A Tool for a Fast and Accurate Evaluation of the Energy Production of Bifacial Photovoltaic Modules
Abstract
1. Introduction
2. The Tool
2.1. Block #1
- The latitude ϕ and the local longitude , denoted as , of the geographical site where the PV module is installed (ϕ is equal to 0° at the equator and ranges from 0° to 90° to the north and from 0° to −90° to the south; is equal to 0° at the Prime, or Greenwich, meridian, and ranges from 0° to 180° to the east and from 0° to −180° to the west).
- The longitude of the standard meridian on which the clock time (CKT, also referred to as watch time or standard local time) is based.
- The day of the year n.
- The CKT values during the day, i.e., the daytime discretization.
- and calculates
- The solar declination δ, i.e., the angle between the Sun rays (the beam radiation) and the equatorial plane, which is positively defined in the northern hemisphere. Angle δ can be reasonably assumed constant during a day (it varies by at most 0.5°) and is dependent on the day of the year n through the empirical Cooper’s relationOn the summer solstice, δ assumes the maximum value of 23.45° (23°27′); on the winter solstice, it is equal to the minimum value of −23.45° (−23°–27′); δ = 0° on the spring and autumn equinoxes. It must be observed that (1) assumes a year of exactly 365 days, that is, it does not account for the extra 0.2422 days. Over a span of four years, this approximation would result in a deviation of about one day. One way to modify (1) is to adjust the constant 360/365 to 360/365.24 in the sine argument; however, this adjustment is not strictly necessary, as the error introduced is negligible.
- The so-called True Local Time (TLT), which can be obtained from the CKT by applying two corrections. The first correction is dictated by the difference between the local longitude and the longitude of the standard meridian ; more specifically, the displacement of 1° between these longitudes corresponds to 4 min. The second correction is made to account for the non-constancy of the rotation rate of the Earth around the Sun during the year. This effect can be described by introducing a characteristic time referred to as Equation of Time (Eqt), expressed in minutes, which depends on n through the following relation [21,22,23]:with K1 = 229.2 min, K2 = 0.000075, K3 = 0.001868, K4 = 0.032077, K5 = 0.014615, and K6 = 0.04089 [22,23] (or 0.040849 [21] without appreciable Eqt variation). By applying both corrections, under standard time (standard conditions) the relation between TLT (in hours) and CKT is given bywhich, under daylight-saving time/conditions, is modified intothat is, a further hour must be deducted.
- The hour angle ω, i.e., the angular displacement of the Sun with respect to the local meridian compared to the case in which TLT = 12 due to the rotation from west to east of the Earth around its axis (also denoted as angle subtended by the Sun [24]). Angle ω is negative in the morning, positive in the afternoon, and given by [21,23,25,26,27,28]As can be seen, a one-hour deviation corresponds to a displacement of 15°.
- The solar altitude, or elevation, α, i.e., the angle between the horizontal plane (also denoted as plane of horizon) and the Sun rays, positive during daytime; α is a function of latitude ϕ, solar declination δ, and hour angle ω according to [21,24,25,26,27]The outcomes of block #1 for some application examples are reported in Table 1.
2.2. Block #2
- The latitude ϕ of the site.
- The CKT values.
- The azimuth angle of the module front γ, which defines the module orientation, as it is the angular displacement from the south of the projection of the normal to the module front onto the horizontal plane. An azimuth γ = 0° means that the front is south-oriented; γ is positive clockwise (to west), reaching 180° next to north, and is negative counter-clockwise (to east), reaching −180° next to north [22]. Hence, γ = 90° corresponds to a module with a west-oriented front, while γ = −90° identifies an east-oriented front.
- The tilt angle of the module front β, which is the inclination with respect to the horizontal plane.
- The solar declination δ and the hour angle ω computed by block #1.
- and calculates
- The azimuth angle of the module rear .
- The tilt angle of the module rear as the supplement of β, that is, .
- It can be inferred that θ = 0° for a horizontal module (β = 0°) at the equator (ϕ = 0°) at TLT = 12 (noon, ω = 0°) of the equinoxes (δ = 0°); angle θ may exceed 90°, which means that the Sun is behind the surface.
- As an example, if it is required to determine the angle of incidence of the Sun rays on the front of a module installed at Madison, WI, USA, with orientation γ = 15° and tilt β = 45° at CKT = 10.7 (10:42 AM) on February 13 (n = 44), then block #1 evaluates that δ = −13.95°, Eqt = −14.26 min, TLT = 10.50 (10:30 AM), ω = −22.50°, α = 29.38°, and block #2 calculates θ = 35° [22].
- is the angle between the Sun rays and the normal to the module back, and is computed as or equivalently from
- Figure 2 is intended to provide a clear understanding of some key angles introduced so far.
2.3. Block #3
- The solar altitude α evaluated by block #1.
- The azimuth angles , , the tilt angles , , and the incidence angles θ, .
- The total irradiance , the diffuse irradiance hitting the horizontal plane (the beam, or direct, irradiance is determined as ), and the ambient temperature vs. CKT at the selected geographical site. For the analysis performed in Section 3, these data were taken from the PhotoVoltaic Geographical Information System (PVGIS) website [29]. Here, it is stated that they were evaluated for the mean day of the chosen month from satellite data through a sophisticated algorithm accounting for sky obstruction (shading) by local terrain features (hills or mountains) calculated from a digital elevation model.
- The albedo value, namely, the ratio of the reflected upward radiation from the ground to the incident downward radiation upon it (typical albedo values are 0.04 for fresh asphalt, 0.1–0.15 for soil ground, 0.25–0.3 for green grass, 0.4 for desert sand, 0.55 for fresh concrete, and 0.8–0.85 for freshly fallen snow).
- Some key parameters available in the datasheet, i.e., the temperature (or ), the short-circuit current , and the percentage temperature coefficient of the short-circuit current , the definitions of which will be provided in the following.
- The block calculates
- The diffuse irradiance on the front coming from the sky, for which there are two options.
- If the sky is completely and densely overcast, the same irradiance comes from any point of the sky, which is thus called isotropic. In this case, the diffuse irradiance is expressed aswhere the dimensionless front-sky view factor (≤1) accounts for the reduction of the sky dome due to the tilt angle β; using the cross-string approach [34], it can be easily determined thatFormulation (11), sometimes referred to as Kondrat’yev’s view factor [35], is widely accepted [2,9,10,12,13,21,22,23,24,25,26,30,31,36,37,38,39,40,41,42,43,44], and coincides with the ratio between the projection onto the horizontal plane of the portion of the hemisphere seen from the tilted panel and the projection of the whole sky dome [45].
- If the sky is clear or at least partially cloudy, the diffuse irradiance depends on the position of the Sun in the sky due to effects like horizon brightening and circumsolar radiation, and the sky is thus referred to as anisotropic. In this case, the diffuse irradiance can be expressed aswhere the front-sky view factor is given by the sum of two terms and accounting for the horizon brightening and circumsolar radiation, respectively [22,31,33].In (13),and is the anisotropic index, given bywhere is the solar irradiance incident on a horizontal plane outside the atmosphere, also referred to as extraterrestrial irradiance on a horizontal surface, whose expression is [22,33]being the solar constant.
- Differently from the isotropic view factor , the anisotropic one can be >1 if the panel is oriented to the portion of the sky dome where the Sun is located. It is worth noting that reduces to if (uniformly cloudy, or isotropic, sky), which implies that and .
- The diffuse irradiance on the front due to the reflection from the ground, typically considered as a Lambertian (isotropic) process, calculated aswhere the front-ground view factor is expressed as [2,9,10,12,13,21,22,23,30,31,32,33,36,37,38,39,40,42,44,46,47]Model (18) works quite well in the entire range of practical β values, namely, from β = 0° (horizontal panel) to β = 90° (vertically-deployed panel); if β = 0° since the panel front does not see the ground (it only sees the sky); increases with β and becomes eventually equal to 0.5 if β = 90° since the front sees half ground.
- It is worth noting that under isotropic conditions the sum of the front-sky and front-ground view factors is 1, that is,
- The beam irradiance landing on the rear
- The diffuse irradiance on the rear coming from the sky. Analogously to the module front, there are two possible options.
- The diffuse irradiance on the rear due to the reflection from the ground, which deserves significant attention, as discussed in our recent work [48]. One might mistakenly apply the same approach used for the frontside and express this irradiance aswith the rear-ground view factor given by [41,42,43,44]
- Unfortunately, different from (17), model (25) does not provide physically meaningful results within the range of practical β values. If β is reduced from 90° to 0°, increases, eventually becoming 1 for β = 0° (horizontal panel with the frontside oriented towards the sky and backside lying on the ground); as a result, incorrectly increases as β decreases and reaches its maximum value for β = 0° when instead it should be 0 W/m2, as the ground beneath the flat panel cannot reflect sunlight. This is the consequence of the incorrectness of (25), which assumes that the ground reflects an irradiance given by independently of the inclination of the module and thus of the sky dome visible to the ground. In addition, (25) does not consider the shadow cast by the module itself onto the ground (self-shading) and does not include the dependence upon the vertical distance d between the module edge and the ground. The standard strategy to account for the self-shading is to express as [6,9,13,42,47,49]where is the view factor between rear and unshaded ground, whereas is the view factor between rear and ground shaded by the panel. For the case d = 0 (lowest panel edge in contact with the ground), such view factors can be determined by resorting to the cross-string rule and are given by [42,48]
- It is worth noting thatHowever, also (27) provides unreasonable results since incorrectly increases with decreasing β and tends to its maximum value for β = 0°, when it is expected to be 0 W/m2 since the backside lies flat on the ground.
- In [48], we proposed an improved version of (27) to solve this inconsistency, namely,where is the view factor between shaded ground and sky, and is given byOur modeling methodology includes formulation (31) with (28), (29), and (32) for , , and , as well as extended variants for these view factors to capture the case of panels mounted on a suspended framework (d > 0 m) [48]. Figure 3 clearly demonstrates the physical validity of our approach. More specifically, such a figure shows the behavior of the 1st and 2nd terms on the right-hand side (RHS) of (31), namely, and by varying β for , , albedo = 0.5, d = 0 m, with α = 30° (Figure 3a) and α = 50° (Figure 3b). It can be inferred that, if β = 0°, both contributions are equal to 0 W/m2, as the backside entirely lies on the ground, so that and, despite , the 2nd term is equal to 0 since the shaded area of the ground does not see the sky (). Also shown in Figure 3 is the meaningless behavior that would be obtained by using the 2nd term on the RHS of (27). Further details can be found in [48].

- The reduction in beam irradiance on the front due to optical losses under realistic operating conditions [50] is modeled by multiplying the irradiance (9) by a dimensionless reduction factor dependent on the incidence angle θ and given bywhere is an empirical parameter; τ is forced to be 0 for θ values giving rise to or . In a similar fashion, the reduction in beam irradiance on the rear is described by multiplying the irradiance (20) byThe optical losses affecting the total diffuse irradiance given by the sum of the sky and ground contributions are only negligibly dependent on θ, and thus they are incorporated by multiplying the diffuse irradiance on both front and rear by a constant reduction factor (typically in the range of 0.9 to 0.95).
- The total irradiances on the front (G) and rear (). As first suggested in [30] and commonly accepted since then, the evaluation of the total irradiance hitting the panel is performed by summing the contributions due to the beam irradiance, the diffuse irradiance from the sky, and the diffuse irradiance reflected from the ground (transposition approach).
- Concerning the front,for an isotropic sky, orfor an anisotropic one.
- Concerning the rear,for an isotropic sky, andfor an anisotropic one.
- The operating temperature T of the cells as a function of CKT. By disregarding the self-heating, which is a reasonable approximation when the cells are producing power, T [°C] is a function of , , and according to the following law [6,9,12,51]:where is the nominal operating temperature (NOCT) measured on the panel backside under open-circuit conditions at , nominal irradiance , air mass AM 1.5, and wind speed lower than 1 m/s. As mentioned earlier, vs. CKT at the selected geographical site is taken from PVGIS, and the total irradiances on the module front (G) and rear () are evaluated by the tool. In (39), it is in principle possible to multiply by an empirical coefficient c (<1) related to the bifaciality factor, i.e., the ratio between the power produced by the rear illuminated under standard test conditions (STCs) while the front is covered, and the power produced by the front illuminated under STCs while the rear is covered; STCs are defined below. Formulation (39) is also referred to as the NOCT model.
- On the other hand, as lucidly expressed in [52], in recent years manufacturers have questioned the uncertainty due to large fluctuations in NOCT and have expressed doubts about the reliability of NOCT-based energy assessments. Consequently, NOCT tests have been replaced by nominal module operating temperature (NMOT) tests; represents the temperature measured on the backside while the module is connected to a load, the experimental procedure being reported in [52,53]. For modern bifacial modules, whose datasheets provide , the tool computes the cell temperature T aswhere is the temperature difference between the cell and backside at , usually in the range of 2 to 3 °C. Formulation (40) is denoted as NMOT model.
- Once the irradiance G and the temperature T vs. CKT are known, the current photogenerated by the module front is evaluated at each CKT as [24,54]where the datasheet parameter is the short-circuit current measured by keeping the frontside under STCs, i.e., nominal irradiance , 1.5 AM, and cell temperature equal to 25 °C, and covering the backside or at least markedly limiting its irradiance. It is worth noting that the first term on the RHS is the photogenerated current that would be obtained for an irradiance G at T = 25 °C. The temperature coefficient κ [A/°C] can be easily determined from the datasheet parameter [%/°C], namely, the percentage temperature coefficient of measured by the module manufacturer under the same conditions mentioned above; is given by
- Equation (41) allows capturing the positive temperature coefficient of due to the bandgap shrinking and the resulting increase in the number of photons with enough energy to generate electron–hole pairs, and can be recast aswhere is a reference temperature and ; by assuming for consistency with PSPICE [41,55],
- The current photogenerated by the module rear vs. CKT is calculated aswhere ERF (<1) is an efficiency reduction factor needed to account for the fact that the PV cell is asymmetric, being technologically designed to maximize light absorption on the front, and T is given by (39) or (40).
2.4. Block #4
- The module is composed of N series-connected cells, each modeled with a subcircuit implementing the SDM described above, which is fed with G, , and .
- The module can be partitioned into a chosen number of subpanels, each equipped with a bypass diode.
- The PSPICE temperature of all components embedded in the circuit is forced to the reference value ; the temperature rise , represented as a voltage, is provided to analog behavioral modeling, or ABM, components, i.e., nonlinear current/voltage sources, to modify the temperature-sensitive parameters (e.g., [69]).
2.5. Simplified Variant of the Tool for Monofacial Modules
- Block #1 coincides with the analogous block of the tool for bifacial panels.
- Block #2 only determines the incidence angle θ.
- Block #4 solves the SDM only with the source for the current photogenerated by the front.
3. Results and Discussion
3.1. Optimization of Orientation and Tilt for a Bifacial Module
- By specifically referring to the monofacial module, the energy produced by orienting the frontside to the west is slightly better than the one obtained by orienting it to the east; this result is reasonable since Naples faces the sea to the west, while mountains lie to the east.
- As a main finding, it is observed that in these cases the bifacial module allows achieving a significant improvement. While the monofacial panel receives beam irradiance for only half of the day, bifacial panels benefit from effective beam irradiance (hitting the module sides with low incidence angles) both in the morning (rear for a west-oriented panel, as sketched in Figure 6b, and front for an east-oriented one) and afternoon (the other way around).
- West- and east-oriented vertical bifacial panels produce the same amount of energy.
- West- and east-oriented vertical bifacial modules offer improved performance with respect to the reference monofacial counterpart during the time span from April to September, in which they benefit from a low incidence angle of the Sun rays hitting the front and rear of the panel in the mid-morning and mid-afternoon [1,5,10]. In terms of yearly energies (all reported in Table 2), the gain compared with the reference monofacial case amounts to 3%, 21%, and 37% for albedo values of 0.2, 0.5, and 0.8, respectively.
- West- and east-oriented vertical bifacial modules also provide a considerable production improvement with respect to the south-oriented vertical bifacial counterpart, which is estimated to be 17%, 14%, and 11% for albedo values of 0.2, 0.5, and 0.8, respectively. This is again due to the much better performance of west- and east-oriented panels from April to September, while during wintertime the south-oriented module performs better. An in-depth insight into this behavior can be achieved by showing the normalized maximum power over CKT on July 15 (Figure 11a) and December 15 (Figure 11b) for such cases. In July (and more in general during the whole period from late spring to early autumn), it is confirmed that the orientations of the module front to west and east allow for a very effective exploitation of the beam light impinging on one of the two sides in the mid-morning and on the other in the mid-afternoon, whereas in December (and more in general during wintertime) the orientation to south is better over the mid-day. Throughout the whole year, the first effect markedly prevails over the second.


3.2. Nonuniform Irradiance Distribution over the Panel Rear
- G = 412 W/m2, , T = 43.2 °C, , at 11:00 AM
- G = 147 W/m2, , T = 44.1 °C, , at 3:00 p.m.
- The normalized power vs. voltage characteristics of the module under uniform irradiance conditions are reported in Figure 13a (CKT = 11:00 AM) and 13b (CKT = 3:00 PM); the maximum powers normalized to the peak value provided in the datasheet are 0.51 and 0.48, respectively. A likely case of a mud spot partially covering the rear of cell #10, sketched in Figure 14, was then considered, which was assumed to reduce the irradiance down to 10% of that of the clean cells. As can be seen, the PSPICE simulations lead to a counter-intuitive result, that is, although the spot is located on the rear, submodule #1 embedding cell #10 is bypassed also in the morning (CKT = 11:00 AM) when the Sun rays hit the module front; such surprising detrimental behavior cannot be overlooked for a more complete comparison between west- or east-oriented vertical bifacial panels and the reference monofacial counterpart. In the afternoon (CKT = 3:00 PM), when the Sun rays impinge on the backside, the power production dramatically drops, as expected.
3.3. Cracked Cell(s)
3.4. Summary of the Main Advantages of the Tool and Comparison with Other Programs
- High flexibility, that is, straightforward customization; it is very easy to modify an analytical model or integrate a new one, to adjust the value of a parameter, and so on.
- Simple monitoring and storing of all the relevant quantities for better insight into the panel behavior and performance.
- Capability of performing extensive simulation campaigns (e.g., parametric studies) in a short time.
- Inclusion of an innovative, physically-meaningful albedo reflection modeling strategy.
- Accurate description of the effects of (even small) architectural or cloud-induced shadows, bird drops, localized accumulation of dirt, dust, snow, other residues, and presence of defective/cracked cells through the PSPICE-based block #4 that benefits from cell-level discretization.
4. Conclusions
Author Contributions
Funding
Institutional Review Board Statement
Informed Consent Statement
Data Availability Statement
Conflicts of Interest
References
- Guo, S.; Walsh, T.M.; Peters, M. Vertically mounted bifacial photovoltaic modules: A global analysis. Energy 2013, 61, 447–454. [Google Scholar] [CrossRef]
- Appelbaum, J. Bifacial photovoltaic panels field. Renew. Energy 2016, 85, 338–343. [Google Scholar] [CrossRef]
- Guerrero-Lemus, R.; Vega, R.; Kim, T.; Kimm, A.; Shephard, L.E. Bifacial solar photovoltaics—A technology review. Renew. Sustain. Energy Rev. 2016, 60, 1533–1549. [Google Scholar] [CrossRef]
- Deline, C.; MacAlpine, S.; Marion, B.; Toor, F.; Asgharzadeh, A.; Stein, J.S. Assessment of bifacial photovoltaic module power rating methodologies–Inside and out. IEEE J. Photovolt. 2017, 7, 575–580. [Google Scholar] [CrossRef]
- Sun, X.; Khan, M.R.; Deline, C.; Alam, M.A. Optimization and performance of bifacial solar modules: A global perspective. Appl. Energy 2018, 212, 1601–1610. [Google Scholar] [CrossRef]
- Gu, W.; Ma, T.; Ahmed, S.; Zhang, Y.; Peng, J. A comprehensive review and outlook of bifacial photovoltaic (bPV) technology. Energy Convers. Manag. 2020, 223, 113283. [Google Scholar] [CrossRef]
- Kopecek, R.; Libal, J. Bifacial photovoltaics 2021: Status, opportunities and challenges. Energies 2021, 14, 2076. [Google Scholar] [CrossRef]
- Bouchakour, S.; Valencia-Caballero, D.; Luna, A.; Roman, E.; Boudjelthia, E.A.K.; Rodriguez, P. Modelling and simulation of bifacial PV production using monofacial electrical models. Energies 2021, 14, 4224. [Google Scholar] [CrossRef]
- Mouhib, E.; Micheli, L.; Almonacid, F.M.; Fernández, E.F. Overview of the fundamentals and applications of bifacial photovoltaic technology: Agrivoltaics and aquavoltaics. Energies 2022, 15, 8777. [Google Scholar] [CrossRef]
- Garrod, A.; Ghosh, A. A review of bifacial solar photovoltaic applications. Front. Energy 2023, 17, 704–726. [Google Scholar] [CrossRef]
- Zhong, J.; Zhang, W.; Xie, L.; Zhao, O.; Wu, X.; Zeng, X.; Guo, J. Development and challenges of bifacial photovoltaic technology and application in buildings: A review. Renew. Sustain. Energy Rev. 2023, 187, 113706. [Google Scholar] [CrossRef]
- Rodríguez-Gallegos, C.D.; Bieri, M.; Gandhi, O.; Singh, J.P.; Reindl, T.; Panda, S.K. Monofacial vs bifacial Si-based PV modules: Which one is more cost effective? Sol. Energy 2018, 176, 412–438. [Google Scholar] [CrossRef]
- Gu, W.; Ma, T.; Li, M.; Shen, L.; Zhang, Y. A coupled optical-electrical-thermal model of the bifacial photovoltaic module. Appl. Energy 2020, 258, 114075. [Google Scholar] [CrossRef]
- Riaz, M.H.; Imran, H.; Younas, R.; Alam, M.A.; Butt, N.Z. Module technology for agrivoltaics: Vertical bifacial versus tilted monofacial farms. IEEE J. Photovolt. 2021, 11, 469–477. [Google Scholar] [CrossRef]
- Ayadi, O.; Jamra, M.; Jaber, A.; Ahmad, L.; Alnaqep, M. An experimental comparison of bifacial and monofacial PV modules. In Proceedings of the IEEE International Renewable Engineering Conference (IREC), Amman, Jordan, 14–15 April 2021. [Google Scholar]
- Tina, G.M.; Bontempo Scavo, F.; Merlo, L.; Bizzarri, F. Comparative analysis of monofacial and bifacial photovoltaic modules for floating power plants. Appl. Energy 2021, 281, 116084. [Google Scholar] [CrossRef]
- Matarneh, G.A.; Al-Rawajfeh, M.A.; Gomaa, M.R. Comparison review between monofacial and bifacial solar modules. Technol. Audit Prod. Reserves–Alternat. Renew. Energy Sources 2022, 6, 24–29. [Google Scholar] [CrossRef]
- Eidiani, M.; Zeynal, H.; Ghavami, A.; Zakaria, Z. Comparative analysis of mono-facial and bifacial photovoltaic modules for practical grid-connected solar power plant using PVsyst. In Proceedings of the IEEE International Conference on Power and Energy (PECon), Langkawi, Malaysia, 5–6 December 2022; pp. 499–504. [Google Scholar]
- Juaidi, A.; Kobari, M.; Mallak, A.; Titi, A.; Abdallah, R.; Nassar, M.; Albatayneh, A. A comparative simulation between monofacial and bifacial PV modules under Palestine conditions. Sol. Compass 2023, 8, 100059. [Google Scholar] [CrossRef]
- PSPICE User’s Manual. In Cadence OrCAD, Version 16.5; Cadence Design Systems, Inc.: San Jose, CA, USA, 2011.
- Eicker, U. Solar Technologies for Buildings; John Wiley & Sons Ltd: Chichester, UK, 2003. [Google Scholar]
- Duffie, J.A.; Beckman, W.A. Solar Engineering of Thermal Processes, 3rd ed.; John Wiley & Sons, Inc.: Hoboken, NJ, USA, 2006. [Google Scholar]
- Tiwari, G.N.; Dubey, S. Fundamentals of Photovoltaic Modules and Their Applications; The Royal Society of Chemistry (RSC): Cambridge, UK, 2010. [Google Scholar]
- Passias, D.; Källbäck, B. Shading effects in rows of solar cell panels. Sol. Cells 1984, 11, 281–291. [Google Scholar] [CrossRef]
- Appelbaum, J.; Bany, J. Shadow effect of adjacent solar collectors in large scale systems. Sol. Energy 1979, 23, 497–507. [Google Scholar] [CrossRef]
- Bany, J.; Appelbaum, J. The effect of shading on the design of a field of solar collectors. Sol. Cells 1987, 20, 201–228. [Google Scholar] [CrossRef]
- Messenger, R.A.; Ventre, J. Photovoltaic System Engineering, 2nd ed.; CRC Press: Boca Raton, FL, USA, 2004. [Google Scholar]
- Sadineni, S.B.; Boehm, R.F.; Hurt, R. Spacing analysis of an inclined solar collector field. In Proceedings of the ASME 2nd International Conference on Energy Sustainability, Jacksonville, FL, USA, 10–14 August 2008. [Google Scholar]
- PVGIS—PhotoVoltaic Geographical Information System. Available online: https://pvgis.com/ (accessed on 4 March 2024).
- Liu, B.Y.H.; Jordan, R.C. A rational procedure for predicting the long-term average performance of flat-plate solar-energy collectors—With design data for the U.S., its outlying possessions and Canada. Sol. Energy 1963, 7, 53–74. [Google Scholar] [CrossRef]
- Reindl, D.T.; Beckman, W.A.; Duffie, J.A. Evaluation of hourly tilted surface radiation models. Sol. Energy 1990, 45, 9–17. [Google Scholar] [CrossRef]
- Quaschning, V.; Hanitsch, R. Shade calculations in photovoltaic systems. In Proceedings of the ISES Solar World Conference, Harare, Zimbabwe, 11–15 September 1995. [Google Scholar]
- Yang, H.; Lu, L. The optimum tilt angles and orientations of PV claddings for building-integrated photovoltaic (BIPV) applications. ASME J. Sol. Energy Eng. 2007, 129, 253–255. [Google Scholar] [CrossRef]
- Hottel, H.C.; Sarofim, A.F. Radiative Transfer; McGraw-Hill: New York, NY, USA, 1967. [Google Scholar]
- Kondrat’yev, K.Ya. Radiative Heat Exchange in the Atmosphere; Pergamon Press: Oxford, NY, USA, 1965. [Google Scholar]
- Garnier, B.J.; Ohmura, A. The evaluation of surface variations in solar radiation income. Sol. Energy 1970, 13, 21–34. [Google Scholar] [CrossRef]
- Calabrò, E. Determining optimum tilt angles of photovoltaic panels at typical north-tropical latitudes. J. Renew. Sustain. Energy 2009, 1, 033104. [Google Scholar] [CrossRef]
- Gueymard, C.A. Direct and indirect uncertainties in the prediction of tilted irradiance for solar engineering applications. Sol. Energy 2009, 83, 432–444. [Google Scholar] [CrossRef]
- Gueymard, C.A.; Myers, D. Solar resource for space and terrestrial application. In Solar Cells and Their Applications, 2nd ed.; Fraas, L., Partain, L., Eds.; John Wiley & Sons, Inc.: Hoboken, NJ, USA, 2010; Chapter 19; pp. 427–461. [Google Scholar]
- Maor, T.; Appelbaum, J. View factors of photovoltaic collector systems. Sol. Energy 2012, 86, 1701–1708. [Google Scholar] [CrossRef]
- d’Alessandro, V.; Magnani, A.; Codecasa, L.; Di Napoli, F.; Guerriero, P.; Daliento, S. Dynamic electrothermal simulation of photovoltaic plants. In Proceedings of the IEEE 5th International Conference on Clean Electrical Power (ICCEP), Taormina, Italy, 16–18 June 2015; pp. 682–688. [Google Scholar]
- Appelbaum, J. The role of view factors in solar photovoltaic fields. Renew. Sustain. Energy Rev. 2018, 81, 161–171. [Google Scholar] [CrossRef]
- Guerriero, P.; Codecasa, L.; d’Alessandro, V.; Daliento, S. Dynamic electro-thermal modeling of solar cells and modules. Sol. Energy 2019, 179, 326–334. [Google Scholar] [CrossRef]
- Durusoy, B.; Ozden, T.; Akinoglu, B.G. Solar irradiation on the rear surface of bifacial solar modules: A modeling approach. Sci. Rep. 2020, 10, 13300. [Google Scholar] [CrossRef]
- Rakovec, J.; Zakšek, K. On the proper analytical expression for the sky-view factor and the diffuse irradiation of a slope for an isotropic sky. Renew. Energy 2012, 37, 440–444. [Google Scholar] [CrossRef]
- Yang, D.; Dong, Z.; Nobre, A.; Khoo, Y.S.; Jirutitijaroen, P.; Walsh, W.M. Evaluation of transposition and decomposition models for converting global solar irradiance from tilted surface to horizontal in tropical regions. Sol. Energy 2013, 97, 369–387. [Google Scholar] [CrossRef]
- Yusufoglu, U.A.; Lee, T.H.; Pletzer, T.M.; Halm, A.; Koduvelikulathu, L.J.; Comparotto, C.; Kopecek, R.; Kurz, H. Simulation of energy production by bifacial modules with revision of ground reflection. Energy Procedia 2014, 55, 389–395. [Google Scholar] [CrossRef]
- d’Alessandro, V.; Daliento, S.; Dhimish, M.; Guerriero, P. Albedo reflection modeling in bifacial photovoltaic modules. Solar 2024, 4, 660–673. [Google Scholar] [CrossRef]
- Yusufoglu, U.A.; Pletzer, T.M.; Koduvelikulathu, L.J.; Comparotto, C.; Kopecek, R.; Kurz, H. Analysis of the annual performance of bifacial modules and optimization methods. IEEE J. Photovolt. 2015, 5, 320–328. [Google Scholar] [CrossRef]
- Krauter, S.; Hanitsch, R. Actual optical and thermal performance of PV-modules. Sol. Energy Mater. Sol. Cells 1996, 41/42, 557–574. [Google Scholar] [CrossRef]
- Leonardi, M.; Corso, R.; Milazzo, R.G.; Connelli, C.; Foti, M.; Gerardi, C.; Bizzarri, F.; Privitera, S.M.S.; Lombardo, S.A. The effects of module temperature on the energy yield of bifacial photovoltaics: Data and model. Energies 2022, 15, 22. [Google Scholar] [CrossRef]
- Bae, J.-H.; Kim, D.-Y.; Shin, J.-W.; Lee, S.-E.; Kim, K.-C. Analysis on the features of NOCT and NMOT tests with photovoltaic module. IEEE Access 2000, 8, 151546–151554. [Google Scholar] [CrossRef]
- Liu, T.; Xu, X.; Zhang, Z.; Xiao, J.; Yu, Y.; Jaubert, J.-N. Bifacial PV module operating temperature: High or low? A cross-comparison of thermal modeling results with outdoor on-site measurements. In Proceedings of the IEEE Photovoltaic Specialists Conference (PVSC), Fort Lauderdale, FL, USA, 20–25 June 2021; pp. 2070–2073. [Google Scholar]
- Rauschenbach, H.S. Solar Cell Array Design Handbook—The Principles and Technology of Photovoltaic Energy Conversion; Van Nostrand Reinhold Company: New York, NY, USA, 1980. [Google Scholar]
- d’Alessandro, V.; Di Napoli, F.; Guerriero, P.; Daliento, S. A novel circuit model of PV cell for electrothermal simulations. In Proceedings of the 3rd Renewable Power Generation (RPG) Conference, Naples, Italy, 24–25 September 2014. [Google Scholar]
- d’Alessandro, V.; Di Napoli, F.; Guerriero, P.; Daliento, S. An automated high-granularity tool for a fast evaluation of the yield of PV plants accounting for shading effects. Renew. Energy 2015, 83, 294–304. [Google Scholar] [CrossRef]
- Bishop, J.W. Computer simulation of the effects of electrical mismatches in photovoltaic cell interconnection circuits. Sol. Cells 1988, 25, 73–89. [Google Scholar] [CrossRef]
- d’Alessandro, V.; Sasso, G.; Rinaldi, N.; Aufinger, K. Thermal behavior of toward-THz SiGe:C HBTs. IEEE Trans. Electron Devices 2014, 61, 3386–3394. [Google Scholar] [CrossRef]
- Banerjee, S.; Andreson, W.A. Temperature dependence of shunt resistance in photovoltaic devices. Appl. Phys. Lett. 1986, 49, 38–40. [Google Scholar] [CrossRef]
- Ding, J.; Cheng, X.; Fu, T. Analysis of series resistance and P–T characteristics of the solar cell. Vacuum 2005, 77, 163–167. [Google Scholar] [CrossRef]
- d’Alessandro, V.; Guerriero, P.; Daliento, S. A simple bipolar transistor-based bypass approach for photovoltaic modules. IEEE J. Photovolt. 2014, 1, 405–413. [Google Scholar] [CrossRef]
- Catalano, A.P.; Scognamillo, C.; Guerriero, P.; Daliento, S.; d’Alessandro, V. Using EMPHASIS for the thermography-based fault detection in photovoltaic plants. Energies 2021, 14, 1559. [Google Scholar] [CrossRef]
- Tsai, H.-L. Insolation-oriented model of photovoltaic module using Matlab/Simulink. Sol. Energy 2010, 84, 1318–1326. [Google Scholar] [CrossRef]
- Celsa, G.; Tina, G.M. Matlab/Simulink model of photovoltaic modules/strings under uneven distribution of irradiance and temperature. In Proceedings of the 6th International Renewable Energy Congress (IREC), Sousse, Tunisia, 24–26 March 2015. [Google Scholar]
- Wang, K.; Ma, J.; Man, K.L.; Hong, D.; Huang, K.; Huang, X. Real-time modeling of photovoltaic strings under partial shading conditions. In Proceedings of the 10th IEEE Data Driven Control and Learning Systems (DDCLS) Conference, Suzhou, China, 14–16 May 2021. [Google Scholar]
- Codecasa, L.; d’Alessandro, V.; Magnani, A.; Rinaldi, N.; Zampardi, P.J. FAst Novel Thermal Analysis Simulation Tool for Integrated Circuits (FANTASTIC). In Proceedings of the 20th International Workshop on THERMal Investigations on ICs and Systems (THERMINIC), Greenwich, London, UK, 24–26 September 2014. [Google Scholar]
- COMSOL Multiphysics, User’s Guide, Release 5.3a, Dec. 2017. Available online: https://www.comsol.it/blogs/introducing-comsol-software-version-5-3a (accessed on 4 March 2024).
- Codecasa, L.; D’Amore, D.; d’Alessandro, V. TONIC: TOol for Nonlinear BCI CTMs of Integrated Circuits. In Proceedings of the 27th International Workshop on THERMal Investigations on ICs and Systems (THERMINIC), Berlin, Germany (held in remote mode), 23 September 2021. [Google Scholar]
- Nenadović, N.; d’Alessandro, V.; La Spina, L. Restabilizing mechanisms after the onset of thermal instability in bipolar transistors. IEEE Trans. Electron Devices 2006, 53, 643–653. [Google Scholar] [CrossRef]
- Heywood, H. Operating experience with solar water heating. J. Inst. Heat. Vent. Eng. 1971, 39, 63–69. [Google Scholar]
- Dhimish, M.; d’Alessandro, V.; Daliento, S. Investigating the impact of cracks on solar cells performance: Analysis based on nonuniform and uniform crack distributions. IEEE Trans. Ind. Informat. 2022, 18, 1684–1693. [Google Scholar] [CrossRef]












| Naples Italy | Stuttgart Germany [21] | Madison WI, USA [22] | Cape Town South Africa |
|---|---|---|---|
| inputs ϕ = 40°50′ λlocal = 14°15′ λstandard = 15° July 15 (n = 196), CKT = 16 (4:00 PM) daylight-saving time | inputs ϕ = 48°46′ λlocal = 9°10′ λstandard = 15° July 1 (n = 182), CKT = 12 (12:00 AM) daylight-saving time | inputs ϕ = 43°04′ λlocal = −89°–23′ λstandard = −90° February 3 (n = 34), CKT = 10.5 (10:30 AM) standard time | inputs ϕ = −33°–55′ λlocal = 18°25′ λstandard = 30° December 10 (n = 344), CKT = 9.25 (9:15 AM) standard time |
| outputs δ = 21.52° Eqt = −5.79 min TLT = 14.85 (2:51 PM) ω = 42.80° α = 49.13° | outputs δ = 23.12° Eqt = −3.46 min TLT = 10.55 (10:33 AM) ω = −21.70° α = 59.15° | outputs δ = −16.97° Eqt = −13.49 min TLT = 10.32 (10:19 AM) ω = −25.26° α = 25.64° | outputs δ = −23.05° Eqt = 7.14 min TLT = 8.60 (8:36 AM) ω = −51.05° α = 44.31° |
| Orientation (γ) and Tilt (β) | Normalized Yearly-Produced Energy [Wh/Wp] | |
|---|---|---|
| Monofacial | Bifacial | |
| γ = 0° (south), β = 30° | 1560 (albedo = 0.2) reference 1590 (albedo = 0.5) reference 1620 (albedo = 0.8) reference | 1680 (albedo = 0.2) 1810 (albedo = 0.5) 1930 (albedo = 0.8) |
| γ = 0° (south), β = 90° | 1020 (albedo = 0.2) 1230 (albedo = 0.5) 1440 (albedo = 0.8) | 1380 (albedo = 0.2) 1690 (albedo = 0.5) 2000 (albedo = 0.8) |
| γ = 90° (west), β = 90° | 930 (albedo = 0.2) 1140 (albedo = 0.5) 1350 (albedo = 0.8) | 1610 (albedo = 0.2) 1920 (albedo = 0.5) 2220 (albedo = 0.8) |
| γ = −90° (east), β = 90° | 780 (albedo = 0.2) 990 (albedo = 0.5) 1200 (albedo = 0.8) | 1600 (albedo = 0.2) 1910 (albedo = 0.5) 2210 (albedo = 0.8) |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2025 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
d’Alessandro, V.; Daliento, S.; Dhimish, M.; Guerriero, P. A Tool for a Fast and Accurate Evaluation of the Energy Production of Bifacial Photovoltaic Modules. Solar 2025, 5, 2. https://doi.org/10.3390/solar5010002
d’Alessandro V, Daliento S, Dhimish M, Guerriero P. A Tool for a Fast and Accurate Evaluation of the Energy Production of Bifacial Photovoltaic Modules. Solar. 2025; 5(1):2. https://doi.org/10.3390/solar5010002
Chicago/Turabian Styled’Alessandro, Vincenzo, Santolo Daliento, Mahmoud Dhimish, and Pierluigi Guerriero. 2025. "A Tool for a Fast and Accurate Evaluation of the Energy Production of Bifacial Photovoltaic Modules" Solar 5, no. 1: 2. https://doi.org/10.3390/solar5010002
APA Styled’Alessandro, V., Daliento, S., Dhimish, M., & Guerriero, P. (2025). A Tool for a Fast and Accurate Evaluation of the Energy Production of Bifacial Photovoltaic Modules. Solar, 5(1), 2. https://doi.org/10.3390/solar5010002

