Experimental Study on Variable Operating Characteristics of Two-Stage Absorption Lithium Bromide Refrigeration Chiller
Abstract
1. Introduction
2. Chiller Description
2.1. Configuration Design
2.2. Working Principle
2.3. Refrigeration Cycle and State Parameters
3. Experimental Setup
3.1. Testing Refrigeration Unit
3.2. Experimental Devices
3.3. Calculation Method
- Heating loadwhere Qheat is the heating load provided by the hot water tank-1; q1 is the mass flow rate of hot water; T1 is the inlet temperature of hot water; T2 is the outlet temperature of hot water; Cw is the specific heat of water, taken as 4.2 kJ/(kg.°C).
- Refrigeration capacitywhere Qrefri is the refrigeration capacity of the testing unit; q2 is the mass flow rate of chilled water; T3 is the inlet temperature of chilled water; T4 is the outlet temperature of chilled water.
- Heat dissipation capacitywhere Qdissi is the heat dissipation capacity of the testing unit; q3 is the mass flow rate of cooling water; T5 is the inlet temperature of cooling water; T6 is the outlet temperature of cooling water.
- Coefficient of performance
- Capacity ratiowhere φ is the capacity ratio of the testing unit; Qrefri-rated is the rated refrigeration capacity of the testing unit, defined as 10 kW; Qrefri-act is the actual refrigeration capacity of the testing unit in different conditions.
3.4. Operation Method
- Adjusting the driving heat source
- 2.
- Adjusting the circulation flow of the solution
- 3.
- Adjusting the cooling water
- 4.
- Adjusting the chilled water
3.5. Uncertainty
4. Results and Discussion
4.1. Experiment Case 1
4.2. Experiment Case 2
4.3. Comparative Analysis of Water Temperature Impact
4.4. Experiment Case 3
5. Conclusions
- The refrigeration capacity and COP will rise with the increase in the chilled water outlet temperature. For every 1 °C increase in the chilled water outlet temperature, the refrigeration capacity of the 10 kW chiller will increase 0.282 kW and its COP will raise 0.0071.
- The cooling water inlet temperature is negatively correlated with the refrigeration capacity and COP. For every 1 °C decrease in the cooling water inlet temperature, the refrigeration capacity will increase 0.366 kW and the COP will increase by 0.0055.
- An increase in hot water inlet temperature significantly enhances the refrigeration capacity, while its effect on COP remains insignificant. As the hot water inlet temperature increases by 1 °C, the refrigeration capacity will increase by 0.324 KW, while the COP remains almost unchanged.
- Increasing the hot water flow rate also improves refrigeration performance. Experimental data shows that a 10% increase in the mass flow rate of hot water results in an approximate 5% increase in refrigeration capacity and 1% improvement in COP. However, the flow rate should generally not exceed 130% of the design value, as higher rates may reduce the unit’s operational lifespan.
Author Contributions
Funding
Data Availability Statement
Acknowledgments
Conflicts of Interest
References
- Gkouletsos, D.; Hoppe, A.; Papadopoulos, A.I.; Kyriakides, A.S.; Seferlis, P.; Hassan, I. Techno-economic assessment of novel and conventional working fluid mixtures for two-stage double- and triple-effect absorption refrigeration systems. Int. J. Energy Res. 2021, 45, 12784–12805. [Google Scholar] [CrossRef]
- Al-Falahi, A.; Alobaid, F.; Epple, B. Thermo-economic comparisons of environmentally friendly solar assisted absorption air conditioning systems. Appl. Sci. 2021, 11, 2442. [Google Scholar] [CrossRef]
- Okwose, C.F.; Abid, M.; Ratlamwala, T.A.H. Performance analysis of compressor-assisted two-stage triple effect absorption refrigeration cycle for power and cooling. Energy Convers. Manag. 2021, 227, 113547. [Google Scholar] [CrossRef]
- Nikbakhti, R.; Wang, X.; Hussein, A.K.; Iranmanesh, A. Absorption cooling systems—Review of various techniques for energy performance enhancement. Alex. Eng. J. 2020, 59, 707–738. [Google Scholar] [CrossRef]
- Zhang, S.; Yu, W.; Wang, D.; Song, Q.; Zhou, S.; Li, J.; Li, Y. Thermodynamic characteristics of a novel solar single and double effect absorption refrigeration cycle. Energy 2024, 308, 132674. [Google Scholar] [CrossRef]
- Alhamid, M.I. Operation strategy of a solar-gas fired single/double effect absorption chiller for space cooling in Indonesia. Appl. Therm. Eng. 2020, 178, 115524. [Google Scholar] [CrossRef]
- Zhou, L.; Li, X.; Zhao, Y.; Dai, Y. Performance assessment of a single/double hybrid effect absorption cooling system driven by linear Fresnel solar collectors with latent thermal storage. Sol. Energy 2017, 151, 82–94. [Google Scholar] [CrossRef]
- Bataineh, K.; Taamneh, Y. Review and recent improvements of solar sorption cooling systems. Energy Build. 2016, 128, 22–37. [Google Scholar] [CrossRef]
- Shirazi, A.; Taylor, R.A.; Morrison, G.L.; White, S.D. A comprehensive, multiobjective optimization of solar-powered absorption chiller systems for airconditioning applications. Energy Convers. Manag. 2017, 132, 281–306. [Google Scholar] [CrossRef]
- Bellos, E.; Tzivanidis, C. Energetic and financial analysis of solar cooling systems with single effect absorption chiller in various climates. Appl. Therm. Eng. 2017, 126, 809–821. [Google Scholar] [CrossRef]
- Sheikhani, H.; Barzegarian, R.; Heydari, A.; Kianifar, A.; Kasaeian, A.; Grof, G.; Mahian, O. A review of solar absorption cooling systems combined with various auxiliary energy devices. J. Therm. Anal. Calorim. 2018, 4, 2197–2212. [Google Scholar] [CrossRef]
- Shirazi, A.T.; Morrison Robert, A.; White Graham, L.; Stephen, D. Solar-powered absorption chillers: A comprehensive and critical review. Energy Convers. Manag. 2018, 171, 59–81. [Google Scholar] [CrossRef]
- Xu, Z.Y.; Wang, R.Z. Simulation of solar cooling system based on variable effect LiBr-water absorption chiller. Renew Energ. 2017, 113, 907–914. [Google Scholar] [CrossRef]
- Huang, B.; Leng, C.; Zhao, J. Low carbon optimized scheduling and operation of combined cooling, heating and power generation energy considering uncertainty. Power Syst. Big Data 2025, 28, 1–9. [Google Scholar] [CrossRef]
- Liu, M.; Cheng, Y.; Cheng, W.; Zhan, C. Dynamic performance analysis of a solar driving absorption chiller integrated with absorption thermal energy storage. Energy Convers. Manag. 2021, 247, 114769. [Google Scholar] [CrossRef]
- Khana, M.S.A.; Badarb, A.W.; Talhaa, T.; Khan, M.W.; Butt, F.S. Configuration based modeling and performance analysis of single effect solar absorption cooling system in TRNSYS. Energy Convers. Manag. 2018, 157, 351–363. [Google Scholar] [CrossRef]
- Zheng, X.; Shi, R.; Wang, Y.; You, S.; Zhang, H.; Xia, J.; Wei, S. Mathematical modeling and performance analysis of an integrated solar heating and cooling system driven by parabolic trough collector and double-effect absorption chiller. Energy Build. 2020, 202, 109400. [Google Scholar] [CrossRef]
- Kyriakides, A.S.; Papadopoulos, A.I.; Seferlis, P.; Hassan, I. Dynamic modelling and control of single, double and triple effect absorption refrigeration cycles. Energy 2020, 210, 118529. [Google Scholar] [CrossRef]
- Goyal, A.; Garimella, S. Multivariable feedback control of small-capacity ammonia-water absorption systems. Energy Convers. Manag. 2019, 191, 159–173. [Google Scholar] [CrossRef]
- Goyal, A.; Rattner, A.S.; Garimella, S. Model-based feedback control of an ammonia-water absorption chiller. Sci. Technol. Built Environ. 2015, 21, 357–364. [Google Scholar] [CrossRef]
- Evola, G.; Le Pierrès, N.; Marletta, L. Simulation of a low capacity absorption cooling system for indoor air-conditioning. Int. J. Heat Technol. 2015, 33, 203–210. [Google Scholar] [CrossRef]
- Xu, Y.; Zhang, S.; Xiao, Y. Modeling the dynamic simulation and control of a single effect LiBr–H2O absorption chiller. Appl. Therm. Eng. 2016, 107, 1183–1191. [Google Scholar] [CrossRef]
- Zhao, S.; Li, X.; Wang, L.; Chang, M. State-space model development and dynamic performance simulation of solar-powered single-effect LiBr-H2O absorption chiller. Renew. Energy 2025, 241, 122327. [Google Scholar] [CrossRef]
- Delač, B.; Pavković, B.; Lenić, K. Design, monitoring and dynamic model development of a solar heating and cooling system. Appl. Therm. Eng. 2018, 142, 489–501. [Google Scholar] [CrossRef]
- Xu, Z.Y.; Wang, R.Z. Comparison of CPC driven solar absorption cooling systems with single, double and variable effect absorption chillers. Sol. Energy 2017, 158, 511–519. [Google Scholar] [CrossRef]
- Kuyatt, T. Guidelines for Evaluating and Expressing the Uncertainty of NIST Measurement Results; NIST TN 1297; National Institute of Standards and Technology: Gaithersburg, MD, USA, 1994. [Google Scholar]











| Status Point | Fluid and Position | Concentration (ω) % | Specific Enthalpy (h) kJ/Kg |
|---|---|---|---|
| 1 | Water in evaporator | 0 | 447 |
| 1′ | Vapor in evaporator | 0 | 2927 |
| 2 | Li-Br solution at outlet of low-pressure absorber | 57 | 275 |
| 2′ | Li-Br solution at outlet of high-pressure absorber | 46 | 311 |
| 3 | Water in condenser | 0 | 581 |
| 3′ | Vapor in condenser | 0 | 2985 |
| 3″ | Vapor in low-pressure generator | 0 | 2951 |
| 4 | Li-Br solution at outlet of high-pressure generator | 50 | 347 |
| 4′ | Li-Br solution at outlet of low-pressure generator | 60.5 | 322 |
| 5 | Li-Br solution at inlet of high-pressure generator | 46 | 353 |
| 5′ | Li-Br solution at inlet of low-pressure generator | 57 | 309 |
| 6 | Li-Br solution at inlet of low-pressure absorber | 60.5 | 298 |
| 6′ | Li-Br solution at inlet of high-pressure absorber | 50 | 315 |
| Design Parameters | Values |
|---|---|
| Rated refrigeration capacity (kW) | 10 |
| Inlet temperature of chilled water (°C) | 12 |
| Outlet temperature of chilled water (°C) | 7 |
| Mass flow of chilled water (kg/s) | 0.472 |
| Inlet temperature of cooling water (°C) | 30 |
| Outlet temperature of cooling water (°C) | 36 |
| Mass flow of cooling water (kg/s) | 1.388 |
| Inlet temperature of hot water (°C) | 75 |
| Outlet temperature of hot water (°C) | 63 |
| Mass flow of hot water (kg/s) | 0.611 |
| Name | Main Parameter | Notes |
|---|---|---|
| Two-stage Li-Br absorption refrigeration unit | Rated refrigeration capacity: 10 kW | See Table 1 for details |
| Air-cooled chiller | Refrigeration capacity: 40 kW Water temperature range: 5~20 °C Control accuracy: ±1 °C | |
| Hot water tank 1 | Heating power: 25 kW Water temperature range: 40~99 °C Control accuracy: ±0.5 °C | |
| Hot water tank 2 | Heating power:10 kW Temperature range: 40~99 °C Control accuracy: ±0.5 °C | |
| Heat exchanger 1 | Rated heat exchange: 10 kW | |
| Heat exchanger 2 | Rated heat exchange: 35 kW | |
| Temperature sensor | Temperature measuring range: −200~260 °C Measurement accuracy: ±0.1 °C | Type: K-type thermocouple |
| Flow meters | Maximum fluid temperature: 120 °C Flow measuring range: 0~100 m3/h Measurement accuracy: ±0.5% |
| No. | Parameters | Symbol | Unit | Uncertainty |
|---|---|---|---|---|
| 1 | Temperature | T | °C | ±0.06 °C |
| 2 | Mass flow rate | q | kg/s | ±0.3% |
| 3 | Heating load | Qheat | kW | ±0.4% |
| 4 | Refrigeration capacity | Qrefri | kW | ±0.4% |
| 5 | Heat dissipation capacity | Qdissi | kW | ±0.4% |
| 6 | Coefficient of performance | COP | ±0.5% | |
| 7 | Capacity ratio | φ | ±0.6% |
| Constant Parameters | Values | Variable Parameters | Values |
|---|---|---|---|
| T2 (°C) | 58 | T1 (°C) | 70, 71, 72, 73, 74, 75, 76, 77, 78, 79, 80 |
| T4 (°C) | 6 | T5 (°C) | 28, 29, 30, 31, 32, 33 |
| T3–T4 | 5 | ||
| T6–T5 | 6 |
| Constant Parameters | Values | Variable Parameters | Values |
|---|---|---|---|
| T1 (°C) | 75 | T4 (°C) | 6, 7, 8, 9, 10, 11, 12, 13 |
| T2 (°C) | 63 | T5 (°C) | 28, 29, 30, 31, 32, 33 |
| T3–T4 | 5 | ||
| T6–T5 | 6 |
| Constant Parameters | Values | Variable Parameters | Values |
|---|---|---|---|
| T1 (°C) | 75 | q1 (kg/s) | 0.44, 0.48, 0.52, 0.56, 0.6, 0.64, 0.68, 0.72, 0.74, 0.78, 0.82 |
| T3 (°C) | 12 | q2 (kg/s) | Not applicable |
| T4 (°C) | 7 | Q3 (kg/s) | Not applicable |
| T5 (°C) | 30 | ||
| T6 (°C) | 36 |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Share and Cite
Chen, B.; Fang, C.; Xiong, B.; Lu, Z.; Yao, Y. Experimental Study on Variable Operating Characteristics of Two-Stage Absorption Lithium Bromide Refrigeration Chiller. Energies 2026, 19, 401. https://doi.org/10.3390/en19020401
Chen B, Fang C, Xiong B, Lu Z, Yao Y. Experimental Study on Variable Operating Characteristics of Two-Stage Absorption Lithium Bromide Refrigeration Chiller. Energies. 2026; 19(2):401. https://doi.org/10.3390/en19020401
Chicago/Turabian StyleChen, Bingbing, Chaohe Fang, Bo Xiong, Zhenneng Lu, and Yuan Yao. 2026. "Experimental Study on Variable Operating Characteristics of Two-Stage Absorption Lithium Bromide Refrigeration Chiller" Energies 19, no. 2: 401. https://doi.org/10.3390/en19020401
APA StyleChen, B., Fang, C., Xiong, B., Lu, Z., & Yao, Y. (2026). Experimental Study on Variable Operating Characteristics of Two-Stage Absorption Lithium Bromide Refrigeration Chiller. Energies, 19(2), 401. https://doi.org/10.3390/en19020401

