A Coordinated Control-Based Power Management Strategy for a Hybrid Solar–Wind–Battery Integrated Standalone DC Microgrid for Rural Electrification

,
,
,
,
and
1
Directorate of Post Graduate Studies, Energy System Engineering, Mehran University of Engineering and Technology, Jamshoro 76062, Sindh, Pakistan
2
Department of Electrical Engineering, Mehran University of Engineering and Technology, SZAB Campus, Khairpur Mir’s 66020, Sindh, Pakistan
3
Department of Electrical Engineering, Mehran University of Engineering and Technology, Jamshoro 76062, Sindh, Pakistan
4
Department of Electrical Engineering, College of Engineering, University of Business and Technology, Jeddah 21361, Saudi Arabia
This article belongs to the Section F1: Electrical Power System

Abstract

Standalone DC microgrids offer a promising solution for providing reliable and sustainable electricity to remote communities in developing countries. However, the intermittent nature of solar and wind resources, combined with continuously varying load demand, presents considerable operational challenges in maintaining real-time power balance, stable DC bus voltage, and ensuring reliable continuous supply. Therefore, there is dire need for user-friendly control solutions tailored to the specific needs of isolated communities. As such, this paper presents a coordinated control and power management strategy for an isolated hybrid solar–wind–battery integrated DC microgrid for rural electrification applications. A comprehensive mathematical model of the standalone DC microgrid incorporating photovoltaic generation, wind energy conversion, battery storage, bidirectional DC-DC conversion, and common DC bus dynamics is developed at the very first stage of the proposed coordinated control framework. The framework utilizes principal local device loops and a secondary dynamic power management strategy to ensure efficient renewable power extraction, dynamic source–storage–load coordination, stable DC bus voltage, and real-time energy management within the developed standalone DC microgrid. It is worthwhile to mention that, instead of using synthesized or online available wind speed and solar irradiance data, this research utilized real-time recorded metrological data obtained from the Mehran University Jamshoro, Pakistan. The obtained results establish a stable DC bus voltage regulation within acceptable operating limits, continuous power balance, seamless bidirectional battery operation, and safe battery state-of-charge (SoC) management to prevent deep discharging or overcharging, thus ensuring reliable operation. The overall performance confirms the technical robustness, operational flexibility, and practical suitability of the proposed standalone hybrid DC microgrid architecture for its resilient operation and rural electrification applications.

1. Introduction

Easy access to affordable, reliable, and modern energy for all is one of the most crucial aspects for driving socioeconomic development, addressing climate change, and improving the quality of life throughout the world [1]. Though there has been significant progress since 2010, the world is still not on track to achieve the targets prescribed under the Sustainable Development Goals (namely SDG 7). This localized energy poverty continues to hinder macro-regional growth, especially within rural and low-income areas of developing nations. Globally, approximately 750 million people live without access to electricity [2], while over 3 billion rely on traditional biomass fuels for cooking. This deficit in modern energy services is most acute in Sub-Saharan Africa and South Asia, where electrical access is either absent, highly unreliable, or economically unaffordable. Also, the growing use of DC-native renewable energy sources (RESs), including solar photovoltaic (PV) and the emergence of DC-compatible energy storage systems (ESSs), have nevertheless caused a paradigm change in contemporary power systems [3]. Consequently, DC microgrids have taken the lead among other microgrid topologies as the suitable option for off-grid electrification in isolated rural areas. This preference stems from the fact that DC microgrids are naturally compatible with contemporary efficient DC load appliances, such as LED lighting, brushless direct current (BLDC) fans, electric vehicles (EVs), and inverter-driven appliances, like refrigerators and air conditioners [4].
Owing to the advantages mentioned, DC microgrids have emerged as valuable architectures for the integration of multiple renewable energy sources (RESs), energy storage systems (ESSs), and local loads, with higher efficiency and more reliability due to their simplicity with less components [5]. The general architecture of the standalone DC microgrid is given in Figure 1.
Figure 1. General architecture of standalone DC microgrids.
In addition, contrary to the AC microgrids where there are two voltage conversion stages are required between source and main bus, the DC microgrid requires only one such conversion stage. This led to a reduction in the cost and smoother control strategy implementation. Nevertheless, despite its key merits, isolated DC microgrids pose unique operational challenges. One of such challenges is their low system inertia which makes their voltage and frequency regulation a tough task for control engineers. The key challenge is the power fluctuations and system instabilities that are fundamentally governed by three different aspects that need to be overcome: power exchange variability, severe power variations within the intermittent renewable power sources and storage systems, and sudden stochastic changes in the localized DC load [4]. This power imbalance, therefore, directly affects the voltage stabilization of the common DC bus, which yields the unpredictable weather profiles and sudden load changes to extreme electrical stress. These voltage fluctuations can cause the battery to be constantly charged and discharged at a high frequency, increasing the rate at which the battery’s internal components degrade, shortening its lifespan, and thus compromising the overall reliability of the DC microgrid system. Sophisticated control solutions that regulate and manage the power imbalance, ensure efficient control of the bus voltage for the DC microgrid, and enhance resilience to transient and steady-state disturbances are critical for addressing these operational challenges. While traditional control methods like droop control are effective in decentralized management, they may suffer from certain drawbacks, such as steady-state voltage fluctuations, current fluctuations, and scalability challenges in complex systems. However, advanced controllers, like fuzzy controllers, sliding mode controls, and model predictive controls, offer robustness but are also computationally intensive with complex implementations [6].
To overcome these problems in standalone power systems, this study proposes a hybrid solar–wind–battery integrated standalone DC microgrid governed by a two-layer hierarchical control structure, combining primary local device loops and a secondary dynamic power management strategy. The major contributions of this research work are presented as follows:
  • Modelling of a standalone DC microgrid with PV, wind, battery storage, and dynamic DC loads integrated into single DC bus, along with a unified coordinated control system for its efficient and reliable operation.
  • Implementation of a Maximum Power Point Tracking (MPPT) system using a perturb and observe (P&O) algorithm for the solar PV unit and an Optimal Torque Control (OTC) loop for the wind turbine. These controls ensure the optimal utilization of renewable energy sources under high environmental volatility.
  • Employing a cascaded outer-voltage inner-current PI controller at the primary layer that successfully maintains the common DC bus voltage at its reference value of 24 V despite variable solar irradiance and wind speed, as well as sudden step-load changes. This approach provides a practical yet effective solution with less implementation complexity compared to complex state-of-the-art control methods.
  • A power management strategy is designed at the secondary hierarchical layer for the proposed developed DC microgrid to handle real-time power sharing between the source, battery, and load. The proposed strategy ensures continuous and stable power balancing under shifting environmental conditions without requiring high-bandwidth communication networks.
The proposed system is designed as a localized 24 V DC rural microgrid for standalone residential applications rather than as a long-distance distribution network. The proposed control framework demonstrates superior and optimal energy performance of the isolated rural DC microgrid by meeting the common DC bus stability and power balance conditions amid variable demand and generation scenarios, marking a key contribution to DC microgrid energy management research. Based on the dynamic performance and results achieved, the proposed standalone DC microgrid can be a viable and scalable option for off-grid rural electrification.
The remainder of this paper is organized as follows. Section 2 presents the related literature review on standalone hybrid DC microgrids, highlighting the existing developments in system planning, renewable integration, control strategies, and the identified research gaps addressed in this work. Section 3 describes the architecture of the proposed hybrid solar–wind standalone DC microgrid and presents the mathematical modelling of its major subsystems, including the photovoltaic unit, wind energy conversion system, battery storage, bidirectional converter, and common DC bus dynamics. Section 4 introduces the proposed power management and coordinated control framework, including renewable power extraction, battery charge–discharge coordination, and DC bus voltage regulation for stable standalone operation. Section 5 presents the simulation results and discussion under different dynamic operating scenarios to evaluate the effectiveness of the proposed framework in terms of renewable power tracking, power balancing, battery dynamic response, and DC bus voltage stability. Finally, Section 5 concludes the paper by summarizing the main findings and outlining future research directions.

3. System Configuration and Proposed Methodology

In this section, the overall configuration of the proposed standalone DC microgrid and the methodology used for modelling, control, and power management is presented. The section is divided into the following subsections.

3.1. DC Microgrid Architecture and System Description

The structural layout of the proposed standalone, off-grid hybrid DC microgrid, tailored for the meteorological profiles of the Jamshoro region in Sindh, Pakistan, is systematically illustrated in Figure 2.
Figure 2. Detailed architecture of the proposed standalone hybrid solar–wind DC microgrid with power management and a coordinated control framework.
The architecture is established with a single 24 V DC bus scheme, which serves as the common point, integrating all generation sources, energy storage, and dynamic loads. In this scheme, the solar PV unit is connected through a DC–DC boost converter governed by a primary perturb and observe (P&O) maximum power point tracking (MPPT) controller to the common DC bus. In parallel with the PV subsystem, the Permanent Magnet Synchronous Generator (PMSG)-based wind turbine is coupled via a three-phase diode bridge rectifier, followed by a DC–DC boost converter, which is optimized by an Optimal Torque Control (OTC) MPPT algorithm tracking the generator rotor speed. This coordinated topology leverages the natural complementary nature of solar and wind resources to improve overall supply reliability.
A centralized battery energy storage system (BESS) is connected to the common DC bus via a bidirectional DC–DC converter in order to address the instantaneous power imbalances between these intermittent sources and the dynamic localized loads. The bidirectional converter, which is intended to address power imbalances between the sources (Ppv, Pw) and the load (Pload), allows the BESS to charge and discharge smoothly. Because of this, the battery system either stores excess generation during resource surpluses or supplies essential supplemental energy during shortages, whereas the PV and wind power generation units inject electricity into the common DC bus and the loads drain whatever is required at the regulated bus voltage. Every element is linked to a common DC microgrid bus, improving the overall resilience of the DC microgrid system. It operates via a decentralized two-layer hierarchical control framework. The primary control layer employs a cascaded outer-voltage inner-current Proportional–Integral (PI) control architecture at the bidirectional interface to maintain 24 V bus regulation. Simultaneously, the secondary layer operates a localized dynamic power management strategy (PMS) that continuously infers microgrid power equilibrium states by tracking localized variables: PV power (Ppv), wind power (Pw), battery state of charge (SoC), and common DC bus voltage (Vbus). Based on these instantaneous inputs, this secondary hierarchical layer coordinates the real-time operational boundaries of the converters to maintain the power balance across the standalone DC microgrid system, effectively mitigating low-inertia vulnerabilities under severe sudden load switching and volatile weather transitions. The microgrid is designed to meet the power demands of applications in remote areas where access to the main power grid is unavailable.

3.2. Solar PV Generation Subsystem and MPPT Control Framework

The PV system serves as the main source in the DC MG due to its availability and ability to generate DC power, thus making it unnecessary to convert it to another form of power. However, direct integration of the PV array into the shared DC bus is not possible due to weather-dependent variations in terminal voltage and power. Therefore, an intermediate DC-DC boost converter is utilized to interface the PV array with the common 24 V DC bus to ensure stable power transfer under varying environmental profiles, as shown in Figure 3.
Figure 3. Schematic of the PV subsystem integration with DC bus.
Notably, the PV boost converter uses direct duty cycle control via the P&O algorithm to inject the extracted power into the DC bus as a controlled current, instead of directly regulating the common bus voltage. To represent the physical behaviour of the PV panel under varying meteorological conditions, a standard five-parameter single-diode equivalent circuit model is utilized [22]. Practical arrays consist of a number of connected PV cells and, in order to measure the characteristics at the terminals of the PV array, additional parameters must be added to the basic equation. The characteristic relationship at the output terminals is governed by the following transcendental Equation (1) [22,23]:
I = I P V − I O [ e x p ( V p v + I p v R s n V T )   − 1 − V p v + I p v R s R s h ]
where I P V and I O are the photovoltaic (PV) and saturation currents, respectively; I0 is the diode reverse saturation current; n is the diode ideality factor; Rs is the intrinsic series resistance; and Rsh is the shunt resistance. The thermal voltage Vt is defined as
V T = N c e l l ⋅ k ⋅ T q
where Ncell is the number of cells per module, k is the Boltzmann constant (1.380 × 10−23 J/K), q is the electron charge (1.6022 × 10−19 C), and T is the cell operating temperature in Kelvin.
In this study, the solar power generation stage comprises a user-defined PV array made of a single module per string (Ns = 1) and two parallel strings (Np = 2), with a maximum rated capacity of 600 W, equivalent to two 300 W modules, and a standard peak irradiance of 1000 W/m2. The temperature coefficients of the voltage (Kv) and current (Ki) are −0.33%/ ℃ and +0.05%/ ℃ , respectively. The array is interfaced to the W DC bus via a DC-DC boost converter operating at 5 kHz (L = 1.0 mH, C = 11,000   μ F ). The effectiveness of the control algorithm at tracking is evaluated by using a dynamic environmental profile in a 10 s execution window under realistic conditions—the solar irradiance starts at 200 W/m2 and increases steadily to maximum value, approximately 1015 W/m2, and then slowly decreases to 100 W/m2 at t = 10 s.
Additionally, a localized perturb and observe (P&O) maximum power point tracking (MPPT) algorithm is implemented. The algorithm is used to maximize the power output of the solar panel. The MPPT algorithm monitors the maximum power by dynamically adjusting the voltage of the solar output at various intervals [7].
The control-loop measures the output voltage V(k) and output current I(k) of the panel at each discrete time instant k when tracking the maximum power point. The flowchart in Figure 4 describes the order in which the tracking mechanism’s operations are carried out. The algorithm calculates the mathematical sign of the discrete power gradient (ΔP) and voltage gradient (ΔV), and then sequentially adjusts the reference command given to the converter switching network to increase or decrease the reference command by a proper value:
D ( k ) = D ( k − 1 ) ± Δ D
where ΔD is a fixed step size for the perturbation and enforced duty cycle saturation bounds (D ∈ [0.0, 0.85]), preventing converter over-modulation and control instability during transient conditions. The power-controlled operation of the interface stage facilitates reliable power injection to the common bus bar without adding a large amount of computational load in the central controller architecture of the microgrid. The P&O-based MPPT method demonstrates reliable power extraction efficacy under changing environmental conditions. In comparison to other methods, the P&O-based MPPT technique provides adequate performance with reasonable computational demands, making it appropriate for the suggested microgrid system.
Figure 4. Flowchart of the P&O MPPT control algorithm.

3.3. Wind Energy Conversion System (WECS) Modelling

In the hybrid renewable-powered DC microgrid, the wind energy conversion system (WECS) contributes as a primary variable energy source in parallel with solar PV generation. The wind’s kinetic energy is converted by the aerodynamic subsystem into mechanical energy, which is then converted into electrical energy via a variable speed generator setup.

3.3.1. Aerodynamic and PMSG Mathematical Modelling

The mechanical power Pm captured from the wind by a variable speed horizontal-axis wind turbine rotor is modelled by the following standard aerodynamic expression:
P me   =   1 2 ρ AC p   ( λ ,   β ) v w 3   =   1 2 ρ   π   R 5 C p   ( λ ,   β ) v w 3
where ρ represents the air density, A = πR2 is the rotor swept area, R is the blade radius, vw is the instantaneous wind speed, and Cp (λ, β) denotes the dimensionless power coefficient. The value of Cp is a non-linear function of the blade pitch angle β and the tip-speed ratio λ, which is defined as
λ = W m R V W
where W m is the mechanical angular speed of the turbine rotor.
V r e c = 3 6 π V p h
An intermediate DC-DC boost converter is utilized to interface this rectified output with the common 24 V DC bus. Therefore, an intermediate DC-DC boost converter is utilized to interface this rectified output with the common 24 V DC bus to ensure stable power transfer under varying environmental profiles. Similarly, the wind boost converter utilizes a closed-loop hysteresis current control to maximize power injection into the DC bus, instead of directly regulating the common bus voltage. The wind generation subsystem consists of a variable pitch wind turbine model of 0.5 kW with a three-phase Permanent Magnet Synchronous Generator (PMSG). The operational tracking performance of the localized control loop is evaluated by applying a dynamic realistic wind speed profile to the rotor of the turbine for a 10 s simulation period, which is between 10 m/s and 12.5 m/s, while conditioning and delivering power to the common 24 V DC bus.

3.3.2. Optimal Torque Control (OTC) MPPT Logic

An Optimal Torque Control (OTC) technique for maximum power point tracking is used to optimize wind energy extraction without the requirement for expensive wind speed sensors. The basic working principle involves modifying the electromagnetic torque of the generator to track the optimal mechanical torque curve of the turbine at any given wind speed.
The relationship can be expressed as follows by separating wind speed V W from the tip-speed ratio equation:
V W = W m R λ
To achieve maximum power extraction, the turbine must operate continuously at its optimal tip-speed ratio ( λ o p t ), where the power coefficient reaches its peak value ( C p _ m a x ) at a fixed pitch angle (β = 0). Substituting the expression for V W   under optimal conditions into the primary mechanical power equation yields the optimal target power curve:
P m e = 1 2 ρ π R 2 C p _ m a x W m R λ o p t 3 = ρ π R 5 C p _ m a x 2 λ o p t 3 3 W m 3 = K p _ o p t W m 3
where K p _ o p t represents the intrinsic optimal power coefficient of the specific turbine design. Noting that mechanical torque is related to power by Tm = P m W m , the optimal reference torque command Tm_opt is derived as:
T m _ o p t   =   P m _ o p t W m =   ρ π R 5   C p _ m a x   2 λ o p t 3 3 W m 2   = K p _ o p t   W m 2
As depicted in the control architecture given in Figure 5, this reference torque Tm_opt is dynamically determined using the measured rotor speed W m . The optimal torque reference is converted into a target rectified current command I r e f via the electrical torque relationship:
I r e f = T m _ o p t ⋅ W m V d c
Figure 5. Schematic of the wind subsystem integration’s with the DC bus.
This reference current is managed by a rapid hysteresis current controller. The existing controller directly controls the power switch of the boost converter (dw), ensuring the actual rectified DC current (iw) accurately tracks Iref. This localized method ensures a quick tracking response and easy implementation without increasing the computational burden on the centralized control system.

3.4. Battery System Modelling and Control

The battery system contributes to the stability and reliability of the isolated DC microgrid by compensating for the fluctuations of both renewable energy sources and load demand, all while maintaining the power balance and voltage stability. The battery is linked to the DC bus through a bidirectional DC-DC converter functioning in both charging and discharging modes. It stores excess energy when there is a generation surplus and provides it when generation is low or when demand is high. This helps to meet load demand, maintain voltage stability, and achieve power balance.
The battery system is modelled using a non-linear controlled voltage source in series with a constant internal resistance, representing the dynamic characteristics of a Lithium-Ion battery pack. The terminal voltage vb (t) is mathematically expressed as:
V b a t t t = E b a t t t − R i n ⋅ i b a t t ( t )
where Rin represents the internal ohmic resistance of the cells, ibatt (t) denotes the instantaneous battery current, and Ebat (t) represents the variable open-circuit internal electromotive force (EMF), which is calculated via the modified Shepherd model:
E b a t ( t ) = E o − K Q m a x Q m a x   −   q t + A e − B   ·   q t
In this expression, Eo signifies the nominal constant voltage of the cell chemistry, K denotes the polarization voltage coefficient, Qmax is the maximum rated capacity of the storage pack, A defines the exponential zone voltage amplitude, and B represents the inverse exponential zone capacity constant. The term q(t) quantifies the extracted charge over the elapsed operating period, which is determined through real-time integration:
q t =   ∫ 0 t i b a t t   ( τ ) d τ
Consequently, the dynamic state of charge (SoC) of the battery system is tracked continuously via standard Coulomb counting, and is expressed as:
S o C t = 1 −   q ( t ) Q m a x   × 100 %
The calculated SoC(t) serves as the primary state variable feedback for the high-level power management algorithm to prevent extreme deep discharge or overcharging regimes. As shown in the primary control schematic, the measured current (ibatt) and voltage (vbatt) are continuously processed to evaluate the real-time power exchange (Pbattery), while the inner-loop proportional–integral (PI) regulator adjusts the complementary PWM gate sequences (S_P, S_N) to handle the fast transient current tracking demands dictated by the system’s power balance requirements.

3.4.1. Bidirectional Converter and Battery Integration

A bidirectional DC-DC converter is used to integrate the battery storage system with the 24 V common DC bus. As shown in Figure 6, this converter configuration consists of a high-side switch S_P, a low-side switch S_N, and a filter inductor Lb.
Figure 6. Integration of the battery subsystem into the common DC bus via a bidirectional converter.
The inductor is placed in series with the positive terminal of the battery. Because of this structural arrangement, the physical inductor current iL(t) directly equals the real-time battery operating current ibatt (t). This relationship provides a direct tracking variable for the inner-current control loop.
The converter adjusts its operating mode to regulate the net power balance of the hybrid microgrid based on the power mismatch value Pnet (t) = PPV (t) + PW (t) − PLoad(t):
  • Buck Mode (Charging): When there is a generation surplus where the total renewable output exceeds the demand (PPV + PW > PLoad), Pnet is positive. The converter operates in buck mode to step down the bus voltage and route the excess power into the battery cells.
  • Boost Mode (Discharging): When the renewable generation falls short of the consumer load requirements (PPV + PW < PLoad), Pnet is negative. The converter transitions to boost mode to step up the battery voltage, injecting power back into the common 24 V DC bus to maintain voltage stability.
The gate drive signals for the power switches are controlled in a complementary arrangement, as illustrated by the schematic in Figure 6. The main pulse width modulation (PWM) command drives the high-side switch S_P directly, while an inverting logic block (NOT gate) drives the low-side switch S_N. This synchronous switching method eliminates diode conduction periods, lowering internal losses during both charging and discharging intervals.

3.4.2. Cascaded Dual-Loop Control Architecture

To manage the bidirectional energy exchange and regulate the common bus voltage under volatile renewable generation profiles, a cascaded dual-loop voltage–current (V–I) control framework is implemented within a unified control-loop structure. The outer-voltage regulation loop minimizes the tracking error between the target reference voltage (Vbus_ref = 24 V) and the actual measured DC bus voltage (Vbus) using a proportional–integral (PI) controller. The mathematical expression for the unconstrained current command (Iref_PI) is given by:
I r e f _ P I ( t ) = K p v ( V b u s _ r e f − V b u s ( t ) ) + ∫ K i v ∫ 0 t ( V b u s _ r e f − V b u s ( τ ) ) d τ
where Kpv and K i v represent the proportional and integral gains of the outer loop, respectively.
The output of the voltage loop PI controller needs to be constrained to produce a current reference that falls within the defined safe operating and charging (discharging) current limits of the battery storage system. A saturation interface imposes these rigid physical constraints, defined by the maximum permissible current during the charging and discharging of the battery (IB,max), to give the final tracking reference current (Iref):
I r e f   =   I B _ m a x   i f   I r e f _ P I   ( t )   >   I B _ m a x I r e f _ P I   ( t )   i f   − I B _ m a x   ≤   I r e f _ P I   ( t ) − I B _ m a x   i f   I r e f _ P I   ( t )   <   − I B _ m a x ≤   I B _ m a x
where I B _ m a x represents the maximum possible magnitude of charging or discharging current of the battery storage. This state allows the storage unit to dynamically adjust to the hybrid microgrid’s instantaneous net power mismatches up to the physical limits of the storage unit, after which the storage unit will operate in a constant maximum current output mode, maintaining its internal cell chemistry within safe operating limits.
The bounded reference signal (Iref) is the direct setpoint signal to the inner high-bandwidth current tracking loop. As shown by the feedback loop layout in Figure 7, the real-time battery operating current (Ibatt) is continuously sampled and fed back to evaluate instantaneous tracking errors. This deviation is filtered by the inner-current loop PI controller to generate the correct duty cycle command of the converter (Dbatt):
D b a t t ( t )   =   K p c ( I r e f   ( t )   −   I b a t t ( t ) )   +   K i c   ∫ 0 t ( I r e f   ( τ ) −   I b a t t ( τ ) ) d τ
where Kpc and Kic represent the inner-loop proportional and integral parameter configurations, respectively. The derived control variable (Dbatt) is directed to a high-frequency triangular carrier-wave pulse width modulation (PWM) generator block to yield synchronous, complementary gate switching commands (SP and SN) for the power switches:
S p = P W M ( D b a t t ) , S N   =   N O T   ( S P   )
Figure 7. Schematic and control layout of the battery system and bidirectional converter.
This continuous cascaded loop architecture effectively isolates high-frequency switching dynamics within the inner loop subsystem, providing a rapid transient response, minimized DC bus voltage ripple, and strict tracking alignment during rapid variations in hybrid generation profiles or sudden step-load perturbations.

3.5. DC Bus Dynamic Modelling

To show how all the DC microgrid components interact at the common point, the current flowing through the main DC bus capacitor (Cdc) is expressed using Kirchhoff’s Current Law (KCL) as follows [24]
C d c d v d c d ( t ) d t = i P V ( t ) + i w ( t ) ± i b a t t ( t ) − i l o a d ( t )
where ipv, iW, ibatt and iload represent the currents from the solar PV array, the wind turbine system, the battery system and the load demand respectively. The ± sign is used with the battery current to show its bidirectional operation. By multiplying this current equation by the DC bus voltage vdc(t), the current terms are converted into power terms, providing the DC bus voltage dynamic equation as:
d v d c d ( t ) d t =   1 C d c v d c d ( t )   P n e t   ±   P b a t t  
Here, Pnet(t) is the net power mismatch calculated by the system as Pnet (t) = PPV(t) + PW (t) − PLoad (t). The battery power term Pbatt (t) is positive (+Pbatt) when the battery is charging during a power surplus, and it is negative (−Pbat) when the battery is discharging to feed the DC bus during a power deficit.
From this equation, it can be concluded that the common DC bus voltage can be regulated and kept stable by maintaining a balanced power flow between the renewable sources, load demand, and battery system. This power balance is the main reason for using the proposed power management strategy explained in the next section, which automatically works with the inner PI loops to adjust the battery power (Pbatt) and offset any power imbalances, keeping the bus voltage at its reference value.

3.6. Power Management Strategy (PMS)

The power management strategy (PMS) operates at the system level to maintain a continuous balance between the generated power and the load demand across the 24 V DC bus. This strategy translates system-level power differences into a localized current reference (Iref_PI) for the battery control loops, eliminating the need for high-bandwidth communication lines. As shown by the control flowchart in Figure 8, the algorithm first reads the measured system variables: the common bus voltage (Vbus), battery operating current (Ibatt), PV array voltage and current (Vpv, Ipv), wind energy system voltage and current (Vw, Iw), total load current (Iload), and battery state of charge (SoC). Using these measured inputs, the individual power values for the solar PV system (PPV), wind system (PW), and consumer load demand (PLoad) are computed. The net power mismatch (Pnet) is evaluated at each simulation step using the following equation:
P n e t t = P p v ( t ) + P w ( t ) − P l o a d ( t )
Figure 8. Flowchart of the power management strategy.
To maximize the operating lifespan of the storage units and prevent battery degradation, the algorithm regulates the converter tracking commands by bounding the electrochemical limits between SoCmin = 20% and SoCmax = 80%.
When the hybrid renewable subsystems generate a power surplus (Pnet > 0) and the battery capacity is below its upper limit (SoC < SoCmax), the converter operates in buck mode with a positive current tracking reference (Iref_PI} > 0) to charge the battery up to the safe continuous charging limit enforced by the Battery Management System. If the battery state of charge (SoC) reaches its maximum safety limit (SoC ≥ 80%), charging is stopped to prevent cell damage, and power curtailment is executed by applying the PMS control command (Dump_Cmd) to trigger the chopper-controlled dynamic braking resistor (Dump Load), which is connected across the common DC bus.
Conversely, during periods of generation deficit (Pnet < 0), the converter shifts operational modes based on the available storage capacity. When the capacity exceeds the minimum threshold (SoC > SoCmin), the converter shifts to boost mode, producing a negative current reference (Iref_PI < 0) to supply power to the common DC bus and maintain bus voltage stability. When a power deficit occurs and the battery level falls below its threshold value (SoC ≤ 20%), discharging operations are stopped to protect the battery, and emergency load-shedding is initiated to restore system equilibrium. By continuously monitoring these variables, the power management strategy decides the appropriate operational mode of the converter, ensuring a stable power balance and reliable voltage regulation across the common DC bus.

4. Simulation Results and Discussion

The effective operation and dynamic behaviours of the proposed standalone rural DC microgrid are evaluated and validated through detailed simulations executed within the MATLAB/Simulink environment. The performance assessment is based on verifying the tracking accuracy of the maximum power point tracking (MPPT) loops; the regulation of the common DC bus voltage (Vbus); and the continuous active power balance between the hybrid renewable generation sources, the battery energy storage system (BESS), and the variable load demands. The system is validated with the proposed control and supervisory power management strategy (PMS) through simulation tests by following two operating scenarios that represent the realistic stress levels and disturbance conditions within the DC microgrid system.

4.1. Simulation Configuration and Meteorological Data

To evaluate the operational performance of the proposed hierarchical control framework, high-resolution empirical environmental datasets are integrated directly into the MATLAB/Simulink microgrid model. The meteorological profiles are sourced from the CSPS ESMAP Tier 2 monitoring station (ID: CSPS.MT.14.219) located at Mehran University of Engineering and Technology in Jamshoro, Pakistan (25.4134° N, 68.2595° E) Within this data acquisition infrastructure, solar irradiance (G) is recorded using a CSPS Twin-sensor Rotating Shadow band Irradio-meter (RSI) and cross-verified by a Kipp & Zonen CMP10 pyranometer for high-precision Global Horizontal Irradiance (GHI) tracking. Concurrently, the localized wind speed (vwind) is captured via an NRG #40C anemometer mounted on a 10 m meteorological mast. All sensor data streams are synchronized and logged using a centralized Campbell Scientific CR1000 data logger. This specific geographical region is characterized by considerable microclimatic variability, resulting in rapid fluctuations in the solar irradiance (G) and localized wind speed (vwind). By incorporating these real-time recorded environmental data profiles into MATLAB/Simulink and integrating them into the DC microgrid model, the renewable conversion stages are continuously subjected to varying input conditions, enabling the evaluation of the proposed power management and coordinated control strategy under realistic conditions.

4.2. Real-Time Metrological Input Profiles

The validation and simulation analysis of the proposed developed standalone rural DC microgrid begins with a performance assessment under real-time metrological input profiles governing the primary renewable power generation. To confirm the system’s complete resilience in real-time conditions, the simulation model utilizes field-measured real-time meteorological profiles. In this regard, the time-varying input profiles of solar irradiance (G) and wind speed (vwind) are applied over the specified 10 s time-compressed execution window as shown in Figure 9. These signals are utilized to replicate realistic changing renewable conditions for the operation of standalone rural DC microgrids.
Figure 9. Real-time meteorological profiles: (a) solar irradiance profile, (b) wind speed profile.
The ambient solar irradiance profile presents a smooth, parabolic trajectory, reflecting clear-sky daytime transitions over the 10 s window, as shown in Figure 9a. The profile starts at an initial value of 200 W/m2 at t = 0 s and increases gradually with the increase in intensity during daytime. It peaks at t = 5 s, with an irradiance of 1015 W/m2 that exactly provides the maximum available energy for the solar PV conversion stage. After this peak, the irradiance drops gradually and reaches to 100 W/m2 by t = 10 s. This large variation tests the maximum power point tracking (MPPT) speed of the PV boost converter under both rapid ramp-up and ramp-down conditions.
The wind resource introduces highly volatile, rapid, and non-linear aerodynamic changes to the system, as shown in Figure 9b. Unlike the smooth solar curve, the wind speed fluctuates continuously throughout the entire profile. It starts at a maximum value of 12.25 m/s at t = 0 s, drops sharply to 11.45 m/s within the first half-second, and spikes back to 11.65 m/s at t = 1 s. The trajectory reflects the variation that decreases over the next few seconds down to a local minimum of 10.0 m/s at t = 2.5 s, followed by an acute drop to a minimum of 9.85 m/s at t = 6.4 s. During the final phase, the wind speed returns with high fluctuations, climbing back to 11.15 m/s at t = 9.5 s and closing at 10.8 m/s at t = 10 s. This severe turbulence provides a rigorous baseline to verify the mechanical-to-electrical tracking efficiency of the wind turbine generator.

4.3. Scenario I: Performance Analysis Under Continuous Resource Volatility and Nominal Demand

Under this operating scenario, the actual electrical power outputs from the solar PV array, wind turbine system, and battery storage unit are evaluated under a steady nominal load profile using the above-mentioned environmental resources. This enables the analysis of how the various generation subsystems transform unprocessed environmental inputs into controlled electrical energy to meet load demands. By subjecting the DC microgrid to these synchronized meteorological variations, the evaluation confirms the control system’s capability to manage real-time source–storage power coordination while keeping the common DC bus voltage stable under continuous resource volatility.

4.3.1. Solar PV Output Power

The output power of solar PV is closely aligned with the parabolic shape of the ambient irradiance profile, as shown in Figure 10a. At t = 0 s, the solar PV output power starts at 120 W; then, it increases smoothly as the maximum power point tracking (MPPT) loop responds to increasing sunshine. The PV array produces its maximum power of 605 W at exactly t = 5 s, which corresponds to the time at which the irradiance is at a maximum. After this peak, the power output falls during the afternoon ramp-down phase, reaching 150 W at t = 9 s and closing on 60 W at t = 10 s. The presented smooth power curve, without any oscillations, demonstrates the PV converter’s accurate tracking of the clear-sky power resource variation without numerical chattering.
Figure 10. Real-time renewable power generated profiles: (a) solar PV power, (b) wind power.

4.3.2. Wind Power Generated

The wind generation profile introduces highly fluctuating, non-linear electrical power variations into the DC microgrid, as shown in Figure 10b. The tracking loop begins with a peak power generation of 490 W at t = 0 s, which corresponds to the initial high wind speed value of 12.25 m/s. In response to turbulent wind input, the generated power decreases swiftly to 360 W at t = 0.5 s before increasing again to 390 W at t = 1 s. The profile shows continuous rapid variations over the middle interval, dropping to a local minimum of 200 W at t = 2.5 s and hitting its lowest tracking point of 200 W at t = 6.4 s. In the final seconds, the wind power recovers through a series of sharp steps, climbing to 340 W at t = 9.5 s before closing the window at 295 W. This rapid tracking response validates the dynamic performance of the generator’s rotor-side controller under turbulent conditions.

4.3.3. DC Bus Voltage Stability Under Continuous Resource Volatility

In this operating scenario, the real-time effectiveness of the proposed control architecture and power management strategy can be clearly illustrated in the response of the DC bus voltage profile, as shown in Figure 11. In the initial part of the simulation, the system experiences an instantaneous load connection of 850 W at the start (t = 0 s), as observed in Figure 12 The momentary transient drop is caused by this sudden step-change in load demand that is required in order to satisfy the immediate current demand, though only lasts for a fraction of a second as the physical capacitors discharge. The action of the PI voltage controller is very fast, while the DC bus voltage recovers completely within 0.2 s with very little undershoot and stabilizes very well to the 24 V reference, as seen in Figure 11. The common DC bus will undergo a potential voltage sag at t = 1 s when the wind power generated sharply decreases from 490 W to 260 W, as illustrated in Figure 10b. As seen in Figure 11, there is no power disturbance in any way in this case. The outer loop immediately changes the reference current (Iref) of the inner loop and, consequently, the bidirectional converter discharges the battery forcefully. As a result, the voltage on the bus stays stable, and the control loop is successful in decoupling the variation in resources from the load side. In the mid interval’s high-penetration period, from 4 s to 5 s, the output power of the solar PV gradually increases to its maximum of 600 W, as seen in Figure 10a. With these higher increases in renewable power generation, the microgrid is brought closer to a surplus state, thus decreasing the battery discharge dependency to just 110 W (see Figure 13). These huge power variations can also cause steady-state drifting or voltages in poorly managed DC microgrids, as seen from a voltage stability point of view. However, in this system, the amplitude of the DC bus voltage is very stable, and only increases slightly and controllably by less than 0.3 V, rising to approximately 24.3 V between t = 4 s and t = 6 s. This tight voltage regulation allows the bidirectional converter to operate at nominal voltage levels and convert between the various depths of the battery’s shortfall mode. The DC microgrid experiences its most severe stress test after t = 7 s. As seen in Figure 10b, the solar PV output power falls sharply by more than 90% (from 580 W to 50 W), requiring the battery power to ramp upward with a steep positive slope to 510 W, as seen in Figure 13. Hence, the voltage profile shows remarkable resilience despite the significant dP/dt stress applied to the common DC bus during this late phase. A minor controlled droop is observed, with the voltage shifting smoothly from 24.2 V down to approximately 23.6 V at t = 10 s. This total deviation remains well within a less than 2% operational tolerance band (23.52 V–24.48 V), satisfying the most high-power quality standards for standalone low-voltage DC microgrids, as shown in Table 2.
Figure 11. DC bus voltage during Scenario I.
Figure 12. Load Power during Scenario I.
Figure 13. Battery power during Scenario I.
Table 2. Dynamic performance metrics for DC bus voltage stability during Scenario I.

4.3.4. Battery State-of-Charge (SoC) Management Under Continuous Resource Volatility

The battery storage system’s dynamic trajectory and real-time capabilities are monitored across the 10 s operational profile, as shown in Figure 14. As the battery continuously discharges to cover the microgrid’s power deficits, the curve exhibits a smooth, steady decline that aligns with and closely tracks the load demand. At the start of the cycle, the battery begins at a nominal charge state of 55.00%. As the microgrid is driven by the initial high load demand and the sudden drop in wind generation at t = 1 s, the battery discharges heavily. This is marked by a clear, steep linear downward slope, with the SoC dropping steadily to 54.98% by t = 3 s. The solar PV generation increases towards its parabolic peak, reducing the need for the microgrid to store energy. This change is clearly visible in the SoC curve: the rate of depletion decreases considerably between t = 3.5 s and t = 6 s. The flattening of the curve indicates that the supervisory controller is indeed reducing battery consumption when renewable energy is available, thus avoiding unnecessary cyclic stress on the cells. After the sudden decrease in solar generation at t = 7 s, the battery steps in to power the grid once again. The SoC curve again bends downward, indicating a faster drop to end the cycle at around 54.944% at the 10 s mark.
Figure 14. Battery State of Charge (SoC). during Scenario I.

4.3.5. Power Flow Management Under Continuous Resource Volatility

The system adheres to the coordinated power management rules outlined in the power balance strategy flowchart in Figure 8 in order to maintain a continuous power balance under shifting resource and demand conditions. The power flows within the entire DC microgrid operation are illustrated in Figure 15. The load demand is substantial during the first phase (t = 0 to 3 s) when the profile begins (t = 0 s), and it stabilizes at 850 W. Simultaneously, the generated wind power contributes 490 W before experiencing a sharp stochastic decline to 260 W at t = 1 s, while the solar PV output power begins at a low level of roughly 120 W. A power deficit (Pnet < 0) results from the combined renewable generation (610 W at t = 0 s and 510 W at t = 1 s) not meeting the load demand. This condition is effectively identified by the supervisory controller, which then compels the battery system to enter the deficit mode (Boost Discharging Mode). In order to maintain system equilibrium, the battery power instantly grows to 350 W, offsetting the decline in wind generation and smoothly filling the net power gap. During this intermediate operating stage (t = 3 to 7 s), the output power of the solar PV exhibits a typical parabolic ramping curve up to a maximum of 600 W around t = 5 s. Meanwhile, there are small fluctuations in wind power generation, contributing approximately 230 W.
Figure 15. Power flows within DC MG.
The total renewable generated power is at its peak around t = 5 s, with the total power reaching about 830 W, which is very close to the load power demand of 880 W. The energy storage element discharge rate is reduced by the inner-current control loop in response to this reduced net mismatch. The battery power gradually decreases to a local minimum at t = 4 s, which is about 110 W. Together with the dynamic conversion and switching losses, as well as the high-current line drops (~60 W) present in a practical 24 V low-voltage DC distribution network, this combined power injection effectively meets the 880 W load requirement. This precise modulation verifies the controller’s ability to optimize the use of renewable resources and meet load demand and internal losses without exceeding the battery unit limits, thus reducing unnecessary stress.
After t = 7 s, solar irradiation drastically decreases. The PV output power decreases drastically from 580 W to 50 W at t = 10 s, while the wind power changes moderately, increasing slightly from 200 W to 280 W. This severe decline in renewables power generation creates an increasing net power deficit. To prevent a catastrophic collapse of the common DC bus voltage, the bidirectional DC-DC converter quickly reverses its downward trend. The battery power starts at 180 W at t = 7 s and increases rapidly to 510 W at t = 10 s. This continuous, highly coordinated resource dispatch in all three operating modes therefore proves that the proposed coordinated control framework and power management strategy is effective and stable enough to ensure real-time power balance for the system, ultimately achieving the desired power balance necessary to ensure the stability of the common DC bus voltage.

4.4. Scenario II: Performance Validation Under Severe Step-Load Perturbations

The real-time power coordination between the generation sources, load network, and energy storage system under sudden step-load perturbations, as given in Figure 16, is evaluated across a 10 s window. Because the renewable profiles (PPV and PW) are kept identical to Scenario I, the entire trajectory highlights the battery converter’s speed and bidirectional flexibility in balancing sudden load changes.
Figure 16. Load power during Scenario II.

4.4.1. Power Flow Management Under Severe Step-Load Perturbations

In this operating scenario, the power flows within the DC microgrid are illustrated in Figure 17. During the initial phase (t = 0 to 3 s), the load power begins at a high demand of 800 W and gradually decreases to about 460 W at t = 3 s. The battery effectively compensates for the generation shortfall by discharging in boost mode, with its power output tracking downward from 330 W to 250 W. At t = 3.0 s, the system is subjected to a step-down load disturbance, instantly reducing demand from 460 W to 300 W (ΔPLoad ~160 W). To prevent transient bus overvoltage, the inner-current control loop reacts within a sub-millisecond dynamic limit, throttling the battery discharge power from 250 W to 50 W. During the mid interval (t = 3 to 7 s), the total renewable energy generation greatly exceeds the low 300 W load as solar generation approaches its parabolic peak of 600 W near t = 5 s. At t = 4 s, the battery power smoothly shifts from discharging (boost) mode to charging (buck) mode at t = 4 s, transitioning into a negative power flow (charging mode) (−20 W).
Figure 17. Power flows within DC MG during Scenario II.
At t = 6 s, the load demand drops to its minimum of 100 W against 840 W total generation, creating a net peak surplus of 740 W. Under PMS regulation, the battery absorbs power up to its safe 150 W BMS continuous charging cap in Buck Charging Mode (Iref_PI > 0, verified by ∆SoC > 0), while the remaining excess power (590 W) is dissipated via the PMS command (Dump_Cmd) through the chopper-controlled dynamic braking resistor to ensure nodal energy balance (P = 0) and maintain DC bus voltage stability at 24 V. During the step-up recovery and final ramping (t = 7 to 10 s), a step-up load perturbation occurs, with the demand increasing from 120 W to 200 W at t = 8 s. In response to the abrupt rise in load, the battery rapidly changes its power from −50 W to −100 W and lowers its charging rate. In the last two seconds (t = 8 to 10 s), as solar generation drops sharply to 50 W and the load ramps back up to 370 W, the battery smoothly crosses back over into a positive territory, discharging at 80 W by t = 10 s to maintain the power balance within the DC microgrid system.

4.4.2. DC Bus Voltage Stability Under Severe Step-Load Perturbations

The common DC bus voltage response, as shown in Figure 18, is used to evaluate the structural stability and disturbance-rejection characteristics of the proposed control framework. During the initial high-demand phase (t = 0 to 3 s), as given in Figure 19, the massive current drawn by the load causes a standard voltage drop across the line resistance. The outer-voltage loop is able to maintain the bus voltage from 23.7 to 23.8 V and stabilizes the operation. This limits the maximum lower deviation to only −1.67% from Vref, which is the nominal setting of the reference voltage of 24 V. This behaviour is effectively stabilized by the outer-voltage loop, which keeps the bus voltage between 23.7 and 23.8 V. This limits the maximum lower deviation to a mere −1.67% relative to the nominal 24 V reference line (Vref). At the t = 3 s and 6 s intervals, a large step-down load disturbance occurs within the system at the same time, reducing the load demand to its minimum level of 100 W, so that the abrupt relief in the current causes the common bus voltage to rapidly increase in a controlled, stepped manner to 24.5 V and 25.0 V. Importantly, the supervisory control system will only allow this worst-case transient voltage spike to reach a maximum peak of precisely 25.0 V. As the load steps back to its initial value, the bus voltage drops to 24.6 V immediately after, with a strong voltage control and transient recovery at t = 8 s. All changes remain within the standard ±5% continuous operational tolerance range, as is required by IEEE/ANSI power quality benchmarks, by rigorously confining the whole multi-step voltage trajectory between 23.6 V and 25.0 V, as highlighted in Table 3. This performance verifies that the system maintains robust voltage stability, even when subjected to extreme load fluctuations.
Figure 18. DC bus voltage during Scenario II.
Figure 19. Battery power during Scenario II.
Table 3. Dynamic performance metrics for DC bus voltage stability during Scenario II.

4.4.3. Battery State-of-Charge (SoC) Management Under Severe Step-Load Perturbations

The battery state-of-charge (SoC) response in cases of sudden load fluctuations during the 10 s testing period is analyzed, as shown in Figure 20. The response illustrates the effect on stored energy in the battery as a result of the power variations caused by sudden load variations. At the starting interval (t = 0 to 3 s), the battery initially has a charge of 55.00%. The graph slopes steadily and linearly downward to compensate for the initial power deficit, reaching 54.980% at t = 3 s. The continuous energy supply needed to maintain the power balance condition is indicated by this steady fall. This gradual decrease outlines the need for a continuous energy supply to maintain the power balance condition. After an initial reduction when the load changes at t = 3 s, the rapid reduction stops. The SoC curve levels off at the zero-Watt mark when the battery charge goes down from t = 3.5 s to t = 6 s. This behaviour validates that the system stops battery discharge when the generation equals the local load. The SoC curve shows an increase when the second step-down load drop occurs at t = 6 s, creating a power surplus condition. The state of charge rises from 54.979% to 54.984% at t = 9 s. This evident increase confirms that the system receives the surplus renewable energy to charge the battery. As the load is again increased, the curve smoothly returns to a smaller discharge path, ultimately reaching 54.983%. This smooth and coordinated transition over all three intervals validates that the charging loops perform well under sudden load shocks while maintaining the protection of the storage system’s deep cycles.
Figure 20. Battery state of charge during Scenario II.

5. Conclusions and Future Work

This study has proposed a coordinated control-based power management strategy for a hybrid solar–wind–battery integrated standalone DC microgrid for reliable rural electrification. The results showed that the proposed control architecture exhibited a superior performance in stabilizing the bus voltage during acute transient disturbances and severe step load disturbances. The power management control layer handled the power transitions in a smooth, non-oscillatory manner during both charging and discharging cycles, all whilst maintaining careful control of the battery SoC across the various power transitions to avoid the possibility of deep depletion and promote energy recovery during periods of power surplus. Despite the promising dynamic results and optimal performance achieved through classical gain tuning, future extensions of this work will explore advanced optimization algorithms to further enhance system efficiency, power-sharing coordination, battery utilization, and adaptive controller tuning under highly variable operating environments. Furthermore, real-time experimental validation of the proposed control architecture may be investigated to assess its effectiveness for practical applications.

Author Contributions

S.H.M.: Conceptualization, Data curation, Formal analysis, Investigation, Methodology, Software, Validation, and Writing—original draft preparation. P.H.S.: Writing—review and editing, Supervision, Resources, Formal analysis, and Validation. Z.A.M.: Writing—review and editing, Supervision, Resources, Validation, and Project administration. M.A.U.: Writing—review and editing, Supervision, Resources, and Project administration. M.I.M.: Writing—review and editing, Funding, and Validation. T.A.J.: Writing—review and editing and Validation. All authors have read and agreed to the published version of the manuscript.

Funding

There is no external funding acquired for this article.

Data Availability Statement

The data supporting the findings of this study were obtained from sensor-based measurements collected at Mehran University of Engineering and Technology. These data are the exclusive property of Mehran University of Engineering and Technology and are subject to institutional ownership and confidentiality restrictions. Therefore, the datasets are not publicly available and cannot be shared due to privacy and proprietary considerations. Researchers interested in the data may contact the corresponding author; however, access is subject to approval by Mehran University of Engineering and Technology and compliance with the University’s data-sharing policies.

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Gyani, R.; Chandel, S.S. A Comprehensive Assessment of Measures for Enhancing Access to Electricity through Decentralised Solar Mini Grids in Remote Regions of Sub-Saharan Africa, Latin America, and Asian Countries Including India. Next Res. 2025, 2, 100963. [Google Scholar] [CrossRef] [Scilit]
  2. Mosetlhe, T.; Yusuff, A.; Ayodele, T.; Ogunjuyigbe, A. Sustainable Rural Electrification through Micro-Grids in Developing Nations—A Review of Recent Development. Energy Rep. 2025, 13, 1171–1177. [Google Scholar] [CrossRef] [Scilit]
  3. Ihammouchen, S.; Chebabhi, A.; Ziane, D.; Rekioua, T.; Benkhoris, M.F.; Belkhier, Y.; Bajaj, M.; Rubanenko, O. A Nonlinear Observer-Based Control Strategy for Hybrid Energy Storage Systems to Improve Voltage Disturbance Rejection in DC Microgrids. Sci. Rep. 2026, 16, 1253. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  4. Gugulothu, R.; Nagu, B.; Pullaguram, D. Energy Management Strategy for Standalone DC Microgrid System with Photovoltaic/Fuel Cell/Battery Storage. J. Energy Storage 2023, 57, 106274. [Google Scholar] [CrossRef] [Scilit]
  5. Ballal, M.S.; Verma, S.R.; Suryawanshi, H.M.; Deshmukh, R.R.; Wakode, S.A.; Mishra, M.K. An Improved Voltage Regulation and Effective Power Management by Coordinated Control Scheme in Multibus DC Microgrid. IEEE Access 2022, 10, 72301–72311. [Google Scholar] [CrossRef] [Scilit]
  6. Tabe, A.; Noroozian, R.; Shayestefard, A.; Eskandari, A. Standalone Operation of Isolated DC Microgrid Based on PV Unit by Hybrid Energy Storage System. J. Energy Storage 2026, 155, 121328. [Google Scholar] [CrossRef] [Scilit]
  7. Sharma, J.; Sundarabalan, C.K.; Balasundar, C. Advanced Energy Management Strategy for Enhancing Battery Lifespan in Solar PV-Powered EV Charging Stations with Hybrid Energy Storage Systems. Renew. Energy 2025, 251, 123443. [Google Scholar] [CrossRef] [Scilit]
  8. Eltamaly, A.M.; Almutairi, Z.A. A Novel Star-Nosed Mole Optimization Algorithm Applied for MPPT of PV Systems. Sci. Rep. 2025, 15, 17807. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  9. Fathabadi, H. Novel High-e Ffi Cient Large-Scale Stand-Alone Solar/Wind Hybrid Power Source Equipped with Battery Bank Used as Storage Device. J. Energy Storage 2018, 17, 485–495. [Google Scholar] [CrossRef] [Scilit]
  10. Eltamaly, A.M. A Novel Musical Chairs Algorithm Applied for MPPT of PV Systems. Renew. Sustain. Energy Rev. 2021, 146, 111135. [Google Scholar] [CrossRef] [Scilit]
  11. Pradhan, S.; Singh, B.; Panigrahi, B.K.; Murshid, S. A Composite Sliding Mode Controller for Wind Power Extraction in Remotely Located Solar PV–Wind Hybrid System. IEEE Trans. Ind. Electron. 2019, 66, 5321–5331. [Google Scholar] [CrossRef] [Scilit]
  12. Ashokkumar, A.; Amutha Prabha, N. Energy Management Strategy for Photovoltaic, Fuel Cell, Battery, and Super Capacitor in Standalone Direct Current Microgrid System. J. Energy Storage 2026, 144, 119600. [Google Scholar] [CrossRef] [Scilit]
  13. Mutlag, A.A.; Abd, M.K.; Shneen, S.W. Power Management and Voltage Regulation in DC Microgrid with Solar Panels and Battery Storage System. J. Robot. Control (JRC) 2024, 5, 397–407. [Google Scholar] [CrossRef] [Scilit]
  14. Suresh Babu, G.V.; Mariprasath, T.; Khadarvali, S.; Reddy, C.H.; Amaresh, K. Autonomous Load Sharing Technique in Solar Photovoltaic System-Based DC Microgrid. Int. J. Ambient Energy 2022, 43, 1677–1684. [Google Scholar] [CrossRef] [Scilit]
  15. Wang, C.; Duan, J.; Fan, B.; Yang, Q.; Liu, W. Decentralized High-Performance Control of DC Microgrids. IEEE Trans. Smart Grid 2018, 10, 3355–3363. [Google Scholar] [CrossRef] [Scilit]
  16. Ding, X.; Wang, W.; Zhou, M.; Yue, Y.; Chen, Q.; Zhang, C.; Tang, X.; Li, J. Feedback Control Strategy for State-of-Charge Balancing and Power Sharing between Distributed Battery Energy Storage Units in DC Microgrid. IET Power Electron. 2023, 16, 1063–1076. [Google Scholar] [CrossRef] [Scilit]
  17. Mazumdar, D.; Guerrero, J.M.; Thakkar, N.; Anand, R.; Sain, C.; Ustun, T.S. A Sustainable Power Management Solution Integrated with Fuel Cell Based Hybrid Energy Storage System in Variable Climate Conditions. Renew. Energy Focus 2026, 57, 100797. [Google Scholar] [CrossRef] [Scilit]
  18. Parida, A. Stand-Alone AC-DC Microgrid-Based Wind-Solar Hybrid Generation Scheme with Autonomous Energy Exchange Topologies Suitable for Remote Rural Area Power Supply. Int. Trans. Electr. Energy Syst. 2018, 28, e2520. [Google Scholar] [CrossRef] [Scilit]
  19. Varghese, A.; Chandran, L.R.; Rajendran, A. Power Flow Control of Solar PV Based Islanded Low Voltage DC Microgrid with Battery Management System. In Proceedings of the 2016 IEEE 1st International Conference on Power Electronics, Intelligent Control and Energy Systems (ICPEICES); IEEE: Piscataway, NJ, USA, 2016; pp. 1–6. [Google Scholar]
  20. Tah, A.; Das, D. An Enhanced Droop Control Method for Accurate Load Sharing and Voltage Improvement of Isolated and Interconnected DC Microgrids. IEEE Trans. Sustain. Energy 2016, 7, 1194–1204. [Google Scholar] [CrossRef] [Scilit]
  21. Anand, S.; Fernandes, B.G.; Guerrero, J.M. Distributed Control to Ensure Proportional Load Sharing and Improve Voltage Regulation in Low-Voltage DC Microgrids. IEEE Trans. Power Electron. 2013, 28, 1900–1913. [Google Scholar] [CrossRef] [Scilit]
  22. Villalva, M.G.; Gazoli, J.R.; Filho, E.R. Comprehensive Approach to Modeling and Simulation of Photovoltaic Arrays. IEEE Trans. Power Electron. 2009, 24, 1198–1208. [Google Scholar] [CrossRef] [Scilit]
  23. Ishaque, K.; Salam, Z.; Taheri, H. Simple, Fast and Accurate Two-Diode Model for Photovoltaic Modules. Sol. Energy Mater. Sol. Cells 2011, 95, 586–594. [Google Scholar] [CrossRef] [Scilit]
  24. Tighirt, A.; Aatabe, M.; El Guezar, F.; Bouzahir, H.; Vargas, A.N. Power Management and Control of a Standalone DC Microgrid with Hybrid Renewable Energy and Battery Storage under Stochastic Load Conditions. J. Energy Storage 2026, 152, 120510. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.