1. Introduction
The trend of increasing prices for energy resources imposes strict requirements on energy consumption [
1,
2,
3,
4]. One of the largest energy-consuming industries is transport, in particular, electric transport [
5,
6,
7,
8]. Therefore, saving electrical energy consumed by electric transport is an urgent task [
9,
10]. The largest part of the energy consumed by electric transport falls on the traction drive (TD). Research analysis shows that the directions for increasing the TD energy efficiency of electric rolling stock (ERS) are: compensation of higher current harmonics in TD circuits [
11,
12], use of on-board energy storage devices [
13,
14,
15,
16] and energy-efficient management of the TD system [
17,
18,
19], implementation of intelligent TD control systems [
20,
21]. When using compensation devices, additional power elements are introduced into the TD [
22,
23,
24,
25]. The introduction of on-board energy storage also requires the introduction of additional power elements into the traction drive system, such as the storage devices themselves and converters, on which the energy exchange system between the storage device and the TD is organized [
26,
27,
28].
Energy-efficient control, as well as intelligent control systems, do not require the inclusion of additional power elements into the TP system when they are implemented. This is explained by the fact that such algorithms are implemented on existing microprocessor control systems of TD. However, the implementation of intelligent control systems requires a large amount of a priori data. Induction motors (IM) are most widely used in modern electric rolling stock (ERS) [
29,
30]. FOC [
31,
32,
33], direct torque control (DTC) systems [
34,
35,
36] and model predictive control (MPC) method [
37,
38,
39] are used as ERS control systems.
Various approaches exist for designing energy-efficient drives with field-oriented control of induction motors. These approaches are presented in [
40] and can be classified as follows:
Improvement of the energy efficiency of induction motors.
Application of energy-efficient control systems for induction motor drives.
Implementation of energy-efficient operating modes of the drives.
Improvement of operational maintenance practices.
Enhancement of manufacturing technologies.
The factors that directly affect the overall efficiency of induction motor drives are summarized in
Table 1 [
30].
Since modifications to the motor design, the type of inverter power semiconductor devices, the inverter hardware topology, and the cooling systems of both the converter and the motor require substantial capital investment—and operating conditions and maintenance practices are beyond the scope of this study—improving the overall efficiency of induction motor drives is primarily achieved through the application of energy-efficient control strategies. In [
41], the effectiveness of various control strategies is analyzed, and their comparative assessment is presented in
Figure 1.
An analysis of the data presented in
Figure 1 indicates that drives employing FOC exhibit the lowest torque ripple, reduced THD of the stator current, and superior fault-tolerance characteristics. In addition, it is reported in [
32] that traction drives with FOC provide better speed regulation performance compared to DTC. This characteristic is particularly important for the traction drive of a mainline locomotive. Therefore, a traction drive based on FOC is considered in the subsequent analysis.
In study [
42], the following classification of field-oriented control methods for induction motors is proposed: direct field-oriented control (DFOC) [
31,
43] and indirect field-oriented control (IFOC) [
44,
45].
In drives employing DFOC, the occurrence of resistance deviations leads to an undesirable drop in speed; however, the speed recovers within a very short time interval once the deviation diminishes. In general, the DFOC method performs poorly when the stator and rotor resistances increase, due to excessive voltage drops across the stator and rotor windings. Moreover, an increase in the rotor magnetic flux is caused by the discrepancy between the calculated flux and the actual flux in the motor, as well as by differences between the resistance values used in the observer and those of the motor. Unlike DFOC, IFOC operates reliably and stably in the field-weakening region [
42]. Since, in contrast to DFOC, IFOC demonstrates robust and stable performance under field-weakening conditions, energy-efficient control algorithms are considered specifically for this method of implementing field-oriented control of induction motors.
An analysis of energy-efficient IFOC algorithms is presented in [
46]. The following algorithms were considered:
Hybrid FOC based on a phase-locked loop (PLL) [
46].
FOC with an extended Kalman filter (EKF) [
47,
48].
FOC with a sliding-mode observer (SMO) [
49,
50,
51].
Baseline IFOC.
The results of the comparative analysis of the above algorithms are presented in
Table 2.
An analysis of the results presented in
Table 2 indicates that the hybrid PLL-based FOC algorithm provides high accuracy and favorable transient performance but exhibits lower robustness to parameter variations than FOC with a sliding-mode observer, as well as higher computational complexity and implementation cost compared to the baseline IFOC approach.
Among the factors affecting the efficiency of FOC-based drives,
Table 2 identifies the switching strategy of the inverter power electronic devices. Therefore, in order to develop an energy-efficient control strategy for a traction drive, an analysis of power losses in its components is carried out below.
From the analysis of the data in [
52,
53] power losses in TDs with FOC can be divided into power losses in TDs and inverters. Power losses in TD are divided into magnetic power losses in motor steel, thermal power losses in the motor windings, and power losses from high-frequency harmonics. Power losses in the inverter are divided into constant and switching.
Magnetic power losses in TM steel depend on the following factors [
54,
55]:
Design parameters and properties of the material from which the corresponding TM elements are made.
Magnetic flux through the structural elements.
Supply voltage frequency.
Thermal power losses in TM windings are caused by the flow of current through them. With increasing current, the amount of heat released by the active resistances of the TM windings increases. An increase in the amount of heat released by the windings leads to an increase in temperature and, as a result, to an increase in the active resistances of the windings. This leads to an increase in power losses in the TM windings [
56,
57].
In systems with FOC, a pulse-width modulation (PWM) algorithm is implemented to control the inverter. THD of the TD stator phase currents depends on the frequency of the PWM pulses. The higher the frequency of the PWM pulses, the lower the THD value [
31,
32,
33]. Reducing the THD value leads to a decrease in power losses in the traction motor from high-frequency current harmonics and a decrease in the torque ripple coefficient on the motor shaft, which leads to an improvement in the reliability indicators of the mechanical part of the TD [
58]. But in TD systems, powerful IGBT modules are used as power switches of the inverter, the maximum switching frequency of which, according to the data of the manufacturers, is limited to a frequency of 1 kHz [
59,
60]. While in general industrial drives this value is within several tens of kHz.
The current flowing through the IGBT and the voltage drop across them cause constant power losses in the inverter. The magnitude of the switching energy losses in the IGBT depends on the values in unstable modes of the currents flowing through the insulated gate bipolar transistor (IGBT), the voltage drops across them and the switching frequency [
59,
60]. Moreover, the magnitude of the switching energy losses is directly proportional to the value of the switching frequency (PWM pulse frequency). In FOC synthesis [
61,
62], the frequency of the inverter PWM pulses is assumed to be constant. And the parameters of such FOC controllers as current, flux linkage and speed are functions of this frequency.
From the analysis of the time diagrams of torque and phase currents of the TM stator [
31,
32,
33] it is seen that THD and the torque ripple coefficient depend on the frequency of the TM supply voltage, with its increase these parameters increase. This fact is explained by the fact that at a lower frequency of the supply voltage the period of the stator phase currents is larger, and it is filled with a larger number of PWM pulses. With an increase in the frequency of the supply voltage, the period of the stator phase currents decreases and, as a result, the corresponding number of PWM pulses decreases. Therefore, when the TD supply voltage frequency decreases due to a larger number of PWM pulses, the THD value decreases and, as a result, losses from high-frequency harmonics of the stator phase currents decrease. The PWM pulse frequency remains constant and, as a result, the switching energy losses in the inverter may be overestimated. Thus, optimizing the choice of PWM pulse frequency to reduce power losses is a relevant task.
The objective of this study is to develop a concept for improving the energy efficiency of the traction drive through the adaptation of the field-oriented control system to the locomotive operating speed.
To achieve the stated objective, the following research contributions were made:
The selection of tuning methods for maximizing the performance of the controllers in the baseline field-oriented control (FOC) system of the induction motor was substantiated.
Analytical relationships were derived, and the parameters of the controllers and filters for the current, flux linkage, and speed control loops of the baseline FOC IM were calculated.
As a result of simulation modeling, the transient responses of each control loop were obtained, on the basis of which the performance indices of the transient processes were evaluated.
Methods for adapting the parameters of the controllers and filters of the baseline FOC induction motor system to the locomotive operating speed were proposed.
A control scheme for the inverter was proposed, enabling the adaptation of the controller parameters of the baseline field-oriented control (FOC) induction motor system to the locomotive operating speed.
A filter structure was developed, allowing the parameters of the filters in the baseline FOC induction motor system to be adapted to the locomotive operating speed.
Based on a comparative analysis of the simulation results of the baseline and adaptive FOC induction motor systems, the effectiveness of the proposed technical solutions was demonstrated.
The article is organized as follows:
Section 2—selection of the object of study.
Section 3 is devoted to the development of a simulation model of the basic FOC scheme.
Section 4 reports on the simulation model of the FOC scheme, the parameters of which are adapted to the speed of the locomotive.
Section 5 presents the simulation results and discussion.
Section 6 summarizes the results.
5. Simulation Results and Discussion
The effectiveness of the proposed technical solutions was carried out by comparing the parameters of the basic and adapted circuit of the output part of the TD. When determining the parameters of the basic circuit on a complex simulation model in the “Parameter calculation unit” signal w_set is taken equal to 1.
When implementing the law of changing the shaft rotation frequency of an induction motor, the following sections were selected:
Operation of the circuit with the speed controller turned off, necessary for the induction motor to enter the saturation mode.
Acceleration of the induction motor to a frequency equals half the nominal speed.
Operation of the induction motor at a frequency equal to half the rated speed.
Acceleration of the induction motor to a frequency equal to the rated speed.
Operation of the induction motor at a frequency equal to the rated speed.
Acceleration of the induction motor to a frequency 25% higher than the rated speed.
Operation of the induction motor at a frequency 25% higher than the rated speed.
The acceleration for all intervals of IM acceleration is the same. The law of change in the motor shaft speed is shown in
Figure 18.
As a result of the simulation modeling, start-up waveforms of the stator phase currents were obtained for the baseline (
Figure 19a) and adaptive (
Figure 19b) schemes.
An analysis of the start-up waveforms of the stator phase currents (
Figure 19) indicates that, in the adaptive scheme, a significant overshoot of the phase-
A current occurs at the moment when the speed change function generator is activated; however, the system stabilizes rapidly. Under transient operating conditions, as the set speed value increases, the stator currents increase in the baseline scheme, whereas they decrease in the adaptive scheme. Under steady-state conditions, the phase current magnitudes remain constant in both schemes. Nevertheless, in the baseline scheme, the phase current magnitude increases with increasing set speed, while in the adaptive scheme it decreases slightly.
Figure 20 presents the time-domain waveforms of the stator phase currents under steady-state conditions at a speed 50% lower than the rated value for the baseline (
Figure 20a) and adaptive (
Figure 20b) schemes. As can be observed from
Figure 20, the baseline scheme exhibits a lower level of higher-order harmonics in the stator phase currents compared to the adaptive scheme. This is attributed to the higher number of PWM pulses per period in the baseline scheme at this operating speed relative to the adaptive scheme.
Figure 21 presents the time-domain waveforms of the stator phase currents under steady-state conditions at the rated speed for the baseline (
Figure 21a) and adaptive (
Figure 21b) schemes. As can be observed from
Figure 21, the level of higher-order harmonics in the stator phase currents is the same for both the baseline and adaptive schemes. This is due to the identical number of PWM pulses per period in the baseline and adaptive schemes at this operating speed.
Figure 22 presents the time-domain waveforms of the stator phase currents under steady-state conditions at a speed 25% higher than the rated value for the baseline (
Figure 22a) and adaptive (
Figure 22b) schemes. As can be observed from
Figure 22, the baseline scheme exhibits a higher level of higher-order harmonics in the stator phase currents compared to the adaptive scheme. This is attributed to the lower number of PWM pulses per period in the baseline scheme relative to the adaptive scheme at this operating speed.
An analysis of the start-up torque waveforms (
Figure 23) indicates that, in the adaptive scheme, a significant torque overshoot occurs at the moment when the speed change function generator is activated; however, the system stabilizes rapidly. Under transient operating conditions, as the set speed value increases, torque ripple increases in the baseline scheme (
Figure 23a), whereas it remains stable in the adaptive scheme (
Figure 23b). Under steady-state conditions, the torque magnitude remains constant in both schemes. Nevertheless, in the baseline scheme, the torque magnitude increases with increasing set speed, while in the adaptive scheme it remains constant.
In
Figure 24, the start-up responses of the motor shaft rotational speed are presented for the baseline (
Figure 24a) and adaptive (
Figure 24b) schemes.
An analysis of the start-up responses of the motor shaft rotational speed (
Figure 24) indicates that, in the adaptive scheme (
Figure 24b), a nonlinear segment appears at the moment when the speed change function generator is activated, after which the motor shaft speed varies according to a linear law. The presence of this nonlinear segment is attributed to the significant overshoot of the stator phase currents. In the baseline scheme, the motor shaft rotational speed (
Figure 24a) varies according to a linear law throughout the start-up process.
Analysis of the energy consumed by both schemes (
Figure 21) shows that the proposed scheme consumes energy by 5.85%. This circumstance is explained by the fact that in the time interval from the motor start to the speed controller activation, the proposed scheme does not consume the power required to saturate the motor magnetic system. This was made possible by adaptively adjusting the FOC parameters to the speed controller frequency.
From the torque diagrams (
Figure 23a,b) for stable operating modes, the average values of the torque (T
av) and the average values of the torque ripples (ΔT) were determined. Based on the obtained average values of the torque and its ripples, the value of the torque ripple coefficient was calculated in accordance with the expression [
93]:
where
Tav the average value of the torque; Δ
T the average value of the torque ripples.
The total values of the energy consumed by TD for both studied schemes and the calculation results are listed in
Table 6.
Based on the phase current waveforms under steady-state conditions for the baseline control scheme (
Figure 20a,
Figure 21a, and
Figure 22a) and for the adaptive control scheme (
Figure 20b,
Figure 21b, and
Figure 22b), the components of the amplitude–frequency spectrum were determined, from which THD was calculated. The amplitude–frequency spectrum components were obtained using the discrete Fourier transform in accordance with Equations [
94,
95]:
where
IsA(
fi) the
i-th component of the stator current spectrum of phase
A;
IsA(
tn) the
n-th time sample of the stator phase-
A current;
N = 128 the number of spectral components of the stator phase-
A current.
THD of the stator phase-
A current were calculated using Equations [
96,
97]:
where
|IsA(
fi)
| the magnitude of the
i-th component of the stator phase-
A current spectrum.
The results of the calculations of the THD of the stator phase-
A current are presented in
Table 6.
Based on
Figure 24a,b, the motor shaft rotational speeds under steady-state conditions were determined for the baseline and adaptive schemes, respectively. The obtained results are summarized in
Table 6.
In accordance with Equation (47), the errors in estimating the motor shaft rotational speed were calculated. The corresponding results are also presented in
Table 6.
The error in estimating the motor shaft rotational speed under rated operating conditions is determined in accordance with the following expression:
where
nrnom = 1110 rpm the rated value of the motor shaft rotational speed according to the manufacturer’s data (
Table 4);
nrm the motor shaft rotational speed value obtained through simulation.
When determining the motor shaft rotational speed estimation error at speeds 50% below and 25% above the rated value, the parameter nrnom in Equation (47) was multiplied by 0.5 and 1.25, respectively.
Comprehensive indicators of energy efficiency include the efficiency factor (η) and the power factor (kP). In the context of a traction drive, the efficiency is defined as the ratio of the useful mechanical power at the motor shaft to the active electrical power drawn from the supply. The power factor is defined as the ratio of the active power drawn from the supply to the apparent power drawn from the supply. However, since the traction drive (inverter) is powered from a DC link, the use of the power factor in this case is not appropriate.
For steady-state operating conditions, the efficiency was calculated in accordance with the following expression:
where
P2 useful mechanical power at the motor shaft;
P1 denotes the active electrical power drawn from the supply.
The useful mechanical power at the motor shaft was determined as:
where
Tav is the average torque, and
nr enotes the motor shaft rotational speed.
The active power drawn from the supply was determined using the following expression:
where
Ud—the direct voltage of the inverter supply, and
Id the direct current consumed by the transformer.
The results of the efficiency calculations are presented in
Table 6. Since determining the efficiency of the drive under transient operating conditions is a nontrivial task, while the drive consumes electrical energy during transients as well, the impact of transient performance on the energy efficiency of the traction drive was analyzed. For this purpose, energy consumption waveforms for the baseline and adaptive schemes were obtained using the simulation model (
Figure 25).
The consumed TD energy was calculated in accordance with the expression:
where
t—time.
From the analysis of the results, it follows that for the basic scheme with an increase in the frequency of the IM supply voltage in a steady state, the value of the torque ripple coefficient increases much faster than for the adapted scheme. This circumstance is explained by the presence of adaptation of the parameters of the inverter, controllers and filters in the proposed scheme.
An analysis of the results presented in
Table 6 indicates that, for the adaptive scheme, the values of the stator phase-
A current harmonic distortion coefficients under steady-state conditions remain constant across the entire speed range. For the baseline scheme, at a speed equal to half of the rated value, this coefficient is lower than that of the adaptive scheme; however, at the rated speed and at a speed 25% higher than the rated value, it is higher than that of the adaptive scheme. The lower THD of the stator phase-
A current observed for the adaptive scheme at the rated speed is attributed to the adaptation of the filters in the current, flux-linkage, and speed control loops to the rotational frequency of the induction motor shaft.
As can be seen from
Table 6, for the baseline scheme, the error in estimating the motor shaft rotational speed is identical at locomotive operating speeds 50% below the rated value and at the rated speed; however, with increasing locomotive speed, the estimation error increases. For the adaptive scheme, the motor shaft speed estimation error remains constant across all three operating conditions, and its value is three times lower than that of the baseline scheme at speeds 50% below the rated value and at the rated speed, and five times lower at a speed 25% above the rated value.
Analysis of the energy consumed by both schemes (
Figure 25) shows that the proposed scheme consumes energy by 5.85%. The obtained results can be explained by the following factors:
During the time interval from motor start-up to the activation of the speed change function generator, the adaptive scheme does not consume the power required to saturate the motor magnetic system.
The adaptive scheme exhibits superior transient performance compared to the baseline scheme, with the exception of the moment when the speed change function generator is activated.
The authors continue to work on this research topic. In particular, ongoing studies are focused on investigating the effects of disturbances of both electrical and mechanical origin on the performance of the locomotive traction drive. In addition, the authors are developing an algorithm for optimizing the controller parameters while accounting for the aforementioned disturbances. Until these studies are completed, a quantitative comparison with other methods in terms of performance indicators such as response time, ripple, and energy efficiency would be inappropriate. Therefore, in the present work, the authors have limited the analysis to qualitative indicators only. As a reference,
Table 2 presented in
Section 1 was used.
When formulating the qualitative assessment of the proposed method, the authors were guided by the following considerations:
Since the proposed method does not require significant circuit-level modifications to the baseline scheme and does not involve computationally intensive calculations, the rotor magnetic flux angle estimation method, transient performance, robustness to parameter variations, computational complexity, and implementation cost are expected to be comparable to those of the baseline scheme.
The steady-state accuracy is expected to be moderately high, as the controller and filter parameters are adapted to the supply frequency of the induction motor.
An analysis of the results presented in
Table 7 indicates that the proposed method is inferior only in terms of steady-state accuracy when compared with the hybrid phase-locked loop (PLL)-based FOC method. This can be explained by the fact that, in the proposed method, the rotor magnetic flux angle is estimated based on slip estimation, which is sensitive to rotor parameter variations.
In the hybrid PLL-based FOC method, the estimation of the rotor magnetic flux angle is based on phase-locked loop (PLL) synchronization. The high accuracy of the hybrid PLL-based FOC approach is attributed to the precise tuning of the PLL.