Abstract
The characteristics of the dynamic reactive power demand of a hybrid multi-infeed HVDC transmission system during the post-fault recovery period are analyzed and a coordinated control strategy to improve the fault recovery characteristics of the hybrid multi-infeed HVDC transmission system is proposed in this paper. During the process of fault recovery, the LCC-HVDC adopts a progressive staggering recovery strategy. At the same time, according to the reactive power shortage of LCC-HVDC, the dynamic power limiter is used to adjust the upper and lower limit values of the outer loop power controller of VSC-HVDC, and the reactive power generated by the VSC-HVDC can be rapidly adjusted. Therefore, the problem of excessive reactive power demand during the recovery process can be solved and the reactive power demand can be satisfied with the proposed strategy. Moreover, the ability of VSC-HVDC to provide reactive power support can be fully utilized. Finally, a simulation model of a hybrid tri-infeed HVDC system is built using PSCAD/EMTDC (Version 4.6.2) software to verify the effectiveness of the proposed control strategy.
1. Introduction
Line-commutated-converter-based high-voltage direct-current (LCC-HVDC) transmission technology, which relies on the AC grid for commutation, offers advantages such as large power transfer capacity, long transmission distance, and low overall cost. It plays a critical role in addressing the reverse geographical distribution of energy resources and load centers in China and serves as a key technical support for the national “West-to-East Power Transmission” strategy, accounting for more than 50% of the total transmitted capacity [1]. Compared with LCC-HVDC, voltage source converter-based high-voltage direct-current (VSC-HVDC) transmission features greater control flexibility, eliminates the need for reactive power compensation, and is free from commutation failure issues, which has led to its rapid development in recent years [2]. With the continuous construction of VSC-HVDC projects, hybrid multi-infeed HVDC transmission systems—where multiple LCC-HVDC and VSC-HVDC links coexist within the same AC network—have gradually emerged [3,4]. The East China and Guangdong power grids represent the most densely concentrated multi-infeed HVDC systems worldwide. In 2020, the Wudongde HVDC project, the tenth HVDC link terminating in Guangdong, was officially commissioned, transforming the Guangdong power grid into a hybrid multi-infeed HVDC transmission system [5,6]. In 2022, the Baihetan–Jiangsu ±800 kV ultra-high voltage direct current (UHVDC) transmission project was completed and put into operation, becoming the first HVDC project employing a hybrid cascaded configuration of LCC and VSC technologies [7,8].
Although multi-infeed HVDC systems enhance operational flexibility and expand transmission capacity, they also increase structural complexity, thereby exacerbating challenges related to system security and stability. When the receiving-end system is subjected to a large disturbance, the converter will consume a large amount of reactive power, especially for the receiving-end system with multiple HVDC converters. The AC system must be strong enough to support the operation of multiple HVDC links. Furthermore, the strong electrical coupling between the converter stations makes the commutation bus voltage drops correspondingly during the fault of the receiving-end grid, which may lead to continuous commutation failure or multiple HVDC links’ simultaneous commutation failure, bringing large dynamic reactive power demand during the recovery process, and the problems of voltage stability will be quite serious [9,10,11,12]. Fortunately, VSC-HVDC can compensate for the dynamic reactive power demand in real time and improve the voltage stability of the receiving-end system after a large disturbance. The problems of how to slow down the interaction between HVDCs during the recovery period and speed up the recovery of active power at the same time, and what strategies are used to coordinate and orderly recover the hybrid multi-infeed HVDC transmission system after fault clearing, need to be further researched.
The post-fault recovery characteristics of LCC-HVDC and MMC-HVDC have been investigated by establishing the transient simulation models [13,14]. The simulation study of Chu-Sui UHVDC shows that the peak value of reactive power demand of the inverter station will not be affected by the severity of commutation bus fault if commutation failure occurs [15]. It is revealed that the voltage interactions among converter stations in multi-infeed HVDC systems are an important factor triggering commutation failures in [16]. A coordinated and progressive recovery strategy for a multi-infeed HVDC system is proposed in [17,18] by setting a first-order lag loop after the VDCOL (Voltage-Dependent Current Order Limiter) of each HVDC system and by controlling the time constant, thus staggering the peak value of reactive power demand of HVDC converters during the post-fault recovery process. A regulation method for the additional current proportional coefficient is proposed in [19], which enables the stronger DC system to recover more rapidly, thereby facilitating a faster restoration of the overall system voltage and transmitted power. An “autonomous coordination” strategy is proposed to decompose the coordinated optimization in [20], taking into account short-term voltage stability constraints and optimal HVDC power recovery, in order to achieve dynamic reactive power support. A control strategy based on a constant extinction area for suppressing commutation failure is proposed in [21]. It also proposes a VSC-HVDC dynamic power limiting regulation control, but its limiting regulation can only be adjusted in segments. It is concluded that harmonics are one of the reasons for continuous commutation failure during HVDC post-fault recovery, and a hybrid HVDC continuous commutation failure suppression strategy based on harmonic voltage compensation is proposed in [22]. A correlation model among the extinction angle and DC current of LCC-HVDC inverter and the output reactive power of VSC-HVDC is deduced to optimize the control within the controllable range of commutation failure in [23]. A reactive power priority control method is proposed to enhance the reactive power output capability of VSC converter stations in [24], allowing them to provide additional reactive power for voltage support during system faults. A control method is proposed to effectively regulate the reactive power of MMC-HVDC in hybrid parallel HVDC systems, which can support the inverter-side AC bus voltage and improve the overall fault recovery performance of the system in [25]. The above-mentioned references only consider the improvement of LCC-HVDC or VSC-HVDC control strategies but do not make full use of the recovery characteristics of the two HVDCs for coordinated control. Therefore, designing a coordinated control strategy that integrates the dynamic reactive power regulation capability of VSC-HVDC into the peak-shifting restoration strategy of LCC-HVDC to achieve precise, bidirectional regulation of reactive power supply and demand during the restoration process has become a critical issue for enhancing the post-fault characteristics of hybrid multi-feed systems.
Based on the analysis of the characteristics of dynamic reactive power during the post-fault recovery period of a hybrid multi-infeed HVDC transmission system, a coordinated control strategy to improve the post-fault recovery characteristics of the hybrid multi-infeed HVDC transmission system is proposed from two aspects: (a) dynamic reactive power demand; and (b) dynamic reactive power supply. The main idea is to reduce the reactive power demand peak value by using a peak staggering recovery strategy for LCC-HVDC and, at the same time, adopt a dynamic adaptive current limiting strategy for VSC-HVDC to provide dynamic reactive power and smooth the reactive power demand during the post-fault recovery process.
The remainder of this paper is organized as follows. The characteristics of dynamic reactive power during the post-fault recovery period are presented in Section 2. Section 3 provides the multi-infeed HVDC transmission system progressive peak staggering recovery strategy. Section 4 proposes a post-fault recovery characteristic improvement strategy for a hybrid multi-infeed HVDC transmission system and its implementation process of VSC-HVDC coordinated control strategy. In Section 5, verification of the effectiveness of the control strategy proposed in this paper is implemented. Finally, conclusions are drawn in Section 6.
2. The Characteristics of Inverter Dynamic Reactive Power Demand After Large Disturbance of Hybrid Multi-Infeed HVDC Transmission System
To reflect the mutual interaction between LCC-HVDCs under large disturbances and the supporting role of VSC-HVDC for LCC-HVDC, this paper employs a hybrid multi-infeed HVDC transmission system model. This model is shown in Figure 1. It consists of two LCC-HVDCs and one VSC-HVDC system. There is an electrical distance between the three receiving converter stations. The line impedance values Z12, Z13, and Z23 can be set according to the actual situation.
Figure 1.
The structure of a hybrid multi-infeed HVDC transmission system.
The dynamic reactive power demand at the receiving end during the recovery period after a large disturbance is bigger than that under a small disturbance, which is even more detrimental to the system voltage stability. This section focuses on the dynamic reactive power characteristics of inverters under large disturbances. In this paper, a large disturbance refers to a serious symmetrical three-phase short-circuit fault occurring at the receiving-end grid, which is serious enough to cause commutation failure and require the rectifier station to adopt the minimum current control during the post-fault period.
2.1. Model of HVDC Control System in Recovery Period After Large Disturbance
The control mode adopted by the converter is a combination of several basic control modes [26], and the switching logic of the control mode is shown in Figure 2. The DC current, DC voltage on rectifier sides, DC voltage on inverter sides, and the extinction angle measured values are Id,mes, Udr,mes, Udi,mes, and γmes, respectively; the setting values are Id,ref, Udr,ref, Udi,ref, and γref, respectively; and the deviation values are Id,err, Udr,err, Udi,err, and γerr, respectively. The selection logic of the control mode increases the difficulty of establishing the mathematical model, and the control mode can be determined according to the values of the operating electric variables during the post-fault recovery period.
Figure 2.
Selection logic of LCC-HVDC control mode.
At the initial stage after fault clearance, as the voltage setting value on the rectifier side is constant, the current setting value increases from the minimum DC current IL to 1 (p.u.) under the action of the VDCOL, and the DC voltage deviation is larger than the current deviation, leading the rectifier side to adopt constant current control. While the DC voltage does not reach the value constant DC voltage control during the post-fault recovery period, the DC voltage deviation is smaller than that decided by the extinction angle, so the inverter side adopts constant extinction angle control.
After the control mode is determined, the control block diagram of the HVDC system can be shown as Figure 3. The HVDC system mainly consists of the DC current setting control, the secondary system of PI control [27], the primary system, the measurement linking the primary system with the secondary system to complete the signal transmission, and the converters. The first-order measurement is ignored to reduce the order of the equation.
Figure 3.
Control block of the LCC-HVDC system.
After the three-phase short-circuit fault is cleared, the primary system can be represented by a quasi-steady-state model [28,29].
In the formula, αr(t) and αi(t) are the firing angles of the sending end and receiving end, respectively, and their cosine values are the input of the primary system, whereas the DC current Id(t) and extinction angle γ(t) are the output of the primary system. The parameters of the primary system include the number of 6-pulse converters in the converter station n, DC line resistance RL, equivalent commutation resistance Rcr at the sending end and Rci at the receiving end, commutation reactance Xci at the receiving end, and commutation bus voltages Er(t) and Ei(t).
2.2. Characteristics of Dynamic Reactive Power Demand of Inverter After Large Disturbance
As shown in Figure 3, for an LCC-HVDC system with parameters determined, the dynamic reactive power curve in the fault recovery process is well-determined by the system input (Id,ref, γref), boundary conditions (firing angle of rectifier and inverter station at the moment of fault clearance), and time-varying parameters in the system (Er(t) and Ei(t)). After the disturbance of different magnitudes occurs at the receiving-end system, if the above parameters are close to each other, the reactive power demand during the recovery period will be relatively fixed.
2.2.1. Time-Varying Parameters in a System
The bus voltages Er(t) and Ei(t) are the time-varying parameters of the system. At the fault-clearing moment, the DC transmission active power begins to climb, the converter consumes little reactive power, and the filter bank provides excessive reactive power. Even with different magnitudes of disturbance, usually the AC voltage can quickly recover to the rated value, and the fault severity has little effect on the commutation bus voltage. As the converter consumption reactive power increases to the peak and then decreases, the bus voltage first drops to the valley and then returns to the rated value. Therefore, after the fault clearance, if the system voltage is stable, the AC voltage will fluctuate around the rated voltage. Ignore the AC voltage fluctuation during the recovery period, and take Er(t) and Ei(t) as the rated operating values.
2.2.2. System Boundary Conditions
During the fault period of the commutation bus at the inverter side, due to the commutation failure of the inverter, the leading firing angle β increases to its upper limit value βmax. Therefore, the constant β control is adopted on the inverter side, and the constant minimum current control is adopted on the rectifier side at the moment of fault clearance. The firing angle of the converter station at the time t0 of fault clearance is:
At steady state, the firing angle is:
Assuming that the AC voltage is the rated value, where k2 = 1.35nEr/Rall, Rall = Rcr + Rd + Rci, k3 = 1.35nEi/Rall, k5 = Xci/Ei, Id,base is the reference value of DC current, and Id,s is the steady-state value of the DC current. After major perturbations of varying severity, the system’s boundary conditions remain largely unchanged.
2.2.3. System Input
System input Id,ref is a nonlinear function of the internal variable DC voltage of the system, as shown in Figure 4, where Id,VDCOL is the current setting value output by VDCOL, and Id,HMI is the current instruction value.
Figure 4.
Control scheme of DC current reference.
If the rise time of the DC voltage is not taken into account, let VH = 0, VL = 0, Id,VDCOL jump from the minimum current IL to the rated value after the fault clearance. Considering the inertia element in the control system, the current setting value under different fault conditions has nothing to do with the disturbance severity, i.e.,
where T is the time constant of the inertial element. The faster the rate of DC voltage rise, the smaller the influence of Id,ref. During the post-fault recovery period, the AC voltage rises rapidly due to the excess reactive power injection of the filter bank; correspondingly, the DC voltage also rises at a fast rate, and Id,ref is less affected by the fault severity.
Usually, the commutation bus voltage will recover quickly; therefore, the system input, the system boundary value conditions, and the time-varying parameters in the system are less affected by the severity of the fault, and the difference in dynamic reactive power demand is also small during the recovery process. Since the actual AC voltage fluctuates around the rated voltage and the DC voltage rises quickly after the fault clearance, a curve similar to the dynamic reactive power characteristics after different magnitudes of disturbance can be obtained by replacing the AC voltage with the rated value, as well as ignoring the DC voltage rise time.
2.3. Calculation of Dynamic Reactive Power Demand in the Recovery Process After Large Disturbance
According to the above section, Er(t) and Ei(t) are set as rated operating values, the setting value of DC current is shown in (5), and the maximum dynamic reactive power demand under different magnitudes of disturbance can be obtained. Equation (1) can be simplified into a linear expression if we replace arccos(x) by −π(x − 1)/2 approximately:
By combining (4)–(6) and selecting x1 and x2 in Figure 5 as state variables, a second-order differential equation can be obtained.
Figure 5.
Partial control components of rectifiers and inverters.
For a simple solution, it is approximately considered that the cosαi(t) in (5) and the Id(t) in (6) are equal to the cosαi,s and Id,s in the steady-state operation of the system. Then, the original second-order differential equation can be changed into two first-order differential equations:
In the above formula, k1, T1, and k4, T2 are PI parameters on both sides, respectively, and k6 = −π/2. The approximation used in (6) is accurate within the range where x approaches 1, corresponding to the typical operating range of the trigger angle αi during recovery. Considering that the inverter operates in fixed-switching-angle control mode, cosαi(t) varies within a range near its steady-state value, resulting in a small calculated Qdi error.
According to (7) and boundary value conditions (2) and (3), the reactive power characteristic curve can be obtained.
The cosine of the firing angle of the rectifier side is:
The cosine of the firing angle of the inverter station is:
Substituting (8) and (9) into (10), the dynamic reactive power demand curve Qdi of the inverter after a large disturbance can be obtained.
The analytical expression for the reactive power demand Qdi of the converter after a fault is shown in (10). By differentiating Qdi and setting it to zero, the maximum value of reactive power demand during fault recovery can be obtained. Analysis indicates that when the inertia time constant T of the current reference value Id,ref varies, the timing at which the reactive power demand reaches its peak also changes accordingly.
For multi-infeed DC transmission systems, simultaneous restoration of multiple LCC-HVDC lines may result in a combined reactive power peak exceeding the AC grid’s capacity. The theoretical analysis indicates that by deliberately setting different time constants Td for each line, the reactive power peaks of individual DC systems during fault restoration can be temporally staggered. This peak-spreading approach effectively reduces the maximum instantaneous reactive power demand on the AC system, thereby mitigating voltage sags during restoration and suppressing the risk of subsequent commutation failures. The above describes the principle of the coordinated interleaved recovery control strategy.
3. Multi-Infeed HVDC Transmission System Progressive Peak Staggering Recovery Strategy
According to the analysis of the dynamic reactive power demand of LCC-HVDC during the fault recovery process in the previous section, there is a peak value of dynamic reactive power demand during the fault recovery process. Therefore, for a multi-feed DC system composed of conventional DC, if the conventional DC control strategy is maintained for each LCC-HVDC during the fault recovery period, there will be continuous commutation failures, the dynamic reactive power demand of each HVDC reaches the peak at the same time, and the total reactive power demand is relatively large. According to the change in T in the previous section, the moment when each HVDC reaches the maximum value during the fault recovery period can be staggered. Therefore, a staggering recovery strategy [17,18] was proposed to smooth the reactive power demand of a multi-infeed HVDC transmission system and reduce the reactive power peak value in the recovery process.
As shown in Figure 6, a first-order delay and a small link after the voltage-dependent current order limit (VDCOL) are set for each LCC-HVDC to realize the staggering recovery strategy of the multi-infeed HVDC transmission system. The small link can guarantee that the first-order delay only works when the current increases, adjusts the recovery speed of the DC current, and achieves the purpose of coordinating the orderly recovery of each HVDC line’s current. Moreover, the time constant Td of the first-order delay is positively correlated with the recovery speed of the DC current. The larger the time constant, the slower the DC recovery speed, and the longer it takes for the DC current to return to a steady state. Therefore, the recovery speed of each HVDC line after a fault can be adjusted by changing the time constant.
Figure 6.
Structure of a staggering recovery strategy for a hybrid multi-infeed HVDC transmission system.
The control effect of DC current under the staggering recovery strategy of each HVDC is shown in Figure 7. Curve 0 is the current characteristic when the time constant of the small link is 0 (equal to the original curve). Curve 1 and Curve 2 are the current characteristics when the time constant is Td1 and Td2, respectively, where Td1 < Td2.
Figure 7.
Current characteristics under different time constants.
To determine the optimal value of this critical parameter Td, an optimization process was implemented using the Multiple Run feature in PSCAD/EMTDC, based on the index mentioned in reference [17]. The procedure was as follows: First, calculate the progressive peak-shaving recovery factor DIR for each DC circuit based on the content of reference [17], and rank the recovery sequence of each DC circuit according to its magnitude. Next, multiple compensation settings for the time constant Td are established within the range of 0–60 ms at 10 ms intervals. Using the multiple-run capability in PSCAD/EMTDC (Version 4.6.2) software, calculations are performed to observe the reactive demand curve and active power delivery curve during the restoration process under different Td values. The following two metrics are comprehensively evaluated: (1) minimum peak total reactive demand; and (2) shortest time required for line active power delivery to recover to 0.9 p.u. The Td value achieving the optimal coordination of these two metrics is ultimately selected as the staggered restoration time constant adopted in this study.
This systematic approach ensured that the selected Td values effectively staggered the reactive power peaks while maintaining satisfactory active power recovery speed. Building upon this optimized staggering recovery of LCC-HVDCs, the following section introduces the coordinated control strategy with VSC-HVDC to further enhance the overall post-fault characteristics.
4. Coordinated Control Strategy for Hybrid Multi-Feed DC Transmission Systems
In order to improve the fault recovery characteristics of a hybrid multi-infeed HVDC transmission system and make full use of the fast dynamic response of VSC-HVDC, this paper proposes a fault recovery performance improvement strategy for a hybrid multi-infeed HVDC transmission system. The basic idea of this strategy is that, in the process of fault recovery, a progressive peak staggering recovery is adopted between LCC-HVDCs. VSC-HVDC adopts an adaptive current limiting strategy; at the same time, VSC-HVDC considers the coordinated reactive power control of each HVDC system, which dynamically adjusts the upper and lower limit value of the VSC-HVDC q-axis reactive power outer loop output iq* according to the reactive power shortage of LCC. A schematic diagram of the absorbed reactive power of the converter station under different control strategies is shown in Figure 8.
Figure 8.
Schematic diagram of absorbed reactive power of the converter station.
In Figure 8, as for the traditional simultaneous recovery control strategy, when the AC voltage at the receiving-end system is restored to near the rated value, the AC voltage will remain basically constant. While the VSC-HVDC control strategy adopts a constant AC voltage, this will lead to weak regulation of the reactive power at this stage. On the contrary, the DC current of each LCC-HVDC increases rapidly, and the arc extinction angle is still at a larger level. At this point, LCC-HVDC will reach the peak reactive power demand almost at the same time, so the first peak reactive power demand is larger in this case. For the progressive peak staggering recovery strategy, the core is to stagger the DC current recovery process of each LCC-HVDC, which reflects that multiple peaks will be formed on the reactive power waveform, but the biggest peak will be smaller than that of the simultaneous recovery strategy. However, this strategy has little effect on the AC voltage of the receiving end, so it still fails to exert the reactive power regulation ability of VSC-HVDC at this stage. As for the hybrid multi-infeed HVDC transmission system improvement strategy proposed in this paper, the reactive power regulation ability of the VSC-HVDC can be adequately utilized. On the basis of the progressive peak staggering recovery, VSC-HVDC will provide more reactive power at the valley of reactive power demand and less at the peak of reactive power demand, so that the total reactive power absorbed during the fault recovery process is closest to its steady-state operating value.
4.1. Dynamic Power Limiting Regulation Strategy
The dynamic power limiting regulation strategy is the core of the coordinated control strategy for a hybrid multi-infeed HVDC transmission system, which is based on the adaptive current limit [30] (the logic diagram of adaptive current limit control is shown in Figure 9).
Figure 9.
The logic diagram of adaptive current limit control.
According to the reactive power shortage of LCC-HVDC, the strategy dynamically adjusts the upper and lower limit values of the VSC-HVDC q-axis reactive power outer loop output iq*, so that the steady-state operating point of the VSC-HVDC can be changed during the fault period. The specific control logic diagram is shown in Figure 10. The outputs iqlim max1 and iqlim min1 serve as the upper and lower limits of the reactive current for the adaptive current limiting controller.
Figure 10.
Specific control logic diagram of VSC-HVDC.
In Figure 10, iqlim1 is calculated according to the instantaneous power theory, and the formula is:
where QLCC is the reactive power absorbed by the LCC from the AC system, Sb is the reference value of system capacity, and vod and voq are the dq axis components of the AC voltage at the receiving end, respectively. According to the phase-locked loop control theory, vod = 1 and voq = 0, and the final iqlim1 can be calculated by:
The dynamic power limiting regulation strategy includes the following parts:
- Selection of upper and lower limits
According to the calculated reference value of iqlim1, calculate its slope. When the slope is positive, modify the lower limit value of iq* and select as iqlim1; otherwise, select as iqlimmin. On the contrary, when the slope is negative, modify the upper limit value of iq* and select as iqlim1, or otherwise as iqlimmax, where iqlimmin and iqlimmax are the static reactive power limiting values.
- 2.
- Slope limitation
Considering the fast regulation speed of VSC-HVDC, the slope controller is added to limit the rate of change in reactive power so as to avoid the continuous commutation failure of LCC caused by the rapid fluctuation of reactive power.
- 3.
- Control enable
Control the operation of the control strategy. The enabling signal is selected as the output signal of the fault identification module. When a fault is identified, the output signal is set to 1 and maintained until the system recovers to near the steady-state value. A detailed control logic block diagram can be found in reference [31].
Through the synergy effects of the above control strategies, VSC-HVDC can quickly compensate for the reactive power shortage of LCC-HVDC and ease the reactive power demand of the converter station on the receiving-end system during the process of fault recovery.
4.2. Implementation Process of VSC-HVDC Coordinated Control Strategy
The coordinated control strategy of the VSC-HVDC mainly includes the adaptive current limiting strategy and the dynamic power limiting regulation strategy. The output of the dynamic power limiting regulation strategy provides the input parameters for the reactive current limiting in the adaptive current limiting strategy. The dynamic power limiting regulation strategy is to limit the reactive current reference value iq*, while the adaptive current limiting strategy is to use the remaining capacity as a limit to id* on the basis of satisfying the demand of the reactive current. The flowchart of the coordinated control strategy for the VSC-HVDC is shown in Figure 11, and the specific steps are as follows:
Figure 11.
The flowchart of the VSC-HVDC coordinated control strategy.
- (1)
- Sample the reactive power absorbed from the AC system by each LCC-HVDC receiving end converter station and transmit it to the VSC-HVDC control system through the communication network. Use the single-phase to ground short-circuit fault and three-phase short-circuit fault criteria of commutation failure predictive control to determine whether the fault occurs. If the result is yes, skip to step 2; otherwise, skip to step 4.
- (2)
- Sum the reactive power shortage value of each converter station and calculate the limiting value iqlim1 of iq by Equation (12).
- (3)
- Send the limit value of iq obtained in the previous step to the dynamic power limiting adjustment controller to calculate the upper and lower limit values of the final signal iq and use it as the upper and lower limits iqlimmin1 and iqlimmax1 of the reactive current limits output by the outer loop of the adaptive current limiting controller. Then, skip to step 5.
- (4)
- Use the static setting values iqlimmin and iqlimmax as the upper and lower limits of the reactive current limits output by the outer loop of the adaptive current limiting controller.
- (5)
- Use the adaptive current limit controller as shown in Figure 9 to calculate iq1* and id1* by iqlimmin1 and iqlimmax1 obtained in the previous step.
5. Experimental Verification
To verify the improvement effect of the control strategy proposed in this paper, a hybrid tri-infeed HVDC transmission system is established in the PSCAD/EMTDC (Version 4.6.2) simulation software. The rated firing angle αN of the inverter side is 142°, the minimum extinguishing angle γmin is 7°, and the line impedance value of three AC lines (L1-2, L1-3, and L2-3) is Z13 = Z23 = Z12/2 = 1.8 + j4.15(Ω). The main parameters of LCC-HVDC and VSC-HVDC are shown in Table 1 and Table 2. The transmission power of each line under initial steady-state conditions is shown in Table 3.
Table 1.
Specific parameters of the LCC-HVDC system.
Table 2.
Specific parameters of the VSC-HVDC system.
Table 3.
Power transmitted by each line under initial steady-state conditions.
Three groups of different cases for comparative analysis are set as follows:
Case 1: Both LCC-HVDCs and VSC-HVDC adopt the traditional control strategy.
Case 2: A progressive peak staggering recovery strategy is adopted between LCC-HVDCs, whereas a traditional control strategy is adopted for VSC-HVDC.
Case 3: The fault recovery improvement strategy proposed in this paper is applied.
In all cases, the contingency faults are applied to the simulation model: after the system stabilizes, a three-phase short-circuit fault is applied at the receiving end commutation bus at 5.0 s. The fault lasts 100 ms, and the simulation runs from 4.9 s to 5.9 s. The time domain simulation waveform comparison diagram of three cases is shown in Figure 12.
Figure 12.
Comparison of simulation waveforms with different Td.
As shown in Figure 12, when the progressive peak staggering recovery strategy between LCC-HVDCs is adopted, from the perspective of the commutation failure duration (the time of duration when γ is below 7.2° [32]), LCC can return to normal commutation 0.04 s earlier than the non-adopted one. It can be seen that the progressive peak staggering recovery can improve the ability of LCC-HVDC to resist continuous commutation failure to some extent. Case 2 and case 3 show that there is little difference in extinction angle between the two cases during the process of fault recovery. From this point, we can know that the proposed VSC dynamic power limiting strategy primarily affects the total reactive power of the converter station. Further comparison of the two cases of VSC output reactive power waveform shows that using a dynamic power limiting regulation control strategy can give full play to the ability of VSC to adjust reactive power quickly. VSC-HVDC can rapidly reduce its output reactive power and reduce the surplus reactive power of the system in the process of voltage recovery after fault clearance. At the same time, the VSC can increase the reactive power output at the peak of the LCC consumption reactive power during the process of fault recovery and reduce the reactive power output at the valley. The speed of reactive power recovery to the pre-fault level in case 3 is better than the traditional control strategy or just adopting the progressive peak staggering recovery strategy.
Some evaluation indexes are given in Table 4. It can be seen that among the three cases, case 3 has the best fault recovery characteristics, with the advantages of a smaller reactive power peak value, faster fault recovery speed, and smaller reactive power fluctuation. Therefore, the fault recovery characteristic improvement strategy proposed in this paper is better than the traditional control strategies, and this strategy gives full play to the ability of the reactive power support of VSC-HVDC.
Table 4.
Fault recovery evaluation index data under different recovery strategies.
The data in Table 3 indicate that despite the strategy employed in case 2 successfully reducing the peak reactive power demand, it results in a longer total recovery time. This is an inherent and expected trade-off. The strategy intentionally slows down the current recovery of one (or more) LCC-HVDC lines by assigning it a larger time constant Td, thereby staggering the reactive power peaks. While this progressive recovery strategy effectively alleviates the instantaneous stress on the AC voltage, it inevitably extends the duration for the entire system to return to its pre-fault steady-state power level. Case 3 demonstrates how this trade-off can be mitigated. By integrating the VSC-HVDC’s dynamic reactive power support, the proposed coordinated strategy not only maintains the benefit of reduced peak demand but also significantly accelerates the overall recovery process, achieving a superior performance on both metrics.
6. Conclusions
In this paper, the characteristics of the dynamic reactive power demand of the inverter after a large disturbance are analyzed, and the method of determining the dynamic reactive power demand curve Qdi of the inverter after a large disturbance is illustrated. Based on the research of reactive power demand, a strategy is proposed to improve the fault recovery characteristics of the hybrid multi-infeed HVDC transmission system, which is a control strategy that combines the progressive peak staggering recovery strategy between the LCC-HVDCs and the dynamic adaptive limiting strategy of VSC-HVDC. The strategy can reduce the reactive power peak value during the process of fault recovery and improve the ability of LCC-HVDC to resist continuous commutation failure by controlling the recovery sequence of each LCC and staggering the time of the reactive power peak value. By adopting the control strategy of dynamic power limiting regulation, the ability of fast reactive power regulation of VSC-HVDC can be fully utilized, the impact of reactive power during the fault recovery process on the receiving-end AC system can be reduced, and the system stability can be adequately improved.
It is worth noting that the proposed coordinated strategy relies on communication between the LCC-HVDC and VSC-HVDC controllers to transmit reactive power information. In practical applications, communication delays may exist. Excessive delays could desynchronize the VSC’s reactive support from the LCC’s instantaneous demand, potentially diminishing the effectiveness of peak shaving and recovery acceleration. Future work will investigate the robustness of the strategy to such delays and explore compensation methods or alternative local measurement-based coordination schemes to mitigate this dependency.
Author Contributions
Conceptualization, B.J.; Methodology, B.J. and G.Z.; Software, B.J. and G.Z.; Formal Analysis, Z.L.; Investigation, S.L. and H.D.; Writing—Original Draft, B.J.; Writing—Review and Editing, C.J. and J.L.; Visualization, X.Z.; Supervision, B.J.; Funding Acquisition, B.J. All authors have read and agreed to the published version of the manuscript.
Funding
Supported by the Science and Technology Projects of China Southern Power Grid. (No. 030000KC24040059).
Data Availability Statement
The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.
Conflicts of Interest
Authors Bingjie Jin, Guangjian Zhang, Zuohong Li, Shuxin Luo, Chu Jin, Xinyue Zhang were employed by the Power Grid Planning and Research Center, Guangdong Power Grid Co., Ltd. Author Hong Dong was employed by the Guangzhou Power Supply Bureau, Guangdong Power Grid Co., Ltd. Author Jindi Luo was employed by the Shantou Power Supply Bureau, Guangdong Power Grid Co., Ltd. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest. The authors declare that this study received funding from China Southern Power Grid. The funder had the following involvement with the study: project administration.
References
- Shu, H.; Shao, Z.; Zhao, W. A Subsequent Commutation Failure Suppression Strategy for LCC Hierarchical Access in Hybrid Multi-Infeed HVDC Transmission Systems. High Volt. Eng. 2024, 50, 2760–2773. [Google Scholar] [CrossRef]
- Rao, H.; Zhou, Y.; Zou, C.; Xu, S.; Li, Y.; Yang, L.; Huang, W. Design Aspects of Hybrid HVDC System. CSEE J. Power Energy Syst. 2021, 7, 644–653. [Google Scholar]
- Mochamad, R.F.; Preece, R. Assessing the Impact of VSC-HVDC on the Interdependence of Power System Dynamic Performance in Uncertain Mixed AC/DC Systems. IEEE Trans. Power Syst. 2020, 35, 63–74. [Google Scholar] [CrossRef]
- Oliveira, D.; Leal, G.C.B.; Herrera, D.; Galván-Díez, E.; Carrasco, J.M.; Aredes, M. An Analysis on the VSC-HVDC Contribution for the Static Voltage Stability Margin and Effective Short Circuit Ratio Enhancement in Hybrid Multi-Infeed HVDC Systems. Energie 2023, 16, 532. [Google Scholar] [CrossRef]
- Rao, H.; Zou, C.Y.; Xu, S.K.; Cai, X.P.; Li, Y.; Zhao, X.B.; Zhou, Y.B.; Yang, Y.; Wei, W.; Chen, J.; et al. The On-Site Verification of Key Technologies for Kunbei-Liuzhou-Longmen Hybrid Multi-terminal Ultra HVDC Project. CSEE J. Power Energy Syst. 2022, 8, 1281–1289. [Google Scholar]
- Rao, H.; Hong, C.; Zhou, B.; Huang, D.; Xu, S.; Yao, W.; Zhou, Y. Study on the Improvement Effect of Flexible DC on Multi-Infeed DC Concentration Problems at the Receiving End of the Wudongde UHV Multi-Terminal HVDC Project. South. Power Syst. Technol. 2017, 11, 1–5. [Google Scholar] [CrossRef]
- Dong, Z.; Wang, G.; Xu, Z.; Li, J.; Ding, H. Operational Characteristics Analysis Method of Baihetan–Jiangsu UHV Hybrid Cascaded HVDC System. Electr. Power Autom. Equip. 2022, 42, 118–125. [Google Scholar] [CrossRef]
- Lei, X.; Yang, L.; Zhu, Y.; Huang, W.; Cui, X.; Pang, G.; Yang, S. Construction and Characteristics Analysis of Digital Simulation Platform for the Baihetan–Jiangsu UHV Hybrid Cascaded HVDC Project. Power Syst. Technol. 2024, 48, 434–443. [Google Scholar] [CrossRef]
- Lu, J.; Yuan, X.; Hu, J.; Zhang, M.; Yuan, H. Motion equation modeling of LCC-HVDC stations for analyzing DC and AC network interactions. IEEE Trans. Power Deliv. 2020, 35, 1563–1574. [Google Scholar] [CrossRef]
- Xiao, H.; Li, Y.; Gole, A.M.; Duan, X. Computationally efficient and accurate approach for commutation failure risk areas identification in multi-infeed LCC-HVDC systems. IEEE Trans. Power Electron. 2020, 35, 5238–5253. [Google Scholar] [CrossRef]
- Mirsaeidi, S.; Dong, X. An enhanced strategy to inhibit commutation failure in line-commutated converters. IEEE Trans. Ind. Electron. 2020, 67, 340–349. [Google Scholar] [CrossRef]
- Liu, X.; Wang, Z.; Zheng, B.; Wang, T.; Qiao, X. Mechanism Analysis and Suppression Measures of Continuous Commutation Failure During Fault Recovery of LCC-HVDC Systems. Proc. CSEE 2020, 40, 3163–3172. [Google Scholar] [CrossRef]
- Zheng, B.; Hu, J.; Wang, T.; Wang, Z. Mechanism Analysis of a Subsequent Commutation Failure and a DC Power Recovery Speed Control Strategy. Electronics 2022, 11, 998. [Google Scholar] [CrossRef]
- Xiao, L.; Li, Y.; Xiao, H.; Zhang, Z.; Xu, Z. Electromechanical Transient Modeling of Line Commutated Converter-Modular Multilevel Converter-Based Hybrid Multi-Terminal High Voltage Direct Current Transmission Systems. Energies 2018, 11, 2102. [Google Scholar] [CrossRef]
- Xia, C.; Lan, H.; Du, Z.; Zhou, B.; Hong, C. Fast Proximate Calculation of Dynamic Reactive Power Peak Demand in Inverter of HVDC. J. South China Univ. Technol. (Nat. Sci. Ed.) 2017, 45, 8–14. [Google Scholar]
- Yang, W.; Miao, S.; Zhang, S.; Li, Y.; Han, J.; Xu, H.; Zhang, D. A commutation failure risk analysis method considering the interaction of inverter stations. Int. J. Electr. Power Energy Syst. 2020, 120, 106009. [Google Scholar] [CrossRef]
- Xia, C.; Huang, H.; Tu, L.; Hong, C. Coordinated and Progressive Recovery Strategy for Failure at Receiving End of Multi-Infeed DC Systems. J. South China Univ. Technol. (Nat. Sci. Ed.) 2016, 44, 47–54. [Google Scholar] [CrossRef]
- Feng, M.; Zheng, L.; Zhang, L.; Zhang, B. Voltage Stability Analysis and Coordinated Power Recovery Control Strategy of MIDC System. In Proceedings of the 2020 5th Asia Conference on Power and Electrical Engineering (ACPEE), Chengdu, China, 4–7 June 2020; pp. 381–385. [Google Scholar]
- Xiang, S.; Wan, Y.; Zhang, C.; Chen, L.; Wu, J.; Liu, F.; Tian, Y. Incremental Recovery Strategy Based on Additional Current Order to Suppress the Successive Commutation Failure of Multi-infeed DC System. Electr. Power Constr. 2021, 42, 20–26. [Google Scholar]
- Lv, Z.; Wang, B.; Guo, Q.; Sun, H.; Zhao, H.; Jiang, M. Coordinated Optimization for Multi-Infeed LCC-HVDCs Transient Control Considering Short-Term Voltage Stability of Receiving-End Grid. IEEE Trans. Power Syst. 2023, 38, 5512–5525. [Google Scholar] [CrossRef]
- Zhu, J.; Li, Y.; Duan, Y. A Constant Extinction Area Based Control Strategy for Suppressing Commutation Failure in Hybrid Dual-Infeed HVDC System. Power Syst. Technol. 2018, 42, 3735–3743. [Google Scholar] [CrossRef]
- Lin, Z.; He, X.; Li, C.; Yao, W.; Xia, C.; Min, X. Control Strategy to Mitigate Risk of Hybrid HVDC Continuous Commutation Failure. In Proceedings of the 2019 IEEE PES Asia-Pacific Power and Energy Engineering Conference(APPEEC), Macao, China, 1–4 December 2019; pp. 1–5. [Google Scholar]
- Xiao, C.; Ouyang, J.; Xiong, X.; Li, M.; Zheng, D. Subsequent Commutation Failure Control Method Based on Coordination Between Active and Reactive Powers in Hybrid Dual-infeed HVDC System. Power Syst. Technol. 2019, 43, 3523–3531. [Google Scholar] [CrossRef]
- Zhao, J.; Li, W.; Wang, D. A coordinated AC-DC recovery strategy for suppressing continuous commutation failures in HVDC transmission. Energy Rep. 2025, 14, 2236–2246. [Google Scholar] [CrossRef]
- Guo, C.; Yang, Z.; Ning, L.; Zhao, C. A Novel Coordinated Control Approach for Commutation Failure Mitigation in Hybrid Parallel-HVDC System with MMC-HVDC and LCC-HVDC. Electr. Power Compon. Syst. 2017, 45, 1773–1782. [Google Scholar] [CrossRef]
- Kwon, D.H.; Kim, Y.J.; Gomis-Bellmunt, O. Optimal DC Voltage and Current Control of an LCC HVDC System to Improve Real-Time Frequency Regulation in Rectifier- and Inverter-Side Grids. IEEE Trans. Power Syst. 2020, 35, 4539–4553. [Google Scholar] [CrossRef]
- Hou, L.; Li, X.; Wang, M. Grey-Fuzzy PI Optimal Control of MMC-HVDC System. In Proceedings of the 2020 IEEE 4th Conference on Energy Internet and Energy System Integration (EI2), Wuhan, China, 31 October–1 November 2020; pp. 3258–3262. [Google Scholar]
- Dong, Y.; Ma, J.; Wang, S.; Liu, T.; Huang, H. Small-Signal Dynamic Model and Stability Analysis of LCC-HVDC System. In Proceedings of the 2020 IEEE International Conference on Applied Superconductivity and Electromagnetic Devices (ASEMD), Tianjin, China, 16–18 October 2020; pp. 1–2. [Google Scholar]
- Wang, J.; Huang, M.; Fu, C.; Li, H.; Xu, S.; Li, X. A New Recovery Strategy of HVDC System During AC Faults. IEEE Trans. Power Deliv. 2019, 34, 486–495. [Google Scholar] [CrossRef]
- Liu, Y.; Chen, Z. A Flexible Power Control Method of VSC-HVDC Link for the Enhancement of Effective Short-Circuit Ratio in a Hybrid Multi-Infeed HVDC System. IEEE Trans. Power Syst. 2013, 28, 1568–1581. [Google Scholar] [CrossRef]
- Yao, W.; Liu, C.; Fang, J.; Ai, X.; Wen, J.; Cheng, S. Probabilistic Analysis of Commutation Failure in LCC-HVDC System Considering the CFPREV and the Initial Fault Voltage Angle. IEEE Trans. Power Deliv. 2020, 35, 715–724. [Google Scholar] [CrossRef]
- Hong, C. Simulation Analysis on the Commutation Failure and Power Recovery Characteristic of an Actual DC Transmission System. South. Power Syst. Technol. 2011, 5, 1–7. [Google Scholar]
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2025 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.