Interaction Analysis of Offshore Power Systems: A Comparative Study
Abstract
1. Introduction
- Determination of control objectives and system models;
- Selection of control structure;
- Interaction analysis;
- Controller design;
- Simulations, experimental validation, and implementation.
- Selection of input and output signals;
- Selection of the control configuration, including the input–output pairing problem.
2. Background and Related Work
3. Offshore Power Systems
4. Offshore Test System Modelling
4.1. Mathematical Background
4.2. Properties of the Test System
- onshore equivalent power system operating at 110 kV (EPS),
- 110 kV transmission line (line L1),
- 110/33 kV transformer (transformer T0),
- 33 kV transmission lines (lines L31, L32, and L33),
- 33/0.69 kV transformers (transformers T11, T21, and T22),
- 33/6.6 kV transformer (transformer T32),
- 33/10.5 kV transformer (transformer T33),
- static loads (OM1, OM2, OM3, and OM4),
- Static Var Compensator (SVC),
- offshore wind farm (WF1) rated at 50 MW,
- offshore wind farm (WF2) rated at 50 MW,
- marine current farm (MCF1) rated at 10 MW,
- gas turbine power plant (SG1) with a synchronous generator rated at 37.24 MW,
- large dynamic load represented by a Variable Speed Drive (VSD1) with an induction motor, rated at 9.5 MW.
4.3. Development of the Test Model
5. Interactions in Offshore Power Systems
5.1. Characteristic of Interactions in Offshore Power System
5.2. Sensitivity Method
5.3. Method of Magnitude Analysis of the Transfer Function G(s)
5.4. Relative Gain Array (RGA)
- —no interaction between control loops; the pairing of input–output signals should follow the diagonal elements of the RGA matrix, i.e., ,
- —no interaction between control loops; the pairing of input–output signals should be off-diagonal, i.e., with ,
- —the gain increases when the control loops are closed, indicating the presence of interactions. The highest level of interaction occurs for large values of ,
- —the gain decreases when the control loops are closed; interactions increase as approaches unity,
- —the control loops are closed, and negative values of indicate strong interaction; the larger the absolute value of , the stronger the coupling between control loops.
- select signal pairs for which the RGA value is close to unity,
- avoid signal pairs with negative RGA values,
- avoid signal pairs for which the RGA values are significantly greater than one.
5.5. Dynamic Relative Gain Array (DRGA)
5.6. Generalized Dynamic Relative Gain (GDRG)
6. Interaction Analysis
6.1. Eigenvalue Analysis
6.2. Amplitude–Phase Characteristics Analysis
6.3. Relative Gain Array (RGA) Analysis
6.4. Dynamic Relative Gain Array (DRGA) Analysis
6.5. Generalized Dynamic Relative Gain (GDRG) Analysis
6.6. Interaction Analysis Discussion
7. Summary
- The transfer function analysis method and the RGA are suitable for studying the properties of controller input signals but do not account for the influence of controller design. Therefore, these methods are most appropriate during the preliminary stage of analysis.
- To obtain a more comprehensive assessment, it is necessary to apply methods such as the DRGA and GDRG, which consider the dynamic characteristics of the designed controllers. Due to the specific nature of offshore power systems, the direct implementation of interaction analysis methods may face difficulties. This has been illustrated in the paper using the example of the DRGA method.
- Direct application of the DRGA led to highly distorted characteristics that prevented proper interaction assessment. To address this, a modified version of the DRGA was proposed, incorporating an additional filtering stage combining Finite Impulse Response (FIR) and Infinite Impulse Response (IIR) filters. The proposed modification effectively reduced distortions and enabled reliable interaction analysis and system property evaluation.
- The results showed that interactions in offshore power systems are influenced by factors such as system configuration and operating point. Therefore, multivariant interaction analyses are required to properly evaluate system behaviour under different operating conditions.
Author Contributions
Funding
Data Availability Statement
Conflicts of Interest
Abbreviations
| AC | Alternating Current |
| CCCs | Capacitor-Commutated Converters |
| CSCs | Current Source Converters |
| DC | Direct Current |
| DFIG | Doubly Fed Induction Generator |
| DRGA | Dynamic Relative Gain Array |
| EPS | Equivalent Power System |
| EU | European Union |
| FACTSs | Flexible AC Transmission Systems |
| GDRG | Generalized Dynamic Relative Gain |
| HVAC | High-Voltage Alternating Current |
| HVDC | High-Voltage Direct Current |
| IL | Industrial Load |
| LCC | Line-Commutated Converter |
| MIMO | Multiple-Input, Multiple-Output |
| OFS | Offshore Substation |
| OWF | Offshore Wind Farm |
| ONS | Onshore Substation |
| PMSG | Permanent Magnet Synchronous Generator |
| PSS | Power System Stabilizer |
| RGA | Relative Gain Array |
| SVC | Static Var Compensator |
| SSCIs | Sub-Synchronous Control Interactions |
| SSR | Sub-Synchronous Resonance |
| VSC | Voltage Source Converter |
References
- Minister Kurtyka on RES in the Polish Energy Mix—Ministry of Climate and Environment—Gov.pl Website. Available online: https://www.gov.pl/web/climate/minister-kurtyka-on-res-in-the-polish-energy-mix (accessed on 15 August 2025).
- Nguyen, P.Q.P.; Dong, V.H. Ocean Energy—A Clean Energy Source. Eur. J. Eng. Res. Sci. 2019, 4, 5–11. [Google Scholar] [CrossRef] [Scilit]
- Robak, S.; Raczkowski, R.; Piekarz, M. Development of the Wind Generation Sector and Its Effect on the Grid Operation—The Case of Poland. Energies 2023, 16, 6805. [Google Scholar] [CrossRef] [Scilit]
- Pruski, P.; Paszek, S. Analiza modalna przebiegów zakłóceniowych mocy chwilowej w krajowym systemie elektroenergetycznym. Elektryka 2011, 4, 81–96. [Google Scholar]
- Mithulananthan, N.; Cañizares, C.A.; Reeve, J. Tuning, Performance and Interactions of PSS and FACTS Controllers. Proc. IEEE Power Eng. Soc. Transm. Distrib. Conf. 2002, 2, 981–987. [Google Scholar] [CrossRef] [Scilit]
- GWEC. Global Offshore Wind Report 2025. Offshore Capacity Reached 83 GW by end-2024 with 8 GW Added. Available online: https://www.gwec.net/gwec-news/offshore-wind-installed-capacity-reaches-83-gw-as-new-report-finds-2024-a-record-year-for-construction-and-auctions (accessed on 7 August 2025).
- WindTech-International. Offshore Wind Additions in 2023 ~10.8 GW; Global Capacity 64.3 GW. 2025. Available online: https://www.mercomindia.com/global-offshore-wind-capacity-rises (accessed on 9 August 2025).
- GWEC. Global Wind Report 2025. Record 117 GW of New Wind Capacity in 2024; Offshore Share ~8 GW. Available online: https://renewablesnow.com/news/global-wind-installations-reach-record-117-gw-in-2024-gwec-1274126/ (accessed on 10 August 2025).
- GWEC. Forecast: Annual Offshore Installations to Rise from 16 GW in 2025 to 34 GW in 2030. 2025. Available online: https://www.gwec.net/gwec-news/wind-industry-installs-record-capacity-in-2024-despite-policy-instability (accessed on 10 August 2025).
- BloombergNEF; IEA. Offshore Capacity Projections: 218–258 GW by 2030. 2024. Available online: https://ember-energy.org/latest-insights/offshore-wind-targets-underpin-acceleration-to-2030-and-beyond/ (accessed on 10 August 2025).
- IRENA; ERM. Required Offshore Capacity for 1.5 °C Pathway: 494 GW by 2030, >2400 GW by 2050. 2024. Available online: https://www.erm.com/about/news/report-finds-most-countries-expected-to-miss-net-zero-offshore-wind-targets/ (accessed on 10 August 2025).
- Xie, X.; Shair, J.; Beerten, J.; Fan, L.; Gomis-Bellmunt, O.; Vorobev, P.; Preece, R.; Shah, S.; Wang, X.; Wang, Y.; et al. Guest Editorial: Control Interactions in Power Electronic Converter-Dominated Power Systems. Int. J. Electr. Power Energy Syst. 2024, 155, 109553. [Google Scholar] [CrossRef] [Scilit]
- Khaki-Sedigh, A.; Moaveni, B. Control Configuration Selection for Multivariable Plants; Lecture Notes in Control and Information Sciences; Springer: Berlin/Heidelberg, Germany, 2009. [Google Scholar] [CrossRef] [Scilit]
- Upadhyaya, S.; Veerachary, M. Interaction Quantification in Multi-Input Multi-Output Integrated DC-DC Converters. In Proceedings of the 2021 IEEE 4th International Conference on Computing, Power and Communication Technologies (GUCON 2021), Kuala Lumpur, Malaysia, 24–26 September 2021. [Google Scholar] [CrossRef] [Scilit]
- Robak, S.; Machowski, J.; Gryszpanowicz, K. Contingency Selection for Power System Stability Analysis. In Proceedings of the 18th International Scientific Conference on Electric Power Engineering (EPE), Kouty nad Desnou, Czech Republic, 17–19 May 2017; Volume 1, pp. 1–5. [Google Scholar]
- IRENA. Global Renewables Outlook 2020—Summary; International Renewable Energy Agency: Abu Dhabi, United Arab Emirates, 2020; Available online: https://www.irena.org/-/media/Files/IRENA/Agency/Publiction/2020/Apr/IRENA_GRO_Summary_2020.pdf (accessed on 4 December 2025).
- Cai, L.J.; Erlich, I. Simultaneous Coordinated Tuning of PSS and FACTS Damping Controllers in Large Power Systems. IEEE Trans. Power Syst. 2005, 20, 294–300. [Google Scholar] [CrossRef] [Scilit]
- Karawita, C.; Annakkage, U.D. HVDC-Generator-Turbine Torsional Interaction Studies Using a Linearized Model with Dynamic Network Representation. Change 2009, 10, 4. [Google Scholar]
- Xiao, H.; Li, Y. Multi-Infeed Voltage Interaction Factor: A Unified Measure of Inter-Inverter Interactions in Hybrid Multi-Infeed HVDC Systems. IEEE Trans. Power Deliv. 2020, 35, 2040–2048. [Google Scholar] [CrossRef] [Scilit]
- Bi, J.; Sun, H.; Guo, J.; Xu, S.; Yi, J.; Song, R. Influence of Dynamic Interaction Between Multiple DFIGs on Low-Frequency Oscillation of Power System. In Proceedings of the 2019 IEEE Power & Energy Society General Meeting (PESGM), Atlanta, GA, USA, 4–8 August 2019. [Google Scholar] [CrossRef] [Scilit]
- Li, P.; Wang, J.; Xiong, L.; Ma, M. Robust Nonlinear Controller Design for Damping of Sub-Synchronous Control Interaction in DFIG-Based Wind Farms. IEEE Access 2019, 7, 16626–16637. [Google Scholar] [CrossRef] [Scilit]
- Ye, J.; Li, S.; Feng, P.; Wang, X. Passive Control Strategy to Mitigate Sub-Synchronous Control Interaction of DFIG-Based Integrated Power Systems. In Proceedings of the 2023 International Conference on Power System Technology (PowerCon 2023), Jinan, China, 21–22 September 2023. [Google Scholar] [CrossRef] [Scilit]
- Tao, G.; Wang, Y.; Wu, Y.; Chen, Y. Subsynchronous Interaction Analysis of PMSG-Based Wind Farm with AC Networks. In Proceedings of the 22nd International Conference on Electrical Machines and Systems (ICEMS 2019), Harbin, China, 11–14 August 2019. [Google Scholar] [CrossRef] [Scilit]
- Li, P.; Wang, J.; Xiong, L.; Huang, S.; Ma, M.; Wang, Z. Energy-Shaping Controller for DFIG-Based Wind Farm to Mitigate Subsynchronous Control Interaction. IEEE Trans. Power Syst. 2021, 36, 2975–2991. [Google Scholar] [CrossRef] [Scilit]
- Liu, Y.; Huang, B.; Sun, H.; Zhang, Y.; Han, Y.; Yu, Y. Optimization of Control Parameters for PMSG-Based Wind Farm and SVG Considering Subsynchronous Interaction. In Proceedings of the 8th Renewable Power Generation Conference (RPG 2019), Shanghai, China, 24–25 October 2019; p. CP764. [Google Scholar] [CrossRef] [Scilit]
- Li, W.; Zheng, W.; Chen, Y. Stability and Interaction Analysis of PMSG-Based Wind Farms Connected with LCC-HVDC. In Proceedings of the 2023 Chinese Control and Decision Conference (CCDC 2023), Yichang, China, 20–22 May 2023; pp. 1361–1367. [Google Scholar] [CrossRef] [Scilit]
- Sun, W.; Wang, Q.; Cai, H.; Zhang, W.; Qi, W.; Xu, S.; Zhao, E. Interaction Between PMSG-Based Wind Farm and VSC-HVDC System in ACC Timescale. In Proceedings of the 2022 IEEE 5th International Electrical and Energy Conference (CIEEC 2022), Nangjing, China, 27–29 May 2022; pp. 2197–2201. [Google Scholar] [CrossRef] [Scilit]
- Bristol, E.H. On a New Measure of Interaction for Multivariable Process Control. IEEE Trans. Autom. Control 1966, 11, 133–134. [Google Scholar] [CrossRef] [Scilit]
- Messina, A.R.; Begovich, O.; López, J.H.; Reyes, E.N. Design of Multiple FACTS Controllers for Damping Inter-Area Oscillations: A Decentralised Control Approach. Int. J. Electr. Power Energy Syst. 2004, 26, 19–29. [Google Scholar] [CrossRef] [Scilit]
- Kinnaert, M. Interaction Measures and Pairing of Controlled and Manipulated Variables for Multiple-Input-Multiple-Output Systems: A Survey. Journal A 1995, 36, 15–23. [Google Scholar]
- Agbemuko, A.J. Dynamic Modelling and Interaction Analysis of Multi-terminal HVDC Systems. Int. J. Electr. Power Energy Syst. 2019, 113, 874–887. [Google Scholar] [CrossRef] [Scilit]
- Shi, J.; Chen, W.; Wei, Z.; Pei, X.; Sun, X. Quantitative Analysis of the Interactive Influence for Harmonic Emission in Wind Farms. Front. Energy Res. 2022, 9, 820963. [Google Scholar] [CrossRef] [Scilit]
- Cheah Mane, M. Sub-Synchronous Interactions in Wind Integrated Power Systems; Wiley: Hoboken, NJ, USA, 2023. [Google Scholar]
- Mugambi, G.R.; Darii, N.; Khazraj, H.; Romano, O.S.; Raducu, A.G.; Sharma, R.; Cutululis, N.A. Methodologies for Offshore Wind Power Plants Stability Analysis. arXiv 2024, arXiv:2410.13521v1. [Google Scholar] [CrossRef] [Scilit]
- Jacobson, M.Z.; Delucchi, M.A.; Cameron, M.A.; Mathiesen, B.V.; Østergaard, P.A.; Boschetti, L.; Cisilino, A.; Fajardy, M.; Briner, G.; Long, G.; et al. 100% Clean and Renewable Wind, Water, and Sunlight (WWS) All-Sector Energy Roadmaps for 139 Countries of the World. Energy Policy 2021, 149, 112111. Available online: https://web.stanford.edu/group/efmh/jacobson/Articles/I/CountriesWWS.pdf (accessed on 4 December 2025).
- European Parliamentary Research Service (EPRS). Japan’s 2050 Goal: A Carbon-Neutral Society; European Parliament: Brussels, Belgium, 2021. Available online: https://www.europarl.europa.eu/RegData/etudes/BRIE/2021/698023/EPRS_BRI(2021)698023_EN.pdf (accessed on 4 December 2025).
- Banet, C.; Willems, B. Scaling up Offshore Wind Energy in Europe; CERRE: Brussels, Belgium, 2023; Available online: https://cerre.eu/wp-content/uploads/2023/10/CERRE-REPORT-OFFSHOREWINDINEUROPE.OCT23-2-1.pdf (accessed on 4 December 2025).
- Icaza-Alvarez, D.; Galan-Hernandez, N.D.; Orozco-Guillen, E.E.; Jurado, F. Smart Energy Planning in the Midst of a Technological and Political Change towards a 100% Renewable System in Mexico by 2050. Energies 2023, 16, 7121. [Google Scholar] [CrossRef] [Scilit]
- Icaza-Alvarez, D.; Jurado, F.; Tostado-Véliz, M. Smart energy transition with the inclusion of floating wind energy in existing hydroelectric reservoirs with a view to 2050. Ecuadorian case study. Energy Rep. 2023, 10, 2804–2816. [Google Scholar] [CrossRef] [Scilit]
- Department of Mineral Resources and Energy (DMRE). Comments and Responses on the Draft Integrated Resource Plan (IRP) 2023; DMRE: Pretoria, South Africa, 2024. Available online: https://www.dmre.gov.za/Portals/0/Energy%20Resources/IRP/IRP%202025/Comments-and-Responses-on-the-Draft-IRP.pdf?ver=SYi03wt4df8ObzUMUkU8Ng%3D%3D (accessed on 4 December 2025).
- Kakoulaki, G.; Gonzalez-Sanchez, R.; Gracia-Amillo, A.; Szabó, S.; Farinosi, F.; De Felice, L.; Bisselink, B.; Seliger, R.; De Felice, M.; Kougias, I.; et al. Benefits of Pairing Floating Solar Photovoltaics with Hydropower Reservoirs in Europe. Renew. Sustain. Energy Rev. 2023, 171, 112989. [Google Scholar] [CrossRef] [Scilit]
- Vidović, V.; Krajačić, G.; Matak, N.; Stunjek, G.; Mimica, M. Review of the Potentials for Implementation of Floating Solar Panels on Lakes and Water Reservoirs. Renew. Sustain. Energy Rev. 2023, 178, 113237. [Google Scholar] [CrossRef] [Scilit]
- Robak, S.; Piekarz, M. Problematyka stabilności kątowej morskich systemów elektroenergetycznych. Przegląd Elektrotech. 2015, 91, 278–283. [Google Scholar] [CrossRef] [Scilit]
- Robak, S. Sources of Uncertainty in Power System Analysis. Przegląd Elektrotech. 2008, 84, 54–57. [Google Scholar]
- Equinor Industriminne. Powering Johan Sverdrup from Shore. Available online: https://www.equinor.com/news/archive/2018-10-09-johan-sverdrup-powered-shore (accessed on 10 September 2025).
- Thema Consulting/OffshoreNorge. Electrification of the Oil and Gas Sector–Thema Report 2022–2023. OffshoreNorge, January 2023. Available online: https://www.offshorenorge.no/contentassets/97cb69dec47d4ecbaff23c16af5ce50c/thema-report_2022-23_electrification-of-the-oil-and-gas-sector-endelig-1.pdf (accessed on 16 September 2025).
- Precise Consultants. Dutch subsidy Enables World’s First Offshore Green Hydrogen Project. Precise Consultants. Available online: https://www.preciseconsultants.com/news/dutch-subsidy-enables-world-s-first-offshore-green-hydrogen-project/ (accessed on 4 October 2025).
- OEDigital. Lhyfe Meets Its Green Hydrogen Objectives with First Offshore Demonstrator; OEDigital: Mildura, Australia, 2024; Available online: https://www.oedigital.com/news/511109-lhyfe-meets-its-green-hydrogen-objectives-with-first-offshore-demonstrator (accessed on 15 October 2025).
- Danish Energy Agency. Denmark Decides to Construct World’s First Wind-Energy Hub Artificial Island—North Sea; Danish Energy Agency: Esbjerg, Denmark, 2021. Available online: https://ens.dk/en/press/denmark-decides-construct-worlds-first-windenergy-hub-artificial-island-north-sea (accessed on 18 October 2025).
- Energinet. EIB Business Case Summary UK. Available online: https://en.energinet.dk/media/fj4bkl1y/eib-business-case-summary-uk.pdf (accessed on 2 November 2025).
- ENTSO-E. Offshore Roadmap 2025; ENTSO-E: 2025. Available online: https://eepublicdownloads.blob.core.windows.net/public-cdn-container/clean-documents/Publications/2025/ENTSO-E_Offshore_Roadmap_2025.pdf (accessed on 4 November 2025).
- Rendecki, R. Kompensacja Mocy Biernej w Sieciach Kablowych WN; Politechnika Warszawska: Warszawa, Poland, 2015. [Google Scholar]
- Kanicki, A. Elektrownia w Systemie Elektroenergetycznym; Wydawnictwo Instytutu Elektroenergetyki PŁ: Łódź, Poland, 2011. [Google Scholar]
- Larsson, J. Transmission Systems for Grid Connection of Offshore Wind Farms; Uppsala Universitet: Uppsala, Sweden, 2021. [Google Scholar]
- Błajszczak, G.; Wasiluk-Hassa, M.; Malinowski, M.; Kaźmierkowski, M.; Jasiński, M. Współczesne Systemy Przesyłu Energii Prądem Stałym HVDC. Elektroenergetyka 2011, 1, 23–41. [Google Scholar]
- Javed, U.; Mughees, N.; Jawad, M.; Azeem, O.; Abbas, G.; Ullah, N.; Chowdhury, M.S.; Techato, K.; Zaidi, K.S.; Tahir, U. A Systematic Review of Key Challenges in Hybrid HVAC–HVDC Grids. Energies 2021, 14, 5451. [Google Scholar] [CrossRef] [Scilit]
- Jafar, M.; Vaessen, P.; Yanushekvich, A.; Fu, Y.; Marchall, R.; Bosman, T.; Irvine, M.; Yang, Y. Hybrid Grid Towards a Hybrid AC/DC Transmission Grid; DNV GL Strategic Research and Innovation Paper, No. 2: Bellum, Norway, 2015. [Google Scholar]
- Kundur, P. Power System Stability and Control; McGraw-Hill Education: Columbus, OH, USA, 1994. [Google Scholar]
- Robak, S.; Rasolomampionona, D.D. Interactions Analysis of UPFC Multifunction Controller. In Proceedings of the 2009 IEEE Bucharest PowerTech, Bucharest, Romania, 28 June 2009–2 July 2009. [Google Scholar] [CrossRef] [Scilit]
- Wang, X.F.; Li, H.F.; Du, W.J.; Chen, Z.; Wang, H.F.; Bu, S.Q. Dynamic Interactions of Multiple Functions of a Power-Angle Controlled and Vector-Current Controlled UPFC. In Proceedings of the 12th IET International Conference on AC and DC Power Transmission (ACDC 2016), Beijing, China, 28–29 May 2016. [Google Scholar] [CrossRef] [Scilit]
- Zhang, Z.; Xiao, Y.; Ruan, H.; Yang, Y.; Blaabjerg, F. Coupling Quantization Among Control Loops of Parallel Grid-Following and Grid-Forming Inverters. In Proceedings of the 2024 IEEE Energy Conversion Congress and Exposition (ECCE 2024), Phoenix, AZ, USA, 20–24 October 2024; pp. 1318–1325. [Google Scholar] [CrossRef] [Scilit]
- Larsen, E.V.; Sanchez-Gasca, J.J.; Chow, J.H. Concepts for Design of FACTS Controllers to Damp Power Swings. IEEE Trans. Power Syst. 1995, 10, 948–956. [Google Scholar] [CrossRef] [Scilit]
- Gibbard, M.J. Interactions Between, and Effectiveness of, Power System Stabilizers and FACTS Device Stabilizers in Multimachine Systems. IEEE Trans. Power Syst. 2000, 15, 748–755. [Google Scholar] [CrossRef]
- Wang, H.F.; Swift, F.J.; Li, M. Indices for Selecting the Best Location of PSSs or FACTS-Based Stabilizers in Multimachine Power Systems: A Comparative Study. IEE Proc. Gener. Transm. Distrib. 1997, 144, 155–159. [Google Scholar] [CrossRef] [Scilit]
- Robak, S. Analiza Interakcji Układów Regulacji w Wielomaszynowym Systemie Elektroenergetycznym—Przegląd Metod. In Proceedings of the XII International Scientific Conference “Aktualne Problemy w Elektroenergetyce APE ’05”, Gdańsk–Jurata, Poland, 8–10 June 2005. [Google Scholar]
- Fan, L.; Feliachi, A.; Schoder, K. Selection and Design of a TCSC Control Signal in Damping Power System Inter-Area Oscillations for Multiple Operating Conditions. Electr. Power Syst. Res. 2002, 62, 127–137. [Google Scholar] [CrossRef] [Scilit]
- Martins, N.; Lima, L.T.G. Determination of Suitable Locations for Power System Stabilizers and Static Var Compensators for Damping Electromechanical Oscillations in Large Scale Power Systems. IEEE Trans. Power Syst. 1990, 5, 1455–1469. [Google Scholar] [CrossRef] [Scilit]
- Wittenmark, B.; Salgado, M.E. Hankel-Norm Based Interaction Measure for Input-Output Pairing. IFAC Proc. 2002, 35, 429–434. [Google Scholar] [CrossRef] [Scilit]
- Halvarsson, B. Interaction Analysis in Multivariable Control Systems: Applications to Bioreactors for Nitrogen Removal; Uppsala University: Uppsala, Sweden, 2010. [Google Scholar]
- Robak, S. Nowa Metoda Hierarchicznego Sterowania Generatorów Synchronicznych Poprawiająca Stabilność Systemu Elektroenergetycznego; Politechnika Warszawska: Warszawa, Poland, 1999. [Google Scholar]
- Milanović, J.V.; Duque, A.C.S. Identification of Electromechanical Modes and Placement of PSSs Using Relative Gain Array. IEEE Trans. Power Syst. 2004, 19, 410–417. [Google Scholar] [CrossRef]
- Huang, H.P.; Ohshima, M.; Hashimoto, I. Dynamic Interaction and Multiloop Control System Design. J. Process Control 1994, 4, 15–27. [Google Scholar] [CrossRef] [Scilit]
- MathWorks. 1-D Digital Filter-MATLAB Filter. Available online: https://www.mathworks.com/help/matlab/ref/filter.html (accessed on 22 August 2025).

















| Type of Interaction | Frequency |
|---|---|
| Steady-state interactions | 0 Hz |
| Electromechanical oscillation interactions | 0–3/5 Hz |
| Control system coupling interactions | 2–15 |
| Sub-synchronous resonance interactions | 2–50/60 Hz |
| Harmonic interactions, high-frequency resonance effects, and electromagnetic transient interactions | >15 Hz |
| Element | Eigenvalue | Frequency [Hz] | Damping [-] | Load |
|---|---|---|---|---|
| Synchronous Generator (Variant I) | −0.236 ± 5.263 | 0.838 | 0.045 | 25% |
| −0.186 ± 5.360 | 0.853 | 0.035 | 50% | |
| −0.123 ± 5.507 | 0.877 | 0.022 | 75% | |
| −0.060 ± 5.674 | 0.903 | 0.010 | 100% | |
| Synchronous Generator (Variant II) | −0.238 ± 5.279 | 0.840 | 0.045 | 25% |
| −0.189 ± 5.374 | 0.855 | 0.035 | 50% | |
| −0.128 ± 5.517 | 0.878 | 0.023 | 75% | |
| −0.065 ± 5.681 | 0.904 | 0.011 | 100% | |
| Synchronous Generator (Variant III) | −0.241 ± 5.281 | 0.840 | 0.046 | 25% |
| −0.193 ± 5.375 | 0.856 | 0.036 | 50% | |
| −0.131 ± 5.518 | 0.878 | 0.024 | 75% | |
| −0.069 ± 5.680 | 0.904 | 0.012 | 100% |
| Element | Eigenvalue | Frequency [Hz] | Damping [-] | Load |
|---|---|---|---|---|
| Synchronous Generator (Variant I) | −17.533 ± 317.279 | 50.496 | 0.055 | 25% |
| −17.539 ± 317.281 | 50.497 | 0.055 | 50% | |
| −17.542 ± 317.283 | 50.497 | 0.055 | 75% | |
| −17.546 ± 317.284 | 50.497 | 0.055 | 100% | |
| Synchronous Generator (Variant II) | −17.480 ± 317.403 | 50.516 | 0.055 | 25% |
| −17.486 ± 317.406 | 50.517 | 0.055 | 50% | |
| −17.490 ± 317.408 | 50.517 | 0.055 | 75% | |
| −17.493 ± 317.408 | 50.517 | 0.055 | 100% | |
| Synchronous Generator (Variant III) | −17.363 ± 317.548 | 50.539 | 0.055 | 25% |
| −17.369 ± 317.551 | 50.540 | 0.055 | 50% | |
| −17.373 ± 317.552 | 50.540 | 0.055 | 75% | |
| −17.376 ± 317.553 | 50.540 | 0.055 | 100% |
| Input–Output | Description |
|---|---|
| |
|
| Variant | 0.5–3 Hz | 47–53 Hz | Load | ||||
|---|---|---|---|---|---|---|---|
| [abs] | [Hz] | [°] | [abs] | [Hz] | [°] | ||
| I | 9.089 | 0.839 | 79.963 | 0.042 | 49.510 | −232.629 | 25% |
| 20.956 | 0.854 | 80.275 | 0.070 | 40.000 | −172.030 | 50% | |
| 43.768 | 0.877 | 81.081 | 0.102 | 40.000 | −171.347 | 75% | |
| 109.918 | 0.903 | 82.016 | 0.135 | 40.000 | −170.730 | 100% | |
| II | 3.690 | 0.837 | 80.848 | 0.039 | 49.474 | −238.269 | 25% |
| 20.220 | 0.856 | 80.476 | 0.071 | 40.000 | −171.986 | 50% | |
| 41.485 | 0.878 | 81.239 | 0.102 | 40.000 | −171.306 | 75% | |
| 99.347 | 0.904 | 82.131 | 0.135 | 40.000 | −170.690 | 100% | |
| III | 8.713 | 0.841 | 80.236 | 0.044 | 49.447 | −231.277 | 25% |
| 19.821 | 0.856 | 80.515 | 0.071 | 40.000 | −171.967 | 50% | |
| 40.307 | 0.878 | 81.271 | 0.102 | 40.000 | −171.287 | 75% | |
| 94.162 | 0.904 | 82.155 | 0.135 | 40.000 | −170.671 | 100% | |
| Variant | 0.5–3 Hz | 47–53 Hz | Load | ||||
|---|---|---|---|---|---|---|---|
| [abs] | [Hz] | [°] | [abs] | [Hz] | [°] | ||
| I | 0.281 | 0.839 | 1614.300 | 0.003 | 47.971 | 1256.201 | 25% |
| 0.898 | 0.854 | 1614.800 | 0.002 | 53.288 | 806.580 | 50% | |
| 1.722 | 0.877 | 1615.800 | 0.002 | 53.287 | 795.829 | 75% | |
| 3.459 | 0.903 | 1616.900 | 0.002 | 53.286 | 789.977 | 100% | |
| II | 0.019 | 0.838 | 1614.900 | 0.003 | 47.972 | 1261.570 | 25% |
| 0.726 | 0.856 | 1614.900 | 0.003 | 47.972 | 1242.520 | 50% | |
| 1.401 | 0.878 | 1615.800 | 0.003 | 47.972 | 1233.770 | 75% | |
| 2.695 | 0.904 | 1616.900 | 0.003 | 47.972 | 1228.440 | 100% | |
| III | 0.157 | 0.841 | 1614.400 | 0.003 | 47.972 | 1253.180 | 25% |
| 0.612 | 0.856 | 1614.800 | 0.003 | 47.972 | 1241.920 | 50% | |
| 1.189 | 0.878 | 1615.700 | 0.003 | 47.972 | 1233.430 | 75% | |
| 2.221 | 0.904 | 1616.700 | 0.003 | 47.972 | 1228.270 | 100% | |
| Signals | Description | |
|---|---|---|
| Input: |
| |
| Output: |
| |
| Variant | I | II | III | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Load | 25% | 50% | 75% | 100% | 25% | 50% | 75% | 100% | 25% | 50% | 75% | 100% |
| RGA (1,1) | 0.0002 | 0.0003 | 0.0004 | 0.0004 | 0.0001 | 0.0003 | 0.0004 | 0.0004 | 0.0002 | 0.0003 | 0.0004 | 0.0004 |
| RGA (1,2) | 0.9998 | 0.9997 | 0.9996 | 0.9996 | 0.9999 | 0.9997 | 0.9997 | 0.9996 | 0.9999 | 0.9997 | 0.9996 | 0.9996 |
| Method | Advantages | Disadvantages |
|---|---|---|
| Eigenvalues | Relatively easy to implement in a simulation tool (built-in function), assuming that the linearized model is available. This method allows for accurate analysis of the test model. | A large number of output data for highly complex models; lack of information identifying specific eigenvalues. |
| Participation Factors | Essential when analyzing eigenvalues, providing complementary information without which the study would be difficult to perform. | More difficult to implement—in the considered simulation tool there is no built-in function available. |
| Frequency Response Characteristics | Useful for signal analysis, providing relatively extensive information over any frequency range. Enables preliminary signal verification before applying other methods. | Fairly laborious implementation—requires manual selection of input–output pairs. Relatively long computation time. |
| RGA | Useful in preliminary analysis of signals selected for the control system; easy to implement and computationally simple. Not sufficient as a standalone interaction analysis method. | Limited matrix size (recommended 2 × 2), does not include the controller model, and analyses only a single frequency point. |
| DRGA | Any frequency range can be analyzed; provides more information compared to RGA. | Difficult to implement; longer computation time. |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2025 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Piekarz, M.; Robak, S.; Polewaczyk, M. Interaction Analysis of Offshore Power Systems: A Comparative Study. Energies 2025, 18, 6531. https://doi.org/10.3390/en18246531
Piekarz M, Robak S, Polewaczyk M. Interaction Analysis of Offshore Power Systems: A Comparative Study. Energies. 2025; 18(24):6531. https://doi.org/10.3390/en18246531
Chicago/Turabian StylePiekarz, Michał, Sylwester Robak, and Mateusz Polewaczyk. 2025. "Interaction Analysis of Offshore Power Systems: A Comparative Study" Energies 18, no. 24: 6531. https://doi.org/10.3390/en18246531
APA StylePiekarz, M., Robak, S., & Polewaczyk, M. (2025). Interaction Analysis of Offshore Power Systems: A Comparative Study. Energies, 18(24), 6531. https://doi.org/10.3390/en18246531

