Research on Fire Smoke Recognition Algorithm with Image Enhancement for Unconventional Scenarios in Under-Construction Nuclear Power Plants

,
,
and
1
Zhangzhou Project Team, China Nuclear Engineering Co., Ltd., Zhangzhou 363300, China
2
School of Safety and Environmental Engineering, Shandong University of Science and Technology, Qingdao 266590, China
*
Author to whom correspondence should be addressed.
This article belongs to the Special Issue Fire Risk Management and Emergency Prevention

Abstract

Accurate identification of fire smoke is a key link in realizing early fire prevention and control. Traditional intelligent video and image processing technologies are significantly restricted by environmental factors, with weak anti-interference capabilities and limitations in distinguishing fire smoke, leading to a high false alarm rate of fires. To address this problem, this paper proposes an unconventional visual field smoke detection method based on image enhancement. The method innovatively improves the Retinex algorithm by integrating improved guided filtering, adaptive brightness correction, and CLAHE-WWGIF joint processing, which realizes targeted optimization for the unique interference factors of under-construction nuclear power plants such as water mist, low illumination, and equipment occlusion. First, an improved Retinex algorithm is used to process the image to improve the image brightness and contrast, retain edge details while avoiding halo artifacts, reduce the impact of noise, and optimize visual features. Then, the sample data set is integrated, and the YOLOv11 target detection algorithm is used to achieve accurate identification and positioning of smoke targets. Experimental data shows that the fire identification method achieves an accuracy rate of 93.6% and 92.3% for fire smoke identification in interference-prone scenarios such as dark nights and water mist, respectively, and the response time to fire smoke is only 1.8 s and 2.1 s. In practical on-site applications at nuclear power plant construction sites, the method is integrated into an “edge computing + distributed deployment” hardware system, which realizes real-time smoke detection in core areas such as nuclear islands and conventional islands with a false alarm rate of less than 5% and a detection delay of ≤300 ms, meeting the ultra-strict safety monitoring requirements of nuclear power projects. Experiments show that this method can be effectively applied to smoke detection scenarios under unconventional visual fields, accurately identify smoke, provide reliable technical support for fire smoke identification under unconventional visual fields, significantly reduce the false alarm rate of fire detection, and provide technical support for the safety of under-construction nuclear power plants.

Article Metrics

Citations

Article Access Statistics

Multiple requests from the same IP address are counted as one view.