pumps depend on system configuration and operating conditions [1]. Špago et al. [2] investigated hybrid renewable-energy systems for buildings, whereas Đuranović et al. [3] compared an existing absorption heat-pump system with a vapor-compression alternative using measured natural gas consumption and an economic assessment.
Recovered PVT heat can be supplied to the heat-source side of a heat pump or used on the load side for DHW preheating or space heating. These arrangements involve different energy flows and operating mechanisms, so their reported performance indicators are not necessarily directly comparable. Assessments of integrated systems should therefore distinguish heat-pump efficiency from whole-system seasonal performance and clearly define the electricity inputs and useful thermal outputs included in each indicator.
Dynamic simulation is commonly used to evaluate PVT–heat-pump systems under varying climatic and operating conditions. Rijvers et al. [4] developed a TRNSYS model of a residential PVT–heat-pump system and reported seasonal performance factors (SPFs) ranging from 3.0 to 3.9 when weather, occupancy, and building orientation were varied. Dannemand et al. [5] combined an experimentally validated TRNSYS model with component-sizing analysis for a PVT–heat-pump system with two storage tanks; their improved configuration reduced electricity consumption by 23% relative to the original demonstration system. These studies illustrate the importance of both system boundaries and component sizing when interpreting reported performance gains.
The influence of storage characteristics has been examined in several related configurations. Barbu et al. [6] analyzed the effects of tank volume, inlet-water temperature, draw-off rate, and DHW demand profile in a PVT-assisted hot-water system. Wang et al. [7] investigated a PVT–ASHP system incorporating phase-change storage, considering tank volume and collector and circulation parameters. Öztürk et al. [8] assessed energy, exergy, and economic performance under two climatic conditions. Liravi et al. [9] examined preheating tanks in a PVT-assisted ground-source heat pump system, showing that storage integration can improve whole-system performance but that the benefit depends on the hydraulic and system arrangement. The latter configuration differs from an air-to-water heat pump coupled to a separate PVT-heated DHW preheating tank.
Storage volume alone does not determine the thermal behavior of a water tank. Temperature stratification, geometry, inlet-induced mixing, and heat-exchanger and flow characteristics also affect the amount and temperature of useful heat. Jodeiri et al. [10] developed and experimentally validated an enhanced stratified-tank model accounting for geometry and hydraulic mixing. Król and Kupiec [11] found that stratification can affect the stability of DHW delivery temperature differently from its influence on annual solar performance. These findings indicate that tank sizing should be assessed together with relevant geometric and hydraulic characteristics and that storage performance cannot be reduced to volume alone.
Related studies by Đuranović et al. addressed thermal energy storage in residential air-to-water heat pump systems. A multi-year analysis for three Croatian locations reported annual electricity savings of 4.8–9.1% after storage integration [12]. A tariff-oriented analysis found electricity cost reductions of 19–23% through load shifting, without significant changes in seasonal heat-pump performance [13]. However, those investigations focused on space-heating storage and operating costs; they did not consider a dedicated PVT-assisted DHW preheating tank or the relationship between its configuration and alternative whole-system performance indicators.
Although the literature establishes the importance of PVT integration, storage sizing, and thermal stratification, the influence of a dedicated PVT-assisted DHW preheating tank on the overall performance of a residential air-to-water heat pump system remains insufficiently resolved. In particular, it is unclear whether the same tank configuration maximizes useful PVT thermal output, maximizes whole-system SPF, and minimizes annual thermal-system electricity consumption. Varying tank volume also changes geometry, immersed heat-exchanger characteristics, and hydraulic operating conditions; these coupled changes should be represented consistently when comparing configurations. Moreover, operational CO2 savings depend on the electricity-consumption boundary used in the calculation.
This study therefore evaluates the effects of PVT-assisted DHW preheating tank configurations on annual energy performance and operational CO2 emissions in a single-family house in Slavonski Brod, Croatia. A TRNSYS model compares a reference air-to-water heat pump system without PVT collectors (K0) with six PVT-assisted configurations (K1–K6) using preheating tanks of 100–600 L. The building model is assessed against space-heating gas consumption estimated from measured total consumption for 2020–2025. The PVT collector area, space-heating buffer volume, and final DHW heating tank volume are held constant. Geometric and hydraulic parameters of the preheating tanks are derived consistently from regressions fitted to manufacturer catalogue data.
The principal contribution is a comparative evaluation of a specific PVT–ASHP arrangement in which recovered PVT heat preheats DHW in a separate tank upstream of the final heating tank, while outdoor air remains the heat-pump source. Rather than seeking a universally optimal tank volume, the analysis identifies performance trade-offs among useful PVT thermal output, whole-system SPF, annual electricity consumption, and the resulting operational CO2 emissions. It shows that the most favorable investigated tank size depends on the selected performance indicator.

2. Materials and Methods

2.1. Case Study Building and Meteorological Conditions

The building examined in this study is a single-family house located in Slavonski Brod, Croatia. Its geometry, room layout, construction assemblies, and occupancy patterns were modeled according to the as-built condition. The building is a single-story house with an unheated attic. The ground floor was divided into thirteen thermal zones, ten of which are heated and three unheated. The attic was represented by an additional, fourteenth unheated zone. External construction elements, internal gains, and air change rates were specified separately for each zone.
The external walls consist of lime-cement plaster, hollow clay blocks, and an external layer of expanded polystyrene thermal insulation. The calculated thermal transmittance of the external walls is 0.255 W/(m2·K). The floor assembly comprises a reinforced concrete slab, an expanded polystyrene layer, an underfloor heating system, a cement screed, and a ceramic tile finish, with a thermal transmittance of 0.315 W/(m2·K).
The ceiling beneath the attic consists of lime–cement plaster, a reinforced concrete slab, a membrane, and a mineral wool layer, with a thermal transmittance of 0.150 W/(m2·K). The internal walls comprise hollow clay blocks plastered on both sides with lime–cement plaster and have a thermal transmittance of 0.890 W/(m2·K). The roof assembly consists of roof tiles, a membrane, and timber boarding, with a thermal transmittance of 1.238 W/(m2·K).
External openings include windows and external doors. The window thermal transmittance is 0.80 W/(m2·K), with glazing and frame fractions of 80% and 20%, respectively, accounted for in the calculation. A thermal transmittance of 1.00 W/(m2·K) was adopted for the external doors, which were defined in the model as opaque elements without glazing. The main building physics and operating parameters of the building model are presented in Table 1.
Table 1. Main building physics and operating parameters of the building model.
The design temperatures of the heated zones were selected based on the actual use of the building and in accordance with the design indoor temperatures specified in HRN EN 12831 [14]. An air change rate of 0.5 h−1 was adopted for most heated rooms with external windows. For the unheated storage room, designated as Zone 5, which has an external window, a value of 0.1 h−1 was adopted because the room is rarely ventilated.
The internal bathroom, designated as Zone 7, and the toilet, designated as Zone 12, have no external windows. Exhaust fans operate intermittently in these rooms, but their operation and the associated make-up airflow from adjacent rooms were not modeled separately. The effect of intermittent ventilation was approximated using an equivalent outdoor air infiltration rate of 0.1 h−1. This value simplifies the actual airflow and constitutes a limitation of the building thermal model.
An infiltration rate of 0.25 h−1 was adopted for the attic because of the lower airtightness of the roof assembly. No infiltration was specified for Zone 8, as it is an internal room without direct openings to the outdoor environment. Figure 1 shows the floor plan of the case study house and the arrangement of its thermal zones.
Figure 1. Floor plan of the case study house and arrangement of the thermal zones.
Specific internal heat gains of 5 W/m2 were defined in the heated thermal zones, collectively accounting for occupants, lighting, and electrical equipment. These gains were specified relative to the net floor area of each thermal zone and applied daily from 06:00 to 22:00, while they were set to 0 W/m2 between 22:00 and 06:00. Consistent with the specification of internal heat gains in TRNBuild, where convective and radiative contributions are defined separately, the total internal gains were divided into 50% convective and 50% radiative components. The convective component is transferred directly to the air node of the respective zone, whereas the radiative component is distributed across the internal surfaces of the zone.
Type 15-3 was used to read and process meteorological data in the simulation model. Weather data for Slavonski Brod were obtained in EnergyPlus Weather (EPW) format from the Climate.OneBuilding.Org database. The downloaded typical meteorological year, TMYx, contained in the file HRV_SP_Slavonski.Brod.143700_TMYx.2011-2025.epw was used; it was compiled from weather data for 2011–2025 [15]. The meteorological location is defined by a latitude of 45.15920°, a longitude of 17.99530°, an elevation of 89 m, and the UTC+1 time zone. The weather data have an hourly resolution, consistent with the simulation time step of 1 h.

2.2. Development of the Dynamic Simulation Model

The TRNSYS 18 (University of Wisconsin–Madison, Madison, WI, USA) software environment was used to develop the dynamic simulation model in this study. TRNSYS is a comprehensive and extensible simulation environment for time-dependent modeling of complex energy systems, including multizone buildings, heating, ventilation, and air-conditioning systems, solar thermal and photovoltaic systems, renewable energy systems, cogeneration plants, and other systems whose behavior varies over time. It is particularly suitable for analyzing interactions among energy components, control strategies, meteorological conditions, and building thermal demands.
A complete dynamic simulation model was developed in TRNSYS. Individual components, known as TRNSYS Types, were interconnected and grouped into dedicated macro blocks for clarity. These blocks represent the main physical, thermal, hydraulic, and control subsystems of the building. The model comprises a coupled ground and building model, a space heating system, a DHW system, a heat pump, PVT collectors, and the associated control elements.
At each time step, temperatures, mass flow rates, heat transfer rates, storage tank states, and control signals are exchanged between components and macro blocks. This enables simultaneous tracking of the building thermal response, heat pump operation, utilization of heat from the PVT collectors, space heating and DHW operation, and changes in the states of the thermal storage tanks.
To improve clarity and manage model complexity, interconnected component groups were organized into functionally complete macro blocks. These comprise the ground and building model, the hydraulic and control model of the heating system, and the DHW system. Meteorological data, the heat pump, the PVT collector, diverting valves, thermostats, and control functions are represented as separate components or control blocks.
The thermal behavior of the building was modeled using Type 56, with the building characteristics defined in TRNBuild [16]. Heat transfer between the floor and the ground was simulated using Type 1244. Underfloor heating was represented by active layers within the building model, while supplementary bathroom radiators were modeled using Type 1231. The space heating buffer tank and DHW storage tanks were represented using Type 1534. The air-to-water heat pump was modeled using Type 525, the gas-fired condensing boiler employed during model validation using Type 751, and PVT collectors using Type 1343 [17]. Circulation pump operation and system control strategies were implemented through the corresponding TRNSYS components and additional control logic developed in MATLAB (version R2024b, The MathWorks, Inc., Natick, MA, USA) [18].
The ground model employed a three-dimensional computational grid of nodes representing the soil in the immediate vicinity of the building and undisturbed soil at the distant boundaries. The remote lateral boundaries of the computational domain were located 10 m from the outer edges of the building. The exchange of output temperatures between Type 1244 and Type 56 enables dynamic determination of heat transfer through the floor assembly. Figure 2 shows the structure of the dynamic simulation model of the integrated PVT–ASHP system developed in TRNSYS.
Figure 2. Structure of the dynamic simulation model of the integrated PVT–ASHP system developed in TRNSYS.

2.3. Heat Pump and Space Heating System

The air-to-water heat pump in the dynamic simulation model was represented using Type 525. This component describes a heat pump that uses outdoor air as its heat source and heats the heat transfer fluid on the load side. The compressor operates at variable speed, adjusting its operation to the prevailing conditions to achieve the specified heat pump outlet fluid temperature. Although the component supports both heating and cooling modes, only heating mode was used in the present model.
Type 525 does not provide a detailed physical description of the individual refrigeration cycle components. Instead, device performance is determined from user-defined data files compiled from manufacturer catalogue data. Performance characteristics are specified as functions of the heat pump inlet air temperature, the outlet fluid temperature setpoint, and the part-load ratio (PLR). This approach allows the simulated heating capacity and electrical input power to vary with operating conditions rather than applying constant rated values throughout the simulation.
A Viessmann Vitocal 200-S (Viessmann, Allendorf, Germany) air-to-water heat pump, type AWB-M-E-AC-AF201.E10, was selected for the simulation model. It is a split system with indoor and outdoor units. The outdoor unit comprises an inverter-driven compressor, an electronic expansion valve, an EC fan, and an evaporator, and the refrigeration circuit uses R32 refrigerant. The inverter-driven compressor allows the heating capacity to adapt to the prevailing operating conditions and system demand [19].
According to the manufacturer, the selected AWB-M-E-AC-AF201.E10 unit has a rated heating capacity of 10.10 kW, an electrical input power of 2.16 kW, and a coefficient of performance (COP) of 4.67 at A7/W35, with a heating capacity modulation range of 2.6–10.4 kW. At A2/W35, the rated heating capacity is 7.09 kW, the electrical input power is 2.05 kW, and the COP is 3.46. At A–7/W35, the corresponding values are 7.89 kW, 2.72 kW, and 2.90 [19].
The heat pump is designed for heating operation at outdoor air temperatures from −20 to 35 °C, with a maximum permissible supply fluid temperature of 60 °C. At A7/W35, the specified outdoor-unit air volume flow rate is 3671 m3/h at a fan speed of 650 min−1 [19]. These catalogue data formed the basis for the heating capacity and electrical input power maps used to parameterize Type 525. The performance data file used for Type 525 contains 128 pairs of normalized heating capacity and electrical power values, covering four part-load ratios (25%, 50%, 75%, and 100%), four outlet water temperatures (35, 45, 55, and 60 °C), and eight outdoor air temperatures (−20, −15, −10, −7, 2, 7, 10, and 20 °C). The normalized factors are converted into heating capacity and electrical power using the reference values specified in the heat pump model. Consequently, the performance map accounts for variations in operating conditions rather than assuming constant COP. The manufacturer-rated operating points reported above provide a reference for assessing the model parameterization; however, they do not constitute independent experimental validation of the complete heat pump model.
The effect of evaporator defrost cycles on heat pump operation was also considered when compiling the heating performance data file. Defrosting was neither modeled as a separate dynamic process in Type 525 nor represented by a direct reduction in COP. Its effect was incorporated into the performance map by correcting the available heating capacity and corresponding electrical input power under conditions requiring defrosting. Since the model determines COP from the ratio of delivered heating capacity to electrical input power, these corrections also affect COP indirectly. Thus, defrost effects were included in the overall heat pump performance characteristics without explicitly modeling individual defrost cycles.
Type 525 allows selection of the load-side pump operating mode and compressor control strategy. A constant-flow pump operating mode was adopted. When a heating demand is active, the pump operates at its rated flow rate; it switches off when the demand ceases. Compressor speed is modulated to maintain the user-specified fluid temperature at the heat pump outlet.
Heat is delivered to the rooms through low-temperature underfloor heating and supplementary bathroom radiators. The hydraulic circuits allow the primary mass flow through the heat pump and the secondary flow to the heat emitters to be tracked separately. A constant mass flow rate of 1400 kg/h was adopted for the primary heat pump circuit during space heating, while the secondary flow varies according to the demands of the individual thermal zones.
The control strategy determines heat pump activation, the fluid temperature setpoint, auxiliary electric heater operation, and flow diversion between space heating and DHW preparation. The bivalent temperature is the outdoor air temperature threshold at which the system operating mode, specifically the priority between space heating and DHW preparation, changes. Above this temperature, DHW preparation takes priority; at or below it, space heating takes priority. Diverting valves were represented by Type 1336 and heating demands by Type 1502 thermostats.

2.4. Thermal Storage and Domestic Hot Water Preparation

Storage tanks in the dynamic simulation model were represented using Type 1534 from the TESS Storage Tank Library. This component accounts for thermal stratification, heat losses to the surroundings, conduction between temperature nodes, mixing caused by thermal instability, and energy exchange associated with inlet and outlet flows. Depending on the tank function, the model is used either without an immersed heat exchanger or with an immersed helical coil heat exchanger. In addition to tank volume, appropriate geometric and hydraulic input parameters must be defined, particularly tank height, immersed heat exchanger length, and the mass flow rate of the working fluid through the heat exchanger. Because these parameters affect tank thermal behavior, heat transfer, and storage dynamics, they must be determined for simulations at different volumes. Linear regression analysis was therefore performed using actual catalogue data for commercially available tanks to establish functional relationships between these input parameters and tank volume. The resulting regression equations provide a consistent method for determining the geometric and hydraulic parameters for each volume analyzed in the dynamic simulation model.
For the comparative annual simulations, both the nominal and actual modeled volumes were set to 300 L for the space heating buffer tank and 300 L for the final DHW heating tank. The reference case, K0, includes no PVT preheating tank. In the integrated configurations K1–K6, the volumes of the separate PVT preheating tank were set to exactly 100, 200, 300, 400, 500, and 600 L. These values are the directly specified tank volumes in the TRNSYS model, rather than rounded commercial tank designations.
Since idealized tanks of these volumes are used, the remaining geometric and thermal–hydraulic inputs are determined using a common regression procedure. The regression functions were derived from the available manufacturer catalogue data [20,21,22]. The catalogue models serve as the dataset for mathematical approximation rather than as individual commercial products directly simulated in this study.
The space heating buffer tank is modeled without an immersed heat exchanger, with the heating fluid entering the tank directly. Tank height was estimated using a volume–height regression derived from selected catalogue tanks in the CAS-HV and CAS (Centrometal d.o.o., Macinec, Croatia) series. The regression was previously determined from six selected catalogue data points, with a coefficient of determination of R2 = 0.8424, and is given by
H TES = 0.58374   V TES + 1.08925
where VTES is the space heating tank volume in m3 and HTES is its estimated height in m.
DHW preparation uses a single final heating tank in the reference case K0 and two tanks connected in series in configurations K1–K6. In the integrated configurations, the first tank preheats water using heat from the PVT collectors, while the second heats the water to the setpoint using the heat pump and, when necessary, an auxiliary electric heater. The DHW tanks were represented by Type 1534 with an immersed helical coil heat exchanger, in which the working fluid does not mix with the domestic water.
Three linear regression functions were used to determine the geometric and hydraulic parameters of the DHW tanks. These were derived from nine catalogue and derived data points for the SKB Digi and SF/E series. The regression dataset covers actual catalogue volumes from 0.080 to 0.559 m3. Tank height is estimated as
H DHW = 2.20665   V DHW + 0.73378
where HDHW is the tank height in m and VDHW is the simulated volume in m3. The coefficient of determination of this regression is R2 = 0.9432. The total tube length of the immersed heat exchanger is determined as
L DHW = 39.24607   V DHW + 2.26438
where LDHW is the heat exchanger length in m, with R2 = 0.9545. The working-fluid mass flow rate through the corresponding heat exchanger is determined from the following regression
m ˙ DHW = 5421.55250   V DHW + 203.14156
where m ˙ DHW is the mass flow rate in kg/h, with R2 = 0.9392. The coefficients of determination describe the agreement between the regression functions and the catalogue dataset, rather than direct experimental validation of tank thermal behavior. The same procedure is used to determine the parameters of the fixed 300 L final DHW heating tank and each PVT preheating tank from 100 to 600 L. The regression relationships for the DHW tanks were derived from catalogue and derived data covering actual storage volumes from 80 to 559 L. Therefore, the parameters of the largest simulated preheating tank (600 L) were obtained by extrapolating the regression equations beyond the upper limit of the original dataset. The extrapolation corresponds to 41 L, or 7.33% of the maximum catalogue volume. The same regression functions were applied to all investigated configurations to maintain a consistent parameterization procedure. However, the 600 L configuration represents a modeled tank with regression-derived geometric and hydraulic characteristics rather than a specific commercially available product. The implications of this extrapolation are discussed in Section 4.5.
Daily DHW demand was defined according to HRN EN 12831-3:2017 [23] as 55 L per person. For four occupants, a total demand of 220 L/day was adopted. The mixed water temperature at the draw-off point is 42 °C, the incoming cold water temperature is 10 °C, and the final DHW heating tank setpoint is 47 °C [23]. Demand is distributed according to a standard hourly profile. The auxiliary electric heater provides supplementary heating and a periodic weekly thermal disinfection cycle up to 65 °C.

2.5. Photovoltaic–Thermal System and PVT Circuit Control

The PVT collector was modeled using Type 1343, which simultaneously describes its electrical and thermal behavior. Part of the solar radiation incident on the collector is converted into electricity by the photovoltaic cells, while a portion of the energy not converted into electricity is transferred through the collector layers to the absorber and the fluid flowing through the channels. Electrical and useful thermal outputs are thus produced simultaneously. Heat removal by the fluid affects the PV cell temperature and, consequently, electrical efficiency.
The mathematical PVT collector model uses a two-dimensional description of heat transfer through the collector layers and along the fluid flow direction in the channels. It includes the cover, upper encapsulant, photovoltaic cells, lower encapsulant, backsheet, absorber plate, flow channels, thermal insulation, and rear cover. The cover and encapsulants transmit solar radiation to the photovoltaic cells, where part of the incident solar energy is converted into electricity. Cell electrical efficiency is determined using linear correction factors dependent on cell temperature and incident solar irradiance, assuming operation at the maximum power point. Solar energy that is not converted into electricity is transferred through the collector layers to the absorber plate and flow channels, where it is absorbed by the working fluid, simultaneously providing useful heat and removing heat from the photovoltaic cells.
The PVT array was initially sized based on the estimated annual household electricity consumption of approximately 4500 kWh/year, excluding electricity required for space heating and DHW preparation. This approach reflects the existing building configuration, in which space heating and DHW are supplied by a gas-fired condensing boiler rather than an electrically driven heat pump.
A preliminary specific annual electricity yield of 1050 kWh/kWp was adopted for the initial sizing estimate. Dividing the assumed annual household electricity demand by this value gives a required rated capacity of approximately 4.286 kWp. Since each PVT module has a rated electrical power of 425 Wp, ten modules would provide 4.250 kWp, which is slightly below the estimated requirement, whereas eleven modules provide 4.675 kWp. Therefore, eleven modules were selected as the smallest integer number satisfying the preliminary capacity estimate.
The selected PVT array comprises eleven modules, each measuring 1.722 × 1.134 m, with an individual area of approximately 1.953 m2 and a total area of approximately 21.48 m2. According to the manufacturer, the modules use monocrystalline N-type TOPCon cells and have a rated electrical efficiency of 21.8% under standard test conditions (1000 W/m2 irradiance and 25 °C cell temperature) [24].
It should be emphasized that the initial sizing procedure did not account for the additional electricity demand associated with the heat pump and other components of the proposed thermal system. Furthermore, the assumed specific annual yield of 1050 kWh/kWp was used only for preliminary capacity selection; it was not imposed as an annual electricity generation value in the TRNSYS simulations. The selected PVT capacity was kept constant in all investigated configurations to provide a common basis for comparison and should not be interpreted as an optimized capacity for meeting the total electricity demand of the integrated system.
The PVT array is installed on the south-facing roof slope, with an azimuth of 0° and a collector tilt of 30°. In TRNSYS, the entire array is represented as a single collector field comprising eleven identical modules. Irradiance on the collector plane is determined by the weather model, which supplies the relevant direct, diffuse, and ground-reflected components and the solar incidence angle to the PVT collector model. PVT electrical generation is not assumed in advance from its rated capacity; it is calculated dynamically at each time step from the available solar irradiance, photovoltaic cell temperature, and other operating conditions.
The thermal part of the PVT system consists of a closed hydraulic circuit containing a propylene glycol–water mixture to provide freeze protection and reliable year-round operation. The numerical model uses a working fluid comprising 40 vol.% propylene glycol and 60 vol.% water, providing freeze protection down to −21.5 °C. The thermophysical properties used in the calculation were determined for this mixture composition and the corresponding operating temperature range. The thermal and hydraulic behavior of the PVT circuit is therefore calculated using physical properties appropriate to the selected working fluid.
The basic PVT circuit control strategy uses the temperature difference between the collector array and the DHW tank. Flow is activated when the PVT collector temperature is at least 5 K above the water temperature in the preheating tank, and the tank water temperature does not exceed 80 °C. This upper temperature limit is a control constraint that prevents further tank heating at high water temperatures. The PVT circuit mass flow rate is determined from the heat exchanger hydraulic characteristics of the corresponding DHW preheating tank configuration, ensuring consistency between the collector and storage subsystems.
The main technical characteristics and control parameters of the analyzed PVT collector array are summarized in Table 2.
Table 2. Main technical and control characteristics of the analyzed PVT collector array.
In Type 1343, photovoltaic cell electrical efficiency is determined from cell temperature and solar irradiance, assuming maximum power point operation. Heat removal by the working fluid affects cell operating temperature and thereby indirectly affects annual electrical generation. PVT electrical and thermal outputs are recorded separately to avoid adding quantities with different uses and system boundaries.

2.6. Simulation Conditions and Validation Procedure

The annual simulations covered 8760 h, from 1 January to 31 December, using a simulation time step of 1 h. This time step was selected considering the hourly resolution of the available TMYx meteorological dataset for Slavonski Brod and the primary objective of comparing annual energy consumption, seasonal performance factors, and operational CO2 emissions across the investigated configurations. The meteorological dataset contains 8760 hourly records; therefore, reducing the simulation time step to 15 min while retaining the same dataset would require interpolation of the meteorological inputs rather than providing additional measured sub-hourly weather information.
Nevertheless, the simulation time step also determines the temporal resolution at which component states and control interactions are evaluated. An hourly time step may not fully resolve short-term heat pump cycling, switching of circulation pumps, changes in the PVT circuit operating state, or rapid temperature variations and charging processes within the stratified storage tanks. Such effects may influence the calculated heat transfers, auxiliary electricity consumption, and annual performance indicators. Consequently, the selected time step is considered suitable for the intended annual comparative assessment, but its numerical influence on the reported results has not been independently quantified through a finer-time-step sensitivity analysis.
The successive substitution method was used to solve the system numerically, with both the minimum and maximum relaxation factors set to 1. The integration and relative convergence tolerances were set to 0.001. The warning threshold for an increased number of iterations was set to 10,000 iterations, while the remaining advanced settings were retained at the simulation model defaults.
Data from the actual building in Slavonski Brod, occupied since 2020, were used to validate the dynamic simulation model. Its geometry, envelope thermal properties, thermal zone layout, and heating system correspond to those used to develop the model. In particular, the installed underfloor heating system, including its heating circuit layout and heat distribution arrangement, matches the system implemented in the dynamic model. This enables direct comparison of simulated thermal demand with energy data from the actual building.
The main difference between the simulated system and the existing installation is the heat source. In the actual building, space heating is supplied by a gas-fired condensing boiler. Actual natural gas consumption data are available for 2020–2025 and can therefore be used for model validation. To support a more detailed analysis, a model of the gas-fired condensing boiler was also developed using the technical and operating characteristics of the installed unit and available manufacturer data.
A model variant with a gas-fired condensing boiler was developed for validation, retaining the building and ground thermal model and the installed heat distribution system. The heat source was adapted to the actual installation, and the operating schedules of individual thermal zones were adjusted to the observed building use during the period covered by the gas consumption data. These specific schedules were not retained in the base model used for the comparative energy analyses, which assumes that all rooms are used according to their intended design functions.
Final validation of the dynamic simulation model was performed after assessing the representativeness of the reference weather data, separating the space heating share of actual natural gas consumption, modeling the installed condensing boiler, and adjusting the operating schedules of individual thermal zones. The simulated annual natural gas energy consumption was compared with the multi-year average estimated natural gas consumption for space heating. Both values were expressed on the same energy basis, namely the higher heating value of natural gas. The gas-fired condensing boiler installed in the reference building, a Viessmann Vitodens 100-W, was represented using TRNSYS Type 751. The maximum thermal output was limited to 12 kW, corresponding to the actual operating setting of the installed unit. Rather than assuming a constant boiler efficiency, Type 751 determines the fuel energy input using a performance data file in which overall boiler efficiency and combustion efficiency depend on the inlet water temperature and part-load ratio (PLR).
The efficiency data file comprises 30 operating points, corresponding to six inlet water temperatures from 30 to 55 °C and five part-load ratios of 0.17, 0.30, 0.50, 0.75, and 1.00. The specified overall boiler efficiency ranges from 90% to 98%, while combustion efficiency ranges from 95% to 99%. Linear interpolation is applied between the tabulated operating points. The overall efficiency values are expressed on a higher-heating-value basis, consistent with the measured natural gas consumption used for validation. The efficiency map represents the adopted model parameterization based on available manufacturer characteristics and should not be interpreted as an independent experimental validation of all operating points.
The heating supply water temperature was controlled according to outdoor air temperature using a weather-compensated heating curve implemented in MATLAB, with the resulting setpoint limited to 25–55 °C. This approach allows variations in boiler operating conditions and efficiency to be considered when calculating annual natural gas consumption.
For model validation, simulated annual natural gas consumption was compared with the six-year average estimated space-heating gas consumption for 2020–2025, obtained by subtracting the estimated domestic hot water and cooking consumption from measured total natural gas consumption. The resulting annual energy balance comparison and relative deviation are presented in Section 3.1. This procedure provides an assessment of the building model under the existing gas-fired heating configuration but does not constitute independent experimental validation of the heat pump, PVT collector, or thermal storage submodels.

2.7. Reference Configuration and Analyzed PVT–ASHP Configurations

The comparative analysis includes a reference space heating and DHW system without PVT collectors and six integrated configurations combining an air-to-water heat pump with PVT-based DHW preheating (PVT–ASHP). A 300 L space heating buffer tank and a 300 L final DHW heating tank were adopted. The integrated configurations incorporate DHW preheating tanks with volumes ranging from 100 to 600 L in increments of 100 L. These values are the actual volumes specified in the simulation model.
Tank geometric and hydraulic parameters were determined using regression functions derived from catalogue data for commercially available tanks, following the procedure in Section 2.4. Regression was used to determine the height of the space heating buffer tank. For the DHW tanks, it also determined the immersed helical coil tube length and working-fluid mass flow rate through the heat exchanger. The same procedure is thus applied to determine the model parameters for each specified volume, without directly reproducing all characteristics of any individual catalogue product. Preheating tank volume is the independently specified variable, while its geometric and hydraulic characteristics vary according to the established regression relationships.
The underfloor heating supply fluid temperature was set to 35 °C. This operating condition enables low-temperature heat pump operation while providing the required heating capacity of the heat-emitting surfaces. The 300 L space heating buffer tank is used to mitigate the temporal mismatch between heat generation and delivery and to stabilize hydraulic circuit operation. Its thermal behavior is represented by the dynamic model of stratification and heat losses.
For the assessment of indoor temperature acceptability, the air temperature in each heated zone was permitted to fall no more than 1 K below its specified setpoint. Accordingly, the minimum acceptable temperatures were 19 °C for rooms with a 20 °C setpoint, 23 °C for bathrooms with a 24 °C setpoint, and 17 °C for the garage with an 18 °C setpoint. This criterion was not applied to zones without active heating. A maximum of 24 h per year with temperatures below these limits was adopted as a study-specific acceptance criterion for comparing the simulated configurations. This threshold was used to identify configurations capable of maintaining approximately the required indoor temperatures throughout the year and should not be interpreted as a prescribed regulatory limit. An hour was classified as unacceptable if at least one heated zone fell below its minimum acceptable temperature. Simultaneous deviations in multiple zones during the same hour were counted as a single unacceptable hour at the building level.
The 300 L final DHW heating tank was selected for a four-person household with an adopted specific daily demand of 55 L per person, corresponding to a total demand of 220 L/day. The required mixed-water temperature at the draw-off point was set to 42 °C, while the final DHW heating tank setpoint was 47 °C. Domestic hot water demand was distributed according to an hourly consumption profile. DHW acceptability was assessed separately from space-heating temperature acceptability by checking whether the specified hot water demand and required draw-off temperature were satisfied in the simulation. The heating tank setpoint represents a control parameter and should therefore be distinguished from the required water temperature at the point of use.
A bivalent outdoor air temperature of +2 °C was adopted to control heat pump priority between space heating and final DHW heating. At or below +2 °C, space heating takes priority, and the auxiliary electric heater in the DHW tank supplies DHW heating as required. Above +2 °C, final DHW heating takes priority whenever a demand is present, after which the heat pump returns to space heating. The same control strategy is applied to all comparative cases, and its acceptability is assessed against the temperature criterion and satisfaction of DHW demand.
The reference case K0 comprises an air-to-water heat pump, a 300 L space heating buffer tank, and a 300 L final DHW heating tank. It includes neither PVT collectors nor a DHW preheating tank and provides the baseline for determining changes in annual energy efficiency, electricity consumption, and associated operational CO2 emissions.
In configurations K1–K6, PVT collectors and a separate DHW preheating tank are added to the reference system. The preheating tank volume is 100 L in K1 and increases in 100 L increments to 600 L in K6. Heat recovered from the PVT collectors is transferred to the water in the preheating tank, which subsequently enters the final DHW heating tank. This reduces the heat required for final water heating. Electricity generated by the PVT collectors is recorded separately and is not deducted from the electricity required to operate the thermal system.
All analyzed cases use identical weather conditions, building thermal characteristics, basic heat pump parameters, a supply fluid temperature of 35 °C, a bivalent temperature of +2 °C, and an hourly DHW demand profile. All configurations K1–K6 use the same 21.48 m2 PVT collector array, comprising eleven modules with a total rated electrical capacity of 4.675 kWp. This allows the effect of PVT subsystem integration to be assessed relative to K0 and enables comparison among configurations with different preheating tank volumes and consistently scaled geometric and hydraulic parameters.

2.8. Energy Performance Indicators and System Boundary

System energy performance is evaluated from annual dynamic simulation results using the heat pump seasonal coefficient of performance (SCOP), the seasonal performance factor of the complete system (SPF), total annual electricity demand, useful heat recovered from the PVT collectors, and annual PVT electrical generation. The comparison includes the reference case K0, representing an air-to-water heat pump system without PVT collectors, and six configurations K1–K6 with PVT-based DHW preheating. Configurations K1–K6 differ in the DHW preheating tank volume and the associated regression-derived geometric and hydraulic parameters, while the PVT array size remains unchanged.
The common operating conditions and PVT array characteristics are described in Section 2.7. The analysis distinguishes comparisons between the reference configuration K0 and the integrated configurations K1–K6 from comparisons among the six PVT-assisted preheating tank configurations. In the equations, subscript j denotes a simulation case (j = 0, 1, …, 6), and subscript k denotes a configuration with PVT preheating (k = 1, …, 6).
SCOP characterizes seasonal heat pump performance within the boundary of the device itself. Its calculation includes the total heat delivered by the heat pump over the year to space heating and final DHW heating. Heat pump electricity use includes the compressor, outdoor-unit fan, auxiliary electric heater belonging to the heat pump, and its circulation pump. Consumption by these components is integrated over the annual simulation, giving the total heat pump electricity use for case j as
E HP , el , j = E comp , j + E fan , j + E HP , aux , j + E HP , pump , j
where EHP,el,j is total annual heat pump electricity use, Ecomp,j is compressor electricity use, Efan,j is outdoor-unit fan electricity use, EHP,aux,j is the electricity used by the heat pump auxiliary electric heater, and EHP,pump,j is the electricity used by its circulation pump. All energy quantities are expressed in kWh.
The heat pump SCOP is defined as the ratio of annual heat delivered to space heating and final DHW heating to the total electricity required for heat pump operation:
SCOP j = Q HP , SH , j + Q HP , DHW , j E HP , el , j
where QHP,SH,j and QHP,DHW,j are the annual amounts of heat delivered by the heat pump to space heating and final DHW heating, respectively. Heat supplied by the auxiliary electric heater belonging to the heat pump is included in the corresponding useful thermal output, while its electricity consumption is included in the denominator. The resulting SCOP is a simulation-based indicator for the device under study, rather than a declared value obtained under standardized test conditions.
SPF is used to assess the complete thermal system, expanding the energy boundary to include additional electrical loads required for space heating, DHW preparation, and, in configurations K1–K6, PVT preheating. In addition to the heat pump, the boundary includes the space heating circulation pump, the PVT circulation pump, the auxiliary electric heater in the DHW tank, and controls. Total annual electricity demand within this expanded system boundary is calculated by summing the individual electrical loads:
E sys , el , j = E HP , el , j + E SH , pump , j + E PVT , pump , j + E DHW , aux , j + E reg , j
where Esys,el,j is total annual electricity use by the thermal system, ESH,pump,j is electricity use by the space heating circulation pump, EPVT,pump,j is the electricity consumption of the PVT circulation pump in configurations K1–K6, which is zero in the reference configuration K0, EDHW,aux,j is electricity use by the DHW tank auxiliary heater, and Ereg,j is electricity use by controls. In the reference case K0, electricity use by components belonging exclusively to the PVT subsystem is zero.
For the SPF calculation, the thermal numerator was defined as the sum of the modeled heat pump thermal output, including its integrated auxiliary heater, useful PVT thermal energy delivered to the DHW preheating tank, and thermal output of the auxiliary electric heater in the final DHW tank. These component-level thermal contributions were not independently reconciled with the net heat delivered to the final end uses or the thermal losses of the storage tanks. SPF for each simulation case is defined as
SPF j = Q HP , SH , j + Q HP , DHW , j + Q PVT , DHW , j + Q DHW , aux , j E sys , el , j
where QPVT,DHW,j is the annual useful heat delivered by the PVT collectors to the DHW preheating tank, and QDHW,aux,j is the annual heat supplied to the water by the DHW tank auxiliary electric heater. In Equation (7), the annual thermal contributions from the heat pump, the PVT preheating circuit, and the auxiliary electric heater in the final DHW tank are considered separately. The auxiliary electric heater integrated into the heat pump is included in the heat pump energy balance, whereas the auxiliary heater installed in the final DHW tank represents a separate thermal and electrical contribution. For the reference configuration K0, the useful thermal contribution from the PVT collectors is zero. The same definitions of thermal output and electricity consumption are applied consistently to all configurations. Although Equation (5) conceptually distinguishes the heat pump contributions to space heating and DHW preparation, their separate annual values were not available from the extracted simulation results. Therefore, SCOP was evaluated using the total modeled annual heat pump thermal output, including its integrated auxiliary heater, and the corresponding total annual heat pump electricity consumption. The resulting SPF represents a simulation-based whole-system performance indicator calculated from the annual thermal energy supplied by the modeled subsystems and their corresponding electricity consumption.
PVT electrical generation is recorded separately and is not deducted from the electricity consumption included in the SPF denominator. The simulation model does not determine how much of the generated electricity is directly consumed by the thermal system, exported to the grid, or stored. Therefore, all electricity required to operate the thermal system is assumed to be imported from the grid. Consequently, under the adopted assumption of no PVT electricity self-consumption, the total modeled electricity consumption of the thermal system is treated as electricity imported from the grid for the purpose of operational CO2 emissions accounting. Actual grid imports and the net electricity balance of the entire household were not simulated. The effect of PVT integration on annual electricity consumption is evaluated by comparing the reference case K0 separately with each configuration K1–K6. The absolute reduction in annual electricity demand for configuration k is calculated as
Δ E el , k = E sys , el , 0 − E sys , el , k ,     k = 1 , … , 6
where Esys,el,0 and Esys,el,k are the annual amounts of electricity required to operate the reference case and the respective configuration with PVT preheating, expressed in kWh/year. A positive ΔEel,k indicates a reduction in electricity consumption relative to K0, while a negative value indicates an increase. The relative reduction is calculated as
δ E el , k = Δ E el , k E sys , el , 0 × 100 %
Results are reported separately for all six configurations, with differences related to preheating tank volume. Annual useful PVT heat and annual PVT electrical generation are presented alongside these results, with a clear distinction between the two energy quantities. This allows the effect of PVT preheating on SPF and electricity consumption to be evaluated without assuming how the generated PVT electricity is used.

2.9. Methodology for CO2 Emissions Assessment

The carbon dioxide (CO2) emissions assessment is based on the simulated annual electricity consumption of the space-heating and DHW system. For the purpose of this assessment, all electricity required by the thermal system is assumed to be supplied from the grid, without accounting for simultaneous PVT electricity generation, on-site self-consumption, or electricity exports. The analysis includes the reference case K0 without a PVT system and six integrated PVT–ASHP configurations K1–K6 with different DHW preheating tank volumes.
The emissions boundary includes annual operational emissions associated with the electricity required by the thermal system, including the heat pump, auxiliary electric heaters, circulation pumps, and controls. Emissions associated with the manufacture and installation of equipment, tanks, and PVT modules, maintenance, component replacement, and end-of-life disposal are excluded. The resulting indicators therefore represent estimated annual operational emissions rather than a full life-cycle emissions assessment.
Electricity use is converted into CO2 emissions using an electricity emission factor (EFel), expressed in kg CO2/kWh. The same factor is applied to all cases K0–K6 in the base calculation so that the effect of changes in electricity consumption can be evaluated independently of changes in grid emission intensity. According to the annual energy review Energy in Croatia 2024, the average specific CO2 emission factor per unit of total electricity consumed in Croatia over 2018–2024 is 0.116 kg CO2/kWh [25]. This is the arithmetic mean of seven annual factors ranging from 0.085 to 0.132 kg CO2/kWh. Using a multi-year average moderates the influence of interannual variations in emission intensity caused by hydrological conditions, renewable energy shares, electricity imports, and the fossil-fuel generation mix. Since system energy performance is assessed using a reference meteorological year that does not represent a specific calendar year, a multi-year average emission factor was selected to provide a more representative estimate of annual operational CO2 emissions. The factor applies to consumed electricity, rather than generated electricity, for which the multi-year average is 0.152 kg CO2/kWh. The resulting assessment concerns operational emissions from grid electricity imports and excludes life-cycle emissions of individual system components.
Under the adopted electricity supply assumption, annual operational CO2 emissions for each simulation case are calculated as the product of the total electricity consumption of the thermal system and the grid electricity emission factor:
m CO 2 , j = E grid , j   EF el ,     j = 0 , 1 , … , 6
where m CO 2 , j is the annual CO2 emissions for case j in kg CO2/year, Egrid,j is the assumed annual grid electricity import, taken as equal to the total modeled electricity consumption of the thermal system under the adopted assumption of no PVT electricity self-consumption, expressed in kWh/year, and EFel is the electricity emission factor in kg CO2/kWh. Accordingly, Egrid,j = Esys,el,j for all configurations K0–K6.
The absolute reduction in operational emissions for each PVT configuration relative to the reference case K0 is calculated as
Δ m CO 2 , k = m CO 2 , 0 − m CO 2 , k
where subscript k denotes one of the six PVT configurations. A positive Δ m CO 2 , k indicates a reduction in annual operational emissions relative to the reference case, while a negative value indicates an increase. The relative emissions reduction is calculated as
δ m CO 2 , k = Δ m CO 2 , k m CO 2 , 0 × 100 %
In the base analysis, electricity generated by the photovoltaic part of the PVT collectors is recorded separately from the electricity required to operate the thermal system. Since time-resolved electricity self-consumption, grid exports, and electrical storage were not modeled, PVT electricity generation was not credited against the thermal-system electricity consumption in the operational CO2 emissions calculation.

3. Results

The results comprise validation of the annual energy balance of the building model and comparison of the reference case without PVT (K0) with six integrated PVT–ASHP configurations (K1–K6). In all cases, the space heating buffer tank and final DHW heating tank each have a volume of 300 L. PVT preheating tank volumes in K1–K6 are 100, 200, 300, 400, 500, and 600 L, respectively. Tank geometric and hydraulic inputs were determined using the corresponding linear regression functions derived from catalogue data, as described in Section 2.4. The volumes were specified as simulation parameters without selecting individual commercial tank models.

3.1. Validation of the Annual Model Energy Balance

The annual energy performance of the building model was assessed by comparing simulated natural gas consumption with consumption data for the period 2020–2025. The total measured natural gas consumption during these six calendar years was 95,227 kWh. Since natural gas was also used for domestic hot water preparation and cooking, the corresponding baseline consumption was estimated separately for each year using the average monthly consumption recorded during May–September, when space heating was inactive. The resulting annual baseline consumption was subtracted from total annual consumption, yielding an estimated cumulative space-heating consumption of 73,259 kWh and a six-year annual average of 12,209.80 kWh.
The estimated annual space-heating consumption varied from 11,269 kWh in 2020 to 14,056 kWh in 2025. Relative to the six-year average, the deviations ranged from −7.71% to +15.12%, demonstrating appreciable interannual variability. The individual annual values and their deviations from the multi-year mean are reported in Table 3.
Table 3. Validation of the annual building energy balance and interannual variability in measured gas consumption.
The annual mean outdoor air temperature of the TMYx weather data (12.950 °C) was very close to the corresponding 2020–2025 average (12.956 °C).
The relative deviation was calculated as
δ = E sim − E actual E actual × 100 %
where Esim is the simulated annual gas consumption for space heating (kWh/year), and Eactual is the six-year average estimated annual gas consumption for space heating, derived from measured total natural gas consumption (kWh/year).

3.2. Annual Results and Satisfaction of Temperature Requirements

All annual simulations covered 8760 h, with a supply fluid temperature of 35 °C and a bivalent temperature of +2 °C. In all PVT configurations, the array comprises eleven modules with a total rated electrical capacity of 4.675 kWp and an area of 21.48 m2. Differences between K1–K6 arise from the specified preheating tank volumes and the associated inputs determined by regression functions. Annual energy and temperature indicators are presented in Table 4.
Table 4. Annual performance indicators and temperature acceptability of simulation cases K0–K6.
The thermal comfort criterion allows indoor air temperature to fall up to 1 K below its setpoint, with no more than 24 unacceptable hours per year across the heated zones of the building. The simulated number of such hours is 16 h for K0 and ranges from 10 to 20 h for K1–K6. All seven cases therefore meet the defined temperature acceptability criterion. These hours refer to space heating temperature deviations and do not represent periods of insufficient DHW provision.
The DHW temperature requirement was met in all analyzed cases. With the adopted daily demand profile of 220 L for four occupants, a draw-off temperature of 42 °C, and a final DHW heating setpoint of 47 °C, no case was identified in which the required DHW temperature was not achieved. Differences in energy performance were therefore compared under conditions satisfying the basic temperature requirements for both space heating and DHW preparation.
Table 4 shows that SPF and SCOP are higher in all configurations with PVT preheating than in the reference case, while total annual electricity consumption is lower. The highest SPF, 2.623, occurs in K4 (400 L), whereas the lowest electricity consumption, 6429.64 kWh/year, occurs in K6 (600 L).

3.3. Seasonal Performance of the Heat Pump and Complete System

The reference case K0 has a SCOP of 2.632 and an SPF of 2.352. Integrating the PVT subsystem increases SCOP to 2.663–2.724 and SPF to 2.521–2.623. The highest SPF, 2.623, is achieved in K4 with a 400 L preheating tank, representing an increase of approximately 0.272, or 11.55%, relative to K0. Increasing tank volume further to 500 and 600 L reduces SPF to 2.615 and 2.609, respectively. SPF variation is shown in Figure 3.
Figure 3. Seasonal performance factor of the complete system (SPF) for the reference case K0 and PVT configurations K1–K6. The yellow marker indicates the maximum seasonal performance factor (SPF = 2.623), achieved for configuration K4.
To provide a more detailed explanation of the observed differences in system performance, the annual thermal energy contributions and electricity consumption of individual system components for configurations K0–K6 are presented in Table 5.
Table 5. Annual component-level thermal energy contributions and electricity consumption for configurations K0–K6.
The highest heat pump SCOP of 2.724 was obtained for K6 (600 L), while the maximum whole-system SPF of 2.623 was achieved for K4 (400 L). The component-level analysis shows that the total thermal energy included in the SPF numerator decreased from 17,514.37 kWh/year in K0 to 16,774.11 kWh/year in K6, corresponding to a reduction of 740.26 kWh/year (4.23%). Over the same range, annual electricity consumption decreased from 7447.06 to 6429.64 kWh/year, representing a reduction of 13.66%. The reduction in electricity consumption was primarily attributable to the heat pump and its integrated auxiliary heater (878.43 kWh/year), followed by the auxiliary heater of the final DHW tank (144.00 kWh/year). The additional electricity consumption of the PVT circulation pump partially offset these savings.
Compared with K4 (400 L), configuration K6 (600 L) exhibited 1.11% lower annual electricity consumption and a 1.66% reduction in the total thermal energy included in the SPF numerator. Consequently, SPF decreased from 2.623 to 2.609 despite the lower electricity consumption of K6. This difference follows from the relative changes in the thermal and electrical quantities included in the SPF calculation. Therefore, the configuration with the lowest annual electricity consumption does not necessarily provide the highest whole-system SPF.
It should be emphasized that the thermal energy included in the SPF numerator represents the sum of modeled component-level thermal contributions rather than an independently verified net heat delivery to the final end uses. Although all configurations satisfy the specified space-heating and DHW temperature requirements, the available simulation outputs do not provide separate annual heat pump contributions to space heating and DHW preparation or independently quantified storage tank heat losses and changes in stored energy. Consequently, the physical causes of the reduction in the calculated thermal contributions cannot be fully quantified from the available results. Furthermore, the relatively small SPF differences between the investigated configurations should be interpreted cautiously because their sensitivity to the simulation time step and regression-derived tank parameters has not been independently established.

3.4. Electricity Consumption and Operational CO2 Emissions

Figure 4 compares the annual electricity consumption of the reference configuration K0 and the six PVT-assisted configurations. As shown by the component-level analysis in Table 5, electricity savings are primarily associated with reduced heat pump and auxiliary heater consumption, while the PVT circulation pump introduces a small additional electrical demand. Compared with K0, annual electricity savings range from 577.56 kWh for K1 to 1017.42 kWh for K6, corresponding to relative reductions of 7.76% and 13.66%, respectively.
Figure 4. Annual electricity consumption of the thermal system in configurations K0–K6. PVT electricity generation is reported separately and is not deducted from the values shown. The darker bars highlight the reference configuration (K0) and the configuration with the lowest annual electricity consumption (K6), while the lighter bars represent configurations K1–K5.
Annual operational CO2 emissions associated with electricity consumption by the thermal system were calculated using a constant emission factor of 0.116 kg CO2/kWh, based on the multi-year average reported in Energy in Croatia 2024. Assuming that all electricity required by the thermal system is supplied from the grid, the estimated annual CO2 emissions decrease from 863.86 kg CO2/year in K0 to a range of 745.84–796.86 kg CO2/year across configurations K1–K6. The corresponding reductions range from 67.00 to 118.02 kg CO2/year (7.76–13.66%). Since the same emission factor is applied to all configurations, the relative reduction in operational CO2 emissions equals the relative reduction in thermal-system electricity consumption. Electricity generated by the PVT modules is reported separately and is not credited in these emission reductions because time-dependent self-consumption and grid exports were not modeled. The comparative results are presented in Table 6.
Table 6. Changes in annual electricity consumption, operational CO2 emissions, and seasonal performance factor relative to the reference configuration (K0).

3.5. Thermal and Electrical Contributions of the PVT Array

Annual PVT electricity generation ranges from 7165.96 to 7181.28 kWh/year across the six PVT-assisted configurations (K1–K6), corresponding to a difference of approximately 0.21% between the minimum and maximum values. Since the PVT array area and rated capacity were identical in all configurations, only minor differences in annual electricity generation were observed among the investigated configurations. The useful thermal contribution of the PVT collectors varies more markedly. It is 1116.90 kWh/year in K1, increases to 1383.70 kWh/year in K2, and reaches its maximum of 1418.74 kWh/year in K3, with a preheating tank volume of 300 L. Increasing volume to 400, 500, and 600 L progressively reduces this contribution to 1393.14, 1304.61, and 1224.03 kWh/year, respectively. The thermal contribution in K6 is therefore 13.72% lower than in K3. Annual PVT outputs are presented in Table 7, and the variation in thermal contribution is shown in Figure 5.
Table 7. Annual useful thermal energy delivered by the PVT array to DHW preheating and gross PVT electricity generation.
Figure 5. Annual useful thermal contribution of the PVT array for preheating tank volumes from 100 to 600 L. The yellow marker indicates the maximum useful PVT thermal energy (1418.74 kWh/year), achieved for configuration K3.
The electrical generation reported in Table 7 represents gross PVT electricity production and is not deducted from the electricity consumption used to calculate SPF or operational CO2 emissions.
The maximum annual useful PVT thermal output of 1418.74 kWh was obtained for K3 (300 L), whereas the highest whole-system SPF of 2.623 was achieved for K4 (400 L). Between K3 and K6, useful PVT thermal output decreased from 1418.74 to 1224.03 kWh/year, whereas annual electricity consumption also decreased from 6562.57 to 6429.64 kWh/year. These results indicate that the annual useful thermal contribution of the PVT collectors is not the sole determinant of the integrated system’s electricity consumption. The component-level analysis presented in Table 5 clarifies the contributions of the heat pump, auxiliary heaters, and circulation pumps to the observed changes in electricity consumption. However, the available results do not independently quantify the heat delivered to individual end uses or the thermal losses of the storage tanks.

4. Discussion

4.1. Model Validation and Comparability of Simulation Cases

The comparison between simulated natural gas consumption and the multi-year average estimated space-heating consumption yielded a relative deviation of −1.96%, indicating good agreement at the annual energy balance level. However, the estimated annual space-heating gas consumption varied from 11,269 kWh in 2020 to 14,056 kWh in 2025, corresponding to deviations of −7.71% to +15.12% from the six-year average. This interannual variability demonstrates that agreement with the multi-year average does not imply equivalent agreement with individual years. Furthermore, the validation was based on a representative TMYx meteorological year rather than weather data corresponding to each year between 2020 and 2025. Therefore, the result supports the annual performance assessment of the building model with the existing gas heating system but does not establish its accuracy for individual years or at monthly or hourly resolution.
The remaining component models were parameterized using input data derived from manufacturer specifications and established TRNSYS component models, ensuring transparency and traceability of the modeling assumptions. The Type 525 heat pump model uses performance maps based on operating conditions, while the Type 1343 PVT model incorporates the manufacturer-specified collector characteristics. Thermal storage was represented using Type 1534, with geometric and hydraulic parameters determined from catalogue-based regression relationships. This approach provides a transparent basis for defining the component models but does not constitute independent experimental validation of the integrated PVT–ASHP system.
Consequently, the reported SCOP, SPF, useful PVT thermal output, and electricity consumption should be interpreted as comparative simulation results under the adopted technical assumptions and control strategies. Further experimental measurements would be required to assess the accuracy of the individual component models and their dynamic interactions.
The comparison of K1–K6 was designed as a parametric analysis of PVT preheating tank volume, with volume as the only independently varied parameter. Tank height, immersed helical coil tube length, and the corresponding mass flow rate were not taken directly from individual commercial models; they were consistently determined for each volume using linear regression functions based on catalogue data. This approach ensures consistent, volume-dependent parameterization of the storage tanks across all investigated configurations. Nevertheless, because the regression-derived parameters vary together with volume, the results describe the combined effect of volume and its functionally related tank characteristics, rather than the effect of volume under strictly unchanged geometric and hydraulic conditions.

4.2. Effect of Tank Volume on Seasonal Performance and PVT Thermal Contribution

The results reveal different trends in useful PVT thermal output, whole-system seasonal performance factor (SPF), and annual electricity consumption. The highest useful PVT thermal contribution of 1418.74 kWh/year was obtained for configuration K3 with a 300 L preheating tank. For the 400 L preheating tank, the useful PVT thermal contribution was 1393.14 kWh/year, while the 500 and 600 L configurations yielded 1304.61 and 1224.03 kWh/year, respectively. Thus, the useful PVT thermal output decreased by 13.72% between K3 and K6.
However, the maximum useful PVT thermal output did not correspond to the highest whole-system SPF. As shown in Table 5, the system performance depends on the combined thermal contributions and electricity consumption of the heat pump, auxiliary electric heaters, and circulation pumps. The highest SPF of 2.623 was achieved for K4 (400 L), whereas K6 (600 L) provided the lowest annual electricity consumption of 6429.64 kWh/year.
The comparison between K4 and K6 indicates that the total thermal energy included in the SPF numerator decreased from 17,056.57 to 16,774.11 kWh/year (−1.66%), while electricity consumption decreased from 6501.82 to 6429.64 kWh/year (−1.11%). Consequently, the relative decrease in thermal energy was greater than the reduction in electricity consumption, resulting in a slight decrease in SPF from 2.623 to 2.609. Therefore, the configuration minimizing annual electricity demand does not necessarily maximize the ratio of thermal energy contributions to electrical input.
It should also be emphasized that the investigated configurations differ not only in storage volume but also in tank height, immersed heat exchanger length, and working-fluid mass flow rate, which were determined using volume-dependent regression relationships. Accordingly, the results reflect the combined influence of these parameters rather than the isolated effect of tank volume. Furthermore, the relative difference in SPF between K4 and K6 is only approximately 0.55%, and the robustness of this difference cannot be assessed without additional sensitivity analysis. The identified configurations should therefore be regarded as the most favorable among the investigated cases under the adopted modeling assumptions, rather than universally optimal tank sizes.
From a practical perspective, increasing the preheating tank volume from 400 to 600 L reduces annual electricity consumption by only 72.18 kWh/year, corresponding to a calculated operational CO2 emissions reduction of 8.37 kg/year. These relatively small absolute differences indicate that a definitive preference between the two configurations cannot be established without further sensitivity analysis and consideration of additional design criteria.

4.3. Thermal Comfort and Achievement of the DHW Temperature Setpoint

Energy performance was assessed under predefined operating temperature requirements. In all seven configurations, the number of hours during which the air temperature in at least one heated zone was more than 1 K below its setpoint remained below the study-specific acceptance limit of 24 h/year. The highest number of hours below the specified temperature limits was 20 h/year for K1, while the lowest was 10 h/year for K2. Thus, all configurations satisfied the same thermal comfort criterion, with none exceeding the specified threshold.
Thus, all configurations satisfied the same thermal comfort criterion, with none exceeding the specified threshold. The reduction in electricity consumption associated with PVT preheating therefore reflects improved system energy performance while maintaining the required DHW temperature, rather than a reduction in hot water supply quality. However, compliance with these temperature criteria does not independently establish identical annual useful heat delivery across configurations, as separate end-use heat contributions and storage losses were not quantified.

4.4. Operational CO2 Emissions and Boundaries of the Decarbonization Assessment

Since the same grid emission factor of 0.116 kg CO2/kWh was applied to all configurations, the relative reduction in operational CO2 emissions is equal to the relative reduction in annual thermal-system electricity consumption. The largest reduction in annual operational CO2 emissions was obtained for configuration K6 (600 L), amounting to 118.02 kg CO2/year (13.66%) relative to the reference configuration K0. The emissions assessment is limited to operational CO2 emissions associated with electricity consumption for space heating and domestic hot water (DHW) preparation. It therefore excludes embodied equipment emissions and emissions potentially avoided through PVT electricity self-consumption or grid exports.
Across the six PVT-assisted configurations (K1–K6), the simulated annual electricity generation from the PVT array ranged from approximately 7.17 to 7.18 MWh. However, PVT electricity generation was not deducted from the thermal-system electricity consumption because time-dependent self-consumption and electricity exchange with the grid were not modeled. Accordingly, the reported reduction in operational CO2 emissions reflects only the decrease in thermal-system electricity consumption associated with PVT-assisted DHW preheating, calculated using the adopted constant grid emission factor. The potential contribution of PVT electricity generation to the overall building electricity balance and associated operational CO2 emissions was not assessed in this study.
Furthermore, multiplying gross PVT electricity generation by the adopted average grid emission factor would not provide a reliable estimate of avoided CO2 emissions, as the actual emissions avoided depend on the time-dependent balance between electricity generation, consumption, and grid exchange. Consequently, the reported maximum reduction of 118.02 kg CO2/year represents only the reduction in operational emissions associated with thermal-system electricity consumption and does not reflect the total potential decarbonization benefit of the PVT installation.

4.5. Study Limitations and Further Analysis

The present study is limited to a single-family residential building in Slavonski Brod, Croatia, one typical meteorological year, and a fixed domestic hot water demand profile corresponding to 220 L/day for four occupants. All investigated configurations were evaluated using the same meteorological conditions, a heating supply temperature of 35 °C, a bivalent temperature of +2 °C, and identical basic control strategies. These assumptions ensure consistent conditions for comparing the investigated configurations but limit the generalizability of the findings to other buildings, climatic conditions, and operating strategies.
Variations in outdoor temperature and solar irradiance may affect heat pump performance and useful PVT thermal output, whereas changes in DHW consumption may influence the charging and discharging behavior of the thermal storage tanks. Similarly, variations in control settings and operating parameters could affect the relative energy performance of the investigated tank configurations. Since no dedicated sensitivity analysis was performed, the influence of alternative operating conditions on the reported results remains unquantified.
An additional numerical limitation is associated with the hourly simulation time step. Although consistent with the temporal resolution of the adopted meteorological dataset, this time step may not adequately resolve sub-hourly variations in heat pump operation, PVT circulation, and thermal storage dynamics. The influence of the simulation time step on the calculated annual energy performance indicators has not been quantified through a dedicated sensitivity analysis. This limitation is particularly important when comparing configurations K4 (400 L) and K6 (600 L), as their calculated SPF values differ by only approximately 0.55%. Therefore, the numerical robustness of the SPF-based ranking of configurations K4 and K6 cannot be established without additional sensitivity analysis. Future research should include targeted simulations with a shorter time step, such as 15 min, to assess the sensitivity of the calculated performance indicators and the ranking of the investigated configurations to temporal resolution.
Another limitation concerns the regression-based parameterization of the DHW preheating tanks. The investigated configurations differ not only in storage volume but also in tank height, immersed heat exchanger length, and working-fluid mass flow rate, with the latter parameters determined using volume-dependent regression relationships. Consequently, the observed performance differences reflect the combined effects of storage volume and the associated geometric and hydraulic parameters, rather than the isolated influence of storage volume.
Particular attention should be given to configuration K6 (600 L), which requires extrapolation of the regression relationships beyond the maximum catalogue volume of 559 L by 7.33%. Table 8 compares the regression-derived geometric and hydraulic parameters for tank volumes of 559 L (the upper limit of the catalogue dataset) and 600 L (configuration K6). The corresponding increases are 4.60% in tank height, 6.65% in heat exchanger tube length, and 6.87% in working-fluid mass flow rate.
Table 8. Comparison of regression-derived tank parameters at 559 and 600 L.
Although the extent of extrapolation is relatively small, the regression-derived parameters have not been independently validated for a 600 L tank. Furthermore, no dedicated sensitivity analysis was conducted to independently assess the effects of tank geometry, heat exchanger characteristics, and working-fluid mass flow rate on system performance. Therefore, the reported results should be interpreted as a comparison of predefined tank configurations based on consistent parameterization assumptions, rather than as evidence of the independent effect of storage volume on system performance.
Finally, this study evaluates six predefined PVT-assisted DHW preheating tank configurations rather than conducting a continuous mathematical optimization of tank volume. The identified tank volumes should be regarded as the most favorable among the investigated configurations for the respective performance indicators, rather than as universally optimal solutions.

5. Conclusions

This study evaluated the annual energy performance and operational CO2 emissions of a residential PVT–ASHP system incorporating thermal energy storage through dynamic simulations performed in TRNSYS. The reference configuration without PVT collectors (K0) was compared with six PVT-assisted configurations (K1–K6), each incorporating a dedicated domestic hot water (DHW) preheating tank with a volume ranging from 100 to 600 L. The volumes of the space-heating buffer tank and the final DHW heating tank were kept constant at 300 L each across all configurations. The geometric and hydraulic parameters of the preheating tanks were determined using regression equations developed from manufacturer catalogue data.
The simulated annual natural gas consumption was 1.96% lower than the six-year average space-heating gas consumption estimated from measured total gas consumption for the period 2020–2025. This agreement supports the suitability of the building model for comparative annual energy assessments. However, it does not constitute independent experimental validation of the heat pump, PVT collectors, or thermal storage components.
All seven configurations satisfied the adopted indoor temperature acceptability criterion. The number of hours during which at least one heated zone was more than 1 K below its setpoint ranged from 10 to 20 h/year, remaining below the study-specific acceptance limit of 24 h/year. All simulated configurations also achieved the required DHW temperature, ensuring that their energy performance was compared under consistent space-heating and DHW operating requirements.
Compared with the reference configuration (K0), which had a whole-system SPF of 2.352, the PVT-assisted configurations (K1–K6) achieved SPF values ranging from 2.521 to 2.623. The highest SPF of 2.623 was achieved in configuration K4 (400 L), corresponding to an improvement of approximately 11.5% compared with the reference configuration K0. Compared with the reference configuration K0 (7447.06 kWh/year), annual electricity consumption in configurations K1–K6 ranged from 6429.64 to 6869.51 kWh/year, corresponding to reductions of 7.76–13.66%. Configuration K6 (600 L) exhibited the lowest annual electricity consumption and the highest heat pump SCOP of 2.724 among all investigated configurations.
The highest annual useful PVT thermal contribution of 1418.74 kWh was achieved in configuration K3, incorporating a 300 L DHW preheating tank. For configurations with preheating tank volumes above 300 L, the useful PVT thermal contribution decreased, while annual PVT electricity generation varied only slightly, ranging from 7165.96 to 7181.28 kWh. These results indicate that the configuration with the highest useful PVT thermal output does not necessarily provide the highest whole-system SPF or the lowest annual electricity consumption.
Based on the adopted Croatian grid electricity emission factor of 0.116 kg CO2/kWh, the estimated annual operational CO2 emission reductions ranged from 67.00 to 118.02 kg CO2/year (7.76–13.66%) compared with the reference configuration K0. These emission reductions are attributable to lower electricity consumption by the space-heating and DHW systems. The potential additional benefits of PVT electricity generation were not quantified, as time-dependent electricity self-consumption and grid exports were not considered in the analysis.
The principal finding of this study is that no single DHW preheating tank configuration achieved the best performance across all evaluated energy performance indicators. Since tank geometry, heat exchanger characteristics, and working-fluid mass flow rate varied together with storage volume, the observed performance differences reflect the combined effects of these parameters rather than the isolated influence of tank volume. Moreover, the results are specific to the considered building, climatic conditions, and control strategy. The results for configuration K6 (600 L) should be interpreted with caution because its geometric and hydraulic parameters were estimated by extrapolating regression equations beyond the range of the manufacturer catalogue data.
Future research should include a more detailed thermal energy balance, separately quantifying the heat pump contributions to space heating and DHW preparation, thermal storage losses, and changes in stored thermal energy. Further sensitivity analyses should separately assess the effects of tank geometry, heat exchanger characteristics, working-fluid mass flow rate, and system control strategies on the calculated energy performance indicators. A sensitivity analysis using shorter simulation time steps is particularly important for assessing the robustness of the calculated performance differences between configurations K4 (400 L) and K6 (600 L). Future studies should investigate different climatic conditions and DHW demand profiles and incorporate time-resolved modeling of PVT electricity self-consumption and grid exports to enable a more comprehensive assessment of system energy performance and operational CO2 emissions.

Author Contributions

Conceptualization, M.Đ. and M.Ž.; methodology, M.Đ.; software, M.Đ.; validation, M.Đ., M.Ž. and L.B.; formal analysis, M.Đ.; investigation, L.B.; resources, M.Đ.; data curation, M.Đ.; writing—original draft preparation, M.Đ. and L.B.; writing—review and editing, M.Ž. and M.V.; visualization, M.Đ. and L.B.; supervision, M.Ž. and M.V.; project administration, M.Đ.; funding acquisition, M.Ž. All authors have read and agreed to the published version of the manuscript.

Funding

This research paper was funded by the University of Slavonski Brod through the institutional research project “Advanced modelling and optimization of compact heat exchangers for integration into renewable energy systems, project number NPOO 008 (MOKIT)” financed by the European Union–NextGenerationEU. The views and opinions expressed in this paper are those of the authors and do not necessarily reflect the official position of the European Union or the European Commission. Neither the European Union nor the European Commission can be held responsible for them.

Data Availability Statement

The meteorological data used in this study were obtained from the publicly accessible Climate.OneBuilding.Org database (https://climate.onebuilding.org/). The building characteristics, system specifications, and simulation parameters are described in the manuscript. Additional data generated during the TRNSYS simulations and supporting the findings of this study are available from the corresponding author upon reasonable request.

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

The following abbreviations are used in this manuscript:
ASHPAir-source heat pump
COPCoefficient of performance
DCDirect current
DHWDomestic hot water
ECElectronically commutated
EPWEnergyPlus Weather
HRN ENCroatian adoption of a European Standard
MATLABMatrix Laboratory
PLRPart-load ratio
PVPhotovoltaic
PVT–ASHPPhotovoltaic–thermal and air-source heat pump system
SCOPSeasonal coefficient of performance
SPFSeasonal performance factor
TESSThermal Energy System Specialists
TMYTypical meteorological year
TOPConTunnel oxide passivated contact
TRNSYSTransient System Simulation Program
UTCCoordinated Universal Time

References

  1. Wang, X.; Xia, L.; Bales, C.; Zhang, X.; Copertaro, B.; Pan, S.; Wu, J. A Systematic Review of Recent Air Source Heat Pump (ASHP) Systems Assisted by Solar Thermal, Photovoltaic and Photovoltaic/Thermal Sources. Renew. Energy 2020, 146, 2472–2487. [Google Scholar] [CrossRef] [Scilit]
  2. Špago, D.; Husika, A.; Isić, S.; Hadžiahmetović, H. Hybrid Renewable Energy Systems for Public Buildings: Optimization and Sustainability. Teh. Vjesn. 2026, 33, 495–502. [Google Scholar] [CrossRef] [Scilit]
  3. Đuranović, M.; Živić, M.; Stojkov, M.; Lujić, R. Analysis of Energy Consumption of a Thermo-Technical System with an Absorption Heat Pump. Teh. Vjesn.—Tech. Gaz. 2024, 31, 967–972. [Google Scholar] [CrossRef] [Scilit]
  4. Rijvers, L.; Rindt, C.; de Keizer, C. Numerical Analysis of a Residential Energy System That Integrates Hybrid Solar Modules (PVT) with a Heat Pump. Energies 2022, 15, 96. [Google Scholar] [CrossRef] [Scilit]
  5. Dannemand, M.; Sifnaios, I.; Tian, Z.; Furbo, S. Simulation and Optimization of a Hybrid Unglazed Solar Photovoltaic-Thermal Collector and Heat Pump System with Two Storage Tanks. Energy Convers. Manag. 2020, 206, 112429. [Google Scholar] [CrossRef] [Scilit]
  6. Barbu, M.; Darie, G.; Siroux, M. A Parametric Study of a Hybrid Photovoltaic Thermal (PVT) System Coupled with a Domestic Hot Water (DHW) Storage Tank. Energies 2020, 13, 6481. [Google Scholar] [CrossRef] [Scilit]
  7. Wang, F.; Liu, M.; Guo, W.; Liu, X.; Zhang, J.; Li, J.; Hu, G.; Yin, J. Photovoltaic/Thermal Integrated Air Source Heat Pump Hot Water System with Phase Change Tank. Renew. Energy 2025, 240, 122204. [Google Scholar] [CrossRef] [Scilit]
  8. Öztürk, M.; Çalişir, O.; Genç, G. Energy, Exergy and Economic (3E) Evaluation of the Photovoltaic/Thermal Collector-Assisted Heat Pump Domestic Water Heating System for Different Climatic Regions in Turkey. J. Therm. Anal. Calorim. 2021, 145, 1431–1443. [Google Scholar] [CrossRef] [Scilit]
  9. Liravi, M.; Karkon, E.; Dai, Y.; Georges, L. On the Proper Integration of Pre-Heating Tanks in Ground Source Heat Pump Systems Combined with Photovoltaic-Thermal Panels. Therm. Sci. Eng. Prog. 2025, 60, 103379. [Google Scholar] [CrossRef] [Scilit]
  10. Jodeiri, A.M.; Soppelsa, A.; Turrin, F.; Pipiciello, M.; Cozzini, M.; Fedrizzi, R. Numerical and Experimental Investigation of Stratified Water Storage Tanks: An Enhanced Adaptive-Grid Model. Appl. Therm. Eng. 2024, 248, 123113. [Google Scholar] [CrossRef] [Scilit]
  11. Król, B.; Kupiec, K. Thermal Stratification in Solar Storage Tanks: Long-Term Modelling and Efficiency Analysis. Energies 2026, 19, 627. [Google Scholar] [CrossRef] [Scilit]
  12. Đuranović, M.; Živić, M.; Batistić, I.; Kozak, D. Impact of Thermal Energy Storage on the Seasonal Performance of an Air-to-Water Heat Pump Under Real Microclimatic Conditions. Buildings 2026, 16, 1432. [Google Scholar] [CrossRef] [Scilit]
  13. Đuranović, M.; Živić, M.; Samardžić, I.; Bikić, S. Tariff-Oriented Operation of Residential Air-to-Water Heat Pumps with Thermal Energy Storage: A Long-Term Analysis of Cost Savings and Energy Flexibility. Energies 2026, 19, 2151. [Google Scholar] [CrossRef] [Scilit]
  14. HRN EN 12831-1:2017; Energy Performance of Buildings—Method for Calculation of the Design Heat Load—Part 1: Space Heating Load, Module M3-3. Croatian Standards Institute: Zagreb, Croatia, 2017.
  15. Lawrie, L.K.; Crawley, D.B. Development of Global Typical Meteorological Years (TMYx), Climate.OneBuilding.Org. Available online: https://climate.onebuilding.org/WMO_Region_6_Europe/HRV_Croatia/index.html (accessed on 20 September 2026).
  16. Klein, S.A.; Beckman, W.A.; Mitchell, J.W.; Duffie, J.A.; Freeman, T.L. TRNSYS 18: A Transient System Simulation Program; University of Wisconsin-Madison: Madison, WI, USA, 2017. [Google Scholar]
  17. Thermal Energy System Specialists (TESS) TESS Libraries V18: General Descriptions. Available online: https://www.trnsys.com/tess-libraries/ (accessed on 15 October 2026).
  18. The MathWorks, Inc. MATLAB, Version R2024b; The MathWorks, Inc.: Natick, MA, USA, 2024.
  19. Viessmann. Vitocal 200-S: Air Source Heat Pumps, Split Version, 2.6–10.4 KW (A7/W35); Viessmann: Allendorf, Germany, 2025. [Google Scholar]
  20. Centrometal d.o.o. Technical Instructions for Installation, Use and Maintenance of the Water Accumulation Tank: CAS 303–5003; CAS-S/B/BS 503–2003; Centrometal d.o.o.: Macinec, Croatia, 2025. [Google Scholar]
  21. Centrometal d.o.o. Technical Instructions for Installation, Use and Maintenance of the Combined Water Heater SKB Digi; Centrometal d.o.o.: Macinec, Croatia, 2023. [Google Scholar]
  22. Centrometal d.o.o. Technical Instructions for Installation, Use and Maintenance of the Enamelled Hot Water Cylinder SF/E 150–2000; Centrometal d.o.o.: Macinec, Croatia, 2021. [Google Scholar]
  23. Croatian Standards Institute. HRN EN 12831-3:2017, Energy Performance of Buildings—Method for Calculation of the Design Heat Load—Part 3: Domestic Hot Water Systems Heat Load and Characterisation of Needs, Modules M8-2, M8-3; Croatian Standards Institute: Zagreb, Croatia, 2017. [Google Scholar]
  24. DualSun. DualSun SPRING4 425 TOPCon I: Technical Datasheet; DualSun: Marseille, France, 2024. [Google Scholar]
  25. Ministry of Economy of the Republic of Croatia; Energy Institute Hrvoje Požar. Energy in Croatia 2024: Annual Energy Report; Ministry of Economy of the Republic of Croatia: Zagreb, Croatia, 2025. [Google Scholar]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.