Article

Experimental Study of Condensation Heat Transfer and Pressure Drop inside a Small Diameter Microfin and Smooth Tube at Low Mass Flux Condition

1
Graduate School of Science and Engineering, Saga University, 1 Honjomachi, Saga 840-8502, Japan
2
Department of Mechanical Engineering, Saga University, 1 Honjomachi, Saga 840-8502, Japan
3
International Institute for Carbon-Neutral Energy Research, Kyushu University, Fukuoka 819-0395, Japan
*
Author to whom correspondence should be addressed.
Appl. Sci. 2018, 8(11), 2146; https://doi.org/10.3390/app8112146
Submission received: 22 October 2018 / Revised: 31 October 2018 / Accepted: 31 October 2018 / Published: 2 November 2018
(This article belongs to the Special Issue Sciences in Heat Pump and Refrigeration)

Abstract

This study was made to investigate the condensation local heat transfer and adiabatic pressure drop of R134a inside a 2.5 mm outside diameter smooth and microfin tube at low mass flux condition. Data were measured for mass fluxes from 50 to 300 kg m−2s−1, vapor qualities from 0 to 1 and saturation temperatures from 20 to 30 °C. The effects of mass flux, vapor quality, saturation temperature, microfin and diameter of test tube were analyzed. The pressure drop of the microfin tube was about 1.5 times higher than that of the smooth tube at mass flux 50 kg m−2s−1. The heat transfer coefficient of the microfin tube was about 2–5 times higher than that of the smooth tube at mass flux 100 kg m−2s−1. Experimental results were also compared with typical correlations. For the microfin tube, however, all the existing correlations do not adequately predict the present data. Poor predictions may be attributed to the lack of the small diameter microfin tube with low mass flux data in their database. Hence, it is essential to develop a condensation and pressure drop correlation for the small diameter microfin tube at low mass flux condition.
Keywords: microfin tube; condensation; heat transfer coefficient; pressure drop; R134a microfin tube; condensation; heat transfer coefficient; pressure drop; R134a

Share and Cite

MDPI and ACS Style

Bashar, M.K.; Nakamura, K.; Kariya, K.; Miyara, A. Experimental Study of Condensation Heat Transfer and Pressure Drop inside a Small Diameter Microfin and Smooth Tube at Low Mass Flux Condition. Appl. Sci. 2018, 8, 2146. https://doi.org/10.3390/app8112146

AMA Style

Bashar MK, Nakamura K, Kariya K, Miyara A. Experimental Study of Condensation Heat Transfer and Pressure Drop inside a Small Diameter Microfin and Smooth Tube at Low Mass Flux Condition. Applied Sciences. 2018; 8(11):2146. https://doi.org/10.3390/app8112146

Chicago/Turabian Style

Bashar, M. Khairul, Keisuke Nakamura, Keishi Kariya, and Akio Miyara. 2018. "Experimental Study of Condensation Heat Transfer and Pressure Drop inside a Small Diameter Microfin and Smooth Tube at Low Mass Flux Condition" Applied Sciences 8, no. 11: 2146. https://doi.org/10.3390/app8112146

APA Style

Bashar, M. K., Nakamura, K., Kariya, K., & Miyara, A. (2018). Experimental Study of Condensation Heat Transfer and Pressure Drop inside a Small Diameter Microfin and Smooth Tube at Low Mass Flux Condition. Applied Sciences, 8(11), 2146. https://doi.org/10.3390/app8112146

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics