3.1. Three-Line-to-Ground Faults
This section analyzes the impact of DERs on fault currents during three-phase-to-ground faults. The currents measured at the OCP relays are presented in
Table 2 for a fault at node 675 and in
Table 3 for a fault at node 680. A negative sign in the tables indicates reverse current flow. The following metrics are used:
is the reference fault current without DERs;
and
are the minimum and maximum recorded fault currents with DERs; and
and
represent the current deviations from the reference case, expressed in amperes (A) and as a percentage (%).
A comparison reveals that the fault at node 680 produced a slightly higher current variation at relay R1, whereas the fault at node 675 caused a greater variation at R2. The impact on R3 during the fault at node 675 was minimal, with a variation of only 3.09%.
A situation occurs during the fault at node 680: DERs on the 671–675 branch contribute to the fault, and under certain DER configurations, the current through R3 reverses direction. This is illustrated in
Figure 4, which shows the case with the maximum reverse current. In this scenario, the current variations at R3 ranged from an increase of 12.49% to a decrease of 1443.22%(reverse flow). This extreme percentage is attributable to the low reference current at R3 without DERs compared to the substantial reverse current of 280.08 A with DERs.
The fault location also influences the DERs’ operational modes. A fault farther from the substation, such as at node 680, results in a less severe voltage sag at the DER terminals, allowing more units to remain connected and actively injecting current. This leads to more pronounced current variations at the OCPs. For example, as shown for relay R2 in
Table 4 and
Table 5, more DERs remain in Mode 2 (injecting current) during the fault at node 680, compared to the fault at node 675 where more DERs enter Mode 1 (disconnected).
To investigate the factors driving these variations, the fault current at R2 was correlated with the number and net power of connected DERs relative to the relay’s position, as shown in
Figure 5. The x-axis indexes the 512 unique DER connection scenarios defined in
Section 2.
The analysis shows that the number of connected DERs (either upstream or downstream) does not strongly correlate with the fault current magnitude. For the same number of active DERs, a wide range of fault currents was observed. This indicates that the mere quantity of connected DERs is not the primary driver; rather, the total power they inject is the key factor.
Conversely, the net injected power exhibits a strong correlation with the fault current at R2, particularly for the fault at node 675. As shown in
Figure 5, a positive net power (indicating higher injection upstream of R2) consistently leads to higher fault currents, while negative net power (higher injection downstream) leads to lower fault currents. For the fault at node 680, this correlation is weaker but still observable.
For relay R3 during the fault at node 680, the relationship is more complex. As seen in
Figure 6, there is no clear correlation between the fault current and either the net number or the net power of the DERs. Multiple combinations of DER status can result in the same fault current, and notably, reverse current can occur even with a net positive power injection upstream of the relay.
3.2. Single-Line-to-Ground Faults
The analysis of single-line-to-ground faults is presented in
Table 6 (fault at node 675) and
Table 7 (fault at node 680) for a fault in a given phase, such as Phase A.
With the exception of relay R3, during the fault at node 680, the current variations for LG faults were more significant than for three-phase-to-ground (3LG) faults. While the maximum variation for a 3LG fault was 3.09%, the range for LG faults was between −10.76% and 11.00%. The variations were more pronounced for faults at node 680, which can be attributed to the greater number of DERs remaining connected and operating in modes that inject more power as a result of less severe voltage sags.
Relay R3 exhibited a reverse current behavior similar to the 3LG case during the fault at node 680, although the magnitude was smaller. The maximum reverse variation for the LG fault was −831.27%, compared to −1443.22% for the 3LG fault.
The currents in the healthy phases were also affected by the presence of DERs at both fault locations. This is an expected consequence of the magnetic coupling between phases and the continued power exchange from DERs connected to the healthy phases.
The influence of DER operating mode is detailed in
Table 8 and
Table 9, which provide a comparative example for a fault in Phase A. To explain the observed
, the key difference lies in the behavior of the DERs at nodes 634 and 645. During the fault at node 680, their operating modes (3-4-4 and 4) result in higher net power injection compared to the fault at node 675, where the modes are 2-4-4 and 5. This occurs because Mode 2 represents a disconnected DER and Mode 5 involves reactive power absorption, both of which reduce the current contribution. A similar logic applies to the
case, where the differing modes at nodes 632–671 and 671 (1-6-5 vs. 2-5-5) explain the different outcomes. This pattern of behavior was consistent across other faulted phases and relays.
The correlation analysis for LG faults, shown for Phase B at relay R2 in
Figure 7, reinforces findings from the 3LG case. The net quantity of connected DERs shows a weak correlation with the fault current. In contrast, the net injected power demonstrates a stronger correlation, although the relationship is less deterministic than in the 3LG case, as multiple current values can be observed for the same net power level.
It is important to note that the findings of this study are based on a simplified feeder model, a choice made to isolate the fundamental impacts of DER power and location. In real-world networks with heterogeneous loading, pre-fault voltage profiles would be more complex, altering the absolute fault current magnitudes. Furthermore, while DER clustering can increase the fault contribution in a specific area, this effect is often moderated by the inherent short-circuit current limits of inverter-based resources. A detailed analysis of these complex scenarios remains a compelling direction for future research.
This study assumes an infinite bus at the substation, representing a strong grid. It is important to consider how these findings translate to weaker grids with higher source impedance, common in rural areas. In such systems, the grid’s fault current contribution is inherently limited. Consequently, the DERs’ contribution would represent a larger fraction of the total fault current, making their behavior and parameters—especially their power output—even more critical to the protection system’s response.
3.3. Impacts on Protection Coordination
This section evaluates the impact of DERs on the CTI between relays. The analysis focuses on the worst-case scenarios—the DER combinations producing maximum and minimum fault currents—for faults at nodes 675 and 680, resulting in 48 critical cases for evaluation.
For a 3LG fault at node 675, the DER combination that caused minimum current at R1 also caused maximum current at R2 and R3. This reduced the R2–R3 CTI from 283 ms to 234 ms. While this is a significant reduction, the CTI remained above the 200 ms coordination margin. Conversely, the R1–R2 CTI increased from 789 ms to 931 ms. For the 3LG fault at node 680, no CTI reduction was observed; for instance, the R1–R2 CTI increased from 725 ms to 1158 ms. The CTI between R2 and R3 was not affected because the fault current through R3 flowed in the reverse direction.
For the combination of maximum current through R2, coordination issues arose.
The analysis revealed that LG faults introduce the most critical coordination challenges. For the LG fault at node 675, several scenarios reduced the coordination margin. In the case producing minimum current at R1, the R2–R3 CTI for a Phase B fault dropped from 219 ms to 208 ms, approaching the 200 ms limit. A loss of coordination was observed for the case producing maximum current at R2. Under these conditions, the R2–R3 CTI for a Phase B fault fell from 219 ms to 199 ms, violating the minimum 200 ms threshold. This demonstrates a clear instance of miscoordination, where R3 would trip before R2. A similar CTI reduction occurred in Phase C, but the margin was not violated.
This finding highlights a critical challenge for protection engineers: even small-scale DERs, despite their low individual fault contributions, can collectively compromise the protection coordination of an entire feeder. In this study, miscoordination occurred from a fault at node 675, which is electrically distant from relay R3. A fault located closer to R3 could potentially lead to even more severe coordination issues. Of course, the specific outcome depends on the complex interplay between fault location, the resulting voltage sags, and the number and power injection of the DERs that remain connected. This conclusion is generalizable to other relay pairs and other distribution systems with high DER penetration.
For LG faults at node 680, the CTI between R1 and R2 decreased in some scenarios but always remained well above 500 ms. Miscoordination between R2 and R3 was not an issue due to the reverse current flow through R3. In such cases, the primary protection concern shifts to the significant risks of sympathetic tripping and fuse miscoordination in downstream laterals. This reverse current flow creates two distinct problems for downstream devices. First, it adds to the grid’s fault current, exposing fuses on healthy laterals to currents that can exceed their rating and cause a loss of coordination. Second, it makes non-directional relays like R3 prone to sympathetic tripping, as they cannot determine the fault’s actual location. A detailed methodology for analyzing and mitigating these risks by resizing protective devices was previously proposed by the authors in [
28].
The analysis in this paper considered faults at two illustrative locations to demonstrate the impact of DERs on protection coordination. The fault location is a critical parameter, and the selection of different points could yield more severe impacts. Applying a fault at the reach limit of a protective device (i.e., just upstream of the next downstream relay) typically represents the worst-case scenario for CTI analysis. In such cases, the DER’s contribution relative to the total fault current would likely cause an even greater reduction in the CTI than what was observed in our results.