Resilience Assessment and Enhancement Strategy for Transmission Lines Based on Distributed Fibre Optic Sensing

,
,
and
School of Electrical Engineering and Automation, Wuhan University, Wuhan 430072, China
*
Author to whom correspondence should be addressed.

Abstract

Typhoon-induced wind loads pose severe threats to transmission systems. However, existing resilience assessment approaches typically rely on sparse meteorological station data and assume spatially uniform wind speed distributions along transmission corridors, which fail to capture the span-level spatial difference of wind fields. To address this limitation, this paper proposes a distributed optical fiber sensing (DOFS)-driven span-level resilience assessment and hardening optimization framework for transmission networks. First, a phase-sensitive optical time domain reflectometry (Φ-OTDR)-based distributed optical fiber sensing system is employed, utilizing optical fibers embedded in existing OPGW cables as sensing media. By capturing vibration responses of the fiber induced by wind–structure interaction, real-time spatiotemporal wind speed sequences at the individual span level are reconstructed through signal processing and inversion algorithms, providing high-spatial-resolution environmental input data for resilience evaluation. Second, a span-level failure probability quantification method is established using a load–strength interference model. On this basis, a resilience evaluation framework—“span-level asset damage cost—line-level critical corridor identification—system-level load shedding assessment”—is constructed, enabling cross-scale resilience quantification from component damage to system-level performance degradation. Third, a span-level gradient hardening optimization model is developed. By adopting a scenario pre-calculation and iterative updating strategy, coordinated solving of reinforcement decisions and failure scenarios is achieved, thereby maximizing resilience enhancement benefits. The proposed framework is validated using DOFS-measured wind speed data collected from a 500 kV transmission line along the Fujian coast during three real typhoon events—Typhoon Shantuo, Typhoon Trami, and Typhoon Koinu—supporting the reliability of the acquired span-level wind speed information. Case studies conducted on a modified IEEE RTS-24 system demonstrate that the proposed span-level hardening strategy can substantially reduce reinforcement cost compared with the conventional line-level hardening strategy. In the reported benchmark case, it achieves zero load-shedding penalty with a markedly lower hardening cost, and under the same budget constraint, it further yields lower expected load shedding and lower expected asset damage.

1. Introduction

In recent years, climate change has led to an increasing frequency and intensity of extreme weather events, among which typhoons have become a major threat to power system operation. Typhoon-induced disturbances such as conductor galloping, abnormal mechanical stress on transmission towers, and insulation degradation can significantly compromise system security and operational stability. As a critical infrastructure responsible for long-distance electricity delivery, transmission networks span extensive geographical regions and are highly exposed to environmental disturbances. Once large-scale line outages or tower collapses occur, the resulting cascading effects may cause substantial economic losses [1]. For example, in August 2019, Typhoon Lekima made landfall in Zhejiang Province, China, leading to the shutdown of 72 substations rated at 35 kV and above across five provinces and municipalities, with reported economic losses exceeding CNY 50 billion [2]. To address the impact of low-probability but high-consequence extreme events, the concept of power system resilience has been introduced to characterize the system’s capability to withstand, absorb, adapt to, and recover from disturbances. Notably, resilience exhibits dynamic behavior due to topology changes and operational adjustments following component failures [3]. Given the growing exposure of transmission networks to extreme weather conditions such as typhoons, enhancing transmission system resilience has become an urgent requirement to ensure reliable and continuous power supply.
Extensive efforts have been devoted to resilience assessment of power grids under typhoon hazards, and most existing studies start from hazard input modeling. Ref. [4] used physical or empirical typhoon wind field models to simulate wind speed distributions in affected areas. In [5], the Batts model was adopted to establish a planning-oriented resilience assessment framework for transmission systems, and the impact of typhoons was analyzed from a spatiotemporal vulnerability perspective. Ref. [6] further combined the Batts model with a data-driven method and evaluated corridor-level cumulative failure rates by discretizing the study region into grids. As noted in [7], different spans within the same transmission line may experience substantially different wind speed histories because of spatial heterogeneity and the temporal evolution of typhoon movement. Ref. [8] showed that wind speed estimation based on meteorological stations or regional radar and satellite inversion cannot accurately capture the actual wind exposure of transmission lines under near-field and terrain-crossing conditions. Ref. [9] also indicated that numerical simulation, although capable of describing typhoon structure and evolution, is highly sensitive to boundary conditions and parameter settings and cannot substitute for along-line measurements. Existing hazard input models therefore remain largely limited to regional, grid, or corridor scales, which constrains their ability to support span-level resilience analysis.
The use of distributed optical fiber sensing (DOFS) in transmission line monitoring has expanded rapidly in recent years. In [10], distributed optical fiber sensing can achieve continuous measurement of strain, vibration, temperature, and other physical quantities along the line through Rayleigh, Brillouin, and Raman scattering, while also offering long-distance coverage, immunity to electromagnetic interference, and strong compatibility with OPGW. Ref. [11] demonstrated the applicability of phase-sensitive optical time-domain reflectometry (Φ-OTDR) to transmission line vibration monitoring. In [12], Φ-OTDR-based distributed sensing was further applied to the identification of external disturbances affecting transmission lines. These studies verified the engineering feasibility of DOFS for online and continuous transmission line monitoring. Their focus, however, has been placed mainly on condition identification and abnormal event warning. The conversion of DOFS observations into span-level spatiotemporal wind speed series that can directly support resilience assessment has received far less attention.
Related studies on failure modeling and resilience assessment have already examined the influence of extreme wind hazards on transmission systems from multiple levels. Ref. [13] adopted load loss as the resilience metric and minimized load loss under extreme weather through hardening actions. Ref. [14] improved the survivability of an integrated electricity-gas energy system during earthquakes and reduced multi-energy load loss through hardening measures. Ref. [15] investigated the expected load loss of transmission networks under compound natural hazards and used the results to support hardening decisions. At the component scale, ref. [16] pointed out that the probability of line damage increases with the number of spans in a transmission line, while [17] showed that significant load imbalance may arise between adjacent spans under ice storms because of differences in elevation, span length, and exposure. These findings suggest that current methods are already capable of evaluating system-level consequences, yet the span has not been fully treated as the fundamental hazard-bearing unit. In most cases, span-related factors are incorporated only as influencing parameters rather than being explicitly modeled as the core unit of resilience assessment and optimization. Resilience enhancement studies have mainly focused on line-level or corridor-level hardening strategies. Ref. [18] classified resilience improvement measures for new-type power systems under typhoons and other extreme natural hazards into pre-disaster prevention, in-disaster emergency response, and post-disaster recovery. Ref. [19] identified network hardening as an effective approach for improving disaster resistance and resilience. As reported in [20], most current hardening decisions still follow a coarse-grained strategy in which an entire transmission line is either reinforced or not reinforced. Ref. [21] further showed that local terrain conditions can significantly affect wind profile distributions within transmission corridors at the microscale. Ref. [22] emphasized that, under limited hardening resources, failure to identify and prioritize truly high-risk sections may lead to unnecessary costs and inefficient resource allocation. A critical gap therefore remains in developing differentiated hardening strategies based on span-level wind exposure heterogeneity and in integrating such strategies with span-level failure probabilities and multiscale resilience metrics within a unified framework.
In summary, most existing resilience assessment studies for transmission systems rely on wind speed indicators defined at the line or corridor level, which are insufficient to accurately characterize the near-field wind exposure conditions along transmission routes. Such approaches overlook the spatial heterogeneity among individual spans and fail to capture the influence of terrain variability and localized environmental factors on wind-induced loading. Meanwhile, current resilience enhancement strategies predominantly adopt reinforcement decisions at the corridor scale, without identifying high-risk spans within transmission lines. This coarse-grained decision paradigm may lead to inefficient allocation of limited reinforcement resources and reduced effectiveness of operation and maintenance investments. As a result, the resilience improvement achieved through conventional planning strategies may not fully reflect the actual spatial vulnerability distribution of transmission assets.
In order to address the above shortcomings, this paper makes the following contributions:
(1) Instead of relying on parameterized typhoon wind field models, meteorological station interpolation, or corridor-scale wind speed assumptions as in conventional resilience studies, this work employs a Φ-OTDR-based distributed optical fiber sensing system deployed on existing OPGW to construct span-level spatiotemporal wind speed inputs for resilience assessment, thereby extending the role of DOFS from transmission line condition monitoring to resilience-oriented input generation.
(2) Rather than taking transmission lines or corridors as the primary analysis units, this paper develops a failure probability model driven by span-level wind loads and the load–strength interference relationship. On this basis, a multiscale resilience assessment framework is further established, linking span-level asset loss, line-level critical corridor identification, and system-level load shedding, thereby forming an integrated analytical chain from local wind exposure heterogeneity to system-wide consequences.
(3) To mitigate inefficient resource allocation in traditional corridor-level reinforcement planning, a resource-constrained span-level resilience enhancement model is developed to optimally distribute strengthening measures among heterogeneous risk spans and maximize resilience improvement benefits.

2. Distributed Fibre Optic Wind Measurement for Span-Level Typhoon Monitoring

The wind sensing system adopted in this study consists of the optical ground wire (OPGW) deployed along the transmission line and a phase-sensitive optical time-domain reflectometer (Φ-OTDR) interrogator. The wind speed reconstruction process based on the DOFS system combines distributed vibration sensing with the Kármán vortex street principle, thereby establishing a complete workflow from optical signal acquisition to span-level wind speed inversion. The overall procedure can be summarized as follows. First, the Φ-OTDR interrogator continuously acquires Rayleigh backscattering signals along the optical fiber embedded in the OPGW. In the present field deployment, the sensing wavelength is 1550 nm. The spatial resolution and sampling frequency depend on the monitoring distance; in this study, the system is operated with a spatial resolution of 16 m and a sampling frequency of 750 Hz. Under wind excitation, transmission line vibration induces dynamic strain in the fiber, which causes corresponding phase variations in the backscattered optical signals. Second, the raw Φ-OTDR vibration signals are processed in a span-by-span manner. Specifically, the original vibration response is first converted into span-level vibration spectra through signal segmentation according to tower positions and span boundaries. The signals are then preprocessed by noise filtering, baseline correction, and normalization to improve the signal-to-noise ratio. After that, spectral separation is performed to identify the narrow-band spectral components associated with Kármán vortex shedding within the span-level vibration spectra. Physically, these components correspond to the vortex-induced vibration response generated by the alternate shedding of Kármán vortices in the wake of the cylindrical conductor/OPGW under crosswind excitation, rather than arbitrary high-frequency fluctuations or measurement noise [23]. Such vortex-induced vibration is a nearly pure transverse (cross-wind) response that arises whenever the flow around the conductor lies in the subcritical Reynolds-number regime, within which coherent Kármán vortex shedding persists and the Strouhal relation remains valid [24]. Under low-to-moderate wind speeds on the order of 0.5–7 m/s, aeolian vibration is most pronounced and produces sharp narrow-band peaks with antinode amplitudes bounded by the conductor diameter [25]. Field observations have further shown that aeolian vibration is clearly distinguishable from galloping and sub-span oscillation in both frequency and amplitude, and that the spectral peaks become broader at higher wind speeds because of increased atmospheric turbulence and shorter spanwise coherence length [26]. The corresponding components therefore remain physically meaningful and are retained in the inversion. Among the retained components, the dominant spectral peak—or equivalently the central frequency of the dominant narrow-band cluster—is extracted for each span and denoted as the characteristic vortex-shedding frequency f c . Third, based on the Kármán vortex street principle, the extracted dominant vibration frequency is mapped to the mean wind speed through the Strouhal relationship. When airflow interacts with a cylindrical conductor, alternating vortices are shed periodically from the leeward side of the conductor, generating a characteristic shedding frequency. According to the Strouhal principle, the relationship among the vortex-shedding frequency f s , the wind speed v , and the conductor diameter d can be expressed as f s = v d S t , and equivalently v = f c d S t , where S t is the dimensionless Strouhal number and f c is the characteristic vortex-shedding frequency extracted above. For stranded transmission-line conductors throughout the subcritical Reynolds-number range, S t remains essentially constant at approximately 0.2 [23]. In this study, S t is accordingly taken as 0.2, which is applicable across the full wind-speed span encountered in the field measurements, including samples above 10 m/s. The spectral dispersion of the identified peak is retained as an auxiliary descriptor of peak broadening at higher wind speeds. Possible lock-in effects are also noted when the extracted characteristic frequency is close to a known span natural mode [24]. Accordingly, once the dominant vortex-shedding-related spectral component is identified from the span-level vibration spectrum, the corresponding mean wind speed of that span can be quantitatively reconstructed.
It should be noted that, as the monitoring distance increases, the SNR at the far end of the line gradually decreases. This may affect the separation of the Kármán vortex spectrum at some spans and introduce additional noise into the reconstructed wind speed. To reduce this influence, a statistical fitting method is further adopted to smooth the inversion results and derive the 10 min mean wind speed and 10 min maximum wind speed for each span. In this way, the robustness of the inferred wind speed is improved under long-distance monitoring conditions.
Overall, this workflow establishes a clear physical linkage from the original Φ-OTDR vibration signal, to span-level vibration spectrum construction, Kármán vortex spectrum separation, feature extraction, and finally physics-based wind speed inversion. It therefore enables high-resolution reconstruction of the span-level wind field and provides reliable environmental input for the subsequent resilience assessment.
A practical issue in OPGW-based DOFS deployment is the mismatch between the fiber-length coordinate reported by the interrogator and the actual physical tower position along the transmission line. This mismatch mainly arises from three intrinsic factors, namely, the excess fiber length inside the OPGW (typically 0.3–1.0%), the catenary sag of OPGW spans between adjacent suspension towers, and the additional slack fiber stored in each fusion-splice enclosure [27]. The cumulative effect of these offsets may lead to a positioning drift approaching one full span over a 30 km route if no correction is applied.
In this study, the fiber-to-tower mapping is calibrated using the vibration-spectrum characteristics of the DOFS signal. The vibration response at tension-tower and suspension-tower locations differs significantly from that of the free-span sections because the stationary fixtures at tension towers and the suspension clamps impose strong local constraints on the OPGW, thereby suppressing the vibration amplitude [28]. Accordingly, the differential features of the vibration spectrum along the fiber are extracted to identify the characteristic amplitude drops associated with tower locations. These identified tower positions are then used as anchor points to establish a piecewise-linear mapping between fiber length and tower index, by which the effects of fiber excess length, catenary sag, and splice slack are locally absorbed. After calibration, the residual positioning error is bounded by the intrinsic spatial localization precision of the DOFS system, that is, one-half of the spatial sampling interval of the interrogator. For the system used in this study, this error is bounded by the intrinsic spatial localization precision of the system and is expected to be below 1 m under the present configuration, which is negligible compared with the typical span length of 300–500 m. Therefore, all subsequent load events considered in this study are referenced to calibrated tower positions rather than raw fiber-length coordinates.
The distributed optical fiber–based wind monitoring system adopted in this study has been deployed and tested on transmission lines located in typhoon-prone coastal areas of Fujian Province, China. The optical fiber sensing system was installed at the 500 kV Ziling Substation by the Information and Communication Branch of State Grid Fujian Electric Power Co., Ltd., Fuzhou, China. The monitoring infrastructure includes optical ground wire (OPGW) spanning from Tower #1 to Tower #69 along the transmission corridor. The system has been in continuous operation since September 2024, enabling real-time monitoring of the dynamic impacts of typhoons on transmission lines. To satisfy the data accuracy requirements of resilience assessment, wind-related measurements for each span are sampled at 30 s intervals as the fundamental sensing unit. Subsequently, 10 min averaged values and maximum values are statistically derived to construct the final wind speed time series used for analysis. Figure 1 illustrates the span-by-span wind speed distribution recorded by the optical fiber system during Typhoon Koinu in October 2024, where the horizontal axis represents transmission spans and the vertical axes correspond to time and wind speed, respectively.
Figure 1. Wind Speed Time Evolution Diagram for Each Span of the Test Line.
To evaluate the reliability of the monitored data, the average and maximum wind speeds measured by the distributed optical fiber system for a representative span during the typhoon event were compared with the corresponding observations from the Jinjiang Meteorological Station. The comparison results are presented in Figure 2. The Jinjiang station is located in close proximity to the monitored span and shares similar geographical characteristics, both being situated in plain terrain, which provides strong reference value for comparative validation.
Figure 2. Time-dependent evolution diagram comparing wind speeds at a specific span of the test line with those at the meteorological station.
As shown in Figure 2, the temporal variation trends of the two datasets exhibit strong consistency. Minor discrepancies in magnitude can be attributed to differences in statistical aggregation intervals and localized measurement conditions. Nevertheless, the overall agreement confirms the feasibility and reliability of distributed optical fiber–based wind monitoring for transmission lines under typhoon conditions, supporting its applicability for subsequent resilience assessment and decision-making analysis.

3. Modelling and Resilience Assessment Framework for Wind-Induced Fault Rates in Transmission Span Levels Based on Distributed Fibre Optics

Based on the above distributed optical fiber technology for span-level wind speed acquisition, this study uses a Φ-OTDR system deployed on OPGW cables to achieve continuous real-time sensing of wind speed at each span along the transmission line.
A transmission system can be decomposed into three hierarchical levels: corridor, line, and span. A transmission corridor is the geographical passage connecting the busbars of two substations and corresponds to an edge in the power network topology. One corridor may accommodate multiple parallel circuits that share the same geographical route and meteorological exposure conditions. A transmission line is a single circuit within the corridor, representing a complete set of three-phase conductors and their supporting structures. Parallel lines within the same corridor operate independently and may fail independently. A transmission span is the conductor section between two adjacent towers and serves as the smallest analysis unit for DOFS-based wind speed measurement, failure probability calculation, and hardening decision-making, as shown in Figure 3.
Figure 3. Schematic of the transmission line corridor structure and span definition.
To further incorporate the span-level wind speed information into resilience assessment and reinforcement optimization, spatiotemporal wind speed sequences measured by the DOFS system at the span level are required. These data have been monitored and collected in practical field applications. On this basis, this paper establishes a quantitative mapping between span-level wind speed and line-level failure rate, and ultimately constructs a multi-layer resilience assessment framework extending from individual transmission line spans to the overall power system.

3.1. Real-Time Wind Load Modelling at Span Intervals and Failure Probability Modelling

Traditional wind load estimation methods typically rely on sparse meteorological station data, which are insufficient to capture the micro-meteorological characteristics encountered along long-distance transmission lines.
Based on the aforementioned distributed optical fiber sensing system and wind speed measurement technology, the real-time average wind speed at each span of the transmission line can be obtained. According to the mechanical characteristics of overhead conductors and the conventional wind load calculation methodology, the real-time wind load acting on the conductor of the i-th span can be expressed as follows:
W f = α v i ( t ) 2 μ l μ s c C d d L p B sin 2 θ
where v i ( t ) is the real-time wind speed at span i at time t after correction; μ s c is the wind pressure non-uniformity coefficient; μ l is the rigging coefficient; C d is the drag coefficient (wind load shape factor); d is the outer diameter of the transmission conductor; L p is the horizontal span length; B is the ice-covered wind load amplification factor; θ is the angle between the wind direction and the line orientation.
It should be noted that the wind speed sequences acquired by the distributed optical fiber sensing system for each span correspond to the average and maximum wind speeds within a given statistical interval. During the typhoon passage, the entire process is divided into equal time intervals. Within each interval, the wind speed at the location of a given span is assumed to remain constant. In this way, the continuous wind speed process is discretized into a time-segmented wind load sequence, which serves as the input for the subsequent time-varying failure probability calculation.
Within the same overhead transmission line, all towers are structurally interconnected. The failure of any individual span may result in the outage of the entire line, requiring it to be taken out of service. Therefore, span-level failure modeling is necessary prior to conducting system-level analysis. In this study, a load–strength interference model is adopted to characterize the failure probability at the span level. A transmission line typically extends from several kilometers to tens of kilometers and consists of multiple spans. Due to spatial variations in environmental conditions along the corridor, different spans are subjected to distinct external loads and thus exhibit different failure probabilities. Accordingly, each transmission line is discretized into multiple spans, where the failure probability of a single span is determined by the interaction between the mechanical strength of the overhead line components and the applied wind load. The strength of transmission lines J and real-time load W ( t ) follow probability density functions f J ( j ) and f w ( w ) respectively, as shown in Figure 4.
Figure 4. Comparison of Line Strength and Load Probability Density Function.
The failure probability of the line gauge at time t is the integral of the area where the load distribution curve overlaps with the strength distribution curve.
P f , i ( t ) = = P J − W t < 0 = ∬ f J ( j ) f w ( w ) d r d w
For tractability, the structural strength J and the wind load W ( t ) are both approximated as statistically independent normal random variables. This is a widely adopted first-order assumption in structural reliability analysis, because the macroscopic mechanical response of transmission components is governed by the combined action of multiple independent uncertainties, such as material dispersion, construction deviation, service degradation, and environmental fluctuation. Under this approximation, the statistical characteristics of strength and load can be written as: J ∼ N ( μ J , δ J 2 ) , W ∼ N ( μ s ( t ) , δ s ( t ) 2 ) , where μ s ( t ) is determined by the real-time mean wind load, and δ s ( t ) is governed by the pulsation characteristics of the wind speed. In this study, the mean wind load is determined from the span-level wind speed measured by the DOFS system through the aerodynamic load model in Equation (1), whereas the load variance reflects the local turbulent fluctuation intensity within the corresponding interval. A more detailed discussion on the engineering rationale of the normality assumption and the potential influence of non-normal deviations is provided in Section 3.3.
Given that the structural strength J and the dynamic wind load W ( t ) are modeled as statistically independent normal random variables, the performance function Z = J − W ( t ) inherently and strictly follows a normal distribution Z ~ N ( μ Z , δ Z 2 ) based on the reproductive property of normal distributions. The intermediate mathematical derivation for the mean μ Z and standard deviation δ Z 2 of the performance state is given by: μ Z = μ J − μ s ( t ) ; δ Z 2 = δ J 2 + δ s 2 ( t )
Since Z is normally distributed, the probability of structural failure (i.e., the probability that Z < 0 ) can be expressed as the integral of the normal probability density function over the failure domain, as shown in Equation (3):
P f , i ( t ) = P ( z ( t ) < 0 ) = ∫ − ∞ − − μ z δ z 1 2 π δ z exp ( − ( Z − μ z ) 2 2 δ z ) d z
By applying the standard normal transformation, the integral in Equation (3) can be reduced to the standard normal cumulative distribution function Φ ( ⋅ ) , yielding the closed-form reliability expression:
P f , i ( t ) = Φ ( − μ J − μ s ( t ) δ J 2 + δ s ( t ) 2 ) = Φ ( − μ z δ z )
Equation (4) indicates that the span-level failure probability is primarily governed by two factors. The first is the statistical characteristics of the load, determined by the wind speeds measured through the distributed optical fiber sensing system. The second is the statistical characteristics of the strength, defined by the structural parameters and service condition of each span. This dual-driven mechanism enables the proposed failure rate model to capture the differentiated risk levels among spans along the same transmission line. Such spatial heterogeneity cannot be adequately represented under the conventional line-level assumption of uniform wind speed. By integrating the distributed wind speed information obtained from optical fiber sensing, the model provides refined input data for subsequent transmission network resilience assessment and differentiated operation and maintenance enhancement strategies.
By applying a sliding-window statistical analysis (e.g., a standard 10 min interval) to the high-frequency inverted DOFS time series, the local turbulent fluctuation is directly and mathematically quantified. Unlike traditional deterministic models that rely on macroscopic empirical gust factors to amplify mean loads, this probabilistic framework captures wind fluctuations through the Turbulence Intensity ( I u ). Specifically, let v k denote the high-frequency wind speed samples captured by the DOFS system within a specific time interval t , comprising N total samples. The real-time turbulence intensity I u ( t ) is quantified as the ratio of the sample standard deviation to the sample mean, expressed as:
I u ( t ) = 1 N − 1 ∑ k = 1 N ( v k − v ¯ ) 2 v ¯
Within the proposed load-strength interference model, this site-specific turbulence intensity directly serves as the dynamic Coefficient of Variation (COV) for the environmental load. Consequently, the localized load fluctuation parameter (standard deviation) is quantitatively derived as δ s ( t ) = I u ( t ) ⋅ μ s ( t ) . This data-driven quantification process ensures that the failure probability is parameterized by the actual micro-meteorological turbulent behaviors captured by the optical fiber, rather than relying on generalized regional approximations.
To ensure the engineering applicability of the proposed model, the distribution parameters are determined through a combination of engineering design codes and empirical DOFS sensing data. Specifically, for the structural strength J , the mean value μ J is analytically anchored to the design wind load threshold specified by typical transmission line design standards (e.g., GB 50545 [29] for Chinese power grids). The strength uncertainty parameter δ J is assigned a Coefficient of Variation (COV) typically ranging from 0.15 to 0.20. Specifically, the Unified Standard for Reliability Design of Building Structures [30] recommends a system resistance COV of 0.07–0.18 for typical steel and reinforced concrete members, which is broadly consistent with the values reported in [31]. For transmission-line components, a value of 0.15 was adopted in [32], while [33] suggested a range of 0.10–0.20, and [34] reported that the value may reach as high as 0.20 when aging effects are considered. Therefore, the COV range adopted in this study is consistent with the representative values reported in the literature. Conversely, for the wind load W ( t ) , the real-time mean value μ s ( t ) is computed deterministically from the localized, high-resolution span-level wind speeds inverted by the DOFS system, following the aerodynamic relationship given in Equation (1). The load uncertainty parameter δ s ( t ) represents the localized aerodynamic gust fluctuations within the typhoon boundary layer and is typically assigned a COV of 0.20 to 0.25. The probabilistic treatment of wind action on overhead transmission lines in this study follows the framework established in [35], which specifies the extreme-value-based modeling approach for annual maximum wind speed and provides the basis for the reliability classification of transmission-line components. Under conventional Terrain Category B conditions, the turbulence intensity is approximately 0.12–0.14 [36], whereas measurements from multiple landfalling typhoons along the southeastern coast of China indicate that the median value increases significantly to 0.18–0.25, far exceeding the baseline level under ordinary terrain conditions [37]. Since the COV of wind load effects is generally of the same order as, but slightly higher than, the turbulence intensity due to the additional uncertainties introduced by gust factors and pressure coefficients, the adopted range is reasonably supported from both physical and empirical perspectives.
This dynamic parameterization ensures that the failure probability evaluation is strictly driven by actual micro-meteorological conditions captured at the span scale, rather than relying on macroscopic empirical assumptions. The determination of the time-varying failure probability operates as a rigorous dynamic loop throughout the disaster process. For each discretized time interval (e.g., 10 min) during the typhoon passage, the localized wind speed measured by the DOFS system dynamically updates the statistical parameters of the wind load distribution, specifically the real-time mean μ s ( t ) and the localized fluctuation variance δ s 2 ( t ) . These updated environmental load parameters are then continuously fed into the closed-form reliability formulation (Equation (4)) alongside the static structural strength parameters ( μ J and δ J ). This sequential updating mechanism fundamentally drives the model, allowing it to translate the real-time meteorological severity captured by the optical fibers into a continuous, high-resolution time series of span-level failure probabilities.
After determining the time-varying failure probability of each span, it is necessary to further generate a set of failure scenarios for resilience assessment. Referring to [38], this study adopts a sequential Monte Carlo simulation approach to perform chronological sampling of the physical states of each span and transmission line throughout the entire typhoon passage process. The wind speeds measured by the DOFS system are treated as deterministic inputs to derive the time-varying failure probabilities of individual spans, thereby providing spatial heterogeneity information. The Monte Carlo simulation is then applied to perform stochastic state sampling based on these probability values.
A transmission line typically consists of tens to hundreds of spans connected in series. The failure of any single span will cause the entire transmission line to be out of service. Therefore, the cumulative failure probability of an entire transmission line comprising N spans at time t, denoted as P l i n e ( t ) , can be expressed as:
P line ( t ) = 1 − ∏ i = 1 N ( 1 − P f , i ( t ) )

3.2. Resilience Assessment Framework

To quantitatively assess and enhance the resilience of transmission networks, this paper proposes a three-layer resilience evaluation framework for transmission lines subjected to typhoon disasters. Built upon the span-level real-time wind load data acquired through the aforementioned distributed optical fiber sensing technology, the framework is designed in accordance with the multi-stage evolutionary characteristics of power system resilience, namely “resistance–absorption–recovery.” The evaluation system focuses primarily on the resistance capability during the disaster (i.e., reducing failure probability) and the absorption capability after fault occurrence (i.e., minimizing system-wide impacts). At the span level, the framework quantifies asset damage and economic losses in the physical dimension, with an emphasis on integrity at the finest granularity. At the line level, it identifies critical transmission corridors within the grid topology. At the system level, it evaluates the overall impact of the disaster on system operation, centering on load shedding due to power supply deficiency. The indicators are aggregated progressively from the span level upward to form system-level metrics, while the system-level evaluation results are fed back downward to guide span-level operation and maintenance reinforcement decisions aimed at resilience enhancement. In this manner, a comprehensive, multi-dimensional situational awareness of transmission network operating conditions under typhoon disasters is achieved.

3.2.1. Span-Level Asset Loss Cost

A span represents the most fundamental physical unit of a transmission corridor and corresponds to the finest granularity monitored by the distributed optical fiber sensing system. Referring to economic evaluation principles in power system studies [39], this paper defines the resilience of a single span as its ability, throughout the entire typhoon event, to maintain physical integrity and support the system in sustaining power supply services. Based on the transmission network asset damage assessment model, a span-level asset loss cost is proposed at this layer to quantify the expected physical and economic loss of a specific span under a given wind speed during a typhoon. This metric primarily accounts for mechanical damage caused by extreme wind and the associated direct economic losses, as expressed in Equation (6).
C S A D F , s p a n t k = ∑ i ∈ S l t k P f , i t k C s p a n , j t k
where C S A D F , s p a n t k represents the asset loss cost at time t k under scenarios. S l t k denotes the set of system states with damaged components at time t k . The period of interest T is divided into equal time intervals, such that Δ t = T / n and t k = t 0 + k Δ t . Within each interval [ t k , t k + 1 ] , the wind speed at the location of the corresponding span is assumed to remain constant. The wind speed sequence obtained by the distributed optical fiber sensing system for each span consists of the average and maximum wind speeds within a statistical interval Δ t , which serve as inputs for failure probability evaluation.
In (6), P f , i t k represents the time-varying failure probability of span i at time t k , calculated based on the wind-speed-dependent load–strength interference model (see Equation (4)). C s p a n , j t k denotes the expected asset loss cost associated with span i at time t k , defined as:
C s p a n , j t k = w c m , l t k C c m v , j ⋅ L s p a n , j , V s p a n t k < V t h r , j , C c o n d , j ⋅ L s p a n , j , V s p a n t k ≥ V t h r , j ,
w c m t k = f V s p a n t k
where w c m t k denotes the damage factor characterizing the extent of damage to span components, which is a function of the wind speed intensity at the span location, as shown in Equation (8). V s p a n t k represents the equivalent wind speed at the location of the span at time, and V t h r , j denotes the wind speed threshold at which span j is considered to be completely damaged. C c m v , j and C c o n d , j are the component value and replacement cost of the damaged component j , respectively. L s p a n , j is physical length of span j .
Taking the expectation over all scenarios and time intervals, the expected asset damage cost at the span level can be obtained as follows:
E A D C s p a n , j = ∑ s ∈ S ∑ t ∈ T C S A D F , s p a n t k

3.2.2. Resilience-Informed Critical Corridor Identification at the Line Level

Consider a transmission line l composed of a set of spans 1 , 2 , … , n s p a n . Under the assumption that span failures are mutually independent, the outage probability of the line can be expressed as shown in Equation (5).
The expected asset damage cost of transmission line l is obtained by aggregating the expected asset damage costs of all its spans, i.e.,
E A D C l = ∑ j = 1 n s p a n , l E A D C s p a n , j
Following the assessment stage, the subsequent resilience enhancement phase must differentiate the importance of transmission corridors within the reinforcement scheme, thereby improving the adaptability of span-level strengthening strategies for critical corridors. Accordingly, at the line level, a critical transmission corridor identification method based on composite importance is adopted. The composite importance index is calculated using weighted network topology entropy and weighted power flow transfer entropy, as expressed below:
C I I = w i H t o p o + w j H f l o w
where w i + w j = 1 . The weights of the composite importance index are determined using the entropy weight method, which is a widely adopted objective weighting approach. In this method, weights are automatically assigned based on the variability of each indicator, thereby avoiding subjective bias.
H t o p o denotes the weighted topology entropy. From the perspective of transmission network topology, the criticality of a given transmission corridor is characterized by the average power flow magnitude at each node after the outage of that corridor, reflecting its structural importance within the overall network. The formulation is given as follows:
H t o p o = − ∑ a = 1 N p a f l o w ln p a f l o w
p a f l o w = F a f l o w ∑ r N F r f l o w
F a f l o w = 1 K ∑ k = 1 K ∑ r ∈ Ω a P a r k
In the above expressions, N denotes the total number of nodes in the network. p a f l o w represents the flow probability distribution of node a, and F a f l o w denotes the average power flow at node a. K is the number of critical transmission corridors considered, and Ω a denotes the set of nodes connected to node a. P a r k represents the power flow from node a to node r after the outage of the k-th critical transmission corridor.
H f l o w denotes the weighted power flow transfer entropy. It evaluates the importance of a transmission corridor within the network by analyzing the magnitude of power flow redistribution to other corridors following its outage. The formulation is given as follows:
H f l o w = − ∑ k = 1 K ∑ g ≠ k K p k g t r a n s ln p k g t r a n s
p k g t r a n s = Δ G k g ∑ k ′ = 1 K ∑ g ′ ≠ k ′ K Δ G k ′ g ′
Δ G k g = G k g − G k
In the above formulation, p k g t r a n s denotes the power flow transfer probability between the k-th and the g-th critical transmission corridors. ∆ G k g represents the amount of power flow transferred from corridor k to corridor g. G k g denotes the power flow of corridor k after the outage of corridor g, and G k is the original power flow of corridor k. ∆ G k ′ g ′ represents the power flow transfer amount between the k′-th and g′-th critical transmission corridors. In Equation (16), k and g denote a specific pair of transmission corridors, where g represents the faulted corridor and k represents the affected corridor whose power flow variation is evaluated. In contrast, k′ and g′ are dummy indices used in the denominator to represent summation over all possible fault–impact corridor pairs in the network. They have no direct correspondence with k and g, and are introduced solely for normalization purposes to ensure that the calculated value represents a probability. By weighting the two indices, the composite importance value is obtained to quantify the overall significance of a given transmission corridor, which serves as the basis for identifying and selecting critical corridors in the reinforcement planning process. To construct the final set of critical corridors for span-level hardening, a Top-K Ranking Criterion based on the Composite Importance (CI) index is employed. Specifically, all transmission corridors are sorted in descending order of their CI scores. The selection criterion involves setting a threshold K (e.g., selecting the top K corridors) that captures the primary structural and operational vulnerabilities of the network. This mathematical truncation ensures that the reinforcement optimization prioritizes the most consequential pathways, thereby significantly reducing the dimensionality of the span-level decision variables and guaranteeing the computational tractability of the system-level optimization model.

3.2.3. System-Level Load Shedding Impact

When a transmission system is subjected to extreme meteorological hazards, a large number of grid components may fail, potentially resulting in widespread power outages. Once failures occur, the system typically operates under power supply deficiency and enters the maintenance and restoration phase. Through progressive repair and recovery actions, the system gradually returns to its normal operating state. The corresponding evolution of system performance over time is illustrated in Figure 5.
Figure 5. System status curve under extreme natural disaster weather conditions.
The proposed assessment framework leverages real-time data acquired by the distributed optical fiber sensing system during typhoon events, with a primary focus on the pre-disaster warning and disaster-in-progress phases, corresponding to the intervals [ T 1 , T 3 ] and [ T 0 , T 2 ] in Figure 5. System-level resilience evaluation is conducted within these two time periods. Accordingly, the expected load shedding during the typhoon duration is adopted as the system-level resilience metric, formulated as follows:
p t , s s h e d = ∑ b ∈ Θ p b , t , s s h e d
d l s = ∑ s ∈ S ω s ∑ t ∈ T p t , s s h e d Δ t
where d l s denotes the system-level load curtailment over the typhoon duration; S is the set of typhoon failure scenarios; T is the set of discretized time intervals during the typhoon process; Θ is the set of load buses; ω s represents the probability weight of typhoon fault scenario s , satisfying ∑ s ∈ S ω s = 1 ; p b , t , s s h e d is the curtailed load at bus b under scenario s during time interval t , and Δ t is the duration of each interval. p t , s s h e d denotes the total curtailed load of the system under scenario s at time interval t , which is obtained by aggregating the curtailed load over all load buses.

3.3. Analysis of Sources of Uncertainty

Within the aforementioned modeling framework, the sources of uncertainty and their corresponding treatment methods can be categorized into the following three types:
(1) Spatial distribution uncertainty of wind speed: The wind speeds measured by DOFS are treated as deterministic inputs. The spatial heterogeneity is directly captured by the distinct measured wind speeds at individual spans.
(2) Wind speed fluctuation uncertainty: This is reflected in the variance of the load distribution. The DOFS provides the mean wind speed over a statistical interval, while the turbulent fluctuation characteristics of wind speed are characterized through the standard deviation of the load distribution.
(3) Randomness of failure occurrence: This is addressed through Monte Carlo random sampling. Even when two spans share an identical failure probability, they may exhibit different failure states across different simulation trials, reflecting the inherent randomness of disaster consequences.
By leveraging DOFS, this study transforms the spatial distribution of wind speed from an uncertain variable into a deterministic input, thereby significantly reducing the epistemic uncertainty in the failure scenario generation process. This enhances both the credibility of the resilience evaluation results and the specificity of reinforcement decisions.
Furthermore, regarding the statistical assumptions in the load-strength interference model, both structural strength and wind load are assumed to follow normal distributions. This is a widely adopted first-order approximation in structural reliability engineering, supported by the Central Limit Theorem when multiple independent material and environmental uncertainties aggregate. It should be acknowledged that if the actual variables exhibit non-normal behaviors—such as extreme meteorological loads following heavy-tailed extreme value distributions (e.g., Gumbel or Weibull) or material strengths following lognormal distributions—the normal assumption might underestimate the absolute failure probabilities at the extreme distribution tails. However, this simplification is retained as a necessary engineering trade-off. Mathematically, it allows the span-level failure probability to be derived into a closed-form analytical solution (Equation (4)), ensuring the computational tractability of the subsequent system-level mixed-integer optimization. More importantly, because the reinforcement prioritization in the proposed framework relies primarily on the relative spatial heterogeneity of wind exposure captured by the DOFS system, potential deviations in the absolute probability values do not fundamentally alter the relative vulnerability ranking among spans. Thus, the optimization strategy and the resulting hardening decisions remain highly robust.

4. A Stepwise Reinforcement Model for Transmission Grids Aimed at Enhancing Resilience

Based on the three-layer span–line–system resilience assessment framework established in Section 3, this section selects the system-level expected load curtailment as the resilience evaluation metric, incorporates the critical corridor identification results and component-level asset damage costs, and further develops a resilience enhancement model tailored for typhoon disasters. The model improves system resilience by formulating span-level maintenance and hardening strategies. Specifically, the hardening decisions at the span level serve as decision variables, simulating the practical scenario in which tower reinforcement along transmission corridors is completed prior to the typhoon season, while vegetation trimming alongside corridors can be carried out in advance based on short-term typhoon warnings. The construction of the hardening model relies on the outputs of the aforementioned assessment framework; accordingly, this section takes the critical corridor identification results and span-level asset damage costs as inputs to formulate the span-level hardening optimization model.

4.1. Construction of Reinforcement Models for Resilience Enhancement

The initial hardening scheme is determined by minimizing the total cost, which comprises three components: the total hardening cost composed of span-level hardening decision variables F h , the system load curtailment penalty cost F c , and the system asset damage cost F a d . By hardening selected spans, the expected load curtailment is reduced, thereby enhancing overall system resilience. The objective function is formulated as follows:
min F = F h + F c + F a d
F h = ∑ l ∈ Θ ∑ j = 1 n s p a n , l C h h l j L j
F c = C d d l s = ∑ s ∈ S ω s ∑ t ∈ T ∑ b ∈ Θ C d p s , t
F a d = ∑ l ∈ L ∑ j = 1 n s p a n , l E A D C s p a n , j ′
E A D C s p a n , j ′ = ( 1 − β h l j ) E A D C s p a n , j
where C h is the per-unit-length span hardening cost; h l j is the individual hardening decision variable for span j, h l j = 1 indicates a corridor hardening decision, h l j = 0 means no hardening; C d is the load loss penalty cost under typhoon disasters, dls is defined in Equation (19); E A D C ′ s p a n , j is the span asset damage cost considering the hardening effect, β is the hardening effectiveness coefficient—when span hardening is applied, the asset loss is reduced by a factor of β. This hardening effectiveness coefficient is set with reference to [20]. the hardening decision changes the strength distribution parameters, which in turn changes the failure probability and the composition of fault scenarios.
Physically, the span-level hardening decision h i j encompasses proactive measures such as structural tower reinforcement (e.g., upgrading crossarms, reinforcing foundations, or adding guy wires) and localized vegetation management. From the perspective of the load-strength interference model established in Section 3.1, structural hardening physically elevates the mathematical expectation of the component strength distribution μ J , whereas vegetation management mitigates the extreme variance and tail probability of the external wind load distribution δ w by eliminating the risk of tree-fall impacts. Both mechanisms inherently expand the safety margin of the performance function Z = J − W ( t ) , consequently driving down the real-time failure probability P f , i ( t ) and mapping to the reduction in expected asset damage. Mathematically, applying a uniform reduction ratio β to the Expected Asset Damage Cost (EADC) implicitly ensures that the absolute reduction in risk is wind-speed-dependent, as the baseline EADC inherently aggregates the localized, wind-dependent failure probabilities. This explicit linear scaling mechanism establishes a rigorous theoretical foundation for the algorithmic convergence. Because β ∈ ( 0 , 1 ) , setting the decision variable h i j = 1 strictly guarantees that the updated expected loss is smaller than the baseline. Consequently, under a fixed failure scenario set during the iterative solution phase, the localized physical state strictly improves or remains constant, mathematically ensuring the monotonic non-increasing property of the objective function sequence.
Furthermore, it should be noted that modeling the hardening effect as a uniform coefficient β across all spans is a carefully considered engineering simplification. In practice, the exact reduction in failure probability depends heavily on heterogeneous span topologies, local terrain, and specific reinforcement types. However, integrating heterogeneous, non-linear strength distribution updates directly into the system-level decision space would introduce severe non-convexities, transforming the expected load curtailment optimization into a highly complex Mixed-Integer Nonlinear Programming (MINLP) problem and compromising the computational tractability for large-scale networks. Therefore, the uniform β is adopted herein as a macroscopic expected-value proxy for these localized physical enhancements, ensuring the tractability of the Mixed-Integer Linear Programming (MILP) model while effectively capturing the dominant economic trade-offs of resilience investment.
The constraints include system nodal power balance, generator unit output limits, load shedding constraints, unit ramp-up/ramp-down rates, wind curtailment rate requirements, etc., as shown in the following equations:
  s . t . ∑ j = 1 N G p j G + ∑ i = 1 N D p i G − ∑ i = 1 N D p i D = 0 P j min G ≤ P j G ≤ P j max G , j = 1 , 2 , ⋯ , N G 0 ≤ P i C ≤ P j max G , i = 1 , 2 , ⋯ , N D − P k max ≤ P k t ≤ P k max , k = 1 , 2 , ⋯ , N L
where p i D denotes the load demand at the i-th bus. P j G , P j max G and P j min G represent the active power output and the upper and lower limits of active power output of the j-th generator, respectively. P k t and P k max denote the active power flow and the active power flow limit of line k at time t, respectively. N D , N G and N L are the total numbers of load buses, generators, and lines, respectively.
In addition, reinforcement budget constraints must be incorporated into the proposed optimization framework:
∑ l ∈ Θ ∑ j = 1 n s p a n , l C h h l j L j ≤   B u d g e t

4.2. Solution Strategy Based on Scenario Iteration Updates

In the above optimization model, reinforcement decisions alter the span-level failure probabilities, which in turn change the composition of the failure scenario set. Thus, the uncertainty set itself becomes decision-dependent. To avoid directly handling this nonlinear coupling relationship, this paper adopts a strategy that combines scenario pre-calculation with iterative updating.
Step 1: Scenario Pre-calculation. For each span j and each typhoon scenario s, two sets of failure probabilities are computed offline: Without reinforcement: P f , j 0 , s t ( h j = 0 );With reinforcement: P f , j 1 , s t   ( h j = 1 ). Meanwhile, the marginal reduction in failure probability due to reinforcement is calculated as: Δ P f , j s t = P f , j 0 , s t − P f , j 1 , s t For high-risk spans, Δ P f , j is typically larger, allowing the differentiated span-level information obtained from distributed optical fiber sensing to be effectively incorporated into the optimization model. In addition, during this step, a fixed set of uniformly distributed random numbers is pre-generated for each span j and each time step t. The same random number sequences are used in all subsequent iterations for state sampling, thereby eliminating the influence of Monte Carlo randomness on the monotonicity of the iterative process.
Step 2: Initial Scheme Solution. Using P f , j 0 , s t (i.e., all spans unreinforced), the initial failure scenario set is generated. The budget-constrained hardening optimization model is then solved to obtain the initial reinforcement scheme. h 0 .
Step 3: Scenario Update and Iterative Solution. (a) According to h k , for all reinforced spans ( h j = 1 ), their failure probabilities are updated to P f , j 1 , s t ; (b) Based on the updated failure probabilities, sequential Monte Carlo sampling is re-executed to generate a new failure scenario set; (c). The optimization model is re-solved under the updated scenario set to obtain h k + 1 .
Step 4: Convergence Check. If the relative change in the objective function between two consecutive iterations satisfies. F k + 1 − F k / F k ≤ ε or if the reinforcement scheme remains unchanged (i.e., h k + 1 = h k ), the iteration is terminated.
The above iterative procedure is performed only on the top M key transmission corridors ranked by comprehensive importance. Spans belonging to non-critical corridors are excluded from the reinforcement decision space. This focused strategy reduces the number of decision variables from several thousand spans across the entire network to only a few hundred, without significantly compromising solution quality. Under the deterministic case where the failure scenario set is fixed, reinforcement strictly reduces the failure probability of the reinforced spans. Therefore, for the scenario set generated based on the updated probabilities, both the expected load shedding and the expected asset loss cost are no greater than those before updating. Consequently, with a fixed scenario set, the objective function sequence is monotonically non-increasing.
Meanwhile, all components of the objective function are non-negative, implying that the sequence is bounded below by zero. According to the monotone bounded convergence theorem, the sequence must converge. Furthermore, since the reinforcement decision variables hj are binary integers, the total number of feasible solutions is finite. The algorithm cannot repeatedly visit the same solution indefinitely. Therefore, the iterative process must terminate within a finite number of steps.
The overall solution procedure of the proposed model is illustrated in Figure 6.
Figure 6. Resilience Enhancement Solution Solving and Iteration Flowchart.

5. Case Study

5.1. Case Study of Stepwise Wind Measurement Using Distributed Fibre Optic Technology During Multiple Typhoon Disasters

In Section 2, the span-level wind speed distribution along the transmission corridor during Typhoon Koinu in October 2024 was reconstructed using the distributed optical fiber sensing system. As shown in Figure 1, the wind field exhibited pronounced spatial heterogeneity along the monitored line, with substantial differences in wind speed among different spans. In particular, spans #13–#14, #36–#39, and #42–#54 experienced relatively higher wind speed levels and stronger temporal fluctuations than the remaining sections. The highest wind speed was observed at spans #47–#51, reaching 18.51 m/s. These results indicate that typhoon-induced wind exposure is highly non-uniform even within the same transmission corridor, and they demonstrate the advantage of DOFS in identifying localized high-wind sections that may not be captured by conventional point-based observations.
To further verify the stability of the sensing system under different typhoon conditions, the same transmission corridor was monitored during Typhoon Trami from 22 to 24 October 2024. During this event, the DOFS system continuously recorded wind speed data over spans #1–#69 of the 500 kV Zitong II line, yielding a total of 25,772 datasets.
As illustrated in Figure 7, the spatial distribution again showed evident non-uniformity. Specifically, spans #10–#17, #19–#27, #31–#33, and #47–#53 exhibited wind speeds significantly above the line average, and the maximum value occurred at spans #15–#16, reaching 21.1 m/s. Compared with the Koinu event, although the exact locations of the peak wind speed differed slightly, the existence of multiple localized high-wind sections remained evident, further confirming that span-level wind exposure cannot be adequately represented by a uniform corridor-level wind speed assumption.
Figure 7. Wind speed distribution along the Zitong II line during Typhoon Trami.
The sensing system was also used to monitor Typhoon Shantuo in late September 2024, during which 577 wind speed datasets were collected. The peripheral circulation of this typhoon generated a sustained and strongly pulsating wind process in Jinjiang and surrounding areas.
As shown in Figure 8, significant spatial differences in wind speed were again observed along the monitored line. High-wind sections were mainly concentrated in spans #13–#14, #36–#39, and #42–#54, while the peak wind speed was still recorded around spans #47–#51. In addition, spans #1–#2 also exhibited relatively high wind speed during certain periods of the typhoon event shown in Figure 8, which is consistent with the distribution pattern observed in Figure 1 and further indicates that the pronounced response in this section is more likely a real localized wind feature rather than an isolated disturbance. These results show that, although the overall intensity and duration of different typhoon events vary, the DOFS system can consistently resolve the spatial variation of wind speed at the span scale and identify wind-sensitive sections along the line.
Figure 8. Wind speed distribution along the Zitong II line during Typhoon Shantuo.
Taken together, the results from the three real typhoon events demonstrate that the distributed optical fiber sensing system is capable of distinguishing wind speed differences among individual spans along the same transmission corridor. More importantly, several sections, such as spans #13–#14, #36–#39, and #47–#51, repeatedly appeared as high-wind regions under different typhoon events. This cross-event consistency suggests that the span-level wind field along the corridor exhibits persistent spatial heterogeneity, which provides an important measurement basis for subsequent failure probability assessment and span-level hardening decision-making.
A unified terrain-based analysis indicates that these high-wind spans are predominantly located in open river valleys, windward slopes of hilly areas, or locally elevated terrain. Under such topographic conditions, airflow acceleration and channeling effects are intensified, resulting in local wind speeds that are significantly higher than the corridor-average level. This consistency suggests that the spatial heterogeneity of span-level wind speeds is strongly governed by terrain-induced wind amplification mechanisms.
To verify the engineering applicability of the inferred wind speed results, the wind speed series of a representative span under a typical typhoon scenario was selected for validation. In practice, it is usually infeasible to synchronously deploy high-precision wind speed measurement devices at every span along a transmission line. As a result, span-by-span ground-truth measurements that exactly correspond to the distributed optical fiber wind sensing results are difficult to obtain. For this reason, the wind speed records from the Jinjiang Meteorological Station, which is located near the transmission corridor and provides continuous synchronous observations, were adopted as the near-surface reference for comparison and validation in this section. The error metrics include peak error, peak relative error, mean absolute percentage error (MAPE), root mean square error (RMSE), and bias. Among them, peak error and peak relative error are used to evaluate the ability of the model to capture strong wind peaks; MAPE and RMSE reflect the overall fitting error over the full process; and Bias describes the overall tendency of the inferred results to be higher or lower than the reference wind speed. Taking Span #12–#13 under the typhoon scenario as an example, the results are presented in Table 1.
Table 1. Single representative span across multiple typhoons.
As shown in Table 1, the distributed optical fiber wind sensing method proposed in this section demonstrates good stability and consistency. The peak error is limited to about 2 m/s, the peak relative error remains within 8%, and the RMSE is kept below 2.3 m/s. These results indicate that the proposed method has practical engineering value and can provide reliable wind speed inputs for subsequent resilience assessment.
Moreover, the scenario visualizations further confirm the necessity of implementing span-level wind speed monitoring technology. They also provide objective and realistic data support for subsequent span-level resilience assessment and for the validation of resilience enhancement strategies.

5.2. Validation of Resilience Enhancement Scheme for Inter-Span Level Operation and Maintenance Upgrades

This paper adopts a modified IEEE RTS-24 reliability test system as the case study platform. The system has a maximum load of 2850 MW and a total installed generation capacity of 3405 MW, including 38 transmission corridors. The network topology is shown in Figure 9. The load shedding penalty cost is set to $5000/MWh. Rather than representing the standard electricity market clearing price, this parameter signifies the Value of Lost Load (VOLL), which is a widely accepted macroeconomic benchmark in power system resilience studies to quantify the severe socioeconomic disruption caused by forced power outages during extreme natural disasters [40]. The span-level wind speed inputs in this study are directly obtained from the DOFS system during three real typhoon events. The three wind speed scenarios correspond to three typhoon events, each containing complete wind speed time series for 68 spans (1438 time steps with a 10 min interval). The line-level and system-level spatiotemporal typhoon wind fields are generated using the parametric wind field model described in [39]. This model characterizes the spatiotemporal evolution of wind speed as a typhoon passes through the power grid area using key parameters such as central pressure difference, moving speed, and moving direction. The probability distributions of key typhoon parameters and the detailed geographical network data are also adopted from [39].
Figure 9. IEEE RTS-24 geographic wiring diagram.
The three wind speed scenarios correspond to the typhoons Trami (maximum wind speed 21.1 m/s), Koinu (maximum wind speed 18.5 m/s), and “Shantuo,” respectively. Each scenario includes the complete wind speed time series of all spans in the system (10 min interval). Based on the historical tropical cyclone database from the China Meteorological Administration (CMA) for the southeast coastal region over the past two decades, the scenario probability weights are assigned as 0.50, 0.35, and 0.15. These weights statistically correspond to three categorized intensity tiers of landfalling events: Moderate Typhoons/Tropical Storms (approx. 50%), Strong Typhoons (approx. 35%), and Severe/Super Typhoons (approx. 15%), ensuring that the stochastic scenario generation aligns with the actual regional meteorological risk profile. All programs in this study are implemented in MATLAB R2021b, and the optimization problems are solved using the Gurobi solver.
The comprehensive importance index is calculated for all transmission corridors in the system, and the results are presented in Figure 10. By sorting the importance values in descending order, the top ten corridors are identified as the key transmission corridors of the system. The corresponding numerical results of the two indicators for each corridor are listed in Table 2.
Figure 10. The comprehensive importance of corridors.
Table 2. Comprehensive importance ranking of transmission corridors.
The weighted network structural entropy and the weighted power flow transfer entropy reflect corridor importance from two different perspectives: the structural topology of the power grid and its operational state characteristics. As shown in Table 2, using only a single indicator may lead to biased evaluation results. For example, Corridor 15–16 has the highest weighted power flow transfer entropy among the ten selected corridors, indicating that its outage would cause significant power redistribution in the system. However, its weighted network structural entropy is not the highest, implying that its structural centrality within the network is relatively less prominent. This comparison highlights the necessity of integrating both indicators to achieve a more balanced and comprehensive assessment of transmission corridor importance.
Based on the identification of key transmission corridors, this paper further selects these corridors for span-level segmentation to conduct detailed assessment and methodological validation. According to the actual span distribution characteristics of transmission lines, each corridor is divided into spans based on its physical length and the corresponding number of spans in practical engineering.
The corridor with the highest comprehensive importance, Corridor 15–16, is divided into 68 spans with a total length of 24.16 km, which is consistent with the engineering parameters of the actual Zitong II transmission line. This configuration ensures that the case study remains closely aligned with real-world structural characteristics, thereby enhancing the practical applicability and engineering relevance of the proposed span-level resilience assessment framework.
On this basis, two comparative scenarios are designed: Scheme 1: No reinforcement measures are implemented. Scheme 2: Span-level resilience enhancement reinforcement is applied. The comparison results of Scheme 1 and Scheme 2 are presented in Table 3.
Table 3. Comparison of Scheme 1 and Scheme 2.
In Scheme 1, due to the absence of reinforcement measures, the system suffers significant load loss under typhoon conditions, resulting in a load shedding cost of 75 M$. In contrast, the reinforcement strategy of Scheme 2 is shown in Table 4. The total reinforcement investment amounts to 239.34 M$, and the load shedding is reduced to zero. The total cost of Scheme 2 is 247.78 M$, including reinforcement and residual operational costs. By comparing the two schemes, it can be concluded that implementing span-level reinforcement measures can effectively enhance power system resilience, substantially mitigating disaster-induced load loss and improving system performance under extreme weather conditions.
Table 4. Span-level Reinforcement Scheme.
Under this scheme, within the transmission corridor with the highest comprehensive importance, the reinforcement priority ranking of spans based on the span-level expected asset loss cost is shown in Figure 11. The figure reflects the prioritization principle of the proposed optimization framework: spans with higher expected asset loss costs—resulting from higher failure probabilities and greater consequence severity—are assigned higher reinforcement priority. This demonstrates that the model effectively integrates hazard intensity, structural vulnerability, and consequence severity at the span level, enabling reinforcement resources to be allocated in a risk-informed and economically efficient manner.
Figure 11. Asset Loss Cost–Based Span Importance Ranking.
To compare the proposed span-level reinforcement model with the traditional line-level reinforcement approach, this paper further designs Scheme 3 as a benchmark case: reinforcement is implemented at the line level without distinguishing individual spans. In this scheme, once a key transmission corridor is selected for reinforcement, all its spans are uniformly strengthened, rather than performing differentiated reinforcement at the span level. For the test system, the set of key corridors can be divided into a total of 594 spans. The corresponding calculation results are presented in Table 5. By comparing Scheme 3 with the proposed span-level reinforcement strategy, the economic efficiency and resilience enhancement capability of fine-grained, span-level decision-making can be quantitatively evaluated, thereby highlighting the advantages of incorporating DOFS-based spatial heterogeneity information into the reinforcement optimization process.
Table 5. Comparison of span-level and line-level reinforcement strategies.
As shown in Table 5, Scheme 3 also reduces the system load shedding cost to zero. However, when implementing the span-level hardening strategy in Scheme 2, the reinforcement cost is reduced by 67% compared with the line-level approach. This result demonstrates that the DOFS-enabled span-level hardening strategy maintains the same resilience enhancement level as the traditional line-level scheme while avoiding unnecessary investment in low-risk spans. By selectively reinforcing only high-risk spans identified through high-resolution wind field measurements, the proposed method effectively eliminates redundant reinforcement and achieves system-level cost optimization.
To further substantiate the superiority of the proposed span-level methodology over conventional practices, a direct benchmark comparison under an strictly identical, resource-constrained budget is conducted. In practical engineering, resilience enhancement budgets are often severely limited following sudden extreme weather warnings. Therefore, a limited budget scenario is established with an upper bound cap of 145.00 M$. Under this identical financial constraint and the same typhoon scenarios, two hardening schemes are compared side-by-side: Scheme 4 (Proposed Span-level Strategy under Limited Budget): Reinforcement resources are allocated strictly based on the span-level Expected Asset Damage Cost (EADC) ranking. Individual high-risk spans are hardened sequentially until the budget is depleted. Scheme 5 (Conventional Line-level Baseline under Limited Budget): Following conventional practice, reinforcement is applied to an entire transmission corridor continuously (span by span along the route) based on the line-level composite importance until the exact same budget is exhausted. The comprehensive quantitative results, including total load shedding ( d l s ), expected asset damage cost ( F a d ), and the extent of reinforced spans, are presented in Table 6.
Table 6. Benchmark Comparison of Hardening Strategies Under Identical Limited Budget.
As clearly demonstrated in Table 6, under the exact same financial constraint, the conventional line-level approach (Scheme 5) quickly exhausts the budget by reinforcing a continuous segment of a single corridor. Because it blindly reinforces consecutive spans—many of which have low wind exposure and do not critically need hardening—it leaves other highly vulnerable spans in the network completely exposed. Consequently, the resilience improvement is marginal, resulting in a severe expected load shedding of 14,820.50 MWh and an asset damage cost of 1.8652 M$.
Conversely, the proposed span-level strategy (Scheme 4) breaks the geographical boundaries of continuous corridors. By precisely targeting and reinforcing only the scattered “weak links” (the 8 spans with the highest EADC) across the entire network, Scheme 4 achieves a profound reduction in both load shedding (reduced to 13,087.24 MWh) and physical asset damage (reduced to 1.2076 M$). This direct benchmark unequivocally visualizes the core advantage of the DOFS-driven span-level framework: maximizing systemic resilience enhancement efficiency through high-resolution spatial vulnerability awareness and precise resource allocation.
Furthermore, regarding the parameter sensitivity and engineering applicability of the hardening effectiveness coefficient β , it is important to note that β acts as a linear scaling factor on the expected asset damage cost reduction in the objective function. Because the reinforcement priority sequence in the proposed optimization framework is intrinsically driven by the spatial heterogeneity of the DOFS-measured wind loads and span topologies, varying the exact value of β within a reasonable physical range will only scale the absolute magnitude of the total cost F a d . In the tested sensitivity range, varying β mainly scales the absolute magnitude of the total cost, while the relative reinforcement priority among spans remains broadly stable. Therefore, the optimal span-level hardening decisions derived from this model are highly robust to the specific calibration of β , ensuring the strong engineering applicability of the proposed identification framework even under parametric uncertainty.

5.3. Sensitivity to Spatially Correlated Failures

In the primary reliability evaluation, individual transmission spans are modeled as statistically independent. While this ensures the linearity and computational tractability of the system-level MILP optimization, assuming strict independence can understate the absolute systemic risk during severe typhoons. In practice, the failure of one span (e.g., conductor breakage) introduces severe unbalanced longitudinal tension on the shared suspension towers, significantly increasing the failure probability of adjacent spans (cascading failure).
To quantitatively evaluate the impact of this phenomenon, a sensitivity analysis incorporating spatially correlated failures was conducted. A Markovian spatial correlation heuristic was introduced, where the failure of a primary span conditionally increases the failure probability of its adjacent spans by a multiplier of 20%. Under the same limited budget constraint (145.00 M$) as Scheme 4, the optimization was re-evaluated. The comparative results are presented in Table 7.
Table 7. Sensitivity Analysis of Hardening Decisions Under Independent vs. Correlated Failure Assumptions.
The results of this sensitivity case reveal two critical findings:
(1) Absolute Risk Amplification: As expected, the inclusion of shared-tower correlated failures amplifies the baseline risk, increasing the absolute expected load shedding (EENS) by 16.0% under the severe typhoon scenario.
(2) Robustness of Optimization Decisions: Despite the substantial increase in absolute risk metrics, the relative vulnerability ranking of the network remains overwhelmingly dominated by the primary localized wind exposure captured by the DOFS system. As shown in Table 7, the “triggering spans” that initiate the cascading failures are almost identical to the high-risk spans identified in the independent model (with only a minor spatial shift from span #37 to the adjacent span #38 due to the shared-tower tension effect). Consequently, the optimal hardening decisions generated by the optimization engine exhibit a high similarity of 87.5% compared to the independent assumption.
Therefore, it is concluded that while the independent span assumption provides a conservative estimate of the absolute cascading risk, it serves as a highly robust, computationally efficient proxy that successfully guarantees the accuracy and engineering reliability of the proposed DOFS-driven span-level resilience hardening strategy.

6. Conclusions

To address the limitations of insufficient wind speed characterization accuracy and overly coarse hardening decision granularity in traditional transmission system resilience assessment, this paper proposes a DOFS-driven span-level resilience assessment and hardening optimization framework. The main conclusions are as follows:
(1) Based on a Φ-OTDR distributed optical fiber sensing system, continuous wind speed monitoring at the individual span level along transmission lines is achieved. Field data collected during three real typhoon events demonstrate that DOFS can effectively capture the spatial non-uniformity of typhoon wind fields within transmission corridors and identify high-wind-speed segments caused by terrain effects. Moreover, the measured results show strong consistency with the temporal evolution trends observed at nearby meteorological stations, validating the engineering reliability of the technology under extreme weather conditions.
(2) Using the DOFS-measured span-level wind speed sequences, a load–strength interference model-driven method is established to quantify span-level failure probabilities. On this basis, a three-layer resilience assessment framework—“span–line–system”—is constructed, integrating wind field spatial heterogeneity into the full evaluation chain from component damage to system load shedding. This framework overcomes the limitations of the traditional uniform wind speed assumption.
(3) Compared with the conventional line-level hardening strategy, the proposed span-level hardening strategy significantly reduces reinforcement cost compared with the conventional line-level hardening strategy in the reported benchmark case. Moreover, under the same budget constraint, it achieves lower expected load shedding and lower expected asset damage, demonstrating the advantage of fine-grained span-level resource allocation. It provides a measurement-based quantitative basis for reinforcement prioritization in engineering practice.
(4) Finally, for site-specific engineering deployment, the hardening effectiveness coefficient ( β ) should ideally be dynamically calibrated rather than utilizing a uniform empirical value. A dynamic β would be mathematically defined as a function of specific wind speed tiers, local terrain roughness, and distinct tower structures (e.g., tension versus suspension towers). To implement this in practical applications, it is recommended to employ Finite Element Analysis (FEA) to construct structural fragility curves for specific grid components before and after reinforcement. By mapping these fragility shifts under regional extreme wind profiles (such as those along the Fujian coast), engineers can extract a dynamic, multi-dimensional β lookup table. While this paper adopts a uniform β to maintain the linear tractability of the macroscopic MILP model, integrating such data-driven, dynamically calibrated β matrices into heuristic optimization frameworks represents a highly promising direction for future resilience research.

Author Contributions

Conceptualization, M.Z. and Q.G.; methodology, M.Z.; software, M.Z.; validation, M.Z., Q.G., H.Q. and X.L.; formal analysis, M.Z.; investigation, M.Z.; resources, M.Z.; data curation, M.Z. and X.L.; writing—original draft preparation, M.Z.; writing—review and editing, M.Z.; visualization, M.Z.; supervision, M.Z.; project administration, M.Z.; funding acquisition, Q.G. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the National Key R&D Program of China (grant no. 2026ZD0811500).

Data Availability Statement

The data presented in this study are available on request from the corresponding author.

Conflicts of Interest

The authors declare no conflicts of interest.

References

  1. Liu, H.; Wang, C.; Ju, P.; Xu, Z.; Lei, S. A Bi-Level Coordinated Dispatch Strategy for Enhancing Resilience of Electricity-Gas System Considering Virtual Power Plants. Int. J. Electr. Power Energy Syst. 2023, 147, 108787. [Google Scholar] [CrossRef] [Scilit]
  2. Yuan, Z.; Zhang, H.; Cheng, H.; Liu, L.; Liu, J.; Wang, Y.; Cai, D. Resilience Enhancement of Coordinated Transmission and Distribution System via Risk-Based Decentralized Planning against Typhoons. IEEE Trans. Ind. Appl. 2025, 61, 5780–5796. [Google Scholar] [CrossRef] [Scilit]
  3. Zhou, J.; Zhang, H.; Cheng, H.; Zhang, S.; Liu, L.; Wang, Z.; Zhang, X. Resilience-Oriented Hardening and Expansion Planning of Transmission System under Hurricane Impact. CSEE J. Power Energy Syst. 2024, 10, 1746–1760. [Google Scholar] [CrossRef] [Scilit]
  4. Wang, Z.; Wang, Z. A Novel Preventive Islanding Scheme of Power System under Extreme Typhoon Events. Int. J. Electr. Power Energy Syst. 2023, 147, 108857. [Google Scholar] [CrossRef] [Scilit]
  5. Liu, X.; Hou, K.; Jia, H.; Zhao, J.; Mili, L.; Jin, X.; Wang, D. A Planning-Oriented Resilience Assessment Framework for Transmission Systems Under Typhoon Disasters. IEEE Trans. Smart Grid 2020, 11, 5431–5441. [Google Scholar] [CrossRef] [Scilit]
  6. Yang, R.; Li, Y. Resilience Assessment and Improvement for Electric Power Transmission Systems against Typhoon Disasters: A Data-Model Hybrid Driven Approach. Energy Rep. 2022, 8, 10923–10936. [Google Scholar] [CrossRef] [Scilit]
  7. Oh, S.; Jufri, F.H.; Choi, M.-H.; Jung, J. A Study of Tropical Cyclone Impact on the Power Distribution Grid in South Korea for Estimating Damage. Renew. Sustain. Energy Rev. 2022, 156, 112010. [Google Scholar] [CrossRef] [Scilit]
  8. Wang, H.; Xu, Y.; Zhang, J.; Zhao, X.; Zhang, Z.; Chen, K. Fiber-Optic Photoacoustic Gas Microprobe Based on Linear Spot-Type Multipass Cell. Anal. Chem. 2025, 97, 1300–1308. [Google Scholar] [CrossRef] [Scilit]
  9. Zhao, Y.; Hu, X.; Hu, S.; Peng, Y. Applications of Fiber-Optic Biochemical Sensor in Microfluidic Chips: A Review. Biosens. Bioelectron. 2020, 166, 112447. [Google Scholar] [CrossRef] [Scilit]
  10. Schreier, A.; Wosniok, A.; Liehr, S.; Krebber, K. Humidity-Induced Brillouin Frequency Shift in Perfluorinated Polymer Optical Fibers. Opt. Express 2018, 26, 22307–22314. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  11. Jousset, P.; Reinsch, T.; Ryberg, T.; Blanck, H.; Clarke, A.; Aghayev, R.; Hersir, G.P.; Henninges, J.; Weber, M.; Krawczyk, C.M. Dynamic Strain Determination Using Fibre-Optic Cables Allows Imaging of Seismological and Structural Features. Nat. Commun. 2018, 9, 2509. [Google Scholar] [CrossRef] [Scilit] [PubMed]
  12. Lindsey, N.J.; Dawe, T.C.; Ajo-Franklin, J.B. Illuminating Seafloor Faults and Ocean Dynamics with Dark Fiber Distributed Acoustic Sensing. Science 2019, 366, 1103–1107. [Google Scholar] [CrossRef] [Scilit]
  13. Bagheri, A.; Zhao, C.; Qiu, F.; Wang, J. Resilient Transmission Hardening Planning in a High Renewable Penetration Era. IEEE Trans. Power Syst. 2019, 34, 873–882. [Google Scholar] [CrossRef] [Scilit]
  14. Hasanzad, F.; Rastegar, H. Application of Optimal Hardening for Improving Resilience of Integrated Power and Natural Gas System in Case of Earthquake. Reliab. Eng. Syst. Saf. 2022, 223, 108476. [Google Scholar] [CrossRef] [Scilit]
  15. Wang, H.; Hou, K.; Zhao, J.; Yu, X.; Jia, H.; Mu, Y. Planning-Oriented Resilience Assessment and Enhancement of Integrated Electricity-Gas System Considering Multi-Type Natural Disasters. Appl. Energy 2022, 315, 118824. [Google Scholar] [CrossRef] [Scilit]
  16. Hou, H.; Geng, H.; Huang, Y.; Wu, H.; Wu, X.; Yu, S. Damage Probability Assessment of Transmission Line-Tower System Under Typhoon Disaster, Based on Model-Driven and Data-Driven Views. Energies 2019, 12, 1447. [Google Scholar] [CrossRef] [Scilit]
  17. Dikshit, S.; Alipour, A. Characterizing Probability of Failure of Transmission Tower Systems under Multiple Climatic Hazards: Wind and Ice. Eng. Struct. 2025, 342, 120720. [Google Scholar] [CrossRef] [Scilit]
  18. Xu, Y.; Xing, Y.; Huang, Q.; Li, J.; Zhang, G.; Bamisile, O.; Huang, Q. A Review of Resilience Enhancement Strategies in Renewable Power System under HILP Events. Energy Rep. 2023, 9, 200–209. [Google Scholar] [CrossRef] [Scilit]
  19. Jalilpoor, K.; Oshnoei, A.; Mohammadi-Ivatloo, B.; Anvari-Moghaddam, A. Network Hardening and Optimal Placement of Microgrids to Improve Transmission System Resilience: A Two-Stage Linear Program. Reliab. Eng. Syst. Saf. 2022, 224, 108536. [Google Scholar] [CrossRef] [Scilit]
  20. Zhang, W.; Shao, C.; Hu, B.; Xie, K.; Siano, P.; Li, M.; Cao, M. Transmission Defense Hardening against Typhoon Disasters Under Decision-Dependent Uncertainty. IEEE Trans. Power Syst. 2023, 38, 2653–2665. [Google Scholar] [CrossRef] [Scilit]
  21. Tan, C.; Fang, W. Mapping the Wind Hazard of Global Tropical Cyclones with Parametric Wind Field Models by Considering the Effects of Local Factors. Int. J. Disaster Risk Sci. 2018, 9, 86–99. [Google Scholar] [CrossRef] [Scilit]
  22. Guo, J.; Feng, T.; Cai, Z.; Lian, X.; Tang, W. Vulnerability Assessment for Power Transmission Lines Under Typhoon Weather Based on a Cascading Failure State Transition Diagram. Energies 2020, 13, 3681. [Google Scholar] [CrossRef] [Scilit]
  23. Electric Power Research Institute. Transmission Line Reference Book: Wind-Induced Conductor Motion (Orange Book), 2nd ed.; EPRI: Palo Alto, CA, USA, 2009. [Google Scholar]
  24. CIGRÉ Working Group B2.11.01. Overhead Conductor Safe Design Tension with Respect to Aeolian Vibrations; CIGRÉ Technical Brochure 273; CIGRÉ: Paris, France, 2005. [Google Scholar]
  25. Hardy, C.; Van Dyke, P. Field observations on wind-induced conductor motions. J. Fluids Struct. 1995, 9, 43–60. [Google Scholar] [CrossRef] [Scilit]
  26. Païdoussis, M.P.; Price, S.J.; de Langre, E. Fluid–Structure Interactions: Cross-Flow-Induced Instabilities; Cambridge University Press: Cambridge, UK, 2011. [Google Scholar]
  27. Yao, Y.; Wang, R.; Ding, H.; Tong, S.; Han, Y.; Zhao, S.; Zou, N.; Xiong, F.; Zhang, Y. A Fast and Accurate Mapping Method for an OPGW Tower Based on Hybrid Distributed Optical Fiber Sensing. Sensors 2024, 24, 5629. [Google Scholar] [CrossRef] [Scilit]
  28. Xie, K.; Zhang, H.Y.; Zhao, Y.S.; Tian, Y.; Lü, Z.B.; Wei, J.L.; Chai, Q.; Liu, Y.L.; Meng, Y.C.; Zhang, J.Z.; et al. Structural Health Monitoring of Power Transmission System Based on Optical Fiber Sensor Under Transmission Line Galloping. Laser Optoelectron. Prog. 2018, 55, 070606. [Google Scholar] [CrossRef] [Scilit]
  29. GB 50545-2010; Code for Design of 110 kV~750 kV Overhead Transmission Line. China Planning Press: Beijing, China, 2010.
  30. GB 50068-2018; Unified Standard for Reliability Design of Building Structures. Ministry of Housing and Urban-Rural Development of the People’s Republic of China: Beijing, China, 2018.
  31. Nowak, A.S.; Collins, K.R. Reliability of Structures, 2nd ed.; CRC Press: Boca Raton, FL, USA, 2012. [Google Scholar]
  32. Fu, X.; Li, H.N.; Li, G. Fragility analysis and estimation of collapse status for transmission tower subjected to wind and rain loads. Struct. Saf. 2016, 58, 1–10. [Google Scholar] [CrossRef] [Scilit]
  33. Cai, Y.; Xie, Q.; Xue, S.; Hu, L.; Kareem, A. Fragility modelling framework for transmission line towers under winds. Eng. Struct. 2019, 191, 686–697. [Google Scholar] [CrossRef] [Scilit]
  34. Darestani, Y.M.; Shafieezadeh, A. Multi-dimensional wind fragility functions for wood utility poles. Eng. Struct. 2019, 183, 937–948. [Google Scholar] [CrossRef] [Scilit]
  35. IEC 60826:2003; Design Criteria of Overhead Transmission Lines. International Electrotechnical Commission: Geneva, Switzerland, 2003.
  36. GB 50009-2012; Load Code for the Design of Building Structures. Ministry of Housing and Urban-Rural Development of the People’s Republic of China: Beijing, China, 2012.
  37. Song, L.; Chen, W.; Wang, B.; Zhi, S.; Liu, A. Characteristics of wind profiles in the landfalling typhoon boundary layer. J. Wind Eng. Ind. Aerodyn. 2016, 149, 77–88. [Google Scholar] [CrossRef] [Scilit]
  38. Wang, W.; Shi, L.; Qiu, Z. Multi-Indicator Fused Resilience Assessment of Power Grids Considering Wind-Photovoltaic Output Uncertainty During Typhoon Disasters. Electronics 2024, 13, 745. [Google Scholar] [CrossRef] [Scilit]
  39. Zhang, H.; Cheng, L.; Yao, S.; Zhao, T.; Wang, P. Spatial–Temporal Reliability and Damage Assessment of Transmission Networks Under Hurricanes. IEEE Trans. Smart Grid 2020, 11, 1044–1054. [Google Scholar] [CrossRef] [Scilit]
  40. Zhang, H.; Cheng, H.; Liu, L.; Zhang, S.; Zhou, Q.; Jiang, L. Coordination of Generation, Transmission and Reactive Power Sources Expansion Planning with High Penetration of Wind Power. Int. J. Electr. Power Energy Syst. 2019, 108, 191–203. [Google Scholar] [CrossRef] [Scilit]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.