Abstract
The flexible DC transmission scheme based on modular multilevel converters (MMCs) is currently the mainstream solution for offshore wind power delivery. With the ongoing growth in both installed capacity and the offshore distance of wind power projects, the dimensions and weight of corresponding offshore converter stations have increased substantially. These developments present significant economic constraints and engineering challenges, thereby complicating the deployment of large-scale, long-distance offshore wind energy systems. Compared with MMCs, diode rectifier units (DRUs) offer advantages such as compact size, light weight, low cost, reduced operating losses, and high reliability. Nevertheless, DRUs lack active control capability, and conventional grid following wind turbines cannot independently support the voltage of the offshore AC network, which severely limits their application in offshore wind scenarios with stringent economic requirements. Grid forming control of wind turbines is an effective approach to address this issue. Given the widespread application of doubly-fed induction generators (DFIGs) in engineering practice and their relatively low capital costs, this study investigates the implementation of grid-forming control strategies in DFIGs to address the stability challenges of DRU-based HVDC transmission systems during fault conditions. First, the mathematical model of the DFIG is established. Then, a suitable control strategy is designed to endow the turbine with certain grid forming capabilities. Finally, the developed simulation model and control strategy are verified in PSCAD/EMTDC. The results demonstrate that the proposed grid forming DFIG control strategy can maintain stable offshore AC voltage and frequency under various fault conditions, ensure continuous and reliable operation of the DRU, and achieve fault ride through. On this basis, to account for engineering practicality and cost considerations, this study further proposes a hybrid transmission scheme combining grid-following and grid-forming DFIGs. Simulation results confirm that this hybrid scheme also achieves satisfactory operational performance, while reducing the potential cost increase associated with full-scale grid-forming retrofits, it effectively ensures fault ride-through capability and system operational stability. This method provides an effective solution for low cost, highly reliable offshore wind power DC transmission.
1. Introduction
Driven by the global energy transition, offshore wind power has emerged as a leading form of renewable energy, owing to its advantages such as abundant resources, stable wind speeds, and proximity to load centers [1]. The recent trends toward larger scales, deep and distant offshore areas, and clustered development have introduced new challenges: when the transmission distance exceeds approximately 70–100 km, AC transmission schemes suffer from high losses and stability issues, making voltage-source converter-based high-voltage direct current (VSC-HVDC) transmission the preferred solution for grid integration of far-offshore wind power [2,3]. However, the core equipment in the industrially mature VSC-HVDC systems generally employ modular multilevel converters (MMCs). The offshore converter stations are not only bulky and heavy but also extremely costly, significantly increasing both capital and operational expenditures [4,5,6]. Under current technological conditions, the cost of an offshore MMC rectifier station can account for up to 40% of the total investment in an offshore wind power transmission project, thereby limiting its application in large-scale grid integration of far-offshore wind farms [7,8].
In recent years, to lower the system cost of DC transmission for offshore wind power, attention from both academic and engineering circles has turned to an alternative based on diode rectifier units (DRUs) [9,10]. Composed of passive diodes, the DRU features a simple structure, high operational robustness, very low losses, and virtually maintenance-free operation, thereby representing a promising and cost-effective solution [11,12,13]. Nevertheless, the DRU does not possess intrinsic active voltage and frequency control capabilities; its proper operation relies critically on a stable offshore AC grid that provides adequate inertia [14,15,16]. Under the conventional grid-following control mode, wind farms behave as current sources synchronized via phase-locked loops (PLLs) and rely on the external grid to provide voltage reference and frequency support. Consequently, this control mode is unsuitable for weak grid environments lacking voltage reference and inertia, and is even incapable of directly interfacing with a passive offshore AC network formed by DRUs [17,18]. Therefore, how to construct an offshore AC grid capable of autonomously establishing and maintaining voltage and frequency stability—so as to effectively support the normal operation of the DRU—constitutes the core challenge of this technical approach [19].
Grid-forming control technology provides an effective solution to the aforementioned problem [20,21,22]. This control strategy enables power sources such as wind turbines to autonomously establish voltage and frequency—behaving like controlled voltage sources—while providing the necessary inertia and damping support to the AC system. It also maintains good dynamic stability even under weak-grid or islanded operating conditions [23,24,25]. In the context of offshore wind power generation, when the offshore converter adopts a DRU, the transmission system imposes new requirements on the wind turbine side. Under this scenario, the control strategy of the wind turbines faces new challenges [26]. To date, grid-forming control has achieved relatively mature research outcomes in permanent magnet synchronous generator (PMSG)-based wind turbine systems [27,28,29]. Related research has demonstrated that under the DRU-HVDC scenario, PMSG-based wind turbines with grid-forming control exhibit favorable control effectiveness, supporting the voltage of a stable offshore network and supplying a stable AC voltage to the DRU [30,31,32,33]. The doubly-fed induction generator (DFIG), which currently dominates the onshore wind power market, features a large installed base, mature technical research, and lower cost compared to PMSG-based wind turbines [34,35,36,37]. Recently, DFIG-based wind turbines have been adopted in offshore wind projects for grid connection, exhibiting superior grid adaptability and stable operation, along with reduced transmission system costs [38,39].
Introducing DFIGs into the DRU-HVDC system could significantly improve the economic performance of the transmission system. Nevertheless, the application of DFIG in far-offshore transmission systems remains limited, especially under the DRU-HVDC scenario, and the grid-forming control strategy for DFIG in this context is still insufficiently studied [40]. This is because the introduction of DRUs into offshore wind power systems renders conventional grid-forming control strategies for wind turbines no longer applicable. The inherent coupling between the rotor-side converter (RSC) and the grid-side converter (GSC) of the DFIG, as well as the coupling between the RSC and the stator-side voltage dynamics, makes it difficult to achieve voltage-source characteristics independently through RSC control alone. The coordination between the RSC and GSC, along with control structure design and parameter tuning, thus faces greater challenges, necessitating the development of new control strategies tailored to this altered scenario [41]. To systematically identify the specific limitations of existing research and position the contributions of this paper, Table 1 provides a critical comparison of representative studies.
Table 1.
A critical comparison of wind turbine control strategies in grid-connected systems.
Based on the above critical comparison, three research gaps can be distilled. First, existing DRU-compatible grid-forming controls are mostly designed for PMSGs, where the DC-link decoupling architecture renders control implementation relatively straightforward; however, the inherent rotor–stator electromechanical coupling characteristics of DFIGs render these methods non-transferable (turbine-type gap). Second, the few studies on grid-forming DFIGs have focused solely on the voltage-source characteristics of the machine itself, generally overlooking the deep-seated interactions between DFIG control dynamics and the DRU commutation process (control-design gap). Third, no study has yet investigated whether a “grid-following and grid-forming hybrid” configuration can significantly reduce retrofitting costs while preserving system stability (system-level configuration gap). The root cause underlying these gaps lies in the fact that the stator voltage of a DFIG is jointly determined by the rotor-side current and grid conditions, exhibiting strong dynamic coupling, unlike PMSGs, where the output voltage can be decoupled and controlled via the grid-side converter. When the DFIG serves as the sole active unit providing commutation voltage for the DRU, the system exhibits an extremely low short-circuit ratio, where control deviations may directly trigger DRU commutation failures or even DC-link voltage collapse. Therefore, the core scientific question of this paper is how to transcend the electromechanical coupling constraints of DFIGs and design a grid-forming control framework that simultaneously satisfies voltage building, inertia support, and fault ride-through under weak-grid conditions.
It is worth noting that a variety of advanced control theories have been developed in the academic community for the implementation of grid-forming control. Finite-time control and fixed-time control can ensure convergence of system states within a determined time, offering distinct advantages in improving transient response speed [45,46]. However, the estimation of their convergence-time upper bounds typically relies on the norm of the system’s initial state or the level sets of Lyapunov functions. In scenarios such as DRU applications, where the initial state varies drastically with operating conditions, these theoretical advantages are difficult to translate into engineering-predictable performance guarantees. Event-triggered distributed control can significantly reduce communication burdens in the coordinated control of wind farm clusters, but its core lies in the design of communication scheduling strategies, which pertains to a different dimension from the intrinsic stability mechanisms of voltage–frequency building at the single-machine level that this study focuses on [47]. Within the VSG control framework, adaptive VSG strategies enhance system adaptability by dynamically adjusting virtual inertia and damping, representing the line of research closest to this study [48]. Nevertheless, existing adaptive laws are mostly designed with respect to frequency deviations or power fluctuations and fail to fully account for the physical constraints imposed by the DFIG rotor-side converter capacity and the transient coupling of stator flux on the adjustable range of virtual inertia. Under the extremely weak grid provided by the DRU, these strategies may incur instability due to excessive parameter tuning. Reinforcement-learning-based VSG methods, while capable of achieving parameter self-tuning under complex operating conditions, suffer from “black-box” characteristics and a lack of theoretical proof for small-disturbance stability, which falls short of the engineering requirements for interpretability and deterministic stability margins in power system control [49]. In summary, none of the existing approaches adequately address the multi-objective, strongly coupled challenge of “voltage support–inertia response–transient stability” in DFIG grid-forming control under the specific weak-grid boundary imposed by DRU-HVDC.
To address the above critical challenges, this paper takes the grid-forming DFIG-integrated DRU-based offshore wind power HVDC transmission system as the research object, and systematically investigates its feasibility and operational characteristics in far-offshore wind power grid integration. The main contributions of this paper are as follows:
- A grid-forming control architecture adapted to the physical constraints of the DFIG rotor-side converter is proposed. By restructuring the reference generation logic of the rotor current inner loop, this architecture decouples the inherent correlation between rotor-side control and stator voltage dynamics, enabling the DFIG to actively establish and maintain the DRU-side AC bus voltage as the sole voltage source without the need for additional energy storage.
- The interaction mechanism between the grid-forming DFIG and the DRU commutation process is revealed, based on which a comprehensive fault ride-through strategy is designed. Through theoretical analysis and time-domain simulations, it is ensured that the system can achieve continuous uninterrupted operation under both severe AC-side faults and DC-side disturbances.
- A “grid-following and grid-forming hybrid” DFIG fleet configuration scheme is proposed and validated for the first time, seeking an engineering-feasible trade-off between system stability and economic viability. This scheme allows a portion of the wind turbines within the farm to remain in grid-following mode, requiring only a subset to be retrofitted to grid-forming mode, which can provide sufficient voltage and frequency support for the entire offshore AC network. This finding provides a direct technical basis for low-cost grid-forming retrofits and significantly enhances the near-term engineering applicability of the proposed scheme.
In this paper, a complete electromagnetic transient simulation model incorporating the wind farm cluster, DRU rectifier station, DC submarine cable, and onshore MMC inverter station is established in PSCAD/EMTDC. Through simulation validation under various operating conditions, including steady-state operation, AC-side faults, and DC-side disturbances, the results demonstrate that the proposed grid-forming DFIG control strategy can effectively support the offshore AC voltage, ensure continuous and stable operation of the DRU under various fault conditions, and exhibit satisfactory fault ride-through capability. Meanwhile, the hybrid transmission scheme with both grid-following and grid-forming DFIGs also achieves favorable operational performance, striking a balance between system stability and economic requirements. This study provides a feasible technical pathway toward cost-effective and highly reliable DC grid integration of far-offshore wind power.
2. Overall Topology of the DRU-HVDC Offshore Wind Power Transmission System
The overall topology of the DRU-HVDC offshore wind power transmission system is illustrated in Figure 1. The system primarily consists of four key components.
Figure 1.
Topology of the DRU-HVDC offshore wind power transmission system.
- The offshore wind farm;
- The offshore rectifier platform;
- The submarine DC cable;
- The onshore MMC station.
The offshore wind farm consists of multiple wind turbine arrays. Each array is created by linking a number of wind turbines in series using AC collection submarine cables. The DRU depends on an external AC voltage source to supply the commutation (or phase-switching) voltage and cannot actively contribute to supporting the offshore AC voltage. Without additional AC voltage source equipment, the offshore AC voltage support can only be provided by the wind turbines, which must therefore operate in grid-forming control mode. The electricity produced by these grid-forming wind turbines is gathered via the AC collection submarine cables and delivered to the AC bus of the offshore rectifier platform.
The offshore rectifier platform comprises three key components: a step-up offshore transformer, AC filters, and the DRU.
The AC power received from the offshore wind farm is first stepped up to a higher voltage level by the offshore transformer. Subsequently, the AC power is fed into the DRU. For high-voltage, high-power transmission systems, a 12-pulse DRU configuration is commonly adopted. This arrangement comprises two six-pulse DRU units linked in series on the DC side and in parallel on the AC side, with their respective AC output voltages offset by a phase angle of 30 degrees. As a result, the dominant harmonic currents appearing on the AC side of the 12-pulse DRU follow the sequence 12k ± 1, where *k* denotes any positive integer (i.e., the 11th, 13th, 23rd, 25th harmonics, etc.).
An AC filter is installed in parallel at the point of common coupling (PCC) to perform AC filtering functions and to supply reactive power compensation for the DRU. To mitigate the characteristic harmonics of the 12-pulse DRU, the AC filter can be configured as a double-tuned filter tuned to the 12th and 24th harmonics, thereby simultaneously suppressing the 11th, 13th, 23rd, and 25th AC harmonic currents. The filter also improves the power quality of the offshore AC network and ensures stable operation of the grid-forming controlled wind turbines.
The filtered AC power is then fed into the DRU. The DRU, composed entirely of passive diodes, rectifies the offshore AC power into DC power without requiring active switching control, offering advantages such as structural simplicity, low losses, and high reliability.
The DC power output from the DRU is transmitted ashore via a submarine DC cable, which may be configured as a monopolar or bipolar system depending on the power rating and transmission distance.
Upon reaching the onshore station, an MMC inverts the DC power back to AC and synchronizes it with the onshore AC grid. The primary functions of the onshore MMC are twofold: controlling the DC voltage of the submarine cable and regulating the reactive power exchanged with the main AC grid.
By maintaining the DC voltage at a constant level, the onshore MMC ensures stable power flow along the HVDC link. Meanwhile, the reactive power control capability of the MMC allows the onshore station to support the voltage profile of the main grid and comply with grid code requirements regarding reactive power exchange or power factor correction.
3. Design of Grid-Forming DFIG Controller
3.1. Fundamentals of Grid-Forming DFIG Control Structure Design
The mathematical model of the DFIG exhibits characteristics of nonlinearity and strong coupling. Therefore, coordinate transformation is required to achieve decoupling during the control process. The mathematical model of the DFIG in the two-phase synchronously rotating reference frame is presented as follows:
Equation (1) presents the voltage equations of the DFIG in the synchronously rotating reference frame.
where and denote the -axis stator voltage components, respectively; and denote the -axis rotor voltage components, respectively; and represent the -axis stator current components, respectively; and represent the -axis rotor current components, respectively; and are the -axis stator flux linkage components, respectively; and are the -axis rotor flux linkage components, respectively; and and denote the synchronous angular speed and rotor angular speed, respectively.
Equation (2) presents the flux linkage equations of the DFIG in the synchronously rotating reference frame.
where represents the mutual inductance between the stator and rotor windings; denotes the stator self-inductance; and denotes the rotor self-inductance.
Equation (3) presents the torque equation of the DFIG.
where denotes the electromagnetic torque; represents the number of pole pairs, respectively.
A typical DFIG grid-connection structure is shown in Figure 2. The system mainly consists of the shaft train, DFIG, a back-to-back power electronic converter, RSC, wind turbine controller, GSC, and step-up transformer. Here, represents the reference values of active power; and are the rotor voltage and rotor current, respectively; and are the stator voltage and stator current, respectively; is the DC voltage across the capacitor; is the inductance on the AC side of the grid-side converter; is the DC-link capacitance; and are the voltage and current at the PCC, respectively; is the rotor angular speed.
Figure 2.
Grid connection diagram of DFIG.
The standard control strategy for DFIGs widely adopted in current offshore wind farms is grid-following vector control. Under this control paradigm, the RSC tracks the voltage phase at the point of common coupling in real time via a phase-locked loop, uses the stator flux or stator voltage orientation as a reference, generates current references from the outer power loop, and performs rapid regulation through the inner current loop, resulting in the external characteristic of the unit behaving as a controlled current source, incapable of autonomously establishing voltage. The DRU, on the other hand, is a passive, uncontrolled rectifier device whose commutation process relies on a stable commutation voltage provided by the AC side. Insufficient AC voltage amplitude or waveform distortion can directly affect the normal operation of the rectifier and may even lead to commutation failure. To enable the DFIG to adapt to the rigid demand of the DRU for a stable AC voltage, its control strategy must be reformed to be grid-forming. Considering that the stator windings of the DFIG are directly connected to the AC grid, its terminal voltage is directly determined by the amplitude and rotational frequency of the stator flux, and the RSC is the only excitation channel for controlling the stator flux. Therefore, the entry point for the reform is to change the control objective of the RSC from “tracking grid phase and injecting specified power” to “autonomously establishing the amplitude, frequency, and phase of the stator flux”, making the DFIG appear externally as an AC voltage source with controllable amplitude and frequency.
3.2. Principles of Wind Turbine Controller Design in DRU-HVDC
In conventional power systems, frequency control is primarily achieved through active power regulation, whereas voltage control is mainly realized via reactive power regulation. However, in DRU-HVDC systems, these two control pairs exhibit distinct characteristics, as further illustrated by the DRU rectifier station model depicted in Figure 3.
Figure 3.
Offshore DRU rectifier station model.
In Figure 3, represents the RMS value of the AC voltage at the PCC, and f denotes the frequency of the offshore AC system. T, , and respectively denote the turns ratio, leakage inductance, and leakage reactance of the DRU converter transformer. is the number of six-pulse DRUs connected in series on the DC side. represents the DC voltage of a single six-pulse DRU, while and are the DC voltage and DC current of the offshore rectifier station, respectively. and correspond to the active power transmitted by the DRU and the reactive power absorbed by the DRU, respectively. and denote the active and reactive power delivered by the offshore wind farm to the PCC, respectively. represents the reactive power output of the AC filters.
The ideal no-load DC voltage of the 6-pulse DRU is given by:
Taking the commutation voltage drop into account, the DC voltage of the six-pulse DRU under loaded conditions is expressed as:
In the pure DRU-based offshore wind power DC transmission system, the onshore MMC adopts constant DC voltage control to keep the DC voltage of the HVDC system constant. Consequently, the DRU DC voltage is approximately a constant value under steady-state conditions. According to Equation (5), the DRU DC current can be expressed as
Combining Equations (5) and (6), the active power transmitted by the DRU can be calculated as
where the constant coefficients and are given by
The power factor of the DRU can be approximated as
Combining Equation (7) through Equation (9), the reactive power absorbed by the DRU can be calculated as
where the constant coefficient is given by
According to Equations (7) and (10), the active power and reactive power generated by the wind turbine can be expressed as
According to Equation (12), the four types of sensitivities of the controlled variables with respect to the control variables for the grid-connected wind turbine can be analytically derived as
It can be derived from Equation (13) that, in the most simplified system, the sensitivity of the grid-connected wind turbine is always positive. Its value is related only to the constant and the frequency f of the offshore AC system, exhibiting minor variations under different active power levels. The sensitivity is directly proportional to the active power transmitted by the DRU, showing significant variations under different active power levels. The sensitivity is jointly influenced by the RMS value of the PCC AC voltage and the offshore AC system frequency f, and demonstrates considerable variations across different active power levels. The sensitivity remains consistently negative. Due to the presence of the large reactive power from the AC filters in its expression, its value does not vary substantially across different active power levels.
It can be seen that, unlike conventional power systems, the combination relationship for the power controllers has changed in the DRU-HVDC system. Therefore, when designing grid-forming control on the wind turbine side, it is essential to focus on the relationship between active power and voltage, as well as the relationship between reactive power and frequency.
3.3. Establishment of Grid-Forming Capability of the RSC
Currently, many studies on grid-forming DFIGs adopt the virtual synchronous generator method to retrofit the RSC. However, the application scenarios of these studies are generally based on onshore wind power grid-connected projects and cannot be directly applied to offshore wind power research. Recent studies on offshore wind power projects based on DRU-HVDC have shown that the sensitivity characteristics of grid-forming wind turbines are mainly determined by the DRU, and that the voltage at the grid-forming wind turbine’s PCC is closely related to its active power, while the frequency is tightly linked to the reactive power. Therefore, in the power loop control strategy, the two pairs of variables—(voltage, active power) and (frequency, reactive power)—are particularly suitable as controlled variables and regulating variables, respectively. Based on the above idea, this paper redesigns the outer power loop of the RSC, thereby endowing the DFIG with certain grid-forming capability.
As shown in Figure 4, the outer power loop consists of an active power–AC voltage amplitude controller and a reactive power–frequency controller.
Figure 4.
Power loop control block diagram.
For active power–AC voltage amplitude control, the active power output of the wind turbine generator is an independent variable, which is expected to accurately track its reference value. Since the proportional-integral (PI) controller exhibits excellent tracking performance for DC signals and is widely adopted in practical engineering applications, the active power–AC voltage amplitude controller employs PI control. This enables zero-error tracking of the wind turbine generator’s output active power to its reference value , and generates the reference value of the AC port voltage amplitude for the wind turbine generator. Here, is provided by the wind turbine controller; and denote the proportional gain and integral time constant of the PI controller, respectively; and s is the differential operator (Laplace variable). The control expression is given by Equation (14):
The reactive power–frequency controller adopts proportional control. To fully utilize the reactive power compensation capability of capacitive AC collector submarine cables and AC filters for the DRU, and to reduce the reactive power output of the wind turbine generators, the reactive power reference value of the wind turbine generator is set to zero. In this context, is the rated frequency; is the phase angle of the stator voltage; is the actual reactive power; is the proportional gain; is the base value of the rated frequency; and is the reference value of the stator voltage frequency. The control expression is shown in Equation (15):
The inner voltage and current loops control the stator voltage indirectly by regulating the rotor excitation voltage.
As shown in Figure 5, the inner voltage-current loop as a whole indirectly controls the stator voltage by regulating the rotor excitation voltage. Here, and are the reference values of the d-axis and q-axis components of the stator voltage, respectively; and are the actual values of the d-axis and q-axis components of the stator voltage; and denote the d-axis and q-axis reference values of the rotor current, respectively; and are the actual values of the d-axis and q-axis components of the rotor current; and are the actual values of the d-axis and q-axis components of the stator current; , are the proportional gain and integral time constant of the PI controller in the voltage loop, respectively; , are the proportional gain and integral time constant of the PI controller in the current loop, respectively; and are the magnetizing inductance and rotor inductance of the induction machine, respectively; is the slip frequency; and are the reference values of the d-axis and q-axis components of the rotor voltage, respectively.
Figure 5.
Control block diagram of the voltage and current loop.
In the voltage loop, takes the output from the previous stage as its input, while is set to zero. The voltage-loop controller still adopts the classical PI control to ensure that and accurately track their reference values. The outputs of this stage are and , which serve as reference variables for the current loop. Equation (16) gives the control equations of the voltage loop.
According to the mathematical model of the DFIG, in addition to the controlled rotor current, the expression of the rotor voltage also contains coupling terms of the stator voltage and current. Therefore, in the design of the current loop, a PI controller is adopted while decoupling these quantities. Equation (17) presents the control equations of the current loop. The modulation stage employs pulse-width modulation (PWM) to achieve control of the rotor voltage and its frequency.
3.4. Controller Parameter Tuning
This paper adopts the trial-and-error method commonly used in engineering for parameter tuning. First, the integral gain is set to zero, and the system operates as a pure proportional controller. The proportional coefficient is gradually increased from a small value, and the system’s response to a step input is observed until a critical proportional gain is achieved, which provides fast response speed without causing severe oscillations. Based on the set proportional coefficient, the integral gain coefficient is then gradually introduced from a small value. While introducing the integral action, the proportional coefficient is appropriately fine-tuned to compensate for the phase lag and increased overshoot caused by the integral action. This process continues until the system eliminates steady-state error while achieving satisfactory dynamic response performance. During the tuning process, the power performance at the wind farm output and the transient behavior under fault conditions are primarily observed, with system stability, rapidity, and zero steady-state error serving as the ultimate criteria for parameter selection. The specific results of parameter tuning are shown in Table 2:
Table 2.
The specific results of parameter tuning.
The primary functions of the GSC are to maintain DC-link voltage stability and to regulate power exchange with the grid. However, owing to its limited capacity, which accounts for only about 30% of the entire wind turbine system, the GSC does not exert a decisive influence on the grid-connected characteristics of the grid-forming DFIG system. From a dynamic perspective, the inner voltage/current control loops of the RSC-based grid-forming scheme operate on a fast time scale (milliseconds). The DC-link voltage dynamics, regulated by the GSC, are comparatively slower and can be effectively decoupled from the grid-forming control design, provided the DC-link capacitance is adequately sized—a standard assumption in such studies. While the GSC is coupled through the DC link, its influence on the core grid-forming mechanism is secondary. Therefore, the conventional vector control strategy for DFIG is retained and will not be further elaborated herein.
4. Analysis of Examples
4.1. The Tested System
To evaluate the performance of the proposed grid-forming control approach for offshore DC transmission utilizing a DFIG, an electromagnetic transient simulation model was developed in the PSCAD/EMTDC environment. The main circuit parameters of the test system are listed in Table 3. The simulation study examined both the startup procedure of the wind farm and fault conditions occurring on the offshore AC network. Within the test configuration, the 1000 MW offshore wind installation was modeled as one or more single equivalent groups made up of grid-forming wind turbine units. The equivalent single group consists of several grid-forming DFIGs, each with a rated active power of 1.5 MW.
Table 3.
System main loop parameters.
4.2. Steady-State and Transient Start-Up Processes
Prior to t = 0.3 s, the MMC inverter station had been started. Meanwhile, DFIG had been started and was operating at its initial rotational speed, as shown in Figure 6a.
Figure 6.
(a) The rotational speed of the DFIG. (b) The DFIG internal converter DC voltage. (c) The frequency of PCC. (d) The RMS voltage of PCC. (e) The power absorbed by the DRU from the entire grid-forming DFIG offshore wind farm. (f) The power output of a single DFIG. (g) The dq-axis voltage components controlled by the RSC and their references. (h) The dq-axis current components controlled by the RSC and their references.
At t = 0.3 s, the converter inside the wind turbine was unlocked. The GSC regulated the DC voltage of the turbine until it reached its rated level, as shown in Figure 6b. Meanwhile, the RSC managed the build-up of the offshore AC system voltage, supplying the necessary AC voltage for the DRU. This allowed the DRU to begin transferring active power from the wind farm, as shown in Figure 6c–e.
Figure 6f–h illustrate the control performance of the power outer loop. After , when the wind speed reaches its rated value (), the active power generated by a single DFIG remains stable around its rated value (), and simultaneously contributes to balancing part of the reactive power. Figure 6g demonstrates the control effect of the voltage loop, where accurately tracks output from the power outer loop, and is also maintained precisely around zero. Figure 6h shows the performance of the current loop, where and accurately track their respective reference values and . In this simulation, the design of the control stages and the parameter tuning presented in the previous chapter are effectively validated, indicating that the wind turbine possesses a certain grid-forming capability.
Furthermore, at the HVDC transmission system level, Figure 6e shows that the grid-forming DFIG-based wind farm is able to deliver power rapidly and stably to DRU at its rated value of . Figure 6c,d present the instantaneous and RMS voltages at the PCC, demonstrating that the grid-forming DFIG designed in this work can establish a stable offshore AC voltage rapidly while providing commutation voltage for the DRU.
4.3. Wind Speed Fluctuation and Power Step Process
Based on the stable operation of the system, this section simulates and analyzes the impact of wind speed variations on the system. Before , the system has already entered a steady-state operation stage. At , the wind speed decreases from to , as shown in Figure 7a. Consequently, the power reference value output from the wind turbine controller changes, as illustrated in Figure 7b. The actual power of the wind turbine responds rapidly to the change in its reference value and achieves zero-error tracking, stabilizing at approximately after , as depicted in Figure 7c.
Figure 7.
(a) The wind speed at the offshore wind farm. (b) The power reference value output from the wind turbine controller. (c) The power output of a single DFIG. (d) The power absorbed by the DRU from the entire grid-forming DFIG offshore wind farm. (e) The RMS voltage of PCC. (f) The frequency of PCC.
Figure 7d presents the variation process of the active power absorbed by the DRU. Approximately after the wind speed change, the power gradually decreases to a new stable value. As the active power declines, the reactive power absorbed by the DRU also decreases accordingly. To maintain the reactive power balance of the offshore AC system, under the action of the power loop controller of the grid-forming wind turbines, the reactive power output of each grid-forming wind turbine also reduces, as shown in Figure 7c. Furthermore, under the effect of the power loop, with the decrease in offshore wind power active power, the grid-forming wind turbines control the PCC AC voltage amplitude to decrease slightly, while the frequency increases, as illustrated in Figure 7e,f.
4.4. System Fault Ride-Through Process
In this section, two representative fault types in practical power system operation, namely the three-phase metallic grounding fault and the single line-to-ground fault, are selected to conduct simulation analyses on the fault ride-through performance of the studied grid-forming DFIG-based wind farm.
4.4.1. Single Line-to-Ground Fault
This subsection simulates the fault ride-through process of the proposed system following a single-phase-to-ground fault on the offshore AC side. Prior to , the system operates steadily under rated conditions. At , a single-phase-to-ground fault occurs at the PCC. The fault is cleared after . As illustrated in Figure 8a, the AC voltage of the faulted phase instantaneously drops to zero, while the voltages of the non-faulted phases increase. Following the fault, the RMS voltage of PCC also declines, as depicted in Figure 8h. As shown in Figure 8e,f, the voltage drop at the AC side of the DRU results in a reduction of both the DC voltage and DC current of the HVDC transmission system. Consequently, the active power transmitted by the DRU decreases correspondingly, impeding the active power output of the offshore wind power, as illustrated in Figure 8d. Following the fault, the output electromagnetic power of the wind turbine generators is constrained, and the imbalance between electromagnetic power and input mechanical power leads to a rapid increase in the generator rotor speed and the DC voltage of the back-to-back converter, as shown in Figure 8b,c. Meanwhile, the internal Crowbar protection circuit of the DFIG is triggered, activating the crowbar resistor and blocking the PWM pulses of the RSC, as shown in Figure 8g. After from the fault inception, the system resumes steady-state operation, thereby completing the fault ride-through process.
Figure 8.
(a) The AC voltage of PCC. (b) The wind turbine speed. (c) The DC voltage of DFIG. (d) The power absorbed by the DRU from the entire grid-forming DFIG offshore wind farm. (e) The DC voltage of HVDC. (f) The DC current of HVDC. (g) The blocking/enabling signal of the crowbar protection circuit. (h) The RMS voltage of PCC.
4.4.2. Three-Phase Metallic Grounding Fault
In this subsection, the most severe fault in power systems—the three-phase metallic grounding fault—is taken as an example to simulate the fault ride-through process of the designed grid-forming DFIG-based wind farm. Before , the system operates steadily under rated conditions. At , a three-phase metallic grounding fault occurs at the PCC, and the fault is cleared 0.1 s later. As shown in Figure 9a, when the fault occurs, the PCC AC voltage instantaneously drops to zero. As illustrated in Figure 9e,f, the voltage drop on the AC side of the DRU leads to a drop in the DC voltage and DC current of the HVDC transmission system. Consequently, the active power transmitted by the DRU also decreases to zero, and the active power output of the offshore wind power is blocked, as shown in Figure 9d.
Figure 9.
(a) The AC voltage of PCC. (b) The wind turbine speed. (c) The DC voltage of DFIG. (d) The power absorbed by the DRU from the entire grid-forming DFIG offshore wind farm. (e) The DC voltage of HVDC. (f) The DC current of HVDC.
When the fault occurs, the electromagnetic power output of the wind turbine is blocked. The imbalance between the output electromagnetic power and the input mechanical power causes the generator speed of the wind turbine and the DC voltage of the back-to-back converter to rise rapidly, as shown in Figure 9b,c. To avoid DC overvoltage of the wind turbine, when the DC voltage of the wind turbine reaches the preset upper threshold of 1.1 p.u., the DC chopper protection device of the wind turbine is activated, dissipating the surplus active power through the braking resistor to maintain the stability of the DC voltage of the wind turbine. After the fault occurs, the system operates stably 0.5 s later, completing the fault ride-through process.
4.5. Hybrid Case of Grid-Following and Grid-Forming DFIG
This section presents a case study of a hybrid system consisting of grid-following DFIGs and grid-forming DFIGs for DRU-HVDC power transmission. Under the condition of a total active power transmission of 1000 MW from the offshore wind turbines, the output power of the grid-forming DFIGs is tested at 700 MW and 850 MW, respectively.
4.5.1. Grid-Forming Wind Turbines Carrying 700 MW of Active Power
In this subsection, the rated power of the grid-forming wind turbine units is set to 700 MW, while the grid-following wind turbine units have a rated power of 300 MW. The remaining parameters are consistent with those in Table 3. As shown in Figure 10a–c, after , the PCC voltage established by the grid-forming wind turbines has stabilized, providing the voltage required for commutation to the DRU. After the PCC voltage is established, the PLL of the grid-following wind turbines can accurately track the phase of this voltage, enabling the grid-following DFIG to enter a stable operating state, as shown in Figure 10d,e. The total active power absorbed by the DRU is presented in Figure 10f. The hybrid wind turbine system is capable of stably delivering power to the HVDC transmission system.
Figure 10.
(a) The AC voltage of PCC. (b) The RMS voltage of PCC. (c) The frequency of PCC. (d) The respective active power generated by grid-following DFIG wind turbines and grid-forming DFIG wind turbines. (e) The respective reactive power generated by grid-following DFIG wind turbines and grid-forming DFIG wind turbines. (f) The power absorbed by the DRU from the entire hybrid DFIG offshore wind farm.
4.5.2. Grid-Forming Wind Turbines Carrying 850 MW of Active Power
In this subsection, the rated power of the grid-forming wind turbine units is set to 850 MW, while the grid-following wind turbine units have a rated power of 150 MW. The remaining parameters are consistent with those in Table 3. As shown in Figure 11a–c, after , the PCC voltage established by the grid-forming wind turbines has stabilized, providing the voltage required for commutation to the DRU. After the PCC voltage is established, the PLL of the grid-following wind turbines can accurately track the phase of this voltage, enabling the grid-following DFIG to enter a stable operating state, as shown in Figure 11d,e. The total active power absorbed by the DRU is presented in Figure 11f. The hybrid wind turbine system is capable of stably delivering power to the HVDC transmission system.
Figure 11.
(a) The AC voltage of PCC. (b) The RMS voltage of PCC. (c) The frequency of PCC. (d) The respective active power generated by grid-following DFIG wind turbines and grid-forming DFIG wind turbines. (e) The respective reactive power generated by grid-following DFIG wind turbines and grid-forming DFIG wind turbines. (f) The power absorbed by the DRU from the entire hybrid DFIG offshore wind farm.
4.6. Small-Signal Stability Analysis via the Impedance-Based Method
To further verify the effectiveness of the control method and the appropriateness of the parameters proposed in Section 3, a small-signal stability analysis of the entire DFIG–DRU–HVDC system is conducted using the impedance-based method. The parameters of each subsystem are configured according to Table 2 and Table 3. The results obtained from the model are presented in Figure 12. The frequency of the injected small-signal perturbation ranges from 1 to 2000 Hz, covering the low-, medium-, and high-frequency bands.
Figure 12.
Small-signal impedance characteristics of the system under normal operating conditions.
As shown in Figure 12, the impedance characteristics exhibit multiple resonance peaks owing to the internal dynamics of the grid-forming DFIG, indicating relatively complex frequency-domain behavior. Near the fundamental frequency (50 Hz), the system impedance remains relatively stable and its magnitude varies within a limited range. In the medium- and high-frequency bands, the impedance magnitude decreases. Near 1000 Hz, the phase characteristics indicate that the system impedance is predominantly inductive.
Taking the proportional gain of the PI controller in the power loop as an example, a comparative small-signal analysis is conducted. The controller parameters used in Figure 12 are configured according to Table 2, where and are set to 0.03 and 0.7, respectively. To examine the performance of the grid-forming DFIG under different proportional gains, Figure 13 presents the small-signal impedance characteristics obtained with different values of . In Figure 13a, and are set to 0.01 and 0.7, respectively. In Figure 13b, and are set to 0.03 and 2.1, respectively, while all other parameters remain unchanged.
Figure 13.
Small-signal impedance characteristics with different PI-controller parameters in the power loop.
Comparing Figure 12 with Figure 13a, it can be observed that when is reduced, the impedance magnitude exhibits a pronounced increase in the frequency band around the fundamental frequency, whereas no significant changes occur near 1 Hz in the low-frequency range or near 1000 Hz in the high-frequency range. The increase in magnitude is attributed to the weaker response of the controller to small voltage perturbations at a lower , which reduces its voltage-regulation capability. By contrast, the impedance magnitude remains nearly unchanged in frequency bands far from the fundamental frequency because these bands lie outside the voltage-control bandwidth of the power loop, where the control effect is negligible.
Comparing Figure 12 with Figure 13b, it can be observed that when is increased, the impedance magnitude also exhibits a pronounced increase in the frequency band around the fundamental frequency, while no significant changes occur near 1 Hz or 1000 Hz. An excessively large amplifies the controller response to small voltage perturbations and may reduce the damping of the dominant oscillatory mode, thereby increasing the risk of system instability. Under the investigated operating conditions, either decreasing or increasing relative to the selected value adversely affects the control performance to some extent. These results further support the effectiveness of the grid-forming DFIG controller and the selected parameter set.
5. Conclusions and Future Prospects
This paper first introduces the topology of the DRU-HVDC offshore wind power transmission system, highlighting the practical significance and research value of integrating DFIG into such a system. Secondly, the internal structure of the DFIG is presented. Through the rational design and parameter tuning of the RSC controller, the DFIG is endowed with grid-forming capability to meet the system requirements on the wind turbine side. Finally, the designed grid-forming DFIG is integrated into the DRU-HVDC offshore wind power system, and an electromagnetic simulation model of the corresponding system is built in PSCAD/EMTDC. Simulations are conducted under various operating conditions, including steady-state operation, wind speed variation, fault ride-through, and hybrid operation with grid-following wind turbines. The simulation results validate the effectiveness of the proposed grid-forming control strategy for DFIGs, while also providing a cost-effective and highly stable solution for future offshore wind power engineering.
However, some limitations remain in this study. First, although the impedance-based analysis provides a small-signal assessment of the system and illustrates the influence of the power-loop parameters, a complete analytical state-space model and eigenvalue analysis have not yet been established. Consequently, the specific interaction mechanisms among the grid-forming DFIG, grid-following DFIG, and DRU require further investigation. Future work will focus on developing such analytical models to quantify system stability margins more rigorously. Furthermore, it should be noted that the control parameters in this study were initially determined using a trial-and-error procedure and were subsequently assessed through the impedance-based analysis. While this provides a functional baseline, analytical bandwidth design and a more systematic investigation of parameter influence on system dynamics are still necessary. In addition, this paper focuses primarily on control technology support. Further research is needed on the lightweight design of offshore wind power systems, including the optimization of main-circuit parameters and the reduction in the weight of converter valves and offshore rectifier stations. Systematic sensitivity analyses of cable-length variations and network conditions should also be conducted to further assess the robustness of the proposed control strategy.
Author Contributions
Conceptualization, J.W. and Z.Z.; methodology, Z.X.; software, W.Y.; validation, J.W., W.Y. and Z.Z.; formal analysis, J.W.; investigation, J.W.; resources, Z.Z.; data curation, J.W.; writing—original draft preparation, J.W.; writing—review and editing, J.W.; visualization, W.Y.; supervision, Z.Z.; project administration, Z.X.; funding acquisition, Z.Z. All authors have read and agreed to the published version of the manuscript.
Funding
This work was supported by the National Natural Science Foundation of China under Grant U24B2089.
Data Availability Statement
The raw data supporting the conclusions of this article will be made available by the authors on request. Requests for data should be directed to Jiateng Wang at 22460675@zju.edu.cn. The data are not publicly available due to ethical and confidentiality restrictions imposed by the data providers.
Conflicts of Interest
The authors declare no conflicts of interest.
References
- Diaz, H.; Guedes Soares, C. Review of the current status, technology and future trends of offshore wind farms. Ocean Eng. 2020, 209, 107381. [Google Scholar] [CrossRef] [Scilit]
- Zou, C.; Wei, R.; Feng, J.; Zhou, Y. Development Status and Application Prospect of VSC-HVDC. South. Power Syst. Technol. 2022, 16, 1–7. [Google Scholar]
- Liu, W.; Li, Q.; Wang, X.; Zhang, F.; Li, L.; Yan, H. Application Status and Prospect of VSC-HVDC Technology for Large-Scale Offshore Wind Farms. Electr. Power 2020, 53, 55–71. [Google Scholar]
- Martinez-Rodrigo, F.; Ramirez, D.; Rey-Boue, A.B.; de Pablo, S.; Carlos Herrero-de Lucas, L. Modular Multilevel Converters: Control and Applications. Energies 2017, 10, 1709. [Google Scholar] [CrossRef] [Scilit]
- Deng, J.; Cheng, F.; Yao, L.; Xu, J.; Mao, B.; Li, X.; Chen, R. A review of system topologies, key operation and control technologies for offshore wind power transmission based on HVDC. IET Gener. Transm. Distrib. 2023, 17, 3345–3363. [Google Scholar] [CrossRef] [Scilit]
- Xiang, X.; Fan, S.; Gu, Y.; Ming, W.; Wu, J.; Li, W.; He, X.; Green, T.C. Comparison of Cost-effective Distances for LFAC with HVAC and HVDC in Their Connections for Offshore and Remote Onshore Wind Energy. CSEE J. Power Energy Syst. 2021, 7, 954–975. [Google Scholar] [CrossRef] [Scilit]
- Rao, H.; Zhou, Y.; Li, W.; Zou, C.; Wang, Z. Engineering Application and Development Prospect of VSC-HVDC Transmission Technology. Autom. Electr. Power Syst. 2023, 47, 1–11. [Google Scholar] [CrossRef] [Scilit]
- Xin, B.; Guo, M.; Wang, S.; Li, X. Friendly HVDC Transmission Technologies for Large-scale Renewable Energy and Their Engineering Practice. Autom. Electr. Power Syst. 2021, 45, 1–8. [Google Scholar]
- Zheng, X. Main Schemes and Key Technical Problems for Grid Integration of Offshore Wind Farm. Autom. Electr. Power Syst. 2022, 46, 1–10. [Google Scholar]
- Tang., Y.; Zhang, Z.; Xu, Z. Diode Rectifier Unit Based LFAC Transmission for Offshore Wind Farm Integration. Electr. Power 2020, 53, 44. [Google Scholar]
- Zang, J.; Yang, R.; Xu, J.; Zhan, H.; Wang, K.; Qin, S. Virtual Synchronous Control for Offshore Wind Power with Low-frequency AC Transmission Using Diode Rectifier. Autom. Electr. Power Syst. 2026, 50, 24–35. [Google Scholar]
- Chen, Q.; Lin, B.; Wang, X.; Liang, P.; Zhang, Z. Harmonic Analysis of Transmission Scheme for Offshore Wind Farms Based on Diode Rectifier Unit. Eng. Rep. 2025, 7, e70438. [Google Scholar] [CrossRef] [Scilit]
- Liang, P.; Pei, X.; Zhou, Y.; Wu, H.; Xu, Y.; Zhang, Z.; Xu, Z.; Qiu, F. Harmonic Analysis and Elimination of Transmission Scheme Based on DRU for Medium-Frequency Offshore Wind Farms. Electronics 2025, 14, 3669. [Google Scholar] [CrossRef] [Scilit]
- Dong, C.; Cheng, Z.; Aisikaer; Wang, W.; Yu, X.; Yang, T. Research on parallel transmission system of offshore wind power by DRU and auxiliary VSC. Renew. Energy Resour. 2025, 43, 1655–1663. [Google Scholar]
- Meng, L.; Wang, W.; Li, X. Black Start Strategy for Hybrid Grid-forming/Grid-following Offshore Wind Farms Based on DRU-HVDC Transmission Systems. High Volt. Appar. 2025, 61, 138. [Google Scholar]
- Cheng, Z.; Li, S.; Yang, T.; Aisikaer; Fang, Z.; Gao, Y. Research on Fault Ride-Through Control Strategy of Grid-Forming Type Converter for Offshore Wind Farms Based on DRU. Acta Energiae Solaris Sin. 2025, 46, 140–150. [Google Scholar]
- Yuan, Q.; Xie, Y.; Jiang, T.; Duan, J. Control Strategies of DRU+MMC Hybrid Converter at the Sending End with Compatibility of Grid-following and Grid-forming Offshore Wind Farm Transmission. Power Syst. Technol. 2024, 48, 4482–4492. [Google Scholar]
- Wu, J.; Li, C.; Li, J.; Zhang, Y. Research on Parameter Design and Control Method of Lightweight Converter Valve for Offshore Wind Power Transmission Based on Hybrid Topology. Energies 2026, 19, 1740. [Google Scholar] [CrossRef] [Scilit]
- Yu, L.; Fu, Z.; Li, R.; Zhu, J. DRU-HVDC for offshore wind power transmission: A review. IET Renew. Power Gener. 2024, 18, 2080–2101. [Google Scholar] [CrossRef] [Scilit]
- Bernal-Perez, S.; Ano-Villalba, S.; Blasco-Gimenez, R.; Rodriguez-D’Derlee, J. Efficiency and Fault Ride-Through Performance of a Diode-Rectifier- and VSC-Inverter-Based HVDC Link for Offshore Wind Farms. IEEE Trans. Ind. Electron. 2013, 60, 2401–2409. [Google Scholar] [CrossRef] [Scilit]
- Ivan Andrade, A.; Blasco-Gimenez, R.; Ruben Pena, G. Distributed Control Strategy for a Wind Generation Systems based on PMSG with Uncontrolled Rectifier HVDC Connection. In Proceedings of the 2015 IEEE International Conference on Industrial Technology (ICIT); IEEE: New York, NJ, USA, 2015; pp. 982–986. [Google Scholar]
- Andrade, A.I.; Pena, G.R.; Blasco-Gimenez, R.; Riedemann, A.J. Control Strategy of a HVDC-Diode Rectifier Connected Type-4 Off-Shore Wind Farm. In Proceedings of the 2015 IEEE 2nd International Future Energy Electronics Conference (IFEEC); IEEE: New York, NJ, USA, 2015. [Google Scholar]
- Yu, L.; Li, R.; Xu, L. Distributed PLL-Based Control of Offshore Wind Turbines Connected with Diode-Rectifier-Based HVDC Systems. IEEE Trans. Power Deliv. 2018, 33, 1328–1336. [Google Scholar] [CrossRef] [Scilit]
- Yu, L.; Li, R.; Xu, L.; Adam, G.P. Analysis and Control of Offshore Wind Farms Connected with Diode Rectifier-Based HVDC System. IEEE Trans. Power Deliv. 2020, 35, 2049–2059. [Google Scholar] [CrossRef] [Scilit]
- Yu, L.; Xu, L.; Zhu, J.; Li, R. Impedance Modelling and Stability Analysis of Diode-Rectifier based HVDC Connected Offshore Wind Farms. IEEE Trans. Power Deliv. 2022, 37, 591–602. [Google Scholar] [CrossRef] [Scilit]
- Bidadfar, A.; Saborio-Romano, O.; Cutululis, N.A.; Sorensen, P.E. Control of Offshore Wind Turbines Connected to Diode-Rectifier-Based HVdc Systems. IEEE Trans. Sustain. Energy 2021, 12, 514–523. [Google Scholar] [CrossRef] [Scilit]
- Li, R.; Yu, L.; Xu, L.; Adam, G.P. DC Fault Protection of Diode Rectifier Unit Based HVDC System Connecting Offshore Wind Farms. In Proceedings of the 2018 IEEE Power & Energy Society General Meeting (PESGM); IEEE: New York, NJ, USA, 2018. [Google Scholar]
- Li, R.; Yu, L.; Xu, L. Offshore AC Fault Protection of Diode Rectifier Unit-Based HVdc System for Wind Energy Transmission. IEEE Trans. Ind. Electron. 2019, 66, 5289–5299. [Google Scholar] [CrossRef] [Scilit]
- Angel Cardiel-Alvarez, M.; Arnaltes, S.; Luis Rodriguez-Amenedo, J.; Nami, A. Decentralized Control of Offshore Wind Farms Connected to Diode-Based HVdc Links. IEEE Trans. Energy Convers. 2018, 33, 1233–1241. [Google Scholar] [CrossRef] [Scilit]
- Zhang, Z.; Jin, Y.; Xu, Z. Two Offshore Wind Farm Integration Schemes Based on Grid Forming Wind Turbines and Diode Rectifier Unit. High Volt. Eng. 2022, 48, 2098–2107. [Google Scholar]
- Xiao, H.; Huang, X.; Li, Y.; Huang, W.; Cai, D.; Peng, F. Reactive Power-synchronization Control for Offshore Wind Turbines Connected to Diode Rectifier. High Volt. Eng. 2022, 48, 3820–3828. [Google Scholar]
- Xiao, H.; Huang, X.; Huang, Y.; Liu, Y. Self-Synchronizing Control and Frequency Response of Offshore Wind Farms Connected to Diode Rectifier Based HVDC System. IEEE Trans. Sustain. Energy 2022, 13, 1681–1692. [Google Scholar] [CrossRef] [Scilit]
- Zhang, Z.; Jin, Y.; Xu, Z. Grid-Forming Control of Wind Turbines for Diode Rectifier Unit Based Offshore Wind Farm Integration. IEEE Trans. Power Deliv. 2023, 38, 1341–1352. [Google Scholar] [CrossRef] [Scilit]
- Ali, S.W.; Sadiq, M.; Terriche, Y.; Naqvi, S.A.R.; Hoang, L.Q.N.; Mutarraf, M.U.; Hassan, M.A.; Yang, G.; Su, C.L.; Guerrero, J.M. Offshore Wind Farm-Grid Integration: A Review on Infrastructure, Challenges, and Grid Solutions. IEEE Access 2021, 9, 102811–102827. [Google Scholar] [CrossRef] [Scilit]
- Nkosi, N.R.; Bansal, R.C.; Adefarati, T.; Naidoo, R.M.; Bansal, S.K. A review of small-signal stability analysis of DFIG-based wind power system. Int. J. Model. Simul. 2023, 43, 153–170. [Google Scholar] [CrossRef] [Scilit]
- Ngamroo, I. Review of DFIG Wind Turbine Impact on Power System Dynamic Performances. IEEJ Trans. Electr. Electron. Eng. 2017, 12, 301–311. [Google Scholar] [CrossRef] [Scilit]
- Bebars, A.D.; Eladl, A.A.; Abdulsalam, G.M.; Badran, E.A. Internal electrical fault detection techniques in DFIG-based wind turbines: A review. Prot. Control Mod. Power Syst. 2022, 7, 18. [Google Scholar] [CrossRef] [Scilit]
- Empowered by High-Speed Rail Reliability Genes, CRRC Zhuzhou Institute’s 12MW Offshore Double-Fed Wind Turbine Unit Was Successfully Hoisted. 2026. Available online: https://news.bjx.com.cn/html/20250806/1454520.shtml (accessed on 26 May 2026).
- Yuanjing’s Fault-Free Wind Farm Scale Reaches a New High! 2026. Available online: http://www.hynyw.com/article/12511.html (accessed on 26 May 2026).
- Yan, K.; Li, G.; Zhang, R.; Xu, Y.; Jiang, T.; Li, X. Frequency Control and Optimal Operation of Low-Inertia Power Systems with HVDC and Renewable Energy: A Review. IEEE Trans. Power Syst. 2024, 39, 4279–4295. [Google Scholar] [CrossRef] [Scilit]
- Wei, J.; Wang, Y.; Huang, S.; Wang, B.; Wang, P.; Shen, F. Review on the Stability Enhancement Method of Grid-forming Control-based Wind Turbines. J. Electr. Eng. 2025, 20, 1–13. [Google Scholar]
- Li, M.; Xie, Z.; Xu, S.; Yang, S.; Zhang, X. Electromechanical Oscillation Analysis and Suppression of Grid Forming DFIG-Based Wind Turbines Under Weak Grid. IEEE Trans. Energy Convers. 2025, 40, 1365–1377. [Google Scholar] [CrossRef] [Scilit]
- Zhang, Z.; Sun, D.; Zhao, C.; Gu, Z.; Nian, H. Enhanced Grid-Forming Control Strategy for DFIG Participating in Primary Frequency Regulation Based on Double-Layer MPC in Microgrid. IEEE Trans. Energy Convers. 2025, 40, 2679–2693. [Google Scholar] [CrossRef] [Scilit]
- Li, C.; Cao, Y.; Li, B.; Wang, S.; Chen, P. A novel power control scheme for distributed DFIG based on cooperation of hybrid energy storage system and grid-side converter. Int. J. Electr. Power Energy Syst. 2024, 157, 109801. [Google Scholar] [CrossRef] [Scilit]
- Zhang, H.; Wei, X.; Zhao, H.; Hu, X. Disturbance observer-based finite-time control for a class of systems with multiple heterogeneous disturbances. Trans. Inst. Meas. Control 2023, 45, 27–36. [Google Scholar] [CrossRef] [Scilit]
- Hosseinabadi, P.A.; Pota, H.; Mekhilef, S.; Schwartz, H. Fixed-time observer-based control of DFIG-based wind energy conversion systems for maximum power extraction. Int. J. Electr. Power Energy Syst. 2023, 146, 108741. [Google Scholar] [CrossRef] [Scilit]
- Ponnarasi, L.; Pankajavalli, P.B.; Lim, Y.; Sakthivel, R. Optimization-Based Event-Triggered State Estimation Algorithm for IoT-Based Wind Turbine Systems. IEEE Internet Things J. 2024, 11, 9645–9655. [Google Scholar] [CrossRef] [Scilit]
- Han, J.; Liu, Z.; Liang, N. Nonlinear Adaptive Robust Control Strategy of Doubly Fed Induction Generator Based on Virtual Synchronous Generator. IEEE Access 2020, 8, 159887–159896. [Google Scholar] [CrossRef] [Scilit]
- Xiong, K.; Hu, W.; Zhang, G.; Zhang, Z.; Chen, Z. Deep reinforcement learning based parameter self-tuning control strategy for VSG. Energy Rep. 2022, 8, 219–226. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.