Single-Ended Fault Detection and Fault Location in Transmission Lines Using Approximate Derivative
Abstract
1. Introduction
- The pioneering application of the AD as an SETW fault location method.
- A comprehensive evaluation of FIA effects, definitively proving the method’s robustness under challenging zero-crossing conditions.
- A rigorous assessment of noise impacts to establish operational boundary noise levels.
- The introduction of a novel peak detection algorithm based on the extraction of LMs.
1.1. Related Work
1.1.1. Impedance-Based Methods
1.1.2. Traveling Wave Methods
1.1.3. Artificial Intelligence Methods
2. Materials and Methods
2.1. TW Theory
2.2. Approximate Derivative (AD)
2.3. Fault Detection with AD
2.4. Fault Location with AD
2.5. Case Study
3. Results
3.1. Software Implementation Details
3.2. Effects of Fault Location, Fault Resistance, FIA, Fault Type and Involved Phases
3.3. Effects of Noise
3.4. Effects of Faults Close to Line Ends
3.5. Effects of Power System Configuration, Loading, and Power Flow
4. Discussion
- Reduced Hardware Requirements: The method requires only a single current or voltage signal, simplifying practical application. Unlike most existing methods that necessitate 1 MHz or higher sampling frequencies, the proposed method operates effectively at just 250 kHz.
- Efficient Detection Strategy: Minimizing data requirements, the algorithm utilizes a brief 2.03 ms signal window for a 300 km line. This ultra-short timeframe decreases computational demands and inherently avoids the impact of CT saturation, which typically initiates at around 5 ms [14].
- Extensive Testing and Noise Tolerance: Tested against the highest number of fault cases listed in Table 6 at the lowest applicable noise levels, the results confirm that the method’s noise tolerance is highly competitive with existing works.
- High Accuracy in Complex Scenarios: The method maintains an exceptionally low average fault location error, successfully resolving challenging zero-crossing and close-fault boundary cases that conventional methods frequently bypass. Its rate of invalid results remains comparable to other leading methods.
- Superior Close-Fault Detection: Despite utilizing a lower sampling frequency, the method accurately locates shorter minimum fault distances and evaluates a substantially higher volume of close-fault cases than most competing techniques.
Author Contributions
Funding
Data Availability Statement
Acknowledgments
Conflicts of Interest
Abbreviations
| 3-P | Three-Phase |
| ABC | Phases A, B and C |
| ABCG | Phases A, B and C-to-ground |
| ABG | Phases A and B-to-ground |
| AD | Approximate derivative |
| AG | Phase A-to-ground |
| AI | Artificial intelligence |
| ANFIS | Adaptive network-based fuzzy inference system |
| ANN | Artificial neural network |
| ATP | Alternative transient program |
| CCVT | Coupling capacitor voltage transformer |
| CT | Current transformer |
| DNN | Deep neural network |
| DWT | Discrete wavelet transform |
| EMD | Empirical mode decomposition |
| FFT | Fast Fourier transform |
| GPS | Global positioning system |
| HHT | Hilbert–Huang transform |
| ICA | Independent component analysis |
| IMF | Intrinsic mode function |
| ITD | Intrinsic time decomposition |
| LBF | Learning-based framework |
| LCC | Line/cable card |
| LL | Line-to-line |
| LLG | Line-to-line-to-ground |
| LLL | Line-to-line-to-line |
| LLLG | Line-to-line-to-line-to-ground |
| LM | Local maximum |
| MLP | Multilayer perceptron |
| MM | Mathematical morphology |
| NFD | Newton’s forward difference |
| PMU | Phasor measurement unit |
| PTL | Power transmission line |
| SETW | Single-end traveling wave |
| SLG | Single line-to-ground |
| SNR | Signal-to-noise ratio |
| SVM | Support vector machine |
| TEO | Teager energy operator |
| TFSA | Transient frequency spectrum analysis |
| TW | Traveling wave |
| UPF | Unified power flow controller |
| WAN | Wavelet-alienation-neural technique |
| WGN | White gaussian noise |
| WMRA | Wavelet multi-resolution analysis |
| WT | Wavelet transform |
| WTMM | Wavelet transform modulus maxima |
Appendix A

| Conductor Type | Parameter | 400 kV | 230 kV |
|---|---|---|---|
| Phase conductors | Number of conductors in bundle | 2 | 1 |
| Outer radius of sub-conductor (cm) | 1.521 | 1.25 | |
| Inner radius of sub-conductor (cm) | 0.557 | 1.0211 | |
| Spacing btw. sub-conductors (cm) | 40 | – | |
| DC resistance (Ω/km) | 0.0596 | 0.0922 | |
| Ground wires | Outer radius of sub-conductor (cm) | 0.8 | 0.476 |
| Inner radius of sub-conductor (cm) | 0.48 | 0.371 | |
| DC resistance (Ω/km) | 0.3527 | 3.51 |
References
- Doria-García, J.; Orozco-Henao, C.; Leborgne, R.; Montoya, O.D.; Gil-González, W. High impedance fault modeling and location for transmission line. Electr. Power Syst. Res. 2021, 196, 107202. [Google Scholar] [CrossRef]
- Liu, Y.; Wang, B.; Zheng, X.; Lu, D.; Fu, M.; Tai, N. Fault Location Algorithm for Non-Homogeneous Transmission Lines Considering Line Asymmetry. IEEE Trans. Power Deliv. 2020, 35, 2425–2437. [Google Scholar] [CrossRef]
- Hashemian, S.M.; Hashemian, S.N.; Gholipour, M. Unsynchronized parameter free fault location scheme for hybrid transmission line. Electr. Power Syst. Res. 2021, 192, 106982. [Google Scholar] [CrossRef]
- Gutiérrez-Cruz, C.M.; Rosas-Ortiz, G.; Ruiz-Vega, D. A new unsynchronized fault location approach based on sequence voltage profiles and a multiconductor line detailed model: Application to symmetrical transmission lines. Electr. Power Syst. Res. 2024, 232, 110419. [Google Scholar] [CrossRef]
- Mishra, S.; Gupta, S.; Yadav, A. Intrinsic time decomposition based fault location scheme for unified power flow controller compensated transmission line. Int. Trans. Electr. Energy Syst. 2020, 30, e12585. [Google Scholar] [CrossRef]
- Xi, Y.; Hu, K.; Wang, K. Lightning strike fault location based on adaptive Kalman filter residual analysis. Power Syst. Prot. Control 2020, 48, 30–39. (In Chinese) [Google Scholar] [CrossRef]
- Wang, S.; Zhuang, C.; Geng, Y.; Wang, T.; Luo, B.; Zeng, R. Fault location method based on edge detection for low SNR traveling waves. Electr. Power Syst. Res. 2021, 201, 107505. [Google Scholar] [CrossRef]
- Zhuang, C.; Xie, S.; Yang, H.; Yu, H.; Geng, Y.; Zeng, R. Flexible Noncontact Approach for Fault Location of Transmission Lines Using Electro-Optic Field Sensors. IEEE Trans. Electromagn. Compat. 2021, 63, 2151–2158. [Google Scholar] [CrossRef]
- Kwasi Anane, P.O.; Huang, Q.; Bamisile, O.; Ayimbire, P.N. Fault location in overhead transmission line: A novel non-contact measurement approach for traveling wave-based scheme. Int. J. Electr. Power Energy Syst. 2021, 133, 107233. [Google Scholar] [CrossRef]
- Aminirad, M.; Shahrtash, S.M. A novel protection and fault location combined algorithm for mixed/hybrid lines. IET Gener. Transm. Distrib. 2022, 16, 2016–2031. [Google Scholar] [CrossRef]
- Chen, W.; Wang, D.; Cheng, D.; Qiao, F.; Liu, X.; Hou, M. Novel travelling wave fault location principle based on frequency modification algorithm. Int. J. Electr. Power Energy Syst. 2022, 141, 108155. [Google Scholar] [CrossRef]
- Akmaz, D.; Mamiş, M.S. Fault location method on two-terminal transmission line using synchronized time information of traveling waves. Electr. Eng. 2022, 104, 979–990. [Google Scholar] [CrossRef]
- Nan, P.; Menghan, C.; Rui, L.; Zare, F. Asynchronous fault location scheme for half-wavelength transmission lines based on propagation characteristics of voltage travelling waves. IET Gener. Transm. Distrib. 2019, 13, 502–510. [Google Scholar] [CrossRef]
- Gaur, V.K.; Bhalja, B.R.; Saber, A. New ground fault location method for three-terminal transmission line using unsynchronized current measurements. Int. J. Electr. Power Energy Syst. 2022, 135, 107513. [Google Scholar] [CrossRef]
- Sawai, S.; Pradhan, A.K. Travelling-wave-based protection of transmission line using single-end data. IET Gener. Transm. Distrib. 2019, 13, 4659–4666. [Google Scholar] [CrossRef]
- Tian, X.; Shu, H. A new method of single terminal traveling wave location based on characteristic of superposition of forward traveling wave and backward traveling wave. Int. J. Electr. Power Energy Syst. 2021, 133, 107072. [Google Scholar] [CrossRef]
- Reis, R.L.A.; Lopes, F.V.; Neves, W.L.A.; Fernandes, D.; Ribeiro, C.M.S.; Cunha, G.A. An improved single-ended correlation-based fault location technique using traveling waves. Int. J. Electr. Power Energy Syst. 2021, 132, 107167. [Google Scholar] [CrossRef]
- Rezaei, D.; Gholipour, M.; Parvaresh, F. A new traveling-wave detection method for fault location based on two sequential sliding windows and curve fitting. IET Gener. Transm. Distrib. 2022, 16, 3333–3348. [Google Scholar] [CrossRef]
- Akbari, E.; Samady Shadlu, M. An Adaptive Simplified Travelling Wave-Based Fault Detection, Classification and Location Estimation Strategy for Series Compensated Transmission Lines. IET Smart Grid 2025, 8, e70041. [Google Scholar] [CrossRef]
- Akdağ, M.; Mamiş, M.S.; Akmaz, D. Enhancing Fault Location Accuracy in Transmission Lines Using Transient Frequency Spectrum Analysis: An Investigation into Key Factors and Improvement Strategies. Electricity 2024, 5, 861–876. [Google Scholar] [CrossRef]
- Almeida, A.R.; Almeida, O.M.; Junior, B.F.S.; Barreto, L.H.S.C.; Barros, A.K. ICA feature extraction for the location and classification of faults in high-voltage transmission lines. Electr. Power Syst. Res. 2017, 148, 254–263. [Google Scholar] [CrossRef]
- Khaleghi, A.; Oukati Sadegh, M. Single-Phase Fault Location in Four-Circuit Transmission Lines Based on Wavelet Analysis Using ANFIS. J. Electr. Eng. Technol. 2019, 14, 1577–1584. [Google Scholar] [CrossRef]
- Khalili, M.; Namdari, F.; Rokrok, E. A fault location and detection technique for STATCOM compensated transmission lines using game theory. IET Gener. Transm. Distrib. 2021, 15, 1688–1701. [Google Scholar] [CrossRef]
- Hamidi, S.M.; Ameli, A.; Ghafouri, M.; Lopes, F.V. A Learning-Based Framework for Locating Faults on Power Grid Lines Based on Distortion of Traveling Waves. IEEE Trans. Instrum. Meas. 2022, 71, 2514115. [Google Scholar] [CrossRef]
- Mirzaei, M.; Vahidi, B.; Hosseinian, S.H. Fault location on a series-compensated threeterminal transmission line using deep neural networks. IET Sci. Meas. Technol. 2018, 12, 746–754. [Google Scholar] [CrossRef]
- Yu, K.; Zeng, J.; Zeng, X.; Xu, F.; Ye, Y.; Ni, Y. A Novel Traveling Wave Fault Location Method for Transmission Network Based on Directed Tree Model and Linear Fitting. IEEE Access 2020, 8, 122610–122625. [Google Scholar] [CrossRef]
- Rathore, B.; Mahela, O.P.; Khan, B.; Padmanaban, S. Protection scheme using wavelet-alienation-neural technique for UPFC compensated transmission line. IEEE Access 2021, 9, 13737–13753. [Google Scholar] [CrossRef]
- Schweitzer, E.O.; Guzman, A.; Mynam, M.V.; Skendzic, V.; Kasztenny, B.; Marx, S. Locating faults by the traveling waves they launch. In Proceedings of the 2014 67th Annual Conference for Protective Relay Engineers, CPRE 2014, College Station, TX, USA, 31 March–3 April 2014; pp. 95–110. [Google Scholar] [CrossRef]
- Høidalen, H.K.; Prikler, L.; Peñaloza, F. ATPDRAW Version 7.5 for Windows Users’ Manual; European ATP-EMTP User Group: Liège, Belgium, 2023. [Google Scholar]
- Marti, J. Accurate Modelling of Frequency-Dependent Transmission Lines in Electromagnetic Transient Simulations. IEEE Trans. Power Appar. Syst. 1982, PAS-101, 147–157. [Google Scholar] [CrossRef]
- Jafarian, P.; Sanaye-Pasand, M. High-frequency transients-based protection of multiterminal transmission lines using the SVM technique. IEEE Trans. Power Deliv. 2013, 28, 188–196. [Google Scholar] [CrossRef]
- Reis, R.L.A.; Lopes, F.V.; Neves, W.L.A.; Fernandes, D.; Almeida Neto, F.G. Effects of CCVT stray capacitances on traveling wave-based applications. Electr. Power Syst. Res. 2021, 195, 107154. [Google Scholar] [CrossRef]















| Location (km) | Type | Fault Resistance (Ω) | FIA (°) | Number of Simulations |
|---|---|---|---|---|
| 5 20 60 100 148 160 200 260 280 295 | AG | 20 | 90 | 10 |
| 50 | 30 | 10 | ||
| BG | 20 | 0/30 | 20 | |
| CG | 50 | 90/30 | 20 | |
| AB | – | 0 | 10 | |
| AC | – | 90 | 10 | |
| BC | – | 30 | 10 | |
| ABG | 20/50 | 0 | 20 | |
| ACG | 50 | 90/30 | 20 | |
| BCG | 20 | 90/30 | 20 | |
| ABC | – | 0/30/90 | 30 | |
| ABCG | 20/50 | 90 | 20 | |
| 20 | 0/30 | 20 |
| Signal | SNR (dB) | Location (km) | Type | Fault Resistance (Ω) | FIA (°) |
|---|---|---|---|---|---|
| Current | 100/90 | 5 | BG | 20 | 0 |
| CG | 50 | ||||
| AB | – | ||||
| Voltage | 35 | 5 | AB | – |
| Type | Location (km) | FIA (°) | Error (%) | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Fs = 250 kHz | Fs = 500 kHz | |||||||||
| No Noise | SNR = 90 dB | SNR = 35 dB | No Noise | SNR = 90 dB | SNR = 35 dB | |||||
| Current | Voltage | Current | Voltage | Current | Voltage | Current | Voltage | |||
| AG | 1.5 | 90 | 0.09 | 0.09 | 0.09 | 0.09 | 0.29 | 0.19 | 0.29 | 0.19 |
| 0 | Invalid | Invalid | Invalid | Invalid | 0.29 | 0.19 | Invalid | 0.19 | ||
| 298.5 | 90/0 | 0.45 | 0.53 | 0.45 | 0.53 | 0.98 | 0.09 | 0.98 | 0.09 | |
| AC | 1.5 | 90 | 0.29 | 0.09 | 0.29 | 0.09 | 0.29 | 0.19 | 0.29 | 0.19 |
| 0 | Invalid | Invalid | Invalid | Invalid | Invalid | 0.09 | Invalid | Invalid | ||
| 298.5 | 90 | 0.14 | 0.53 | 0.14 | 0.53 | 0.04 | 0.53 | 0.04 | 0.53 | |
| 0 | 0.14 | 0.53 | 0.14 | 0.53 | 0.14 | 0.53 | 0.14 | 0.53 | ||
| ABC | 1.5 | 90/0 | 0.29 | 0.09 | 0.29 | 0.09 | 0.29 | 0.19 | 0.29 | 0.19 |
| 298.5 | 90/0 | 0.14 | 0.53 | 0.14 | 0.53 | 0.04 | 0.53 | 0.04 | 0.53 | |
| ACG | 1.5 | 90 | 0.29 | 0.09 | 0.29 | 0.09 | 0.29 | 0.19 | 0.29 | 0.19 |
| 0 | 0.09 | 0.09 | 0.09 | 0.09 | 0.29 | 0.19 | 0.19 | 0.19 | ||
| 298.5 | 90 | 0.14 | 0.53 | 0.14 | 0.53 | 0.04 | 0.53 | 0.04 | 0.53 | |
| 0 | 0.14 | 0.53 | 0.14 | 0.53 | 0.14 | 0.53 | 0.14 | 0.53 | ||
| ABCG | 1.5 | 90/0 | 0.29 | 0.09 | 0.29 | 0.09 | 0.29 | 0.19 | 0.29 | 0.19 |
| 298.5 | 90/0 | 0.14 | 0.53 | 0.14 | 0.53 | 0.04 | 0.53 | 0.04 | 0.53 | |
| Type | Location (km) | FIA (°) | Error (%) | |||
|---|---|---|---|---|---|---|
| No Noise | SNR = 90 dB | SNR = 35 dB | ||||
| Current | Voltage | Current | Voltage | |||
| AG | 1.5 | 3 | 0.09 | 0.09 | 0.09 | 0.09 |
| 5 | 0.09 | 0.09 | 0.09 | 0.09 | ||
| AC | 1.5 | 3 | 0.29 | 0.09 | invalid | 0.09 |
| 5 | 0.29 | 0.09 | 0.29 | 0.09 | ||
| Type | Location (km) | FIA (°) | VS | VR | Error (%) | |
|---|---|---|---|---|---|---|
| (rms,) | (rms,) | Current | Voltage | |||
| AG | 1.5 | 90 | 0.28 | 0.28 | ||
| 0 | Invalid | 0.28 | ||||
| 5 | 0.28 | 0.28 | ||||
| AB | 20 | 90/0 | 230∠0 | 225.4∠−15 | 0.78 | 0.19 |
| 0 | ||||||
| ABG | 48 | 90 | 230∠0 | 225.4∠−15 | 0.09 | 0.09 |
| 0 | 0.25 | 0.09 | ||||
| 0.25 | ||||||
| 0.09 | 0.09 | |||||
| ABC | 70 | 90/0 | 230∠0 | 225.4∠−15 | 0.65 | 0.06 |
| 0 | 225.4∠−15 | 230∠0 | ||||
| 230∠0 | 210∠−30 | |||||
| 210∠−30 | 230∠0° | |||||
| ABCG | 98.5 | 90/0 | 230∠0 | 225.4∠−15 | 0.06 | 0.06 |
| 0 | 225.4∠−15 | 230∠0 | ||||
| 230∠0 | 210∠−30 | |||||
| 210∠−30 | 230∠0° | |||||
| Reference | [13] | [14] | [15] | [16] | [17] | [18] | [19] | Prop. | Prop. |
|---|---|---|---|---|---|---|---|---|---|
| Method | TEO of DWT and S-transform | WTMM | NFD | Time-length decomposition | Correlation of the Park transformation | Curve fitting and sliding window | Gabor transform | AD | AD |
| Processed signal | Voltage | Current | Current | Voltage and current | Voltage and current | Voltage | Voltage | Voltage | Current |
| Measurement | 3-terminal unsynchronized | 3-terminal unsynchronized | Single-end | Single-end | Single-end | Single-end | Single-end | Single-end | Single-end |
| Fault detection | No | No | Yes | No | No | No | Yes | Yes | Yes |
| Sampling freq. (kHz) | 1000 | 1000 | 1000 | 1000 | 1560 | 1000 | 10 | 250 | 250 |
| Number of test case conditions (simulations) | 192 | ~59 | ≥78 | 135 | 120 | ~102 | 88 | 244 * | 244 * |
| Lowest applicable SNR (dB) | 90 | 50 | 54 | 35 | 70 | 35 | 30 | 35 | 90 |
| Number of test case conditions with specified lowest applicable SNR | 2 | ~59 | 1 | 1 | 120 | 3 | 5 | 244 | 244 |
| Number of erroneous computations without/with noise (invalid or >1%) | 0/0 | 3/5 | 3/4 | 0/0 | 3/12 | 0/5 | 0/0 | 2/3 | 3/6 |
| Average fault location estimation error (%) | ~0.14 | 0.14 | 0.34 | 0.18 | ~0.19 | 0.01 | 0.21 | 0.19 | 0.12 |
| Number of zero-crossing (FIA = 0°, 180° and 360°) simulations without/with noise | 96/4 | 10/0 | 1/0 | 0/0 (closest 5°) | 40/40 | 0/0 (closest 3°) | 2/0 | 80/80 | 80/80 |
| Closest faults to line end in km | 5 | 0.5 | 0.9 | 2 | 10 | 2 | 3 | 1.5 | 1.5 |
| Number of closest faults to line end simulations without/with noise | 1/0 | 1/0 | 1/0 | 7/0 | 48/48 | 28/28 | 2/0 | 24/24 | 24/24 |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Share and Cite
Akdağ, M.; Mamiş, M.S.; Akmaz, D. Single-Ended Fault Detection and Fault Location in Transmission Lines Using Approximate Derivative. Electronics 2026, 15, 2591. https://doi.org/10.3390/electronics15122591
Akdağ M, Mamiş MS, Akmaz D. Single-Ended Fault Detection and Fault Location in Transmission Lines Using Approximate Derivative. Electronics. 2026; 15(12):2591. https://doi.org/10.3390/electronics15122591
Chicago/Turabian StyleAkdağ, Mustafa, Mehmet Salih Mamiş, and Düzgün Akmaz. 2026. "Single-Ended Fault Detection and Fault Location in Transmission Lines Using Approximate Derivative" Electronics 15, no. 12: 2591. https://doi.org/10.3390/electronics15122591
APA StyleAkdağ, M., Mamiş, M. S., & Akmaz, D. (2026). Single-Ended Fault Detection and Fault Location in Transmission Lines Using Approximate Derivative. Electronics, 15(12), 2591. https://doi.org/10.3390/electronics15122591

