1. Introduction
The seismic design of reinforced concrete (RC) tall buildings, whose first translational period exceeds five seconds, operates outside the regime in which classical structural control intuition applies. Spectral acceleration at the fundamental period falls to a small fraction of the short-period plateau, the inertial base shear ratio stays modest, and peak floor drift rather than base shear governs the demand, with spectral displacement reaching values that wall thickening and section growth cannot economically suppress. Passive tuned mass dampers (TMDs) have served as the operative supplemental damping pathway on this building class since the 1990s, with the closed-form trio of Den Hartog [
1], Warburton [
2] and Sadek [
3] remaining the dominant calibration choices. Two analytical problems and one verification gap nevertheless persist. The trade-off between nominal peak suppression and detuning robustness lacks a rank-oriented scalarization that survives a wide-band parameter sweep. The deterministic period drift produced by inelastic action is not bound by closed-form anchors. Beyond these two analytical problems, joint validation across a parametric tower family with an explicit joint parameter sweep is absent. The present paper resolves the two analytical problems through a two-layer rank-oriented calibration procedure verified on a 30-to-60-storey RC core tower family on the Istanbul ZB reference site and establishes the parametric verification platform that closes the third gap.
Istanbul lies within tens of kilometers of the right lateral North Anatolian Fault. The Turkish Building Earthquake Code TBDY 2018 [
4] hazard map identifies moment magnitudes of 7.0 to 7.4 along the Marmara segment as plausible within the service life horizon of the present high-rise inventory, of which more than two hundred RC towers exceeding 150 m have been built in the Marmara basin since 2010. Field surveys of pre-2007 RC frame stock on neighboring sites document detailing limitations that no economical stiffening can close [
5,
6], and shake table evaluations of tube-in-tube buckling-restrained brace retrofits on substandard frames [
7,
8] establish that brace family as the complementary device for the older non-ductile stock, leaving the TMD as the operative choice for the new long-period inventory.
The passive TMD holds the longest analytical record among supplemental damping devices. Frahm [
9] patented the undamped absorber. Ormondroyd and Den Hartog [
10] introduced viscous damping and the fixed-point solution, later consolidated by Den Hartog [
1]. Warburton [
2,
11] adapted the criterion of white noise base acceleration through displacement-variance minimization. Sadek et al. [
3] embedded the primary structure damping ratio in the optimization, obtaining a larger damper damping ratio that trades a modest loss in nominal peak suppression for a broader effective bandwidth. Asami et al. [
12] derived closed-form
and
solutions for damped primary systems. The Den Hartog, Warburton and Sadek trio constitute the canonical baseline against which numerical and metaheuristic frameworks are benchmarked.
The seismic effectiveness of TMD has been questioned for more than four decades on the basis of early parametric evidence. Kaynia et al. [
13] evaluated peak response ratios of damped systems under an ensemble of historical records and found reductions that were modest and widely scattered, with conventional stationary random vibration theory shown to overpredict the benefit. Sladek and Klingner [
14] tuned a rooftop damper to a realistic high-rise prototype at a mass ratio of 0.026 and observed no reduction in peak seismic response. Three mechanisms explain these negative findings, and their separation defines the scope of the present study. Short-duration broadband input supplies too few response cycles for the absorber to develop the counterphase inertial force. A calibration anchored to the elastic period becomes detuned once cracking and plastic hinge rotation lengthen the effective period. A practical mass ratio of nearly 2% limits the attainable supplemental modal damping. The first mechanism loses relevance as the fundamental period lengthens, since the drift governing first-mode response of a tower beyond 5 s is narrow-band and long in duration regardless of the broadband character of the base input, which explains the renewed adoption of the device for this building class. The second and third mechanisms remain, and they correspond to the two layers of the present framework. The Robust Tuning Index quantifies the suppression loss under detuning at a given mass ratio, and the period-elongation-aware anchor converts the inelastic period drift into a bounded deterministic design input.
Supplemental damping systems for tall buildings fall into three groups: distributed velocity-dependent devices, damped outriggers, and tuned mass devices, and the selection among them depends on the structural configuration. Distributed viscous and viscoelastic dampers dissipate energy through inter-storey velocity and remain the standard supplemental system for mid-rise frames [
15,
16], yet at a fixed drift amplitude the inter-storey velocity decreases as the fundamental period lengthens, so the first-mode contribution of these devices diminishes on a core-governed tower. A specialized branch of the same passive family develops dry friction devices built on cut and slotted shells with deformable fillers, whose stiffness and damping follow from the configuration of the shell cut. A helical cut shell damper has been modeled numerically for energy sector and construction applications [
17], and a slotted shell friction damper has been resolved analytically for the elastic suspension of sucker rod strings [
18]. These devices and their hybrid combinations with elastic elements operate at the component and equipment scale rather than on the global first mode of a tower, and they share with the closed-form TMD route the principle of dissipation parameters set analytically rather than searched numerically. The damped outrigger converts the differential rotation between the core and the perimeter columns into damper stroke and restores concentrated energy dissipation in the super-tall range. Chen et al. [
19] derived the modal damping of the damped outrigger in closed form together with its sensitivity to outrigger location, and Wang et al. [
20] extended the configuration through stochastic optimization of combined negative stiffness and conventional damped outriggers under nonstationary seismic excitation. The outrigger solution requires dedicated stiffened storeys, transfers the damper forces into the perimeter columns, and depends on the architectural section. The rooftop TMD requires none of these provisions. It is installed at a single upper storey, does not alter the gravity or lateral load path below the installation level, and admits transparent closed-form calibration. For the core-governed 30-to-60-storey family studied here, which contains no outrigger storeys, the roof-mounted TMD is the applicable passive alternative.
Numerical optimization has since expanded the design search space. Genetic algorithm calibration of multiple TMDs [
21], gradient-based numerical optimization [
22], a transfer function formulation [
23], and machine learning parameter regression [
24] have all enlarged the search beyond the closed-form era, while Çoşut et al. [
25] consolidated Jaya and hybrid Jaya-Teaching-Learning variants and reported tuning parameter recovery within 2% of the closed-form Den Hartog and Sadek targets, an independent numerical benchmark for the closed-form rankings examined.
Multi-mode and distributed configurations have been studied since the early 1990s. Distributed mass dampers under random loading [
26], sequential placement with shake table verification [
27,
28], vertically distributed multiple TMDs for tall buildings [
29], the generalization to irregular structures [
30] and to the contemporary tall RC inventory [
31], a 36 storey equivalent friction type verification [
32], strategic floor-level placement [
33], and the resolution of dry friction and cubic stiffness nonlinearities [
34] have progressively widened the device space, with offshore multihazard configurations [
35] and genetic algorithm tuning on a cross laminated timber tower [
36], extending it further. Farsijani et al. [
37] reported invariant optimum tuning envelopes spanning a frequency ratio between 0.75 and 1.10 and a damper damping ratio between 0.03 and 0.20 across 5-to-20-storey structures under 150 near-field pulse-like records, a direct precedent for the parametric multi-tower approach adopted in the present study.
Robustness-oriented work has addressed uncertainty in the device and in the host structure through robust min–max design for mass uncertain rolling-pendulum devices [
38], analytical relations for the recorded motion response [
39], a time-domain minimax formulation with event optimum parameters per record [
40] and the subsequent balance of split modal mass criterion for a priori unknown input [
41], frequency detuning studies on highspeed railway bridges [
42], and the inerter-augmented configuration that lowers the required damper mass [
43,
44]. This sub-stream has not packaged the trade-off as a rank-oriented scalar reduction on the canonical closed-form trio, nor demonstrated invariance of the induced ordering under joint parametric perturbation of the host tower.
The soil–structure interaction- and performance-based backbones relevant to extending this framework rest on the rigid mat impedance theory of Veletsos and Meek [
45], Kausel et al. [
46], Gazetas [
47] and Mylonakis et al. [
48], with TMD-specific extensions that include foundation compliance [
49,
50], and on the performance-based framework of Cornell and Krawinkler [
51] and FEMA P-58 [
52], with record selection after Iervolino and Manfredi [
53] and the appendage-damping theory of Villaverde and Koyama [
54]. Field practice on the Taipei 101 [
55] and Shanghai Tower [
56] pendulum and eddy current dampers, recent active control algorithms [
57], and consolidating reviews [
15,
16,
58,
59,
60,
61,
62] identify semi-active and adaptive variants as the principal extension directions.
Two analytical issues remain open for the long-period RC tower application, alongside the verification gap that the parametric platform of this paper is designed to close. First, the Den Hartog formulation maximizes nominal peak suppression but degrades steeply when the structural frequency drifts, while the Sadek formulation surrenders a small nominal margin for a wide robustness zone. The robustness sub-stream [
37,
38,
39,
40] treats this trade-off through minimax and robust min–max design rather than as a rank-oriented scalar on the canonical trio, and the recent reviews [
58,
59,
60,
61] discuss it only qualitatively. Second, cracking of the concrete core, plastic hinge formation, and long-term creep all push the first-mode period upward, yet conventional design proceeds from the elastic value alone, and the available literature treats detuning as a stochastic perturbation rather than as a deterministic input derivable from the secant period evolution that a modal pushover [
63] supplies directly. The inelastic response stream approaches the same phenomenon from the device side. Soto-Brito and Ruiz [
64] showed on a nonlinear twenty-two-storey frame that the effectiveness of an elastically tuned device degrades as the intensity drives the structure into yielding. Lukkunaprasit and Wanitkorkul [
65] proposed the hysteretic energy absorption ratio as the effectiveness measure for elastoplastic buildings under narrow-band distant motions, since the peak displacement ratio conceals the reduction in dissipated energy in the yielding storeys, and Pinkaew et al. [
66] showed on the same building class that with past yields the device stops reducing the peak displacement and yet continues to reduce the hysteretic damage. Sgobba and Marano [
67] optimized the linear device on a Bouc–Wen host and found the optimum displaced from its linear position, and a recent high-mass-ratio retrofit application sustained its reductions through incremental dynamic analyses on the nonlinear model [
68]. This stream establishes that the device remains worth tuning past the elastic range and that its optimum moves with the softening host, yet it stops short of converting that movement into a calibration rule. The present framework supplies the rule in closed form. Field and numerical evidence on damaged RC systems supports the deterministic character of this drift. Damage accumulation models reproduce the progressive stiffness degradation and the associated period lengthening of the damaged RC stock as a traceable function of the demand history [
69], and fragility analyses of degraded RC configurations confirm that the softened state governs the subsequent response [
70]. A damper anchored to the intact elastic period therefore operates at a growing tuning offset as damage develops, and the present framework bounds this deterministic detuning in closed form.
This paper resolves both issues and establishes a parametric verification platform through three contributions. The first is the Robust Tuning Index (RTI), a multiplicative rank-oriented scalar formed from the mean roof drift reduction of an eleven-record spectrum-matched set, minus the average relative growth of the frequency response peak under a bounded ±10% mistuning band. A closed-form dominance condition identifies the detuning bandwidth beyond which the Sadek formulation overtakes Den Hartog, with a unique bandwidth crossover located at the ±13.2% band at the reference tower, and the Sadek formulation ranks first in 122 of the 144 scenarios of the joint parameter envelope and at every tower under the worst-case measure. The second is the period-elongation-aware (PEA) anchor, set at the arithmetic mean of the elastic and DD-2 secant first-mode periods, the DD-2 level denoting the 10% in 50 years design earthquake of TBDY 2018 [
4], which bounds the worst-case damage state-of-tune offset to ±9.0%, ±11.0%, and ±12.1% at the three towers against +19.7% to +27.6% under elastic anchoring. The anchor is a proven minimax optimal across symmetric monotone off-tune cost functions, and the proof extends to the asymmetric case. The two layers interlock through the frequency response envelope. The frequency response point losses at the anchor offsets are 13.6% to 18.6% for the Sadek calibration against 33.5% to 42.3% for its elastic-anchored Den Hartog counterpart, so the PEA-anchored robust device sustains a bounded loss at the damage-state detuning extremes rather than the runaway off-tune of an elastic-anchored device. The third is the three-tower parametric platform of 30-, 48-, and 60-storey RC core towers with first periods of 3.80, 6.824, and 8.45 s, on which a Sherman–Morrison–Woodbury [
71] rank-one update accelerates the 216,000-point grid search by a factor of 8.1 at a residual norm of order 10
−12, and eleven-record Newmark-β response histories on openly redistributable inputs verify the band-conditional ordering, the Sadek formulation leading beyond the crossover and at the damage state offsets. This platform supplies a standalone modeling basis.
The remainder of the paper proceeds as follows.
Section 2 describes the three-tower parametric family, the cracked-section assumptions, the TBDY 2018 [
4] design spectrum at the Istanbul ZB reference site, and the eleven-record ground motion set scaled separately for each tower.
Section 3 develops the design framework, including the per-tower calibration matrix, the SMW-accelerated grid search, the RTI with its rank-invariance verification, and the PEA procedure with the two lemmas and their corollary.
Section 4 reports the frequency-domain and time-domain results, centered on the reference 48-storey Tower B with the parametric extension to Towers A and C summarized in cross-tower Tables.
Section 5 discusses the analytical origin of the formulation ranking, the period elongation bound, and the computational acceleration, together with the scope limitations and the closed-form extension directions.
Section 6 draws conclusions.
3. TMD Design Framework
3.1. Analytical Hierarchy and Scope
The analyses of
Section 3 and
Section 4 rest on a single modeling approach stated up front so that each result is read against the kinematic regime in which it is valid. The modeling approach used throughout the present paper is a linear-elastic modal-condensed two-modal-coordinate host model, augmented by the TMD coordinate after device attachment, retaining Mode 1 and Mode 4 of each ETABS [
72] model with the Rayleigh damping assignment of
Section 2.1. It supplies the frequency response magnitudes, the eleven-record Newmark-β response histories, the RTI frontier and the per-tower calibration. The shared kinematic decomposition of Equation (1) underlies this model. The retained pair comprises the two X translational modes that govern the roof drift on which the calibration operates, and the remaining quarter of the X direction modal mass spreads over modes with periods below 0.8 s. Their omission biases the absolute floor accelerations low, which the acceleration assessment considers, while the drift quantities converge with the two retained modes, and a residual vector correction is required before the acceleration results are used for design.
The linear-elastic tier and the pushover-derived secant period serve two distinct roles within one equivalent linearization scheme, and the pairing is deliberate. The closed-form calibration theory of the Den Hartog, Warburton and Sadek trio is defined as a linear system, so the tier on which the devices are calibrated, ranked and verified must remain linear for the closed-form structure to hold. The inelastic behavior of the host enters the calibration through its leading order effect on the device, the elongation of the first-mode period, which the modal pushover [
63] supplies as the secant period of the design damage state in the standard equivalent linearization sense. The damaged configuration is therefore represented as a linear system with the secant first-mode period, the PEA anchor is set between the elastic and secant configurations, and the frequency response function (FRF) envelope evaluates the device at the resulting off-tune offsets. The response history analyses run on the elastic configuration, where the closed-form reductions are defined, while the damage state is examined through the off-tune envelope rather than through inelastic response histories.
Two effects of hysteretic action remain outside the scheme: the added equivalent damping of the damaged host and the amplitude dependence of the secant elongation within a single record, and both act to reduce the actual resonant response and tuning error, so the reported off-tune losses sit on the conservative side. The nonlinear literature supports both sides of this scheme. On the response side, the device retains its effectiveness past yield when the effectiveness is measured on the hysteretic energy demand [
65,
66], which is the quantity that governs damage in the yielding storeys. On the calibration side, the optimum of a linear device attached to a hysteretic host displaces from its linear position toward the softened configuration [
67], the direction the PEA anchor takes in closed form, and a recent retrofit application carried comparable reductions through incremental dynamic analyses on the full nonlinear model [
68]. The fiber section inelastic verification that removes the equivalent linearization is identified as an extension direction.
3.2. Closed-Form Optimization Formulations
The closed-form framework rests on three formulations whose optima under harmonic and white noise base excitations are known analytically. The Den Hartog formulation [
1] minimizes the peak amplification of an undamped primary system through the fixed-point theorem:
The Warburton formulation [
2] minimizes the displacement variance under white noise base acceleration:
The Sadek formulation [
3] embeds the structural damping ratio
in the optimization and minimizes the displacement variance of a damped primary system:
At the design mass ratio with structural damping , the three formulations produce optimum frequency ratios of 0.9804, 0.9755, and 0.9735. The Den Hartog formulation gives the smallest damper damping ratio at . The Warburton formulation reduces this further to with a marginally narrower bandwidth. The Sadek formulation gives , more than twice the Den Hartog value, trading a small loss in nominal peak suppression for a substantially wider effective bandwidth. The bandwidth-loss term quantifies the trade-off. The Sadek loss is 4.3% against 11.3% for Den Hartog and 12.2% for Warburton at the design reference ±10% mistuning band.
3.3. Sherman–Morrison–Woodbury Accelerated Grid Validation
A parametric grid search over the (
) space identifies the numerical optimum per tower, spanning 60 × 60 × 60 = 216,000 logarithmically spaced points. The rooftop TMD is a rank-one perturbation of the dynamic stiffness matrix at every grid point and frequency, so the Sherman–Morrison–Woodbury (SMW) identity [
71] updates the frequency response inverse without re-factorizing the bare-structure inverse:
where Z is the bare-structure dynamic stiffness,
is the unit vector at the roof degree of freedom, and
is the frequency-dependent equivalent impedance of the TMD. The TMD is attached to the roof through a spring
a dashpot
and a damper mass
, and static condensation of the damper coordinate yields the closed-form impedance:
Equation (9) carries the full inertial, elastic and dissipative content of the device and approaches the locked mass spring dashpot form
as the damper mass grows without bound, while it vanishes when the damper mass is removed, since a massless attachment transmits no steady force. The rank-one structure of Equation (8) is therefore preserved with the inertial term embedded in
. The cost drops from
per grid point for direct lower–upper (LU) factorization to
yielding an 8.10-fold speedup with the SMW reconstruction residual bounded by 2.1 × 10
−12 against the direct solution at three control points per tower. The grid search completes in 11.1 min against 90.0 min for the direct baseline.
Table 6 summarizes the benchmark. The rank-one character is a structural property of any single-rooftop device, so the update transfers without modification to the soil–structure interaction and tuned mass damper inerter (TMDI) configurations.
3.4. Per-Tower TMD Calibration
The mass ratio
is held at 0.02 across the three towers and enters the framework as a design constraint rather than an optimization variable. The closed-form trio treats μ as the independent parameter from which the frequency ratio and the damper damping ratio follow, and the response reduction grows monotonically with μ over the practical range, so a joint optimization over the three parameters would return the largest admissible mass rather than an interior optimum. The admissible value is set by the roof-level capacity of the tower. The damper masses that follow from μ = 0.02 are 184 t at Tower A, 312 t at Tower B, and 396 t at Tower C, which are of the same order as the 660 t pendulum of the Taipei 101 [
55] and the 1000 t device of the Shanghai Tower [
56], so the adopted ratio represents the practical roof-level capacity of this tower class rather than a universal engineering constant. The consequences of departing from this value are quantified through the perturbation envelope, which sweeps μ over {0.01, 0.02, 0.03, 0.05}, and the formulation ranking remains invariant over the whole axis, and through the stroke verification, which confirms that the resulting devices remain within commercially available pendulum and roller bearing supports.
The TMD parameters are scaled per tower from the modal properties of
Table 1 and
Table 2, with the frequency-ratio and damping-ratio Equations (2)–(7) evaluated for each tower–formulation pair. The damper mass
. The Den Hartog damper damping coefficient
is comparable across the trio at 47.4 to 50.2 kN·s/m, since
decreases in proportion to
while
increases proportionally. The Sadek formulation requires about 2.23 times the Den Hartog coefficient at every tower, which was the direct consequence of the ratio
imposed by Equations (3) and (7) at the design mass ratio. The complete calibration matrix is reported in
Table 7.
3.5. Robust Tuning Index
The trade-off between nominal peak suppression and detuning robustness has been treated through the minimax and robust min–max frameworks [
37,
38,
39,
40] reviewed in
Section 1. The RTI introduced here complements these frameworks with a scalar that orders the canonical trio directly, and the induced ordering is tested for invariance over the joint parameter envelope.
The remaining sources are the as-built modal period uncertainty, taken as 10% to 15% in assessment practice on the basis of the effective stiffness ranges of ASCE 41-17 [
73] and reduced to about 8% once the calibration follows a system identification of the completed tower, and there was 3% to 5% manufacturing tolerance on the spring and dashpot. Treated as independent and combined in root-sum-square form at the upper tolerance, the two sources give about 9.4%, which the ±10% band covers with a margin.
The multiplicative form of Equation (10) follows from the four requirements that an engineering robustness index should satisfy on the plane of mean drift reduction and bandwidth loss. The first is strict monotonicity in each argument. The second is degenerate-extreme collapse, with the index vanishing when the mean reduction vanishes and when the bandwidth loss saturates at 100%. The third is dimensional consistency as a dimensionless percentage scalar. The fourth is consistency with product from multi-criteria aggregation [
77]. The additive alternative that subtracts a weighted bandwidth loss from the drift reduction satisfies the first and third requirements but violates degenerate-extreme collapse, with its zero-crossing falling at a weight dependent point rather than at the degenerate extremes, so its sign carries no admissibility content. The Salvi–Rizzi minimax measure of Equation (11) belongs to the same multiplicative family, replacing the band mean loss with the worst-case loss. These requirements restrict the admissible family without singling out one member, since any monotone transform of the product satisfies them as well. Equation (10) is adopted as the simplest member of the family, and the ordering it induces is checked against the minimax member below, so the design conclusion rests on the family rather than on one scalarization. The index is positive whenever the band mean loss stays below 100%, the device reduces the mean response, and a non-positive value marks the calibration as inadmissible at that bandwidth rather than measuring a degree of performance.
The RTI combines the mean roof drift reduction
from the eleven-record set with the mean relative growth
of the FRF peak over a ±10% mistuning band around the closed-form optimum:
with a per-building scalar, since
and
are evaluated against the host tower’s modal properties and its tower-specific record set. Any calibration rule that yields a mean reduction and a bandwidth loss on the same band, including multiple device layouts and inerter-augmented variants, enters the same ordering, so the index is not tied to the closed-form trio examined here. The values are RTI = 3.99 for Den Hartog, 4.04 for Warburton, and 3.86 for Sadek at the ±10% reference band, so the reference tower at its nominal parameters sits below the Sadek crossover, which Lemma 2 places at the ±13.2% band. The ranking is band conditional rather than universal.
Figure 3 maps the three calibrations on this plane at the three towers, with the iso-RTI contours displaying the trade-off behind the ordering.
The physical content of the Sadek advantage and the contribution of the index structure deserve explicit separation. The criterion-independent fact is the calibration itself. The Sadek optimum embeds the structural damping ratio and returns a damper damping ratio more than twice the Den Hartog value, 0.189 against 0.084 at the reference tower, which flattens the FRF envelope across the band and lowers the nominal notch depth. At exact tuning, the Den Hartog and Warburton notches lie within 2% of each other and the eleven-record mean reductions are statistically inseparable across the trio. The criterion-dependent step is aggregation. A multiplicative index that retains a bandwidth factor rewards a wide effective tuning range by construction, so the Sadek lead at Towers A and C in
Table 8 states that robustness carries measurable weight in the ranking, not that the Sadek notch is the deepest. Two features bound the influence of the adopted criterion. The ±10% band is fixed by the physical allowances of the preceding paragraph rather than adjusted to favor a formulation, and the minimax comparison below shows a worst-case criterion containing no band mean ranks for the robust calibration first at every tower.
To verify that the ordering is not an artifact of the band mean loss, the RTI is compared against the Salvi–Rizzi minimax robustness measure
[
40], which replaces the band mean loss with the worst-case loss within the band. The worst-case losses at the ±10% band edges are 36% to 38% for the Den Hartog and Warburton calibrations against 15% for the Sadek calibration, whose flat FRF envelope holds the edge loss below one half of its competitors, so that:
Table 8 reports the side-by-side comparison. The minimax measure ranks the Sadek formulation first at all three towers, including the reference tower where the RTI at the ±10% band still leaves the Sadek index behind the Den Hartog and Warburton values, so the worst-case criterion strengthens the robustness content of the ranking rather than reversing it. The ratio RTI/
is 1.40 for the Den Hartog and Warburton calibrations against 1.13 for the Sadek calibration, with the smaller Sadek ratio showing that its index degrades least when the band mean loss is replaced by the worst-case loss. The cross-tower values are listed in
Table 8.
The empirical RTI ordering admits the following analytical characterization.
Lemma 1 (Sadek-top condition)
. Let and
denote the mean drift reductions and
and
the bandwidth-loss factors of the Den Hartog and Sadek formulations at a common mass ratio and bandwidth. Define
and , with both positive on the canonical closed-form trio. The Sadek formulation dominates the Den Hartog formulation in the RTI ordering if and only if: Proof. The dominance condition
reads:
which is equivalent to:
Substituting
and
gives:
and hence
. □
When the right-hand side is positive and division by yields the stated condition. When , the Den Hartog index is non-positive, and the Sadek formulation dominates trivially.
Lemma 1 explains the bandwidth-sensitivity entries of
Table 9 quantitatively. At Tower B, the ratio
rises from 3.0 at
bandwidth to 14.9 at
, 24.0 at
and 30.2 at
The thresholds of Equation (12) at the same bands are 24.1, 22.0, 20.0, and 18.4. The rank crossover lies between
and
bands, at ±13.2%, and the
design reference sits just below the crossover at the reference tower, while the PEA damage state offsets reach into the Sadek-led range. The boundary case where
equals the threshold marks the regime where the multiplicative scalarization of Equation (10) provides no resolution. The engineering decision should then fall back to the Salvi–Rizzi minimax measure of Equation (11) or to direct inspection of the FRF envelope.
Lemma 2. Assume
> , > for all > 0, and that the weighted loss difference · − is strictly increasing in over (0, ), as the computed losses of Table 9 satisfy over the ±5% to ±20% range. If < , then the difference − is continuous and strictly decreasing on (0, ), with a unique crossover at where the two indices coincide, and the Sadek formulation leads for .
Proof. The difference equals
− [
·
−
]/100, so it is continuous, and its strict decrease is equivalent to the assumed strict increase in the weighted loss difference. At zero bandwidth,
=
= 0 gives a positive initial value
−
, the assumed negativity at
provides the sign change, and the intermediate value theorem together with strict monotonicity yields exactly one crossover. This unique crossover property is the analytical reason why the bandwidth sensitivity sweep of
Table 9 contains a single band interval in which the rank inverts. □
At a fixed formulation, the RTI is a smooth function of the mass ratio, the mistuning bandwidth, the structural damping, and the first-mode period. The mean drift reduction depends linearly on the kinematic decomposition of Equation (1) and, to first order about the optimum, quadratically on the tuning frequency ratio, while the bandwidth loss is a smooth function of the mass ratio, the mistuning bandwidth, and the damper damping. The partial derivatives of the index then follow in closed-form and support design-time interpolation across the parameter space without re-running the eleven-record analysis.
3.6. Robustness of the Formulation Ranking to Joint Parameter Perturbation
The relation between Lemma 1 and the parameter envelope is direct. The bandwidth loss factors are closed-form properties of the calibrations, with the Sadek value being roughly one-third of its competitor’s at every band, so the Sadek top condition of Lemma 1 is met once the band widens past the crossover of Lemma 2. The envelope below locates that crossover inside the ±10% to ±15% interval at the nominal cell of the reference tower and shows that most other cells of the parameter space satisfy the condition already at ±5%, which quantifies how far the ranking extends beyond the design point.
The rank invariance of the formulation ordering is tested over a 144-point joint-perturbation envelope built from four mass ratios, four mistuning bands, and three structural damping levels at the three towers:
The site class is not a separate axis of the envelope, since it enters the index only through an amplitude rescaling of the target spectrum, and a linear reduction ratio is invariant to a uniform scaling of the input, so the envelope spans the parameters on which the ratio depends. For each scenario, the RTI is computed independently for the three towers and the three formulations, yielding 432 RTI evaluations in total.
Of the 144 scenarios, the Sadek formulation ranks first in 122 (84.7%), the Warburton formulation in 20 (13.9%), and the Den Hartog formulation in two (1.4%). The exceptions concentrate at the tight bands: eight of 36 cells at ±5% and six of 36 at ±10%, thinning to five and three cells at ±15% and ±20%, and they lie in the cells where the mean reductions of the three calibrations are statistically inseparable. The worst-case measure of Equation (11) ranks the Sadek formulation first at all three towers at the design point.
3.7. Period-Elongation-Aware Calibration
The closed-form formulations of
Section 3.2 assume the calibration period coincides with the period during the event. Cracking of the C45 core during a moderate event, plastic hinge formation at the design-level event, and long-term creep all push
upward. A modal pushover with the first-mode load pattern scaled to the design-level roof drift gives secant first-mode periods of 4.55 s at Tower A, 8.51 s at Tower B, and 10.78 s at Tower C, elongations of +19.7%, +24.7%, and +27.6%. A device tuned at the elastic
alone would reach an off-tune approaching +27.6% at DD-2 for Tower C, far beyond the ±10% envelope of every closed-form solution.
The PEA calibration anchors the device at the arithmetic mean of the elastic and DD-2 first-mode periods:
so that the worst-case off-tune at the extremes of the damage band is bounded to ±9.0%, ±11.0%, and ±12.1% at Towers A, B, and C, against the asymmetric +19.7% to +27.6% of elastic-only anchoring. The off-tune offset is measured as the frequency-ratio deviation of the device, tuned at the anchor period, from the structural period at each extreme of the damage band. With the device anchored at the arithmetic mean, the two extremes are equidistant in frequency-ratio terms, so the symmetric bound reduces to the closed-form expression:
Equation (14) evaluates to these bounds per tower. The Tower A offset lies inside the ±10% reference band, while the Tower B and C offsets exceed it by 1.0 and 2.1 percentage points. The off-tune offset is a period quantity and the bandwidth loss is a response quantity, so the two are linked through the FRF envelope rather than compared directly. For the Sadek calibration, the point losses at the anchor offsets, evaluated directly on the frequency response, are 13.6% at Tower A, 16.8% at Tower B, and 18.6% at Tower C, against 33.5%, 39.4%, and 42.3% for the Den Hartog calibration, so the anchored robust device carries between 2.3 and 2.5 times less off-tune penalty at the damage band extremes.
The ±10% band remains the reference for the RTI ranking, while the offset-specific loss governs the PEA verification. Retuning the Sadek device to the anchor leaves the elastic state performance essentially unchanged, with the eleven-record mean reduction moving from 2.94%, 4.03%, and 3.06% at the elastic tuning to 2.96%, 3.91%, and 2.78% at Towers A, B and C, so the bounded damage state exposure costs at most 0.3 percentage points in the intact state. The minimax optimality of the arithmetic mean weight w = 0.5 is established next.
Lemma 3. Let
denote the convex combination anchor with
and
. Let
be any cost function that is non-negative, continuous, strictly increasing away from zero and satisfies
. Then, the anchor that minimizes the worst-case off-tune costis the arithmetic-mean choice , independent of the specific form of .
Proof. The two off-tune distances are:
and
so that the worst-case cost may be written as:
The worst-case cost is the maximum of two functions of . For , the second term dominates, since and are monotone and non-decreasing. For , the first term dominates.
Hence, is strictly decreasing on and strictly increasing on , with the unique minimum at , where the two distances coincide and the common value is attained. □
Lemma 3 generalizes the absolute-time-shift minimax result to the broad class of cost functions defined by the four requirements. The class includes the linear absolute shift the quadratic shift , the percentage shift , the exponential penalty and any cost function obtained by composing these with a strictly increasing transform. The arithmetic mean anchor is therefore the minimax optimum across the entire engineering family of symmetric monotone off-tune cost functions, which renders the PEA anchor of Equation (13) robust to the specific scalarization adopted at the design stage.
Remark 1. If the off-tune cost is defined in logarithmic or ratio-based period space, the corresponding minimax anchor becomes the log-space midpoint, that is, the geometric mean of the elastic and DD-2 secant periods. For the present towers, the arithmetic and geometric anchors differ only marginally, so the arithmetic form is retained for closed-form transparency.
Corollary 1. Let
and
be continuous, strictly increasing penalties with
for every
(the elongation side toward the DD-2 boundary is more strongly penalized, with w measuring the anchor position toward the DD-2 period as in Lemma 3, the stronger penalty acting on the offset toward the DD-2 boundary, and the weaker on the offset toward the elastic boundary). The minimax anchor satisfies the equal-cost condition
, and the optimum
sits in the interval
, shifted toward the more strongly penalized elongation side, so that the offset on that side is the shorter one.
Proof. At the minimax optimum, the two off-tune costs are equal, which gives the following equal-cost condition:
Since exceeds at every positive argument while both penalties are strictly increasing, equality of the two costs requires the argument of to be smaller than the argument of , that is, the offset on the strongly penalized side must be the shorter one. This yields in the interval . □
The damage-state modal map of
Table 10 records, at each ductility level, the secant first-mode period, the first-mode drift-amplification factor
of the secant configuration and the Mode 4 mass participation. The map is constructed from the first-mode bilinear capacity envelope of each tower with the secant stiffness
evaluated at the current roof displacement:
Table 10 reports the secant period evolution and Mode 4 participation across ductility ratios
=
/
from 1 to 4 for the three towers.
Figure 4 plots the modal pushover secant first-mode period against roof displacement for the three towers, with the PEA anchor marked at each tower. The participation of Mode 4 grows from 0.157 at
to 0.257 at
at the reference Tower B, with similar trends at Towers A and C. The PEA anchor of Equation (13) is set over the elastic to DD-2 interval of this map, where the secant period reaches its design-event value, so that the bounded off-tune of ±9.0% to ±12.1% holds across that interval. Beyond DD-2, toward the higher ductility states of
Table 10, the offset grows past the anchor bound and the loss climbs along the flat Sadek envelope of
Table 9, so the device degrades gradually rather than abruptly. The variable mode analysis that reads the full map at every intensity step is identified among the extensions.
The equivalent linearization bounds the intra-event detuning as well as the end-state offsets. At the DD-2 intensity, the instantaneous secant period migrates monotonically from the elastic value toward the damage state value of
Table 10, so the period trajectory remains inside the interval whose extremes define the anchor bound, and the instantaneous off-tune of the anchored device never exceeds the ±9.0% to ±12.1% envelope at any point of the response history. The linear tier does not resolve the transient side of this migration, the re-engagement of the absorber as the resonance moves through the tuning band, an effect that acts on the conservative side of the bound as noted in
Section 3.1, and the inelastic verification that explicitly resolves the transient is identified as the leading extension direction.
The performance-axis numerical optimum
reported in
Table 11 sits in the range 0.68 to 0.72, since the underlying cost function in that case is asymmetric. The FRF amplification of the elastic-anchored TMD is steeper on the positive period-shift side, where the structural period has elongated toward
, than on the negative side. The performance optimum trims the worst-case point loss from 16.8% to 9.6% at the reference tower, and the arithmetic mean anchor is retained at this bounded premium. The Corollary 1 condition predicts a shift above 0.5 toward the more strongly penalized elongation side, consistent with the numerical optimum.
5. Discussion
The band-conditional ranking observed in the parametric study follows from the analytical structure of the Robust Tuning Index rather than from a numerical accident. The multiplicative form penalizes bandwidth loss in proportion to the underlying reduction, so the ordering at a given cell is fixed by the ratio of the loss difference to the reduction difference; Lemma 1 makes the threshold explicit, and Lemma 2 locates a single crossover beyond which the robust calibration leads. The 144 scenario envelope quantifies the reach of this mechanism, with the Sadek formulation ranking first in 122 cells, the worst-case measure ranking it first at every tower, and the exceptions confined to the tightest bands, so the design recommendation rests on the crossover geometry rather than on a universal dominance claim.
The period-elongation-aware anchor addresses a different category of detuning. Manufacturing tolerance, modelling uncertainty, and modest cracking move the calibration period within the canonical ±10% band; the secant period elongation between the elastic configuration and the DD-2 damage state shifts it by an order of magnitude more. Anchoring the device at the arithmetic mean of the two limit periods converts an asymmetric one-sided detuning into a symmetric bounded envelope. Lemma 3 shows that this symmetric choice is optimal under any monotone cost defined on absolute period distance, which means the PEA bound is robust to the analyst’s preference for the form of the off-tune penalty. The combination with the RTI ranking yields a design baseline that controls both the bandwidth and the period elongation contributions to the off-tune envelope through a single closed-form procedure.
Wind serviceability constitutes a separate design condition for the towers considered here, and its optimization objective differs from the seismic one. Crosswind response near the vortex-shedding frequency governs occupant comfort through peak floor acceleration at the service return period; the structure remains elastic at the associated amplitudes, and the corresponding TMD calibration minimizes the acceleration variance at the elastic first-mode period. Multihazard evaluations of damped systems outrigger hybrid systems under combined crosswind and seismic excitation and confirm that the two objectives select different device parameters [
79]. Within the present framework, the divergence is bounded rather than resolved. The PEA anchor displaces the calibration period from the elastic value by one half of the DD-2 secant elongation, so a device anchored for the damage state operates off-tune under service wind by the same bounded offset that
Section 3.7 establishes for the seismic side, and the loss at the wind-side offset is bounded through the same frequency response envelope argument. A joint wind–seismic calibration with an explicit comfort constraint requires an acceleration variance term in the index and is identified as an extension direction.
The Sherman–Morrison–Woodbury acceleration of the parametric grid search is methodological rather than analytical. It preserves the closed-form structure of the framework while removing the computational obstacle that otherwise restricts transparent calibrations to coarse grids or surrogate models. The downstream consequence is that the analytical claims of the RTI ordering and the PEA bound can be verified on a dense parametric envelope on a workstation rather than on cluster resources, which keeps the framework within reach of the design office. On the practical side, the governing constraint identified by the verification is the stroke, whose mean demands of 0.5 m to 0.8 m and record extremes beyond 1.5 m call for long-stroke pendulum hardware, dedicated travel clearance, and hard stop design, and the 40 to 50% stroke saving of the robust calibration is the decisive practical argument for it at this scale.
The experimental basis of the framework rests on its ingredients rather than on a dedicated test of the assembled procedure. The closed-form optima of the Den Hartog, Warburton and Sadek calibrations and the detuning behavior of the FRF envelope, which together generate the RTI ordering, are established device physics, verified on shake table structures with multiple tuned mass dampers [
28] and on the experimental verification of a 36-storey equivalent high rise [
32], while the full scale field performance of rooftop devices is documented on the Taipei 101 [
55] and Shanghai Tower [
56] installations. The period elongation input of the PEA layer descends from the modal pushover, whose secant period representation of the damage state is standard practice in performance-based assessment. What lacks a direct experimental counterpart is the assembled two-layer procedure itself, the RTI ranking under controlled detuning, and the PEA anchor at the damage state. The reduced-scale shaking table program identified among the extension directions is defined for this purpose: a long-period specimen with an adjustable rooftop device, tested at the elastic-tuned and secant-tuned configurations under the record set of
Section 2.3.
The framework operates within an explicit analytical envelope and lends itself to closed-form extensions that broaden its applicability while preserving its analytical core. A fiber-section formulation with cyclic hysteresis would extend the RTI–PEA structure into the inelastic regime while retaining the bandwidth-loss interpretation. A TMDI variant offers a closed-form generalization that lowers the absolute damper mass at the longest-period towers, and the bandwidth-loss formalism naturally accommodates a hybrid passive–semi-active complement at the upper ductility extreme. A shaking-table program on a reduced-scale long-period model would extend the analytical verification into the empirical domain. A damped outrigger benchmark on a companion tower family with dedicated stiffened storeys would quantify the comparison of
Section 1.
Figure 7 assembles the complete two-layer procedure, from the modal and spectral input through the RTI ranking layer and the PEA anchoring layer to the response history verification and the design output. The index itself is a deterministic comparison measure, and propagating the record-to-record and parameter uncertainties through it toward a reliability-based robustness statement is a further extension direction.
6. Conclusions
This paper has developed a closed-form, rank-oriented design framework for passive tuned mass dampers on long-period reinforced concrete high-rise structures and verified it on a three-tower parametric family of 30-, 48-, and 60-storey towers with first translational periods of 3.80, 6.824, and 8.45 s. Long-period towers expose the limits of elastic-anchored, single-point closed-form calibration, and the framework closes that gap with two analytical results and one verification platform that together turn the suppression against robustness trade-off and the inelastic period drift into transparent design quantities.
Three contributions advance the calibration of these devices beyond the current closed-form practice. The first recasts the suppression against robustness trade-off, hitherto resolved only through numerical minimax search or treated qualitatively in review, as a single multiplicative scalar built from four design requirements, which we call the Robust Tuning Index. Lemma 1 gives the necessary and sufficient condition under which the Sadek formulation dominates Den Hartog across any mistuning bandwidth, and Lemma 2 fixes the unique crossover, so the Sadek lead established at the design mass ratio is shown to be a structural property of the formulation rather than the outcome of a single calibration point, a ranking that leads in 122 of the 144 scenarios of the joint-perturbation envelope, at every tower under the worst case measure, and beyond the ±13.2% crossover at the reference tower, with the exceptions confined to tight band cells with statistically inseparable means.
The second converts the deterministic inelastic period drift, conventionally set aside in favor of the elastic period, into a closed-form tuning target. The period-elongation-aware anchor is placed at the arithmetic mean of the elastic and DD-2 secant periods, with which Lemma 3 proves minimax optimal across symmetric monotone off-tune costs and Corollary 1 extends to the asymmetric case. The anchor caps the worst-case damage state-of-tune offset at ±9.0%, ±11.0%, and ±12.1% at the three towers, against the asymmetric +19.7% to +27.6% of elastic-only anchoring. The frequency response envelope links the two layers, the Sadek point losses at the anchor offsets staying at 13.6% to 18.6% against 33.5% to 42.3% for the elastic-anchored Den Hartog device, and the anchor costs at most 0.3 percentage points of intact state performance.
The third supplies the parametric verification platform on which both analytical claims are tested. A Sherman–Morrison–Woodbury rank-one update accelerates the 216,000-point grid search 8.1-fold at a residual norm of order 10−12, which keeps the dense verification within reach of a workstation. The eleven-record Newmark-β histories on the 30-, 48-, and 60-storey towers, built on openly redistributable inputs, verify the band-conditional ordering of the index and its Sadek-led range beyond the crossover.
Numerically, the Sadek calibration produces mean roof drift reductions of 2.9%, 4.0% and 3.1% at the three towers, modest in the mean and widely scattered across records, with a per-record dispersion roughly one-third below its competitors. Peak floor acceleration reductions stay below 1.5%, with the higher modes carrying the acceleration demand that the rooftop device does not reach. The inter-storey drift maxima stay below the 0.01 immediate occupancy limit in the eleven-record mean, and the stroke demands of 475 mm to 828 mm on the mean, 40 to 50% below the Den Hartog values, govern the device design. Within the closed-form trio, the bandwidth loss factor of 4.3% against 11.3% and 12.2% accounts for the robust ranking.
The framework applies within a stated envelope, core-governed RC towers with first periods between 3.80 and 8.45 s, a rooftop device at a mass ratio of 0.02, rock-like site conditions, and a linear-elastic verification tier with the inelastic period drift represented through the pushover-derived secant period. Within this envelope, the designer obtains, in closed form and without iterative retuning, the ranked formulation, the calibration period, the frequency and damping parameters of the device, and the bounded off-tune envelope of the design. The verification of the inelastic tier by fiber section response histories, the TMDI generalization that lowers the damper mass at the longest periods, and the soil–structure interaction that sweep across the softer site classes remain the concrete extension directions.