This section analyses the numerical results obtained from the proposed EV cut-off energy planning and multi-objective optimization framework. The analysis proceeds from single point planning evaluation to feasibility regions, cost emission trade-off, optimization outcomes, and grid peak constraints.
4.2.2. Feasibility Regions in the and Plane
Figure 3 and
Figure 4 represent the feasibility maps for
and
planes respectively. In both figures, the yellow region indicates the feasible domain where the corresponding condition is satisfied, while the blue region represents the infeasible domain where the condition is violated. Especially in
Figure 3, the feasible (yellow) region corresponds to operating conditions where EV emissions are lower than ICEV emissions (
). In
Figure 4, the feasible (yellow) region represents combinations of electrification share and renewable energy penetration for which the fleet-wide emission constraints are satisfied (
).
Figure 3 is generated by evaluating the EV–ICEV emission condition over the
space using the fleet emission formulation in Equation (4). For each pair of renewable share (
) and grid carbon intensity
values, the condition defined by Equation (13) is assessed to determine wherever EV deployment results in lower emissions than ICEVs.
The feasibility region in
Figure 3 (value = 1) corresponds to operating points where the inequality is satisfied, while infeasible regions (value = 0) indicate that EV emissions exceed those of ICEVs. The computation is performed using the emission factors provided in
Table 3, and parameter ranges are systematically varied to construct the full feasibility map.
Figure 4 is obtained by evaluating the emission cap constraint over the
space using the system-level emission formulation. For each combination of electrification share
and renewable share
, the fleet emission factor computed from Equation (4) is compared against the cap constraint defined by Equations (12) and (13). The white circular marker shown in
Figure 4 corresponds to the representative baseline operating point adopted in this study, defined by an electrification share of
and a renewable-energy penetration of
. This operating point represents the initial user-defined planning scenario before optimization and sensitivity analysis. Its position within the feasible electrification region confirms that the selected operating condition satisfies the imposed emission and grid-capacity constraints under the adopted case-study assumptions.
Feasible regions (value = 1) correspond to operating points where the fleet emission remains below the specified cap
, while infeasible regions (value = 0) indicate violation of the constraint. The calculations are based on the emission parameters listed in
Table 3 and evaluated scenarios summarized in
Table 4.
The key observations from the above results are as follows:
A large proportion of the space is infeasible for EV deployment under carbon-intensive grids.
Increasing the electrification share α tightens the feasibility constraints, especially when emission caps are enforced.
The feasible region shrinks rapidly for low renewable penetration, highlighting the system-level coupling between transport and the power sectors.
These results are consistent with previous scenario-based studies [
19,
39] but are now extended by providing continuous feasibility boundaries rather than discrete case comparisons.
4.2.3. Fleet Emission Surface and Sensitivity Analysis
Figure 5 and
Figure 6 depict the contour and surface plots of the fleet emission intensity
. The emission surface exhibits strong monotonic decrease with increasing renewable energy share
, and nonlinear sensitivity to electrification share
particularly at intermediate renewable levels.
Figure 5 is generated by evaluating the fleet emission formulation given by Equation (4) over a discretized grid of electrification share
and renewable share
. For each pair
, the fleet emission intensity
is computed using the emission factor defined in
Table 3.
The contour line represents iso-emission levels, i.e., constant values of
, allowing visualization of the intensity of emissions to variations in
and
. The operating point
shown by the white circular marker corresponds to the scenario defined in
Table 4 and is superimposed for reference.
Figure 6 is obtained using the same dataset as
Figure 5 by evaluating the fleet emission formulation in Equation (4) across the
space. The three-dimensional surface represents the variation in
as a function of electrification share and renewable penetration.
The surface illustrates the monotonic decrease in the fleet emissions with increasing renewable share
, as well as the nonlinear interaction between
and
. The plotted values are computed using the emission parameters listed in
Table 3, and the highlighted operating point shown as a white circular marker corresponds to the evaluated scenario in
Table 4.
4.2.4. Energy Demand, Renewable Capacity and Cost Implication
Figure 7 is defined by evaluating the emission expressions at the selected operating point
. The ICEV emission corresponds to the constant emission factor
, while the EV emission is computed using the formulation in Equation (3). Fleet emission is calculated using the fleet-average expression given in Equation (4). All values are derived using the emission parameter listed in
Table 3 and the operating conditions defined in
Table 4. The comparison highlights the relative emission performance of each technology at the selected operating point.
Figure 8 is generated by evaluating the annual emission formulation as a function of renewable share
, while keeping the electrification share fixed at
. The annual emission is computed using the system-level formulation defined by Equation (9), based on the fleet emission intensity obtained from Equation (4).
The renewable share
is varied over its full range, and corresponding emission values are calculated using the parameters listed in
Table 3. The vertical reference dashed line indicates the selected operating point
, as defined in
Table 4. The vertical reference dashed line shown in
Figure 8 corresponds to the selected baseline renewable-share operating point
, as defined in
Table 4. This reference value represents the renewable-energy penetration adopted for the representative case-study scenario prior to optimization and sensitivity analysis. The dashed line therefore provides a graphical indication of the baseline planning condition relative to the complete renewable-share sensitivity range investigated in the study.
Figure 9 is obtained by evaluating the renewable energy requirement as a function of the renewable share
, for a fixed electrification level
. The required renewable capacity is computed from the energy balance formulation given by Equation (14), which relates the total electrified demand to the unavailable generation capacity.
The renewable share
is varied across its full range, and the corresponding required capacity is calculated using the system parameters defined in
Table 4. The vertical dashed reference line shown in
Figure 9 corresponds to the selected baseline renewable-share operating point
, while the horizontal dashed reference line represents the corresponding required renewable-generation capacity
necessary to sustain the selected electrification level under the adopted case-study assumptions. The intersection of these two dashed reference lines therefore identifies the baseline planning operating condition before optimization and sensitivity analysis. This graphical representation illustrates the direct relationship between renewable-energy penetration and the renewable-generation capacity required to support transport electrification.
The key observations from the above results are as follows:
Total system cost exhibits a convex shape with respect to r, reflecting the trade-off between the carbon taxation and renewable capital investment.
Renewable capacity requirement increases linearly with r.
Minimum cost operating region does not necessarily coincide with the minimum emission region.
The above findings highlight the importance of multi-objective optimization, as cost-optimal and emission-optimal solutions differ substantially. This insight aligned with integrated planning studies such as [
13,
15,
20].
Annual emission results obtained are identical because the effective renewable share equals the tested value
, meaning that all emission metrics are evaluated under the same operating condition. Consequently, the annual fleet emission (basic), annual fleet emission (total), and annual CO
2 emission using
have the same value of 1.796 kT per year. On the other hand, the energy demand and renewable sizing results are summarized in
Table 6.
The values reported in
Table 6 are obtained from the energy balance and renewable sizing formulation. EV electricity demand
is computed from the annual travel demand and electrification share using the energy consumption model using the annual EV energy demand relationship derived from fleet electrification demand. The target renewable energy
is then determined as a fraction of this demand based on the renewable share
.
The requested renewable capacity
is calculated using the relationship between annual energy and installed capacity given by Equation (14), which incorporates the capacity factor (CF). The renewable capacity used
corresponds to the available capacity under system limits, and the achieved renewable share
is obtained by comparing the actual renewable energy supplied to total EV energy demand. All values are evaluated at the operating point defined in
Table 4.
4.2.5. Sensitivity Analysis Results and Discussion
A comprehensive sensitivity analysis is conducted in this study to evaluate the robustness of the proposed analytical and optimization framework under variations in transport–energy system parameters, including grid carbon intensity, renewable energy penetration, charging efficiency, charging window duration, charging simultaneity, carbon taxation, and renewable energy investment cost. The results obtained are presented in
Figure 10.
Figure 10a demonstrates that the EV emission declines linearly with
, and the fleet emission exhibits diminishing returns at high
values due to residual ICEV and PHEV contributions. These trends confirm that electrification alone is insufficient without parallel decarbonization of the electricity supply, as emphasized in studies [
1,
4,
8]. The curve in
Figure 10a is generated by evaluating the emission formulations and functions of the renewable share
. The EV emission curve is obtained from the emission expression defined by Equation (2), while the fleet emission curve is computed using the fleet-average formulation in Equation (4), for a fixed electrification share
.
The ICEV emission level is represented as a constant reference corresponding to
, and the emission cap is introduced using the constraint defined in Equation (12). The renewable share
is varied over its full range, and the corresponding emission values are calculated using the parameters listed in
Table 3. The resulting plot illustrates the relative behavior of EVs, ICEVs, and fleet emissions under increasing renewable penetration. The horizontal dashed reference lines shown in
Figure 10a represent the ICEV emission level
, and the imposed emission-cap threshold
. These dashed reference lines provide graphical benchmarks for evaluating the reduction in EV and fleet-level emissions as renewable-energy penetration increases. Their intersections with the emission trajectories indicate the renewable-share conditions under which the corresponding electrification scenarios satisfy the imposed environmental constraints.
In terms of the sensitivity of the renewable cut-off threshold,
Figure 10b illustrates the sensitivity of the minimum renewable share threshold
to grid carbon intensity
under different charging efficiencies
. The results show that the renewable share required for EVs to achieve lower emissions than ICEVs increases substantially as grid carbon intensity increases. Under low-carbon electricity systems (
), the cut-off condition remains weakly restrictive even at moderate charging efficiencies. However, under carbon-intensive grids, the required renewable penetration rises rapidly.
The analysis further demonstrates that charging efficiency has a significant influence on electrification feasibility. Lower charging efficiency increases indirect EV emissions because additional electricity generation is required to compensate for charging losses. Consequently, the required renewable share threshold shifts upward as charging efficiency decreases. For example, at , the required renewable share exceeds approximately 0.37 for , while it decreases to approximately 0.26 for ideal charging conditions (). These results confirm that both grid decarbonization and charging efficiency improvement are essential for environmentally beneficial electrification under carbon-intensive electricity systems.
Figure 10c presents the variation in fleet emission intensity with renewable energy penetration under different grid carbon intensity scenarios. The results indicate that increasing renewable penetration consistently reduces fleet-level emissions across all electricity generation conditions. Under low-carbon grids (
), the fleet emission intensity remains below the imposed emission cap threshold over the entire renewable share range, indicating favorable electrification conditions. The horizontal dashed reference line shown in
Figure 10c represents the imposed fleet-emission cap
. This reference line provides a graphical indication of the admissible environmental boundary used to evaluate whether the fleet-emission trajectories under different grid carbon-intensity conditions satisfy the imposed emissions constraint. The intersections between the emission trajectories and the dashed cap line identify the minimum renewable-share levels required to maintain fleet emissions below the allowable threshold.
In contrast, highly carbon-intensive grids () with low renewable penetration produce fleet emissions substantially above the emission cap boundary. However, increasing renewable penetration progressively reduces the fleet emissions until convergence occurs near fully renewable charging conditions. The results therefore confirm that renewable energy deployment acts as a structural enabling condition for large-scale electrification and that electrification without simultaneous grid decarbonization may fail to produce meaningful emission reductions.
Figure 10d illustrates the variation in annual CO
2 emissions with electrification share for different renewable energy penetration levels. The results reveal that electrification alone does not guarantee substantial emission reduction when renewable penetration remains low. At
r = 0, increasing electrification produces only marginal emission reduction because EV charging remains strongly dependent on fossil fuel-based electricity generation. Conversely, under high renewable penetration (
r = 0.9), increasing electrification significantly reduces total annual emissions, demonstrating strong coupling between renewable deployment and electrification effectiveness. The analysis further indicates that the slope of the CO
2 reduction trajectory becomes steeper as renewable penetration increases, confirming that renewable energy integration amplifies the environmental benefit of electrification.
Figure 10e and
Figure 10f present the sensitivity of peak charging demand to charging window duration and charging coincidence factor, respectively.
Figure 10e shows that shorter charging windows substantially increase peak charging demand because the total charging energy becomes concentrated over shorter time intervals. For example, the peak charging load under a 4 h/day charging window is significantly larger than under a 10 h/day charging window for the same electrification share. These results demonstrate that charging coordination and load spreading can substantially improve grid feasibility without changing total annual electricity demand. Similarly,
Figure 10f indicates that charging simultaneity represented by the coincidence factor
strongly influences peak network loading. Highly synchronized charging behavior (
) produces substantially higher peak charging demand than coordinated charging behavior (
). The results therefore confirm that charging-management strategies and smart-charging coordination may significantly enlarge the feasible electrification region while reducing required grid reinforcement. The horizontal dashed reference lines shown in
Figure 10e,f represent the maximum admissible grid-capacity limit adopted in the charging-demand analysis. These reference boundaries are used to evaluate whether the peak EV charging demand associated with different charging-window durations and charging coincidence factors remains within the allowable network hosting capacity. In
Figure 10e, the intersections between the charging-demand trajectories and the dashed grid-capacity limit identify the maximum feasible electrification levels under different charging-duration scenarios. Similarly, in
Figure 10f, the intersections between the charging-demand curves and the dashed capacity boundary indicate the maximum feasible electrification share that can be supported under varying charging simultaneity conditions without exceeding the available grid hosting capacity.
Figure 10g illustrates the sensitivity of total annual system cost to renewable penetration under different carbon tax levels. The results indicate that higher carbon taxation shifts the economic operating region toward lower-emission electrification pathways. Under zero carbon taxation, the total system cost remains comparatively low because fossil fuel-intensive electricity and ICEV operation are not penalized economically. However, increasing carbon taxation progressively increases the economic attractiveness of renewable-supported charging and low-emission electrification scenarios. The analysis therefore confirms that carbon pricing can act as a strong economic driver for coordinated renewable energy deployment and transport electrification.
Figure 10h presents the influence of renewable energy capital expenditure on total annual system cost. The results indicate that higher renewable energy investment cost increases the economic burden associated with deep decarbonization pathways.
Nevertheless, despite increased renewable CAPEX, the system still benefits environmentally from higher renewable penetration because the emission reduction obtained from cleaner electricity generation compensates for the additional investment cost from a long-term sustainability perspective. The results therefore demonstrate the existence of an economic–environmental trade-off between renewable infrastructure investment and transport sector decarbonization.
Figure 11a,b summarize the global sensitivity response of annual CO
2 emissions and total system cost under multiple perturbation scenarios. The results show that high grid carbon intensity increases emissions significantly, low charging efficiency moderately increases emissions and operational cost, larger coincidence factors and shorter charging windows primarily affect grid feasibility rather than annual emissions, higher carbon taxation strongly increases total system cost while promoting low-emission operating regions, and higher renewable energy CAPEX increases the cost associated with deep decarbonization strategies.
Overall, the completed sensitivity analysis confirms that the proposed framework remains qualitatively robust under moderate parameter variations. However, the quantitative values of the renewable share threshold, admissible electrification region, peak charging demand, and Pareto-optimal operating points remain strongly dependent on regional grid conditions, renewable availability, charging behavior, and economic policy assumptions.
4.2.6. Optimization Results
Figure 12 presents the Pareto front obtained from Monte Carlo sampling of
. It graphically shows the Monte Carlo solution, solver-derived Pareto front, knee point solution and the user-defined operating point. The resulting Pareto frontier clearly illustrates the fundamental trade-off between annual CO
2 emissions and total system cost when electrification, renewable energy integration, and grid constraints are considered together. Solutions with lower emissions are generally associated with the higher system costs, while cost minimal solutions tend to exhibit higher carbon footprints, confirming the necessity of a multi-objective planning approach.
The Pareto-optimal solutions obtained should therefore be interpreted as planning-level optimal operating regions derived under representative average system conditions rather than exact time-resolved operational dispatch solutions.
Relative to the user-defined operating point, the Pareto-optimal knee point solution achieves substantial annual CO2 emission reduction while maintaining moderate total system cost increase within the admissible planning region. The minimum-emission operating region is associated with significantly higher renewable deployment and infrastructure investment requirements, whereas the minimum-cost region exhibits comparatively higher operational emissions and lower renewable penetration. These results quantitatively demonstrate the inherent trade-off between economic affordability, renewable energy integration, and transport sector decarbonization under coupled grid capacity constraints.
Wide dispersion of the non-dominated solution along the Pareto front indicates substantial flexibility in achieving feasible planning strategies, allowing policymakers to select solutions aligned with local priorities and constraints. In contrast, the user-defined operating point is frequently dominated by the Pareto-optimal solutions, revealing untapped improvement potential in commonly adopted electrification targets. Relative to the representative operating point , the identified knee point solution achieves approximately 34.2% lower annual CO2 emissions while requiring increased renewable energy deployment and moderate additional system cost. Conversely, the minimum-cost operating region exhibits lower renewable penetration and reduced infrastructure investment but significantly higher operational emissions. The minimum-emission operating region achieves the largest emission reduction but requires substantially higher renewable capacity allocation and associated capital expenditure, thereby illustrating the economic–environmental trade-offs inherent in large-scale transport electrification planning.
Compared to deterministic scenario-based analysis, the Monte Carlo approach captures uncertainty and diversity across the feasible solution space, leading to more robust planning insights. The integrated visualization in
Figure 11 provides a comprehensive decision support view. This unified representation facilitates benchmarking of existing strategies, identification of optimal and near-optimal solutions, and transparent communication of the cost emission trade-offs.
Figure 12 also indicates how the Pareto front obtained using the
gamultiobj solver compares to Monte Carlo sampling. The key observations are listed below:
The solver yields a smoother and denser Pareto front.
Extreme solutions correspond to minimum emission and minimum cost regime.
A knee point solution is clearly identifiable.
The identified knee point solution corresponding to renewable share r = 0.9832 represents a balanced transition operating condition where additional emission reductions beyond this point require disproportionately larger economic investment. The knee point therefore defines a practically attractive compromise between environmental performance and economic feasibility, making it particularly relevant for long-term transport–energy planning. In policy terms, this operating point suggests that substantial fleet decarbonization can be achieved through coordinated renewable deployment and partial electrification without necessarily requiring immediate full fleet electrification under carbon-intensive grid conditions.
The knee point solution presented in
Table 7 offers a practical balanced planning recommendation by achieving substantial emission reductions without disproportionate increases in the system cost. This solution is particularly relevant for policymakers seeking cost-effective decarbonization pathways.
The values reported in
Table 7 are obtained from multi-objective optimization process described in
Section 3.4.2. The optimization simultaneously minimizes annual CO
2 emissions and total system cost using the formulations defined in Equation (9) and the cost model. The Pareto front is generated using the Matlab generic algorithm solver
gamultiobj, where each solution represents a trade-off between emission and cost.
The knee point solution is selected from the Pareto front as the point providing the best compromise between the two objectives, corresponding to the region of maximum curvature. The associated decision variables, namely the electrification share and renewable share , are directly extracted from this solution, while the corresponding emission and cost values are computed using the system-level formulations. The reported values therefore represent the optimal balanced operating point identified by the algorithm.
Table 8 summarizes the optimization results. The summarized results are obtained from the multi-objective optimization procedure implemented using the Matlab genetic algorithm solver
gamultiobj. The problem is formulated using two decision variables, namely the electrification share
and the renewable share
, and two nonlinear inequality constraints responding to the emission cap and renewable capacity limits as defined by Equations (12)–(14).
The optimization is executed over the predefined number of generations, where each function evaluation corresponds to the computation of the objective functions, including annual CO2 emissions (see Equation (9)) and total system cost. The final average Pareto distance and spread quantify the convergence and diversity of the obtained Pareto front. The termination condition indicates that the algorithm stopped upon reaching the maximum number of generations, and the reported value reflects the final optimization performance.
4.2.7. Peak Charging Load and Grid Constraint Analysis
Figure 13 and
Figure 14 present the analyses of the impact of the charging behavior on grid peak load.
Figure 13 is generated by evaluating the peak charging load formulation as a function of the electrification share
for the different charging scenarios defined in
Table 2. The average EV charging power is computed using Equation (23), and the corresponding peak charging demand is obtained using Equation (24). Each curve corresponds to a particular charging scenario characterized by
and
. The colored solid lines represent the peak EV charging load as function of
, while the circular markers indicate the operating point
for each case. The variation across cases reflects the impact of charging duration and coincidence factors on peak demand.
Figure 14 is obtained by evaluating the peak EV charging load at the operating point
for each scenario defined in
Table 2. The peak load values are computed using the same formulation as in
Figure 13, based on Equations (23) and (24), and are compared against the corresponding grid capacity limits
.
In
Figure 13, for each case, the parameters
,
and
from
Table 2 are used to compute the corresponding peak charging curves. The blue circular markers connected by a solid line indicate the peak EV charging power evaluated at the operating point
for each case, whereas the red dashed line represents the maximum grid capacity limits for each scenario. The markers therefore highlight the operating condition, while the dashed line defines the system constraint.
The comparison of the above two figures illustrates whether the charging demand remains within grid constraints for each case, thereby validating the feasibility of the selected operating point under different charging durations and coincidence factors.
The results demonstrate the following:
Peak EV charging power scales linearly with the electrification share α.
Shorter charging windows and higher coincidence factors significantly increase peak demand.
Grid constraints impose strict upper bounds on allowable electrification levels.
Although the charging scenarios adopted in this study are based on representative planning-level charging behavior reported in the prior EV–grid integration literature, the resulting peak demand trends remain consistent with observed feeder-level hosting-capacity limitations reported in practical distribution network studies. The analysis therefore provides a scalable approximation of electrification-induced grid stress suitable for strategic planning assessment, while acknowledging that detailed feeder-specific studies would be required for operational deployment and localized infrastructure design. Future validation using feeder-level network datasets, chronological charging measurements, and distribution system power-flow simulations would further strengthen the applicability of the proposed framework under practical operational conditions.
The aforesaid multi-case analysis shows that the behavioral and operational factors such as charging duration and simultaneity can be as critical as total energy demand. This supports the findings in [
5,
16,
17].
While
Section 4.1 quantified system performance and trade-offs, the next section translates the findings into policy and planning implications, addressing how regulators and planners can operationalize the proposed framework.