Rethinking Winter Heating in University Classrooms in China’s Hot Summer and Cold Winter Regions: Setpoint–Preference Mismatches, Pre-Heating, and Comfort Assessment

1
School of Architecture and Civil Engineering, Chengdu University, Chengdu 610106, China
2
Faculty of Environmental Engineering, The University of Kitakyushu, Kitakyushu 808-0135, Japan
3
Innovation Institute for Sustainable Maritime Architecture Research and Technology (ISMART), Qingdao University of Technology, Qingdao 266520, China
*
Author to whom correspondence should be addressed.
Buildings 2026, 16(7), 1304; https://doi.org/10.3390/buildings16071304
Submission received: 24 February 2026 / Revised: 21 March 2026 / Accepted: 23 March 2026 / Published: 25 March 2026
(This article belongs to the Section Building Energy, Physics, Environment, and Systems)

Abstract

Winter thermal comfort in university classrooms in China’s Hot Summer and Cold Winter (HSCW) regions remains problematic due to mismatches between institutional heating setpoints and students’ actual thermal preferences. To investigate students’ thermal perceptions and behavioral responses, a post-occupancy evaluation (POE) survey was conducted, followed by field measurements in a typical classroom in Chengdu under three conditions: no-heating condition, heating conditions at 20 °C and 25 °C. Indoor environmental parameters were continuously monitored, and thermal comfort was assessed using the Predicted Mean Vote (PMV) and Predicted Percentage of Dissatisfied (PPD) model. The results show that no-heating conditions were unacceptable, highlighting the necessity of heating. While the 20 °C setpoint provided partial improvement, thermal comfort was not consistently achieved throughout the day. In contrast, the 25 °C setpoint maintained near-neutral conditions during most occupied periods. In addition, a pre-heating duration of approximately 30 min was found to be essential for reducing initial thermal discomfort. Overall, the findings indicate that fixed institutional heating standards may not adequately satisfy students’ thermal needs. Adaptive heating strategies that combine appropriate setpoints with sufficient pre-heating duration are therefore recommended to balance thermal comfort and energy efficiency in university classrooms in the HSCW regions.
Keywords: winter thermal comfort; university classroom; pre-heating duration; post-occupancy evaluation; hot summer and cold winter regions winter thermal comfort; university classroom; pre-heating duration; post-occupancy evaluation; hot summer and cold winter regions

Share and Cite

MDPI and ACS Style

Gong, Q.; Ye, X.; Yang, X.; Zhang, T.; Gao, W. Rethinking Winter Heating in University Classrooms in China’s Hot Summer and Cold Winter Regions: Setpoint–Preference Mismatches, Pre-Heating, and Comfort Assessment. Buildings 2026, 16, 1304. https://doi.org/10.3390/buildings16071304

AMA Style

Gong Q, Ye X, Yang X, Zhang T, Gao W. Rethinking Winter Heating in University Classrooms in China’s Hot Summer and Cold Winter Regions: Setpoint–Preference Mismatches, Pre-Heating, and Comfort Assessment. Buildings. 2026; 16(7):1304. https://doi.org/10.3390/buildings16071304

Chicago/Turabian Style

Gong, Quyi, Xin Ye, Xiaoyi Yang, Tao Zhang, and Weijun Gao. 2026. "Rethinking Winter Heating in University Classrooms in China’s Hot Summer and Cold Winter Regions: Setpoint–Preference Mismatches, Pre-Heating, and Comfort Assessment" Buildings 16, no. 7: 1304. https://doi.org/10.3390/buildings16071304

APA Style

Gong, Q., Ye, X., Yang, X., Zhang, T., & Gao, W. (2026). Rethinking Winter Heating in University Classrooms in China’s Hot Summer and Cold Winter Regions: Setpoint–Preference Mismatches, Pre-Heating, and Comfort Assessment. Buildings, 16(7), 1304. https://doi.org/10.3390/buildings16071304

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop