2.1. Current Characteristics of Active Distribution Networks with IIDG
The schematic diagram of the active distribution network containing an IIDG is shown in
Figure 1.
Es denotes the electromotive force (EMF) of the main system source,
EDG denotes the EMF of the IIDG,
IM and
IN denote the currents at both ends of the protection zone,
LL denotes the load connected at the end of the feeder; ZMN denotes the equivalent impedance of feeder MN;
f1 denotes the internal fault point,
f2 and
f3 denote external fault points;
α denotes the position coefficient of
f1.
Given the widespread adoption of non-effectively grounded neutral points in China’s distribution networks, this paper focuses on analyzing two-phase faults. Influenced by fault resistance and load impedance, a non-metallic fault in an IIDG feeder may cause part of the short-circuit current to bypass the fault point, flowing into non-faulted sections as a through-current. This phenomenon affects the magnitude and phase characteristics of the currents at both ends of the system, potentially leading to the failure of relevant protection schemes.
When the system operates normally or an external fault occurs on line MN, the current flowing through both sides of the protection is through-current. Due to the short length of distribution network feeders, the influence of capacitive current can be neglected. The currents at both ends, IM and IN have identical magnitudes and opposite phases.
When an internal fault occurs on line MN, the output current of the IIDG is controlled by power electronic devices. It can be considered that the IIDG still satisfies the superposition principle and is equivalent to a current source in the fault additional network.
Figure 2 shows the equivalent network diagram of the active distribution network containing the IIDG.
In the figure, Idg denotes the output current of the IIDG; ZM denotes the equivalent impedance on the system side; Zdg denotes the internal impedance of the DG; ZF denotes the fault resistance; and ZL denotes the load impedance.
According to the superposition principle, the system in
Figure 2 can be decomposed into equivalent networks where the system power source and the IIDG act separately.
In the figure, I1s and I2DG denote the short-circuit currents provided by the system power source and the IIDG, respectively; I2S and I1DG denote the through-currents provided by the system power source and the IIDG, respectively.
The positive direction of current is defined as flowing from the busbar to the line. Thus, from
Figure 3, it follows that
From Equation (1) to Equation (3), it can be concluded that the phase angles of the currents IM and IN at both ends are influenced by the through-currents I1DG and I2S in the faulted section, while the magnitudes and phase angles of I1DG and I2S are determined by the system power source, IIDG, load, and fault resistance. Due to the randomness of fault resistance values and fault locations, as well as the limited capacity of grid-connected DG, the currents flowing through both ends of line MN are no longer equal, resulting in significant differences in current waveforms.
First, the difference in the magnitude of the current waveforms at both ends is analyzed. Under normal circumstances, the short-circuit current supplied by the system power source in the distribution network is at least three times the rated current [
19], whereas the maximum short-circuit current provided by an IIDG is 1.2 to 2 times the rated current. Therefore, when an internal fault occurs, the magnitude ratio of the fault current components at both ends of the feeder in a distribution network with an IIDG is significantly greater than 1. Here, the amplitude ratio of the fault current components at both ends is defined as
ε, with
ε > 1. Considering extreme conditions [
20], current transformer measurement errors, and a certain margin,
εmin ≈ 1.6.
Furthermore, the phase relationship of the current waveforms at both ends is analyzed. Beyond the inverter’s current-limiting control, the IIDG’s fault current is also influenced by Voltage Through (LVRT) requirements [
21,
22]. The output current of an IIDG under LVRT conditions exhibits the following characteristics: First, within a certain voltage sag range, the IIDG must remain grid-connected and prioritize reactive current output to provide voltage support, per regulatory requirements. Secondly, to maintain the active power balance of the grid and ensure the safe operation of the IIDG, it should inject as much active current as possible within the inverter’s allowable limits. Therefore, the reactive current
Iq and the active current
Id provided by the IIDG during LVRT can be expressed as follows
In the formula, K is the proportionality coefficient; IN is the rated current of the IIDG; γ is the voltage sag coefficient; Imax is the maximum allowable output current of the IIDG after the fault; Pref is the active power reference value output by the IIDG during normal operation; and UPCC is the voltage magnitude at the DG grid-connection point after the fault.
From Equation (1) to Equation (5), it can be seen that the fault components of the currents on both sides of the upstream feeder of the IIDG are influenced by multiple factors such as fault location, fault type, transition resistance, and the output limits of the IIDG, resulting in extremely complex fault characteristics. When the fault point is far from the IIDG grid-connection point and involves high transition resistance, the short-circuit current provided by the system power source continues to flow downstream to the fault point, while the short-circuit current provided by the DG no longer flows upstream to the fault point, causing a through-current to appear on the N side. In this case, the phase difference
θMN of the fault current components between the two sides is large. According to research [
23],
θMN can reach up to 180°.
2.2. Analysis of Adaptability Issues in Traditional Differential Protection
The entirely different fault characteristics of IIDGs compared to traditional synchronous machines lead to adaptability issues in conventional current differential protection. The principle of traditional current differential protection is described as follows:
In the formula, Idif denotes the operating current; Ires denotes the restraint current; and Kres denotes the restraint coefficient, typically set between 0.5 and 0.8.
It is further derived from Equation (6) that
In the formula,
θMN denotes the angle between the short-circuit currents
IM and
IN at both ends of the protected line; and
IM and
IN denote the magnitudes of the current phasors at both ends of the protection zone. Let
λ =
Idif/
Ires. Combining with Equation (7), it follows that
Equation (8) shows the restraint coefficient is determined by ε and cos
θMN, where
ε relates only to the amplitude characteristics of the currents at both ends, and cos
θMN depends solely on their phase angle characteristics. The relationship between the restraint coefficient
λ,
ε, and
θMN is illustrated in the planar graph shown in
Figure 4.
As can be seen from
Figure 4, when a fault occurs downstream of an IIDG, the phase difference between the short-circuit currents at both ends varies significantly, with a maximum value reaching 180° as discussed in
Section 2.1. In extreme cases, the amplitude ratio at both ends approaches
εmin ≈ 0.67. As the fault condition approaches this extreme state, the operating point moves away from the restraint boundary, ultimately preventing correct protection operation. While reducing the setting value can improve sensitivity for internal faults, an excessively small
Kres value may lead to maloperation during external faults, thereby reducing reliability.