Optimizing Control Chain Latency in Liquid Cooled Data Center for Load Responsive Operation
Abstract
1. Introduction
- First, existing system control optimization often concentrates on minimizing steady state energy use and choosing operating points that run close to safety limits. It pays less attention to the control adjustment delays introduced by factors such as the pipe network’s thermal inertia and equipment actuation time. That bias can cause transient fluctuation risks during regulation to be underestimated or overlooked.
- Second, a single manipulated variable is rarely able to satisfy two competing requirements at once, namely fast tracking and stable operation with low fluctuations. That makes it necessary to build an evaluation framework and operating point matching method that can support screening and decision making across a wider operating space, one defined by the coordinated action of multiple pieces of equipment.
2. Materials and Methods
2.1. System Construction and Experiment Apparatus
2.2. Dynamic Simulation Model
2.2.1. CDU Heat Exchanger Model
2.2.2. Cooling Tower Model
2.2.3. System Delay Model
2.2.4. Simulation Model Validation Metrics
2.2.5. Control-Theoretic Abstraction of Actuator Pathways
2.3. Performance Indicator
2.4. Simulation Methods and Operating Condition Design
2.4.1. Simulation Model and Validation
2.4.2. Step Response Simulations for Single Manipulated Variable Strategies
- Constant differential pressure valve control: In engineering practice, this strategy corresponds to operating the primary side pump under constant differential pressure and regulating flow by adjusting the primary side control valve opening. The test conditions fix the secondary side CDU return water temperature and flow. The cooling tower fan is switched off so that the tower operates under natural convection. Outdoor conditions are set to 25 °C and 60% relative humidity. The primary side pump runs under constant differential pressure, with the setpoint equal to its rated head. Valve opening is stepped upward in 10% increments across a range of 30% to 100%. Starting from 30% opening, the step magnitude is taken from 0.1 to 0.7.
- Variable flow pump control: This strategy varies the speed of the primary side pump to change primary side flow and quickly regulate heat transfer. The test conditions again fix the secondary side CDU return water temperature and flow. The cooling tower fan remains off, and the tower operates under natural convection, with outdoor conditions set to 25 °C and 60% relative humidity. To remove the influence of changes in local valve resistance, the primary side valve is held fully open at 100%. The primary side pump frequency is stepped upward from a 20 Hz baseline, in 5 Hz increments. The step magnitude ranges from 0.1 to 0.6, corresponding to frequency increases from 5 Hz to 30 Hz.
- Cooling tower outlet temperature control: This strategy changes the heat exchange intensity on the tower side by adjusting cooling tower fan frequency. In doing so, it alters the cooling plant outlet water temperature and regulates cooling capacity. The test conditions fix the secondary side CDU return water temperature and flow. The primary side valve remains fully open at 100%. The primary side pump operates at constant flow, holding system flow at 35 kg/s. Outdoor conditions are set to 25 °C and 60% relative humidity. The cooling tower fan frequency is stepped upward from an initial value of 15 Hz. The step magnitude ranges from 0.1 to 0.7, corresponding to increases of 5 Hz to 35 Hz.
2.4.3. Positive and Negative Step Response Simulations
2.4.4. Step Response Simulations for Combined Operating Conditions
3. Results
3.1. Case Study and Model Validation
3.2. Analysis of Single Component Control Strategies
3.2.1. Constant Differential Pressure Valve Control
3.2.2. Variable Flow Pump Control
3.2.3. Cooling Tower Outlet Temperature Control
3.2.4. Cross-Strategy Analysis
3.2.5. Frequency-Domain Interpretation
3.3. Differences Between Positive and Negative Steps
3.4. Dynamic Performance of the Combined Control Strategy
3.5. Engineering Validation of the Optimisation Results
4. Discussion
4.1. Control-Pathway Interpretation of the Investigated Strategies
4.2. Comparison of the Present Findings with Existing Literature
4.3. Environmental Boundary Effects and Applicability
4.4. Hierarchical Summary of Contributions
- Delay-aware system-level modeling contribution: This study develops and validates a delay-aware dynamic Modelica model for a liquid-cooled data center cooling system. Unlike studies that treat the cooling plant mainly from a steady-state or quasi-steady perspective, the present model explicitly incorporates control-chain delay, transport delay, and thermal inertia within a unified plant-level framework. This provides the basis for reproducing and interpreting actuator-dependent transient behavior under abrupt load-responsive operation.
- Transient-performance evaluation contribution: This study proposes a standardized percentage step-test framework together with three transient metrics, namely dynamic response time, dynamic fluctuation amplitude, and dynamic fluctuation ratio. By combining these indicators under a unified settling criterion, the work converts transient cost and fluctuation risk into directly comparable quantities across different control strategies. The use of the 99.6% settling threshold further strengthens the engineering relevance of the framework for high-value liquid-cooled computing scenarios requiring tighter thermal stability.
- Control-pathway and mechanism interpretation contribution: Beyond reporting engineering phenomena, this study provides a control-oriented interpretation of the actuator-dependent differences among valve control, pump control, and cooling-tower fan control. The identified differences in effective delay, dominant time constant, and effective bandwidth clarify why valve control is fastest but more fluctuation-prone, pump control offers a more balanced trade-off, and cooling-tower control is slow but highly stable. In this sense, the study elevates the comparison of single-actuator strategies from empirical observation to a physically interpretable control-pathway analysis.
- Coordinated control and deployable strategy contribution: Building on the above modeling and evaluation framework, this study further develops a coordinated pump–fan operating strategy through operating-point matching and transient-risk screening. The key innovation is not the proposal of a new online advanced controller, but the establishment of a low-complexity, delay-aware, and BAS-deployable explicit coordination framework that reallocates control authority between fast flow-side actuation and slow source-side thermal regulation. This provides a practical path for achieving both faster convergence and lower fluctuation risk in engineering operation.
4.5. Limitations and Future Work
- The current validation range remains limited: Model validation and strategy comparison are mainly conducted under a limited set of standardized step disturbances. Therefore, absolute metrics such as response time and fluctuation amplitude remain dependent on the specific system configuration, operating point, and environmental boundary conditions. Further validation is needed under wider climate conditions and more complex load trajectories.
- Multi-loop coupling has not been fully resolved: The present study mainly focuses on plant-side delay-sensitive dynamics, while the fast local secondary-side regulation is treated as a boundary condition. In real liquid-cooling systems, more complex dynamic coupling may exist between the primary- and secondary-side control loops. Future work should therefore consider explicit dual-loop modeling and coordinated optimization.
- Environmental-boundary analysis is still limited to single-parameter variation: The current discussion and appendix-based analysis mainly focus on wet-bulb temperature. The main conclusion is that environmental variation primarily shifts the steady-state thermal boundary and the final cooling-capacity level, while having limited influence on the dynamic characteristics of the variable water-temperature strategy. Future work should extend this analysis by treating wet-bulb temperature, dry-bulb temperature, and load disturbance as combined boundary conditions.
- The current optimization does not explicitly include energy as an objective: At the present stage, the optimization mainly prioritizes response speed under a fluctuation constraint, and, therefore, emphasizes the trade-off between speed and stability. The additional energy cost during transient regulation is not yet included as an explicit objective. Future work may introduce event-level energy metrics and establish a multi-objective framework that jointly considers response speed, fluctuation risk, and energy penalty.
- The control framework can be extended to a higher level: The proposed method is essentially a low-complexity coordinated strategy based on an offline database and online explicit lookup, which gives it strong engineering deployability. In future work, this advantage can be retained while integrating surrogate models, boundary-aware coordinated optimization, or time-varying delay modeling to further improve the robustness and adaptability of the pump–fan coordinated strategy under complex environmental boundaries.
5. Conclusions
- Delay-aware system-level modeling contribution: A delay-aware Modelica model was developed and validated for a liquid-cooled data-center cooling system. Under the engineering setpoint-change event from 30 °C to 28 °C, the model reproduced the dominant temporal trends and turning-point behavior of the measured plant response. After excluding the start-up transient and evaluating the interval from 100 s to 655 s, the maximum error of the secondary-side supply temperature decreased from 1.71 °C to 0.68 °C, while the RMSE decreased from 0.48 °C to 0.26 °C. These results indicate that the model is suitable for plant-level dynamic analysis of secondary-side supply temperature under abrupt operating changes.
- Transient-performance evaluation contribution: A standardized percentage step-test framework was established together with three transient metrics, namely dynamic response time, dynamic fluctuation amplitude, and dynamic fluctuation ratio. Using a 99.6% settling criterion, this framework enabled direct comparison of different control strategies under the same disturbance definition. The results show that the framework can clearly quantify the trade-off between response speed and fluctuation risk. For example, under single-actuator positive steps, the response time remained at 38.3–41.3 s for valve control, increased from 44.2 s to 72.9 s for variable-flow pump control, and rose to 684.3–825.9 s for cooling-tower outlet temperature control, while the corresponding fluctuation behaviors differed markedly across strategies.
- Control-strategy and coordinated-control contribution: Among the three single-actuator strategies, constant differential pressure valve control was the fastest but also the most fluctuation-prone. As the valve step increased from 0.1 to 0.7, the cooling-capacity overshoot increased from 91.6 kW to 476.9 kW, and the dynamic fluctuation ratio increased from 9.2% to 38.7%. Variable-flow pump control provided a more balanced trade-off between speed and smoothness: its response time ranged from 44.2 s to 72.9 s, and the maximum cooling-capacity overshoot at the largest step was 195 kW with a fluctuation ratio of about 15.8%. Cooling-tower outlet temperature control was the most stable but much slower, with response times of 684.3–825.9 s and a maximum overshoot of only 6.6 kW. Building on these pathway differences, the proposed coordinated pump–fan strategy reallocated control authority across operating conditions and reduced the response time from 688.3 s to 73.7 s under fluctuation constraints, while lowering the dynamic temperature-deviation risk by up to 1.3 °C in the engineering comparison.
Author Contributions
Funding
Data Availability Statement
Acknowledgments
Conflicts of Interest
Abbreviations
| BAS | Building Automation System |
| CDU | Coolant Distribution Unit |
| HSE | Heat Storage Efficiency |
| NTU | Number of Transfer Units |
| PUE | Power Usage Effectiveness |
| PID | Proportional–Integral–Derivative |
| UA | Overall Heat Transfer Conductance |
| CPU | Central Processing Unit |
| GPU | Graphics Processing Unit |
Appendix A
| Control Strategy | Step | 95% | 98% | 99% | 99.6% |
|---|---|---|---|---|---|
| Cooling Tower Outlet Temperature Control | 0.2 | 373.9 | 503.3 | 600.2 | 721.8 |
| 0.4 | 404 | 542.1 | 644.8 | 775.7 | |
| 0.6 | 423.8 | 567.6 | 674.2 | 811.3 | |
| Constant Differential Pressure Valve Control | 0.2 | 40.6 | 40.6 | 40.7 | 40.7 |
| 0.4 | 41.1 | 41.1 | 41.2 | 41.2 | |
| 0.6 | 41.2 | 41.3 | 41.3 | 41.3 | |
| Variable Flow Pump Control | 0.2 | 52.4 | 54.5 | 55.4 | 56.2 |
| 0.4 | 68.1 | 68.7 | 68.9 | 69 | |
| 0.6 | 71.1 | 72.2 | 72.6 | 72.9 |
| Control Strategy | Step | 95% | 98% | 99% | 99.6% |
|---|---|---|---|---|---|
| Cooling Tower Outlet Temperature Control | 0.2 | 374.2 | 503.5 | 600.6 | 722.2 |
| 0.4 | 404.3 | 542.3 | 644.9 | 775.8 | |
| 0.6 | 424 | 567.9 | 674.4 | 811.6 | |
| Constant Differential Pressure Valve Control | 0.2 | 40.7 | 40.8 | 40.8 | 40.8 |
| 0.4 | 41.3 | 41.3 | 41.4 | 41.4 | |
| 0.6 | 41.4 | 41.5 | 41.5 | 41.5 | |
| Variable Flow Pump Control | 0.2 | 52.6 | 54.7 | 55.6 | 56.4 |
| 0.4 | 68.3 | 68.9 | 69.1 | 69.2 | |
| 0.6 | 71.3 | 72.4 | 72.8 | 73.1 |
Appendix B

| ηlim (%) | Feasible Points | pstep | ystep | tresp,T2 (s) | ΔT2ext (°C) | ηT2 |
|---|---|---|---|---|---|---|
| 3 | 42 | 0.2 | 0.1 | 73.9 | 0.083 | 0.0024 |
| 5 | 42 | 0.2 | 0.1 | 73.9 | 0.083 | 0.0024 |
| 7 | 42 | 0.2 | 0.1 | 73.9 | 0.083 | 0.0024 |
| 10 | 42 | 0.2 | 0.1 | 73.9 | 0.083 | 0.0024 |
| Control Strategy | Step | ηx (%) | ηstep (%) |
|---|---|---|---|
| Cooling Tower Outlet Temperature Control | 0.2 | 0.00 | 0.00 |
| 0.4 | 0.00 | 0.00 | |
| 0.6 | 0.00 | 0.00 | |
| Constant Differential Pressure Valve Control | 0.2 | 2.88 | 78.60 |
| 0.4 | 5.68 | 109.59 | |
| 0.6 | 6.66 | 120.90 | |
| Variable Flow Pump Control | 0.2 | 1.63 | 80.22 |
| 0.4 | 2.59 | 84.93 | |
| 0.6 | 2.73 | 78.94 |
Appendix C
| Controller | kp | Ti | Td | yMin | yMax | wp | Ni |
|---|---|---|---|---|---|---|---|
| Retuned PID | 0.045 | 30 s | 0 s | 0 | 1 | 1 | 0.9 |
Appendix D
| Case | Tapp | dTapp/dTwb | T2 |
|---|---|---|---|
| 18 °C | 2.92 °C | -- | 32.08 °C |
| 20 °C | 2.39 °C | −0.27 | 32.69 °C |
| 22 °C | 1.92 °C | −0.23 | 33.33 °C |
| 24 °C | 1.52 °C | −0.20 | 34.01 °C |
| 26.5 °C | 1.13 °C | −0.16 | 34.89 °C |
| Case | Steady-State Cooling Capacity | Response Time | Dynamic Fluctuation Ratio |
|---|---|---|---|
| 18 °C | 1658 kW | 755.5 s | 0.00% |
| 20 °C | 1529 kW | 763.5 s | 0.00% |
| 22 °C | 1395 kW | 772.4 s | 0.00% |
| 24 °C | 1255 kW | 781.0 s | 0.00% |
| 26.5 °C | 1069 kW | 793.2 s | 0.00% |
References
- Ma, Y.Z.; Ma, G.Y.; Zhang, S.; Xu, S.X. Experimental investigation on a novel integrated system of vapor compression and pump driven two phase loop for energy saving in data centers cooling. Energy Convers. Manag. 2015, 106, 194–200. [Google Scholar] [CrossRef]
- Wang, X.Y.; Li, H.; Wang, Y.Z.; Zhao, J.; Zhu, J.B.; Zhong, S.Y.; Li, Y. Energy, exergy, and economic analysis of a data center energy system driven by CO2 ground source heat pump: Prosumer perspective. Energy Convers. Manag. 2021, 232, 113877. [Google Scholar] [CrossRef]
- Qian, X.D.; Li, Z.; Li, Z.X. A thermal environmental analysis method for data centers. Int. J. Heat Mass Transf. 2013, 62, 579–585. [Google Scholar] [CrossRef]
- Nada, S.A.; El Zoheiry, R.M.; Elsharnoby, M.; Osman, O.S. Experimental investigation of hydrothermal characteristics of data center servers’ liquid cooling system for different flow configurations and geometric conditions. Case Stud. Therm. Eng. 2021, 27, 101276. [Google Scholar] [CrossRef]
- Zhang, Y.B.; Shan, K.; Li, X.M.; Li, H.X.; Wang, S.W. Research and Technologies for next generation high temperature data centers State of the arts and future perspectives. Renew. Sustain. Energy Rev. 2023, 171, 112991. [Google Scholar] [CrossRef]
- Zhou, F.; Gu, W.; Ma, G. Advancements in data center cooling systems: From refrigeration to high performance cooling. Energy Build. 2024, 320, 114634. [Google Scholar] [CrossRef]
- Zhang, Y.; Zhang, Y.; Bakir, M.S. Thermal Design and Constraints for Heterogeneous Integrated Chip Stacks and Isolation Technology Using Air Gap and Thermal Bridge. IEEE Trans. Compon. Packag. Manuf. Technol. 2014, 4, 1914–1924. [Google Scholar] [CrossRef]
- Qu, S.; Duan, K.; Guo, Y.; Pan, L.; Zhang, H.; Wang, S. Real time optimization of the liquid cooled data center based on cold plates under different ambient temperatures and thermal loads. Appl. Energy 2024, 363, 123101. [Google Scholar] [CrossRef]
- Azarifar, M.; Arik, M.; Chang, J.Y. Liquid cooling of data centers: A necessity facing challenges. Appl. Therm. Eng. 2024, 247, 123112. [Google Scholar] [CrossRef]
- Wu, X.L.; Yang, J.L.; Liu, Y.; Yang, Z.; Li, H.; Zhang, J.F. Investigations on heat dissipation performance and overall characteristics of two phase liquid immersion cooling systems for data center. Int. J. Heat Mass Transf. 2025, 239, 126575. [Google Scholar] [CrossRef]
- Ge, J.L.; Xia, F.F.; Zhang, C.B.; Zhai, X.W.; Guo, W. Performance Enhancement of Single Phase Immersion Liquid Cooled Data Center Servers. J. Therm. Sci. 2024, 33, 1757–1772. [Google Scholar] [CrossRef]
- Huang, Y.P.; Liu, C.D.; Zhong, Y.F.; Han, X.; Feng, X.F. Experimental study on jet enhanced immersion liquid cooling for energy efficient data centers. Energy 2025, 334, 137584. [Google Scholar] [CrossRef]
- He, W.; Zhang, J.F.; Li, H.L.; Ding, S.; Yang, B.; Huang, S.; Yan, J. Effects of different water cooled heat sinks on the cooling system performance in a data center. Energy Build. 2023, 292, 113162. [Google Scholar] [CrossRef]
- Li, J.; Luo, X.; Wang, M.; Ma, G. Study of flow and heat transfer characteristics of tandem cold plates for data center cooling. Case Stud. Therm. Eng. 2025, 73, 106590. [Google Scholar] [CrossRef]
- Heydari, A.; Shahi, P.; Radmard, V.; Eslami, B.; Chowdhury, U.; Saini, S.; Bansode, P.; Miyamura, H.; Agonafer, D.; Rodriguez, J. Liquid to liquid cooling for high heat density liquid cooled data centers. In Proceedings of the ASME International Technical Conference and Exhibition on Packaging and Integration of Electronic and Photonic Microsystems (InterPACK), Garden Grove, CA, USA, 25–27 October 2022; p. V001T01A007. [Google Scholar]
- Chang, Q.K.; Huang, Y.F.; Liu, K.Y.; Xu, X.; Zhao, Y.H.; Pan, S. Optimization Control Strategies and Evaluation Metrics of Cooling Systems in Data Centers: A Review. Sustainability 2024, 16, 7222. [Google Scholar] [CrossRef]
- Shao, X.T.; Zhang, Z.B.; Song, P.; Feng, Y.Z.; Wang, X.L. A review of energy efficiency evaluation metrics for data centers. Energy Build. 2022, 271, 112308. [Google Scholar] [CrossRef]
- He, W.; Ding, S.; Zhang, J.F.; Li, H.L.; Yang, B.; Yan, J.; Huang, S. Performance optimization of server water cooling system based on minimum energy consumption analysis. Appl. Energy 2021, 303, 117620. [Google Scholar] [CrossRef]
- He, W.; Zhang, J.F.; Li, H.L.; Ding, S.; Yang, B.; Huang, S.; Yan, J. Optimal thermal management of server cooling system based cooling tower under different ambient temperatures. Appl. Therm. Eng. 2022, 207, 118176. [Google Scholar] [CrossRef]
- Wang, S.Q.; Tu, R.; Chen, X.Z.; Duan, Y.Y.; Xia, X.Y. Thermal performance analyses and optimization of data center centralized cooling system. Appl. Therm. Eng. 2023, 222, 119817. [Google Scholar] [CrossRef]
- Li, J.J.; Li, Z.W. Model based optimization of free cooling switchover temperature and cooling tower approach temperature for data center cooling system with water side economizer. Energy Build. 2020, 227, 110407. [Google Scholar] [CrossRef]
- Song, W.S.; Hong, S.H.; Park, T.J. The effects of service delays on a BACnet based HVAC control system. Control Eng. Pract. 2007, 15, 209–217. [Google Scholar] [CrossRef]
- Price, C.; Park, D.; Rasmussen, B.P. Cascaded Control for Building HVAC Systems in Practice. Buildings 2022, 12, 1814. [Google Scholar] [CrossRef]
- Grimholt, C.; Skogestad, S. Optimal PID Control on First Order Plus Time Delay Systems & Verification of the SIMC Rules. IFAC Proc. Vol. 2013, 46, 265–270. [Google Scholar] [CrossRef]
- Ning, B.; Schiavon, S.; Bauman, F.S. A novel classification scheme for design and control of radiant system based on thermal response time. Energy Build. 2017, 137, 38–45. [Google Scholar] [CrossRef]
- Krajčík, M.; Šikula, O. Heat storage efficiency and effective thermal output: Indicators of thermal response and output of radiant heating and cooling systems. Energy Build. 2020, 229, 110524. [Google Scholar] [CrossRef]
- Chen, Q.; Li, N. Thermal response time prediction based control strategy for radiant floor heating system based on Gaussian process regression. Energy Build. 2022, 263, 112044. [Google Scholar] [CrossRef]
- Qi, D.; Liu, Y.; Zhao, C.; Dong, Y.; Song, B.; Li, A. Thermal response and performance evaluation of floor radiant heating system based on fuzzy logic control. Energy Build. 2024, 313, 114232. [Google Scholar] [CrossRef]
- Wang, M.Z.; Hu, E.; Chen, L. Radiation-enhanced thermal diode tank (RTDT) for refrigeration and air-conditioning (RAC) systems. Int. J. Refrig. 2023, 146, 237–247. [Google Scholar] [CrossRef]
- Yu, R.W.; Fan, S.H. Time-modulated near-field radiative heat transfer. Proc. Natl. Acad. Sci. USA 2024, 121, e2401514121. [Google Scholar] [CrossRef]
- Akbarzadeh, S.; Sefidgar, Z.; Valipour, M.S.; Elmegaard, B.; Arabkoohsar, A. A comprehensive review of research and applied studies on bifunctional heat pumps supplying heating and cooling. Appl. Therm. Eng. 2024, 257, 124280. [Google Scholar] [CrossRef]
- Wang, M.Z.; Hu, E.R.; Chen, L. TRNSYS Simulation of a Bi-Functional Solar-Thermal-Energy-Storage-Assisted Heat Pump System. Energies 2024, 17, 3376. [Google Scholar] [CrossRef]
- Sangi, R.; Müller, D. Dynamic modelling and simulation of a slinky coil horizontal ground heat exchanger using Modelica. J. Build. Eng. 2018, 16, 159–168. [Google Scholar] [CrossRef]
- Abugabbara, M.; Lindhe, J.; Javed, S.; Bagge, H.; Johansson, D. Modelica based simulations of decentralised substations to support decarbonisation of district heating and cooling. Energy Rep. 2021, 7, 465–472. [Google Scholar] [CrossRef]
- Dumont, É. Mass Transfer in Multiphasic Gas/Liquid/Liquid Systems. KLa Determination Using the Effectiveness Number of Transfer Unit Method. Processes 2018, 6, 156. [Google Scholar] [CrossRef]
- Benton, D.J.; Bowman, C.F.; Hydeman, M.; Miller, P. An improved cooling tower algorithm for the CoolTools™ simulation model. ASHRAE Trans. 2002, 108, 760–768. [Google Scholar]
- Zhu, J. Modeling, Simulation and Control Strategy Optimization of a Centralized Cooling Station Based on Modelica. Master’s Thesis, Tianjin University, Tianjin, China, 2019. [Google Scholar]
- Liu, C.; Yu, H. Evaluation and Optimization of a Two-Phase Liquid-Immersion Cooling System for Data Centers. Energies 2021, 14, 1395. [Google Scholar] [CrossRef]
- Zhao, J.; Hou, J.W.; Yang, Z.L.; Liu, D.H.; Xu, B.T.; Zhang, W.L.; Yao, M.; Cui, J.J.; Liu, S.P.; Qi, X.Q.; et al. Collaborative model predictive control for indirect evaporative cooling systems in data centers based on dynamic hot-spot tracking. Energy 2026, 344, 139888. [Google Scholar] [CrossRef]
- Li, Y.R.; Yang, C.; Xia, Y.Q. A robust data-driven model predictive thermal control for rack-based data center. J. Build. Eng. 2024, 98, 110877. [Google Scholar] [CrossRef]
- Sermsuk, M.; Sukjai, Y.; Wiboonrat, M.; Kiatkittipong, K. Utilising Cold Energy from Liquefied Natural Gas (LNG) to Reduce the Electricity Cost of Data Centres. Energies 2021, 14, 6269. [Google Scholar] [CrossRef]
- Vertiv™ CoolChip CDU: In-Rack Liquid-to-Liquid Coolant Distribution Unit. Available online: https://www.vertiv.com/4a1992/globalassets/shared/vertiv-coolchip-cdu-100_datasheet_en.pdf (accessed on 5 March 2026).
- Xia, L.; Wu, J.F.; Khosravi, A.; Sun, L. Modelica based modelling and control design of counter-flow SOFC system considering temperature distribution. Energy 2025, 331, 137011. [Google Scholar] [CrossRef]
- Sanchis, R.; Peñarrocha-Alós, I. Optimal tuning of PID controllers with derivative filter for stable processes using three points from the step response. ISA Trans. 2023, 143, 596–610. [Google Scholar] [CrossRef]
- Lawrence Berkeley National Laboratory. Buildings.Fluid.HeatExchangers.CoolingTowers.Correlations. Available online: https://simulationresearch.lbl.gov/modelica/releases/v12.0.0/help/Buildings_Fluid_HeatExchangers_CoolingTowers_Correlations.html (accessed on 14 April 2026).














| Instrument | Model | Manufacturer | City, State/Country | Operating Parameters |
|---|---|---|---|---|
| Server Rack | NVIDIA GB200 | NVIDIA Corporation | Santa Clara, CA, USA | Rack Rated Power: 120 kW |
| Plate exchanger | — | — | — | Heat exchange area Ae: 13.85 m2; Heat transfer coefficient Ke: 3125 W/(m2⋅K). |
| Primary side Pump | CR 125 | Grundfos Pumps (Shanghai) Co., Ltd. | Shanghai, China | Rated Flow Rate: 125 m3/h Liquid Temperature: 20 °C Rated Head: 85.65 m |
| Secondary side Pump | CR 95 | Grundfos Pumps (Shanghai) Co., Ltd. | Shanghai, China | Rated Flow Rate: 94.98 m3/h Liquid Temperature: 20 °C Rated Head: 93.67 m |
| Primary side control Valve | Belimo SRF24A SR 5 | BELIMO Automation AG | Hinwil, Switzerland | Pipe Diameter: DN150 Actuation Time: 90 s |
| Temperature and Humidity Data Logger | Testo 174H | Testo Instruments International Trading (Shanghai) Co., Ltd. | Shanghai, China | Temperature: −20 °C~+70 °C Relative Humidity: 0~100%RH Accuracy: ±0.5 °C, ±3% RH |
| Mass Flow Meter | CFMI DN150 | Q&T Instrument Limited | Kaifeng, China | Temperature: 60 °C~+200 °C Measurement Range: 0~250 T/h Accuracy: ±0.1 kg/s |
| Pressure Sensor | WMB2780 | Xi’an Shenghongchuang Instrument Co., Ltd. | Xi’an, China | Measurement Range: 0~100 MPa Accuracy: ±0.25 MPa |
| Dataset Time | Metric | Valve Opening | Flow Rate | Secondary Side Supply Temperature | Primary Side Return Temperature |
|---|---|---|---|---|---|
| 0–655 s | RMSE | 0.02 | 0.51 | 0.48 | 0.44 |
| NRMSE | 8.20% | 8.55% | 11.49% | 9.39% | |
| NMBE | 2.20% | −0.77% | −0.74% | 0.23% | |
| MAE | 0.01 | 0.39 | 0.32 | 0.35 | |
| Max error | 0.04 | 2.50 | 1.71 | 1.31 | |
| 100–655 s | RMSE | 0.01 | 0.37 | 0.26 | 0.35 |
| NRMSE | 7.29% | 7.59% | 13.14% | 17.21% | |
| NMBE | 1.85% | −1.02% | −0.34% | 0.49% | |
| MAE | 0.01 | 0.31 | 0.21 | 0.30 | |
| Max error | 0.04 | 0.88 | 0.68 | 0.68 |
| Strategy | Manipulated Variable | Controlled Output | K | θ | τ | θ/τ | ωeff |
|---|---|---|---|---|---|---|---|
| Constant Differential Pressure Valve Control | αv | Secondary-side supply temperature Ts,in | −4.431 | 37.7 | 2.0 | 18.85 | 0.0252 |
| Variable Flow Pump Control | np | Secondary-side supply temperature Ts,in | −2.599 | 38.7 | 13.4 | 2.89 | 0.0192 |
| Cooling Tower Outlet Temperature Control | nf | Secondary-side supply temperature Ts,in | −4.243 | 42.8 | 76.9 | 0.56 | 0.0084 |
| Method | Representative Literature | Core Characteristic | Model Requirement | Online Optimization | Constraint Handling | Online Computational Burden | Position Relative to this Study |
|---|---|---|---|---|---|---|---|
| Classical PID/PI control | Grimholt and Skogestad [25] | Low-order feedback control based on measured error | Low | No | Weak | Very low | Engineering baseline without explicit delay-aware operating-point selection |
| Robust data-driven MPC | Li et al. [40] | Predictive control with data-driven thermal model and uncertainty handling | Medium | Yes | Strong | Medium to high | More powerful online optimization, but higher deployment complexity |
| Collaborative MPC | Zhao et al. [39] | Component-level coordinated predictive optimization | High | Yes | Strong | High | Suitable for richer sensing and computation in tightly coupled systems |
| This study | Present work | Offline dynamic database plus online explicit operating-point lookup | Medium (offline calibrated model) | No | Moderate through offline screening | Very low | Low-complexity BAS-deployable delay-aware explicit coordination strategy |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Share and Cite
Shi, H.; Pan, S.; Liu, K.; Wan, T.; Li, C.; Niu, B. Optimizing Control Chain Latency in Liquid Cooled Data Center for Load Responsive Operation. Buildings 2026, 16, 1752. https://doi.org/10.3390/buildings16091752
Shi H, Pan S, Liu K, Wan T, Li C, Niu B. Optimizing Control Chain Latency in Liquid Cooled Data Center for Load Responsive Operation. Buildings. 2026; 16(9):1752. https://doi.org/10.3390/buildings16091752
Chicago/Turabian StyleShi, Haotian, Song Pan, Kaiyan Liu, Taocheng Wan, Chao Li, and Baolian Niu. 2026. "Optimizing Control Chain Latency in Liquid Cooled Data Center for Load Responsive Operation" Buildings 16, no. 9: 1752. https://doi.org/10.3390/buildings16091752
APA StyleShi, H., Pan, S., Liu, K., Wan, T., Li, C., & Niu, B. (2026). Optimizing Control Chain Latency in Liquid Cooled Data Center for Load Responsive Operation. Buildings, 16(9), 1752. https://doi.org/10.3390/buildings16091752
