Next Article in Journal
Natural Cold Source Computing Cluster Thermal Management Coupled with PCM
Previous Article in Journal
Optimization of Mix Proportions for Flexible Ecological Concrete Blankets in Slope Restoration: An Experimental Study
Previous Article in Special Issue
Environmental Analysis of Traditional House with Patios in Hot Summer and Warm Winter Zone of Southern China
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Investigation on Adaptive Building Shape Design Indicator Based on the Interaction of Building, Climate and Energy

1
China Southwest Architectural Design and Research Institute Co., Ltd., Chengdu 610041, China
2
School of Building Services Science and Engineering, Xi’an University of Architecture and Technology, Xi’an 710055, China
3
College of Geography and Planning, Chengdu University of Technology, Chengdu 610059, China
4
Sichuan Hongji Architectural Design Co., Ltd., Chengdu 610051, China
*
Author to whom correspondence should be addressed.
These authors contributed equally to this work.
Buildings 2026, 16(11), 2209; https://doi.org/10.3390/buildings16112209 (registering DOI)
Submission received: 24 April 2026 / Revised: 18 May 2026 / Accepted: 28 May 2026 / Published: 30 May 2026
(This article belongs to the Special Issue Sustainable Architecture and Healthy Environment)

Abstract

The building shape coefficient is an important metric in building design and energy analysis for describing the geometric compactness of a building. However, the conventional shape coefficient neglects the beneficial contribution of transparent building envelopes in utilizing solar radiation. To address this limitation, this study proposes a novel indicator, the building shape energy-saving coefficient (E), which accounts for the thermal performance differences between transparent and non-transparent building envelopes. A key intermediate parameter in the development of this indicator is the transparent envelope equivalent coefficient (Ci). Numerical simulation results indicate that climate conditions and building orientation are the primary factors influencing Ci. Based on these results, reference Ci values for different orientations of linear buildings in typical cities are provided. Subsequently, the corresponding E values are calculated, and the correlations between E, the traditional shape coefficient, and building air conditioning energy consumption are systematically compared. The results show that the coefficient of determination between E and air conditioning energy consumption exceeds 0.80, significantly higher than that between the traditional shape coefficient and energy consumption, demonstrating the improved predictive capability of the proposed indicator.

1. Introduction

With the increasing global focus on sustainability and carbon neutrality, building energy consumption has become a significant area of concern. Buildings account for approximately 30–40% of global energy use, making them one of the largest contributors to greenhouse gas emissions [1,2,3]. As urbanization intensifies and populations grow, improving the energy efficiency of buildings is essential to mitigating environmental impacts and achieving global climate goals.
Ways to reduce building heating and cooling energy consumption can be divided into active and passive energy saving technologies; active energy saving technologies focus on controlling building heating and cooling energy consumption through equipment energy efficiency improvement and system optimization, while passive energy saving technologies achieve energy saving goals through the inherent characteristics of the building itself and the use of natural resources [4]. Passive energy efficiency technologies mainly include two paths: design optimization of three parameters, including building orientation, window-to-wall ratio, and building shape; and building envelope thermal insulation improvement. Building envelope insulation improvement can be realized by adding insulation or replacing windows with better insulation after the building is constructed. However, it is difficult to change the orientation, window-to-wall ratio (WWR), and shape of the building once they have been solidified, and even if a lot of money is spent on upgrading the building envelope insulation at a later stage, it is still difficult to reduce the energy consumption and carbon emissions of the building. Therefore, it is important to optimize the design of the three parameters of building orientation, building window-to-wall ratio, and building shape in the early design stage of a building [5,6,7].
Building orientation plays a critical role in determining the intensity and duration of solar radiation received by a building, and proper orientation enables the maximization of solar energy utilization [8,9]. Jadhav and Minde investigated the influences of building and window orientations on energy consumption in the Maharashtra region, finding that orientations between 0° and 90° under specific conditions significantly reduced energy demand. Similarly, the WWR, defined as the proportion of the window area in the building’s external wall, is another critical factor influencing building energy performance [10]. Troup et al. analyzed energy use in commercial buildings and reported that larger WWRs resulted in higher cooling loads [11]. Foroughi et al. extended this analysis to various climatic zones using thermal performance simulations of standard office units and further evaluated the effects of WWR changes on heating, cooling, and lighting energy demands [12]. Their findings indicated that the sensitivity of energy consumption to WWR varies with the thermal standards of the building envelope, with optimal WWRs reducing total energy use by 2% to 15% in extreme climates. Premrov et al. proposed a facade system combining glass and wood, showing that a south-facing WWR of 35% minimized heating and annual energy demands [13]. Furthermore, building shape significantly influences the exterior surface area and the solar radiation-exposed facade, thus affecting both energy gains and losses [14]. The building shape coefficient (S) is defined as the ratio between the external surface area and the internal volume of a building. It represents the external envelope area corresponding to a unit building volume and can be calculated by the following equation [15].
S = F V
where F is the ratio of the external surface area in direct contact with outdoor air to the volume enclosed by the building, though the external surface area excludes the ground floor and the internal walls of unheated stairwells, m2; and V is the volume enclosed by the building envelope, m3. According to the relevant national standard [15], variations in building form in severe cold and cold regions directly affect building heating energy consumption. A larger building shape coefficient indicates a greater external surface area per unit of building area, resulting in higher heat loss and increased heating energy demand.
Even though building shape coefficient has been extensively adopted to characterize the correlation between building shape and building energy consumption, it still exhibits limitations and inaccuracies under different climatic conditions. Depecker et al. demonstrated that in cold regions such as Paris, building energy consumption was indeed correlated with the shape coefficient [16]. However, in warmer southern regions, this correlation became less significant. They pointed out that in mild climates and solar-rich regions, the relationship between building energy consumption and shape coefficient is no longer relevant, but their study did not propose corresponding measures to address this problem. Additionally, Albatici et al. introduced a new indicator named the South Exposure Coefficient to highlight the significant role of solar radiation in building energy consumption, and they emphasized the importance of considering solar energy for building design in solar-rich regions [17]. Shi et al. analyzed the inadequacy of the relationship between shape coefficient and energy consumption in solar-rich regions and proposed the concept of the equivalent shape coefficient S′ [18]. Their results revealed that the correlation between S′ and energy consumption was significantly better than that between the traditional shape coefficient and energy consumption.
The primary cause of these discrepancies lies in the fact that the traditional shape coefficient does not differentiate between transparent and non-transparent building envelopes, thus reducing its accuracy in capturing the energy performance of buildings especially in regions with rich solar resources. Given the unique optical and thermal properties of glass materials, the heat transfer mechanisms of transparent and non-transparent enclosures are quite different. Transparent building envelopes allow shortwave solar radiation to penetrate into indoor spaces, which plays a dominant role in daylighting design and solar heat gain [19,20,21]. However, thermal energy could not be effectively stored due to their material limitations. In contrast, non-transparent building envelopes can store and release heat through thermal capacity. In addition, the thermal performance of transparent and opaque structures differs significantly. Transparent envelopes generally have lower thermal resistance, resulting in much higher heat transfer coefficients compared to non-transparent structures [22]. Research indicates that 30–50% of heat gain through building envelopes can be attributed to transparent components [23].
However, the traditional shape coefficient considers only geometric characteristics and neglects the differences in thermal performance between transparent and opaque building envelopes. As a result, it cannot accurately reflect building air conditioning energy consumption. To overcome this limitation, more comprehensive indicators that integrate key design parameters and climatic factors are required. In this study, a new indicator, termed the (E), is proposed based on the conventional shape coefficient. This indicator accounts for the thermal performance differences between transparent and opaque envelopes, while also incorporating the effects of building orientation, window-to-wall ratio, and climate on heating and cooling loads. Consequently, it exhibits a stronger correlation with building air conditioning energy consumption and provides more effective guidance for building form, orientation, and facade design. This study first introduces the definition and calculation methods of the E value and Ci. Then, numerical simulations are conducted to investigate the effects of climate, orientation, and window-to-wall ratio on the Ci value. Finally, the correlation between the E value and building air conditioning energy consumption is verified.

2. Methodology

2.1. Building Shape Energy-Saving Coefficient

The building shape energy-saving coefficient is defined as the ratio of the sum of the non-transparent envelope area and the equivalent area of the transparent envelope to the building volume, denoted by E and expressed by Equation (2):
E = F n + i = 1 m ( C i × F c , i ) V
where Fn is the non-transparent envelope area of the building, m2; Ci is the equivalent coefficient of the transparent envelope; Fc,i is the transparent envelope area in different orientations, m2; and V is the volume enclosed by the building envelopes, m3.
Ci is an intermediate variable used in the calculation of the E value. It is defined as the ratio of the air conditioning electricity consumption caused by the transparent envelope to that caused by the non-transparent envelope. When Ci > 1, it indicates that the air conditioning energy consumption induced by the transparent envelope is greater than that caused by the non-transparent envelope. When Ci = 1, the air conditioning energy consumption contributions of the transparent and non-transparent envelopes are equal. When 0 ≤ Ci < 1, the air conditioning energy consumption caused by the transparent envelope is lower than that caused by the non-transparent envelope. When Ci < 0, the transparent envelope acts as a beneficial component; through net heat gains, it can reduce the heating load demand and offset part of the air conditioning electricity consumption caused by the non-transparent envelope. Since the indoor heat gains associated with the transparent envelope are strongly influenced by factors such as climate and orientation, the value of Ci is significantly affected by these factors. Its calculation method is given in Equation (3):
C i = W c , i W n
where Wc,i represents the cumulative air conditioning electricity consumption per unit area caused by the transparent envelope in different orientations, kWh/m2; and Wn is the cumulative air conditioning electricity consumption per unit area caused by the non-transparent envelope, kWh/m2.
For the calculation of Ci, the cumulative air conditioning electricity consumption of the non-transparent and transparent envelopes can be expressed as the sum of the cooling season and heating season electricity consumption. Specifically, the cumulative electricity consumption during the cooling season can be expressed as the ratio of net heat gains to the cooling seasonal performance factor of the air conditioning system. Similarly, the cumulative electricity consumption during the heating season can be expressed as the ratio of net heat losses to the heating seasonal performance factor of the air conditioning system, as shown in Equations (4) and (5).
W c , i = Q c , i , summer CSPF Q c , i , winter HSPF F c , i
W n = i = 1 Q n , i , summer CSPF i = 1 Q n , i , winter HSPF i = 1 F n , i
where Qc,i is cumulative heat gain and heat loss per unit area of the transparent envelope in different orientations, with heat gain being positive and heat loss being negative, kWh/m2; Qn,i is cumulative heat gain and heat loss per unit area of the non-transparent envelope in different orientations, with heat gain being positive and heat loss being negative, kWh/m2; CSPF is the cooling seasonal performance factor; and HSPF is the heating seasonal performance factor. Compared with the traditional shape coefficient, the proposed E indicator offers a more comprehensive representation of building air conditioning energy performance. It shows a positive correlation with air conditioning energy consumption; under identical conditions, a lower E value corresponds to lower air conditioning energy use. Therefore, the E indicator can more accurately capture trends in building air conditioning energy consumption and support optimized design strategies.

2.2. Study Case Simulation

2.2.1. Simulation Software

In this study, 3D modeling software SketchUp 2017 is utilized to construct building model to provide a foundational framework for subsequent energy simulation and analysis. EnergyPlus 8.9.0 is further used to obtain energy consumption data and relevant performance indicators of the developed models under various operating conditions.

2.2.2. Constraints

In this study, three different building types are analyzed, which are linear-shaped buildings, U-shaped buildings, and courtyard-shaped buildings. As shown in Figure 1, the linear-shaped building features a straight alignment with relatively uniform lighting and ventilation. The U-shaped building has a semi-enclosed structure, resulting in poorer lighting and ventilation in central areas. The enclosed courtyard-shaped building is a fully surrounded structures with the most significant self-shading problem. All three building types are modeled as single-story buildings, with their detailed dimensions shown in Figure 1. In Section 3.4, to investigate the effect of self-shading on the transparent envelope, all three building types are further modeled as six-story configurations for simulation purposes.
According to the “Design Standard for Energy Efficiency of Public Buildings” as specified in GB50189–2015, the ratio of window area to wall area for a single building facade should be maintained between 0.2 and 0.8 [15]. In this study, the window-to-wall ratios of 0.25, 0.35, 0.45, 0.55, 0.65, and 0.75 are selected in order to better understand the influences of different window-to-wall ratios on the performance of transparent building envelopes. These scenarios are analyzed to reveal the variation in the equivalent coefficient of transparent envelopes under different WWR conditions. Additionally, using a due south orientation (0°) as a reference point, the building is rotated clockwise in 30° increments through a full 360° to analyze the effects of orientation on the heat transfer characteristics of building facades.
According to the regulations specified in GB55015–2021 [24] and the actual conditions of studied buildings, the thermal performance parameters for transparent and non-transparent envelopes are given in Table 1.
In this study, the building model is treated as a single thermal zone. In addition, the indoor design air temperatures are defined based on the Chinese national standard GB 50736-2012 [25]. Specifically, the indoor air temperature is set to 26 °C under summer cooling conditions and 18 °C under winter heating conditions.

2.2.3. Studied Cities

China is a vast country with diverse climatic and environmental conditions, leading to uneven distribution of solar energy resources. Based on the regulations specified for the thermal design of civil building [26] and the assessment method for solar energy resource [27], seven cities are selected in this study to encompass the climatic characteristics for most regions in China, with the information detailed in Table 2. Regions with mild climates, which do not require heating or cooling, are excluded from this study.
The monthly average outdoor temperatures and annual horizontal solar irradiation for these cities are presented in Figure 2.

2.2.4. Air Conditioning Cooling and Heating Periods

According to national standards [25], the heating period is defined as the number of days with a stable multi-year daily average temperature lower than or equal to the critical outdoor temperature for heating, while the cooling period is defined as number of days with a stable multi-year daily average temperature higher than or equal to the critical outdoor temperature for cooling. The critical outdoor temperature for heating and cooling is set at 5 °C and 25 °C, respectively. Table 3 lists the cooling and heating periods, as well as CSPF and HSPF, for each studied city.

3. Results and Discussion

The control variable method is adopted in the present study to investigate the influence of various factors on the equivalent coefficient of the transparent envelope Ci. Calculations are carried out for linear-shaped, U-shaped, and courtyard-shaped buildings in the studied cities under different orientation and window-to-wall ratio conditions. Furthermore, sensitivity analysis is also conducted.

3.1. Influence of Climate Conditions on Ci

Figure 3a,b illustrate the hourly solar transmittance heat gains through the south-facing transparent envelope of a linear building with a window-to-wall ratio of 0.45 in different cities on a typical summer day and a typical winter day. On a typical summer day like July 19, the duration of solar radiation received is approximately the same across studied cities. However, due to variations in solar altitude angles, the amount of solar radiation received differs among cities. Cities at higher latitudes, such as Harbin, Lanzhou, and Beijing, receive more solar transmittance radiation compared to lower-latitude cities like Chengdu, Shanghai, and Guangzhou. On a typical winter day like January 12, this difference becomes even more distinct. Lhasa, located on the Qinghai–Tibet Plateau with solar-rich resources, receives significantly more solar radiation than other cities and has longer sunshine durations peaking at 12 kW at 14:00. In contrast, Chengdu, situated in the Sichuan Basin with the lowest annual solar irradiation, receives its maximum of only 1 kW on the same day.
Figure 3c,d present the hourly convective heat gains through the south-facing transparent envelope of a linear building with a window-to-wall ratio of 0.45 in different cities on a typical summer day and a typical winter day. Due to variations in outdoor temperatures among cities, the heat transfer through windows varies significantly. In Harbin, Lanzhou, Beijing, and Chengdu, heat loss through windows occurs during the nighttime even in summer. In Guangzhou, the room remains in a heat-gain state throughout the entire day. On a typical winter day, Lhasa’s unique geographic location allows sufficient solar radiation to be absorbed by the windows from 12:00 to 18:00. Therefore, the surface temperature of the windows is higher than the indoor temperature, resulting in a heat-gain state. In other cities on the same day, heat loss occurs throughout the entire 24 h period. Harbin, located in the severe cold region, experiences the highest heat loss, reaching a maximum of 1.5 kW at midnight.
The air conditioning demand varies across different cities, which can be categorized into three scenarios: cooling only demand, heating only demand, and both cooling and heating demands. Figure 4 illustrates the hourly heat transfer of transparent and non-transparent envelopes during cooling and heating periods in studied cities. It can be observed that the durations of cooling and heating periods vary among cities. Guangzhou requires cooling only, while Lhasa requires heating only. In other cities, cooling dominates in Shanghai and Chengdu, whereas heating is predominant in Beijing, Lanzhou, and Harbin. Additionally, heat transfer through windows is significantly higher than that through walls, indicating that windows are the primary source of indoor heat gain in buildings across these cities.
Figure 5 illustrates the cumulative heat gain through the south-facing windows of a linear building during the cooling and heating periods, as well as the corresponding Ci values for the building’s south-facing facade in different cities. During the summer cooling period, the transparent envelope on the south-facing facade generally exhibits a heat gain, with Guangzhou experiencing a cumulative heat gain of up to 40 kWh/m2 due to its high-temperature climate. In winter, Harbin, with its extremely low outdoor temperatures, shows a heat loss through the south-facing windows of up to 30 kWh/m2. In contrast to Harbin, regions such as Beijing, Lanzhou, and Lhasa have positive cumulative heat gains through south-facing windows during the winter heating period. Notably, Lhasa achieves a significant heat gain of 115 kWh/m2.
The equivalent coefficient of transparent envelope Ci reflects the annual comprehensive energy performance of facade windows. In cases of Ci > 0, the transparent envelope gains heat in summer and loses heat in winter, indicating that it is an energy-consuming component. Conversely, in cases of Ci < 0, the transparent envelope contributes to energy savings and helps reduce air conditioning energy consumption. As shown in Figure 5, the equivalent coefficients of south-facing windows in Lhasa, Beijing, and Lanzhou are −7.48, −2.83, and −1.05, respectively. Ci is always positive in other cities. The difference in Ci values can be attributed to variations in the heat transfer and thermal characteristics of building envelopes due to different geographical environments and climatic conditions. Therefore, in regions like Lhasa, Beijing, and Lanzhou, solar energy should be effectively utilized during the winter to maximize the passive energy-saving potential of buildings.

3.2. Influence of Building Orientations on Ci

Figure 6a illustrates the variation trends of cumulative solar transmittance radiation through south-facing windows, cumulative net heat gain through south-facing windows, and cumulative heat conduction through walls per unit area during the heating period. A linear building, with a window-to-wall ratio of 0.45 located in Lhasa under different orientations, is selected as the study case. It can be observed from Figure 6a that, as the building orientation rotates, the solar radiation received by the windows exhibits a trend of initially decreasing and then increasing, which achieves its maximum value at 160 kWh/m2 when the building is oriented directly south. When the building rotates to face directly north (180°), the solar radiation received by the windows drops to its lowest value, only 21.7 kWh/m2. Regarding the net heat gain of the windows, the windows exhibit significant heat loss when the building orientation lies within the range of 120° to 270°. This is primarily due to the reduced solar radiation received when the building faces north. In contrast, the heat conduction through walls is significantly lower than that through windows and remains in a heat-loss state across all orientations. The maximum heat loss through walls occurs when the building faces directly north, reaching 20 kWh/m2.
Figure 6b shows the hourly net heat gain of windows under different orientations on the typical winter day of January 12. The result reveals that, when the building is rotated 30° westward, the cumulative net heat gain of the windows reaches its maximum value of 9 kW. Furthermore, the time-dependent nature of hourly net heat gain is evident, with midday hours showing the highest heat gains due to direct solar incidence.
To more clearly illustrate the impact of orientation changes on the equivalent coefficient Ci of transparent enclosures, we further calculated the mean and standard deviation of Ci for windows on each facade of the linear building at three angles. Figure 7 displays the Ci values, along with their means and standard deviations, for windows at different angles in the single-line building model across various cities. As illustrated, the Ci values for transparent envelope equivalent coefficients vary across windows when buildings are located in different regions. When the building orientation shifts from 0° to 60°, the changes in Ci for each window also exhibit distinct differences. Detailed analysis follows below.
Figure 7 shows the variation in the Ci for windows on different facades of a linear building at various rotation angles in different cities. In cities dominated by cooling demand, such as Chengdu, Shanghai, and Guangzhou, during the rotational adjustment process of the building, the equivalent coefficients of east- and west-facing windows gradually decrease by 24–42%, while the values for south- and north-facing windows increase by 16–62.5%.
In heating-dominated regions such as Harbin, Lhasa, and Lanzhou, the equivalent coefficients of south- and west-facing windows increase as the building rotates. Among these, the west-facing windows in Lhasa exhibit the largest increase, rising from 0.22 to 3.94. In contrast, the Ci values for east- and north-facing windows decrease, with reductions generally exceeding 17%. Notably, the east-facing windows in Lhasa show the most significant decline, with the equivalent coefficient dropping from 1.15 to −2.22.

3.3. Influence of Window-to-Wall Ratios on Ci

A north–south oriented linear building located in Lhasa under different window-to-wall ratios is selected as the study case. Figure 8a illustrates the variations in solar transmittance radiation, convective heat transfer, net heat gain per unit area of the south-facing windows, and conductive heat transfer per unit area of the walls under different window-to-wall ratios. It can be obviously observed that, as the window-to-wall ratio increases, the solar transmittance heat gain per unit area of the windows remains relatively stable, while the convective heat transfer between the windows and indoor air decreases. This leads to an 8.61% reduction in the net heat transfer through the windows into the indoor space.
Furthermore, the equivalent coefficients Ci for windows on each facade are calculated, with the results shown in Figure 8b. The results indicate that as the window-to-wall ratio increases from 0.25 to 0.75, the Ci value for the east-, south-, west-, and north-facing windows increase by 0.25, 1.57, 0.38, and 0.21, respectively.
Similarly, based on the analysis of the above typical cases, we simulated and calculated the heat loss of the envelope structure and the air conditioning electricity consumption for the linear building in different typical cities at window-to-wall ratios of 0.25, 0.35, 0.45, 0.55, 0.65, and 0.75 for each facade.
Figure 9 shows the variation in the equivalent coefficient of transparent envelopes on different facades of the linear building under various window-to-wall ratios across different cities. It can be observed that, as the window-to-wall ratio increases from 0.25 to 0.75, the Ci value of the transparent envelope exhibits relatively small overall variation. Among these, the south-facing transparent envelope in Lhasa shows the largest increase in Ci, reaching 18.8%. However, in most cases, the variation in Ci remains below 10%.

3.4. Influence of Building Shapes on Ci

To investigate the influence of self-shading on the equivalent coefficient of transparent envelopes for buildings with different shapes, a U-shaped building and a courtyard-shaped building in Chengdu are selected as study cases. These two building both have six floors, a window-to-wall ratio of 0.45, and are oriented north–south. Regarding the U-shaped building and courtyard-shaped building, the most shaded south-facing window is referred to as Surface 1 (S1) and Surface 2 (S2), respectively. Obviously, S2 experiences more shading in comparison to S1.
Figure 10a compares the cumulative heat gain in summer, cumulative heat loss in winter, annual electricity consumption, and Ci per unit area between S1 and overall south-facing windows of the U-shaped building. The results show that the cumulative summer heat gain for S1 is 0.84 kWh/m2 lower than that of the overall south-facing windows of the building. However, the cumulative winter heat loss for S1 is 5.88 kWh/m2 higher, leading to an increase of 1.66 kWh/m2 in annual electricity consumption. This is due to the shading effect of the walls in front of S1 which reduce the amount of sunlight received on this surface. Moreover, the Ci value for the overall south-facing windows and S1 of the building is 2.44 and 2.93, respectively, showing a difference of 0.49.
Figure 10b presents a comparison of various values between S2 and the overall south-facing windows of the courtyard-shaped building. It can be obviously found that the heat gain in summer for S2 is 50% less than that of the overall south-facing windows. In winter, the shading effect results in 33.78% more heat loss for S2 compared to the overall south-facing windows. However, the difference in annual electricity consumption and Ci between S2 and the overall south-facing windows is only 6.56% and 7.86%, respectively.
Figure 11 shows the variation in the equivalent coefficient of transparent envelopes on different facades for the three six-story building types under rotation angles of 0°, 30°, and 60° across various cities. Due to differences in geographical and climatic conditions, the Ci values for the windows on various facades of linear-shaped, U-shaped, and courtyard-shaped buildings exhibit the same tendency with minimal differences during the rotation.

3.5. Quick Reference of Ci Values

Based on the above analysis above, it can be concluded that climatic conditions and building orientations are the primary factors leading to differences in the equivalent coefficient of transparent envelopes. To facilitate the effective application of these parameters in design, the Ci values of are summarized in Table 4 for typical linear-shaped buildings.

3.6. Verification of the Accuracy of E

For the studied cases, energy consumption data of each building model is obtained based on 756 numerical simulations using the EnergyPlus 8.9.0 software. In addition, the S and E for each building model are calculated. To validate the correlation between S and building energy consumption, as well as the correlation between E and building energy consumption in different cities, fitting analyses of these two coefficients against the energy consumption data of the building models for each city are further carried out, denoted by coefficient of determination (R2).
Figure 12 presents the correlation between S and building energy consumption, as well as the correlation between E and building energy consumption in different cities. It results show that in all the studied cities, the correlation between E and energy consumption is consistently stronger than that of S and energy consumption. In Harbin, which is located in a severe cold zone, the coefficient of determination R2 between S and energy consumption is 0.4459, while R2 between E and energy consumption is 0.9767. In cold zones, such as Lhasa, Lanzhou, and Beijing, the value of R2 between S and energy consumption is 0.0649, while R2 between E and energy consumption is up to 0.8724. In Chengdu, Shanghai and Guangzhou, R2 between E and energy consumption is always higher than 0.8. These findings demonstrate that the E is a more accurate indicator than the S for evaluating building energy consumption. Moreover, the applicability of the building shape energy-saving coefficient across the different studied cities is validated.

3.7. E-Based Building Design Optimization

To demonstrate the practical applicability of the E value in building design, this study takes building orientation optimization as an example for analysis. A linear building with a south-facing window-to-wall ratio of 0.35 and WWR of 0.25 on the other three facades was simulated under different orientations, and the results are shown in Figure 13. As the building orientation rotates from due south (0°) to due north (180°), both the E value and the annual building air conditioning energy consumption first increase and then decrease. When the building is oriented due south (0°), both the E value and the annual cooling and heating energy consumption reach their minimum values, indicating that a south-facing orientation is preferable in building design to maximize the utilization of solar energy resources.
In Figure 13, the building shape coefficient remains constant across the 49 simulation cases, whereas the annual air conditioning energy consumption varies consistently with changes in the building shape energy-saving coefficient. The two exhibit highly similar trends, further confirming that the E value has a stronger correlation with building air conditioning energy consumption than the traditional shape coefficient.

3.8. Discussion

3.8.1. Limitations of the Study

This study investigates the influence of climate, orientation, and window-to-wall ratio on the Ci coefficient using numerical simulation and provides Ci values for different orientations in typical cities, offering reference for optimized building form design. However, due to certain constraints, several limitations remain and should be addressed in future work:
  • This study considers only three typical building configurations, namely linear, U-shaped, and enclosed courtyard forms, without including circular or other irregular and more complex geometries. In addition, only one set of envelope parameter combinations was used for each city, and the influence of variations in envelope parameters on the Ci value was not systematically examined. Therefore, the findings have certain limitations in general applicability, and future research should expand both building types and parameter ranges to improve the robustness and universality of the conclusions.
  • The simulation models adopted in this study assume a single-zone internal space and do not account for internal space subdivision, functional differences, or orientation-dependent variations among zones. Moreover, the seasonal performance coefficient of the air conditioning system was represented by a single overall value without zoning-based differentiation. These simplifications may introduce deviations in the simulation results.
  • Different building functions typically have different HVAC operating schedules; for example, office buildings usually operate during daytime hours only, whereas hotels require continuous 24 h operation. In this study, all simulation cases assume a uniform 24 h HVAC operation schedule, without considering alternative operating patterns. Future work will further investigate the impact of different HVAC operation schedules on the results.

3.8.2. Influence of E on Building Cost

Under the condition that the building location is fixed, the proposed E indicator primarily influences construction cost through two factors: building shape and window-to-wall ratio. When building volume, Ci, and WWR remain constant, a larger external surface area in direct contact with outdoor air leads to a higher E value. In this case, the total envelope area increases accordingly, resulting in higher construction costs. When the total envelope area is fixed, the impact of WWR on construction cost is mainly reflected in two aspects. On the one hand, the unit cost of transparent envelope components is generally higher than that of opaque ones; therefore, a higher WWR increases the overall cost of the building envelope. On the other hand, an increased WWR leads to higher solar heat gains during daytime in the cooling season and greater heat losses at night during the heating season, which in turn increases the required capacity of the heating and cooling systems, thereby raising initial investment costs.

4. Conclusions

In this study, a novel building shape design indicator E, integrating window-to-wall ratio, building orientation, and climate, is proposed and named as the building shape energy-saving coefficient. In addition, numerical simulation is further carried out to validate the applicability and accuracy of this indicator. The following conclusions can be drawn:
  • The equivalent coefficient of the transparent building envelope Ci is a key parameter in the calculation of the E value. A larger Ci indicates that the transparent envelope leads to higher air conditioning energy consumption relative to the non-transparent envelope. When Ci < 0, the transparent envelope acts as a beneficial component, which can reduce the heating load demand and offset part of the air conditioning electricity consumption caused by the non-transparent envelope through net heat gains.
  • The value of Ci is primarily influenced by climate and building orientation. For a linear building configuration, the equivalent coefficient of south-facing windows in Lhasa is the lowest, reaching −7.48, whereas in Guangzhou, it is as high as 6.65.
  • Across the seven typical cities studied, the coefficient of determination between the E and air conditioning energy consumption exceeds 0.80 in all cases, which is significantly higher than that between S and air conditioning energy consumption. This indicates that the E coefficient provides a more accurate evaluation of building air conditioning energy use.
  • For the linear building configuration studied in the seven typical cities, where the window-to-wall ratio is 0.35 on the south facade and 0.25 on the other three facades, the E value reaches its minimum when the building is oriented due south. This corresponds to the lowest envelope-related contribution to building air conditioning energy consumption.

Author Contributions

Conceptualization, F.Q. and X.R.; methodology, F.Q. and X.R.; validation, L.P., D.H. and J.S.; formal analysis, J.J. and Y.J.; investigation, D.H.; resources, P.S.; data curation, L.P. and Y.J.; writing—original draft preparation, J.J. and L.P.; writing—review and editing, J.J. and L.P.; visualization, J.J. and S.F.; supervision, P.S.; project administration, L.S.; funding acquisition, L.S. All authors have read and agreed to the published version of the manuscript.

Funding

The research was funded by the financial support of the National Natural Science Foundation of China (Grant No. 52378113).

Data Availability Statement

The original contributions presented in this study are included in this article. Further inquiries can be directed to the corresponding author.

Conflicts of Interest

Authors Jikang Jia, Fang Qian, Xiangyang Rong, Pengfei Si, Lijun Shi and Songsong Feng were employed by the company China Southwest Architectural Design and Research Institute Co., Ltd.; Author Daya He was employed by the company Sichuan Hongji Architectural Design Co., Ltd. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

References

  1. China Association of Building Energy Efficiency; Institute of Urban and Rural Construction and Development, Chongqing University. Research Report on Building Energy Consumption and Carbon Emissions in China. Constr. Archit. 2024, 2, 46–59. [Google Scholar]
  2. Lin, Y.; Zhong, S.; Yang, W.; Hao, X.; Li, C.Q. Towards zero-energy buildings in China: A systematic literature review. J. Clean. Prod. 2020, 276, 123297. [Google Scholar] [CrossRef]
  3. Thangavelu, S.; Myat, A.; Khambadkone, A. Energy optimization methodology of multi-chiller plant in commercial buildings. Energy 2017, 123, 64–76. [Google Scholar] [CrossRef]
  4. Sharston, R.; Singh, M. The role of passive, active, and operational parameters in the relationship between urban heat island effect (UHI) and building energy consumption. Energy Build. 2024, 323, 114720. [Google Scholar] [CrossRef]
  5. Hong, T.; D’Oca, S.; Turner, W.J.; Taylor-Lange, S.C. An ontology to represent energy-related occupant behavior in buildings. Part I: Introduction to the DNAs framework. Build. Environ. 2015, 92, 764–777. [Google Scholar] [CrossRef]
  6. Asadi, S.; Amiri, S.; Mottahedi, M. On the development of multi-linear regression analysis to assess energy consumption in the early stages of building design. Energy Build. 2014, 85, 246–255. [Google Scholar] [CrossRef]
  7. Gimenez, J.; Bre, F.; Nigro, N.M.; Fachinotti, V. Computational modeling of natural ventilation in low-rise non-rectangular floor-plan buildings. Build. Simul. 2018, 11, 1255–1271. [Google Scholar] [CrossRef]
  8. Marino, C.; Nucara, A.; Pietrafesa, M. Thermal comfort in indoor environment: Effect of the solar radiation on the radiant temperature asymmetry. Sol. Energy 2017, 144, 295–309. [Google Scholar] [CrossRef]
  9. Benincá, L.; Sánchez, E.; Passuello, A.; Leitzke, R.K.; da Cunha, E.G.; Barroso, J.M.G. Multi-objective optimization of the solar orientation of two residential multifamily buildings in south Brazil. Energy Build. 2023, 285, 112838. [Google Scholar] [CrossRef]
  10. Jadhav, P.; Minde, P. BIM-based energy consumption analysis for residential buildings: Effects of orientation, size, and type of windows. Discov. Civ. Eng. 2024, 1, 110. [Google Scholar] [CrossRef]
  11. Troup, L.; Phillips, R.; Eckelman, M.J.; Fannon, D. Effect of window-to-wall ratio on measured energy consumption in US office buildings. Energy Build. 2019, 203, 109434. [Google Scholar] [CrossRef]
  12. Foroughi, R.; Asadi, S.; Khazaeli, S. On the optimization of energy efficient fenestration for small commercial buildings in the United States. J. Clean. Prod. 2021, 283, 124604. [Google Scholar] [CrossRef]
  13. Premrov, M.; Leskovar, V.; Mihalic, K. Influence of the building shape on the energy performance of timber-glass buildings in different climatic conditions. Energy 2016, 108, 201–211. [Google Scholar] [CrossRef]
  14. Qi, F.; Cui, F.; Lv, W.; Zhang, T.; Musonda, B.M. Regional similarity of shape coefficient of rural residences—Taking Hangzhou rural region as a case. Build. Simul. 2019, 12, 597–604. [Google Scholar] [CrossRef]
  15. GB 50189–2015; Design Standard for Energy Efficiency of Public Buildings. China Architecture & Building Press: Beijing, China, 2015. (In Chinese)
  16. Depecker, P.; Menezo, C.; Virgone, J.; Lepers, S. Design of buildings shape and energetic consumption. Build. Environ. 2001, 36, 627–635. [Google Scholar] [CrossRef]
  17. Albatici, R.; Passerini, F. Bioclimatic design of buildings considering heating requirements in Italian climatic conditions. A simplified approach. Build. Environ. 2011, 46, 1624–1631. [Google Scholar] [CrossRef]
  18. Shi, L.; Si, P.; Rong, X.; Qian, F.; Lei, Y.; Liu, X. Equal efficiency shape factor for building in solar rich areas. Heat. Vent. Air Cond. 2019, 49, 62–68. (In Chinese) [Google Scholar]
  19. Chen, Q.; Huang, Y.; Wu, H.; Liang, X.; Ma, X. A review and prospect on research progress of adjustable transparent envelope. Build. Simul. 2023, 16, 2225–2244. [Google Scholar] [CrossRef]
  20. Hegazy, M.; Yasufuku, K.; Abe, H. An interactive approach to investigate brightness perception of daylighting in Immersive Virtual Environments: Comparing subjective responses and quantitative metrics. Build. Simul. 2022, 15, 41–68. [Google Scholar] [CrossRef]
  21. Lu, L.; Law, K. Overall energy performance of semi-transparent single-glazed photovoltaic (PV) window for a typical office in Hong Kong. Renew. Energy 2013, 49, 250–254. [Google Scholar] [CrossRef]
  22. Huo, H.; Ji, Y.; Qin, Y.; Chen, C.; Yuan, T. Theoretical study of the synergic relationships between the design parameters in energy-saving building design. Sci. Rep. 2024, 14, 4400. [Google Scholar] [CrossRef] [PubMed]
  23. Cuce, E.; Riffat, S.B. Aerogel-Assisted Support Pillars for Thermal Performance Enhancement of Vacuum Glazing: A CFD Research for a Commercial Product. Arab. J. Sci. Eng. 2015, 40, 2233–2238. [Google Scholar] [CrossRef]
  24. GB 55015–2021; General Code for Energy Efficiency and Renewable Energy Application in Buildings. China Architecture & Building Press: Beijing, China, 2021. (In Chinese)
  25. GB 50736–2012; Design Code for Heating Ventilation and Air Conditioning of Civil Buildings. China Architecture & Building Press: Beijing, China, 2012. (In Chinese)
  26. GB 50176–2016; Code for Thermal Design of Civil Building. China Architecture & Building Press: Beijing, China, 2016. (In Chinese)
  27. GB/T 37526–2019; Assessment Method for Solar Energy Resource. China Meteorological Administration: Beijing, China, 2019. (In Chinese)
Figure 1. Models of (a) linear-shaped building; (b) U-shaped building; (c) courtyard-shaped building.
Figure 1. Models of (a) linear-shaped building; (b) U-shaped building; (c) courtyard-shaped building.
Buildings 16 02209 g001
Figure 2. Average outdoor temperatures of (a) Harbin, (b) Lhasa, (c) Lanzhou, (d) Beijing, (e) Chengdu, (f) Shanghai, and (g) Guangzhou; and (h) annual horizontal solar irradiation of studied cities.
Figure 2. Average outdoor temperatures of (a) Harbin, (b) Lhasa, (c) Lanzhou, (d) Beijing, (e) Chengdu, (f) Shanghai, and (g) Guangzhou; and (h) annual horizontal solar irradiation of studied cities.
Buildings 16 02209 g002
Figure 3. Solar transmittance heat gain and convective heat gain on typical summer and winter days: (a) solar transmittance heat gain on 19 July; (b) solar transmittance heat gain on 12 January; (c) convective heat gain on 19 July; (d) convective heat gain on 12 January.
Figure 3. Solar transmittance heat gain and convective heat gain on typical summer and winter days: (a) solar transmittance heat gain on 19 July; (b) solar transmittance heat gain on 12 January; (c) convective heat gain on 19 July; (d) convective heat gain on 12 January.
Buildings 16 02209 g003
Figure 4. Dynamic hourly heat transfer of building envelopes throughout the year in different cities.
Figure 4. Dynamic hourly heat transfer of building envelopes throughout the year in different cities.
Buildings 16 02209 g004
Figure 5. Cumulative heat gain and Ci of south-facing windows for linear buildings during cooling and heating periods in different cities.
Figure 5. Cumulative heat gain and Ci of south-facing windows for linear buildings during cooling and heating periods in different cities.
Buildings 16 02209 g005
Figure 6. (a) Heat transfer between south-facing windows and walls at different rotation angles; (b) hourly net heat gain of windows at different rotation angles.
Figure 6. (a) Heat transfer between south-facing windows and walls at different rotation angles; (b) hourly net heat gain of windows at different rotation angles.
Buildings 16 02209 g006
Figure 7. Variations in Ci for windows on different facades at various rotation angles: (a) east-facing window; (b) south-facing window; (c) west-facing window; (d) north-facing window.
Figure 7. Variations in Ci for windows on different facades at various rotation angles: (a) east-facing window; (b) south-facing window; (c) west-facing window; (d) north-facing window.
Buildings 16 02209 g007
Figure 8. (a) Comparison of heat transfer between south-facing windows and walls under different window-to-wall ratios; (b) Ci values for different facades.
Figure 8. (a) Comparison of heat transfer between south-facing windows and walls under different window-to-wall ratios; (b) Ci values for different facades.
Buildings 16 02209 g008
Figure 9. Variations in Ci for windows on different facades at various window-to-wall ratios: (a) east-facing window; (b) south-facing window; (c) west-facing window; (d) north-facing window.
Figure 9. Variations in Ci for windows on different facades at various window-to-wall ratios: (a) east-facing window; (b) south-facing window; (c) west-facing window; (d) north-facing window.
Buildings 16 02209 g009
Figure 10. (a) Comparison between S1 and the overall south-facing windows; (b) comparison between S2 and the overall south-facing windows.
Figure 10. (a) Comparison between S1 and the overall south-facing windows; (b) comparison between S2 and the overall south-facing windows.
Buildings 16 02209 g010
Figure 11. Variations in Ci values for windows with different orientations and building shapes under rotation angles: (a) Ci in Lhasa, (b) Ci in Harbin, (c) Ci in Lanzhou, (d) Ci in Beijing, (e) Ci in Chengdu, (f) Ci in Shanghai, and (g) Ci in Guangzhou.
Figure 11. Variations in Ci values for windows with different orientations and building shapes under rotation angles: (a) Ci in Lhasa, (b) Ci in Harbin, (c) Ci in Lanzhou, (d) Ci in Beijing, (e) Ci in Chengdu, (f) Ci in Shanghai, and (g) Ci in Guangzhou.
Buildings 16 02209 g011
Figure 12. Relationship between the building shape coefficient (S), the building shape energy-saving coefficient (E), and air conditioning energy consumption across different climate zones: (a) severe cold region; (b) cold region; (c) hot summer and cold winter region; and (d) hot summer and warm winter region.
Figure 12. Relationship between the building shape coefficient (S), the building shape energy-saving coefficient (E), and air conditioning energy consumption across different climate zones: (a) severe cold region; (b) cold region; (c) hot summer and cold winter region; and (d) hot summer and warm winter region.
Buildings 16 02209 g012
Figure 13. E and air conditioning energy consumption variations with building rotation angle in (a) Lhasa, (b) Harbin, (c) Lanzhou, (d) Beijing, (e) Chengdu, (f) Shanghai, and (g) Guangzhou.
Figure 13. E and air conditioning energy consumption variations with building rotation angle in (a) Lhasa, (b) Harbin, (c) Lanzhou, (d) Beijing, (e) Chengdu, (f) Shanghai, and (g) Guangzhou.
Buildings 16 02209 g013
Table 1. Thermal performance parameters of envelopes.
Table 1. Thermal performance parameters of envelopes.
Climate ZonesU-Value of Transparent Building Envelope (W/(m2·K))Solar Heat Gain Coefficient (SHGC) of Transparent EnclosureU-Value of Non-Transparent Building Envelope
(W/(m2·K))
Severely cold zone1.60.290.3
Cold zone1.80.40.45
Hot summer and cold winter zone2.20.30.8
Hot summer and warm winter zone2.70.31.5
Temperate zone2.50.251.5
Table 2. Climate zones and solar zones of the studied cities.
Table 2. Climate zones and solar zones of the studied cities.
Climate Zone
Solar Zone
Severe Cold ZoneCold ZoneHot Summer and Cold Winter ZoneHot Summer and Warm Winter ZoneTemperate Zone
Zone A/Lhasa///
Zone B/Lanzhou///
Zone CHarbinBeijingShanghaiGuangzhou/
Zone D//Chengdu//
Table 3. Cooling and heating periods of studied cities.
Table 3. Cooling and heating periods of studied cities.
CityCooling PeriodHeating PeriodCSPFHSPF
Harbin29 June to 24 July17 October to 10 April6.762.17
LhasaNo demand1 November to 12 March/2.59
Beijing9 June to 2 September12 November to 14 March6.172.6
Lanzhou13 July to 12 August5 November to 14 March7.252.52
Chengdu9 June to 19 September8 December to 14 February6.153.27
Shanghai31 May to 26 September1 January to 11 February5.873.16
Guangzhou27 April to 19 OctoberNo demand5.77/
Table 4. Quick reference of Ci values for typical linear-shaped buildings.
Table 4. Quick reference of Ci values for typical linear-shaped buildings.
CitiesEast-Facing WindowSouth-Facing WindowWest-Facing WindowNorth-Facing Window
30°60°30°60°30°60°30°60°
Harbin5.163.932.511.571.883.164.715.755.986.056.025.81
Lhasa1.24−2.23−5.43−7.52−6.31−3.590.363.584.394.564.473.79
Beijing3.611.52−1.14−2.90−1.840.833.444.744.534.384.464.45
Lanzhou2.621.430.05−1.04−0.700.582.113.233.413.403.423.30
Chengdu3.853.562.972.692.813.564.214.153.613.413.453.65
Shanghai4.874.092.812.322.834.325.535.294.193.874.034.49
Guangzhou9.068.286.656.657.9910.812.0210.797.495.956.367.66
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Jia, J.; Pu, L.; Jiao, Y.; Qian, F.; Rong, X.; Si, P.; He, D.; Shi, L.; Feng, S.; Sun, J. Investigation on Adaptive Building Shape Design Indicator Based on the Interaction of Building, Climate and Energy. Buildings 2026, 16, 2209. https://doi.org/10.3390/buildings16112209

AMA Style

Jia J, Pu L, Jiao Y, Qian F, Rong X, Si P, He D, Shi L, Feng S, Sun J. Investigation on Adaptive Building Shape Design Indicator Based on the Interaction of Building, Climate and Energy. Buildings. 2026; 16(11):2209. https://doi.org/10.3390/buildings16112209

Chicago/Turabian Style

Jia, Jikang, Li Pu, Yinghui Jiao, Fang Qian, Xiangyang Rong, Pengfei Si, Daya He, Lijun Shi, Songsong Feng, and Jiansong Sun. 2026. "Investigation on Adaptive Building Shape Design Indicator Based on the Interaction of Building, Climate and Energy" Buildings 16, no. 11: 2209. https://doi.org/10.3390/buildings16112209

APA Style

Jia, J., Pu, L., Jiao, Y., Qian, F., Rong, X., Si, P., He, D., Shi, L., Feng, S., & Sun, J. (2026). Investigation on Adaptive Building Shape Design Indicator Based on the Interaction of Building, Climate and Energy. Buildings, 16(11), 2209. https://doi.org/10.3390/buildings16112209

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Article metric data becomes available approximately 24 hours after publication online.
Back to TopTop