1. Introduction
Industrial steam is widely used for drying, evaporation, sterilization and chemical processing, and its production is, therefore, an important application for electrification in industrial heating [
1,
2,
3]. Heat pumps offer a means of recovering low-temperature heat for steam production by using electrical work to increase the temperature at which heat is supplied. When steam is required near 300 °C, however, the large temperature lift places demanding operating conditions on the refrigerant, compressor and heat exchangers, while the associated power consumption determines whether the process uses electricity efficiently. Evaluating a heat pump for this application, therefore, requires consideration of the delivered steam temperature and flow together with the electrical power input, rather than the compressor discharge temperature alone [
2,
4].
Heat-pump steam generation generally involves either heating pressurized water before flashing or combining a heat pump with additional steam compression [
3,
5,
6,
7,
8]. The first arrangement avoids a steam compressor, although the steam conditions that it can achieve depend on the refrigerant temperature and the temperature differences available in the heat exchangers; the second arrangement uses additional compression work to increase steam pressure and temperature. For example, Kang et al. [
5] investigated a steam-generating heat pump with an internal heat exchanger at approximately 120 °C, whereas hybrid systems produce steam at higher temperatures by compressing the steam generated using the heat pump [
7,
8]. Since these studies use different heat-source temperatures, steam conditions and definitions of electrical power input,
Table 1 compares their configurations and operating conditions without ranking their reported COP values as if they were obtained under identical conditions.
Above its critical pressure, CO
2 releases heat over a continuous temperature range, so the high-temperature part of its cooling process can be used for steam superheating and the remaining heat for pressurized water heating. Li et al. [
9] used this arrangement with internal recuperation to investigate steam generation near 300 °C from an ambient heat source; their configuration, including the two gas coolers and recuperative heating before compression, is adopted in the present study. Related research has considered data-center heat recovery combined with steam compression [
10] and heat-pump technologies above 250 °C [
4], while transcritical heat-exchanger calculations [
11] address the temperature differences that constrain heat transfer within these systems. At the component level, studies of internal heat exchangers and mechanical subcooling [
12,
13,
14] examine how cycle modifications affect performance, and advanced exergy analysis [
15] identifies the processes responsible for thermodynamic losses. Direct steam-generation experiments [
16] provide a further basis for evaluating the performance of operating equipment. These studies establish the configurations and analysis methods relevant to high-temperature steam generation, although the heat-source conditions must be specified before their application to CAES heat recovery can be assessed.
For a heat pump supplied with industrial cooling water, the recoverable heat is determined by both the water flow and its supply and return temperatures. These quantities specify the heat available to the evaporator and the temperature differences between the source water and CO2, which must remain sufficient throughout heat transfer. An ambient-air source requires a different evaporator design and varies with weather; consequently, a comparison between cooling-water and air-source systems would need consistent CO2-cycle assumptions and identical steam-delivery conditions to isolate the effect of the heat source.
CAES charging provides a potential cooling-water heat source because the air must be cooled between compression stages and before entering storage [
17,
18,
19,
20,
21]. Research on CAES heat recovery has primarily considered storing higher-temperature compression heat for discharge or using it in a power cycle [
17,
18,
19,
20,
21], whereas the use of lower-temperature cooling water for steam generation above 300 °C has received less attention. Meanwhile, studies of transcritical CO
2 steam generation have examined cycle configurations under heat-source conditions that differ from those of a CAES charging process [
4,
9,
10]. Applying such a cycle to CAES, therefore, requires quantifying the recoverable cooling-water heat and determining how it is transferred through the evaporator, recuperator and gas coolers to produce steam at the required conditions.
This study evaluates a recuperated transcritical CO
2 heat pump supplied by the low-temperature cooling-water circuit of a CAES plant, using the staged water-heating and steam-superheating configuration proposed by Li et al. [
9]. The steam circuit includes a flash separator, a recycle pump and a mixer, through which the separated saturated liquid is returned to the water heater together with pressurized make-up water. With this configuration, a steady-state model is used to calculate steam production, electrical power consumption and COP, while temperature profiles and component exergy balances are evaluated to identify heat-transfer constraints and the principal sources of irreversibility. The parametric analysis then examines how compressor suction temperature, discharge pressure, make-up water temperature and circulating-water flow affect heat distribution, compressor and expander powers, and the temperature and flow of the delivered steam. In this way, the study assesses the use of low-temperature CAES heat for industrial steam generation and explains why operating conditions that increase CO
2 discharge temperature do not necessarily improve COP or steam delivery temperature.
The reported COP values use different heat-source temperatures, steam conditions and definitions of power input, and, therefore, should not be compared as efficiencies under identical conditions. The examples from Refs. [
5,
7,
8] are also discussed in Ref. [
9]. For the present cycle, pumping is excluded and the expander power is subtracted from the compressor power.
Table 1.
Representative pathways for heat-pump steam generation.
Table 1.
Representative pathways for heat-pump steam generation.
| Route/Study | Source (°C) | Steam (°C) | Pressure (MPa) | COP | Steam Compressor |
|---|
| IHX heat pump [5,9] | Not specified in this comparison | 120 | Saturated steam | 3.24 | No |
| Heat pump + steam compression [7,9] | Ambient 5–35 | 120 to >160 | Different delivery cases | Different power-input definitions | Yes |
| Waste-heat hybrid [8,9] | 60–80 | 160 | Source-specific | 3.1 (R601) | Yes |
| Staged CO2 cycle [9] | Ambient air | About 300 | 0.10–0.70 investigated | Up to 1.85, configuration-specific | No |
| CAES-coupled baseline | Water 50→25 | 303.33 | 0.40 | 1.533 (pumps excluded) | No |
3. Results and Discussion
3.1. Baseline Thermodynamic Performance
At the baseline, gas coolers A and B supply a combined 31.96 MW, while the compressor consumes 23.42 MW and the expander produces 2.57 MW, producing a net cycle power input of 20.85 MW and a COP of 1.533. Under these conditions, the system produces 10.79 kg s−1 of steam at 303.33 °C and 0.40 MPa, with an equal make-up water flow replacing the steam delivered to the user. The remaining 26.21 kg s−1 of the separated liquid is recycled and mixed with the make-up water, raising the water-heater inlet temperature to 110.00 °C and making the total circulating-water flow 3.43 times the steam flow. Most of the water heated in gas cooler B, thus, remains in the circuit, retaining the sensible heat of the separated liquid for the next heating process.
Including mechanical losses of approximately 0.468 MW in the compressor and 0.052 MW in the expander, the difference between the CO2-cycle energy input and output is approximately 0.009 MW, equivalent to 0.029% of the total gas-cooler duty. Independent REFPROP calculations also give water-side heat-transfer rates of 3.600 and 28.357 MW for gas coolers A and B, respectively, which agree with the Aspen results to the reported precision. For the mixer, the combined enthalpy flow of make-up water and recycled liquid differs from that of the mixed stream by less than 0.001 MW; the difference between the enthalpy flow entering the water throttling valve and the combined steam and liquid enthalpy flows leaving the separator is likewise below 0.001 MW. These comparisons support the consistency of the reported states with the cycle and water-circuit energy balances.
Gas cooler B supplies 88.7% of the total heating duty because it heats the entire 37 kg s
−1 circulating-water stream, whereas gas cooler A supplies the remaining 11.3% to the separated steam. At the specified water flow and separator pressure, the heat transferred in gas cooler B determines the water enthalpy before throttling and, hence, the amount of steam generated, while the approximately 334 kJ kg
−1 transferred in gas cooler A determines the subsequent steam-temperature increase. In addition to these external heating duties, the recuperator transfers 8.19 MW between the high- and low-pressure CO
2 streams, equivalent to 25.6% of the total gas-cooler duty. Since this heat is transferred internally rather than supplied from an additional source, the effect of recuperation on COP depends on the associated changes in compressor and expander powers, which are examined in
Section 3.2.
3.2. Effects of Compressor Suction Temperature and Discharge Pressure
Increasing compressor suction temperature from 94.5 to 100.5 °C raises discharge temperature from 336.21 to 344.02 °C, as shown in
Figure 6a–c, while the required recuperator duty increases from 5.57 to 11.28 MW. This additional heat is supplied by the high-pressure CO
2, whose recuperator outlet temperature decreases from 104.00 to 79.20 °C, thereby reducing the energy available for recovery in the expander. Over the same range, compressor power increases from 23.21 to 23.65 MW and expander power decreases from 2.90 to 2.25 MW, so the net power input rises by 5.4%, compared with a 3.3% increase in heating duty. COP, therefore, decreases from 1.550 to 1.520, demonstrating that the increase in discharge temperature obtained through stronger recuperation is accompanied by a greater proportional increase in electrical power consumption than in useful heat output.
Steam flow increases from 10.61 to 11.00 kg s
−1 over this suction-temperature range, although steam delivery temperature decreases from 306.06 to 300.19 °C. Because the superheater duty is fixed at 3.60 MW, the additional steam receives less heat per kilogram, which explains why the steam temperature falls even as the CO
2 discharge temperature rises. The evaporator temperature difference also decreases as the suction temperature is reduced: at 94.5 °C suction, the CO
2 outlet temperature is 45.93 °C, producing a terminal difference of 4.07 K from the 50 °C source-water inlet. Although this value is below the 5 K reference, a positive temperature difference of approximately 4 K can still support heat transfer if sufficient heat-transfer area is provided. The 94.5 °C case is, therefore, retained in the thermodynamic analysis and identified by an open square in
Figure 6, while the other four cases exceed 5 K at both evaporator terminals. Because the present analysis examines thermodynamic potential rather than selecting exchanger dimensions, retaining this case does not imply that a particular exchanger design has been demonstrated.
Increasing compressor discharge pressure from 25.6 to 26.4 MPa also increases both the heating duty and net power input, as shown in
Figure 6d–f. Although the discharge temperature rises by 4.38 K and the total heating duty increases from 31.58 to 32.33 MW, the larger proportional increase in net power input, from 20.46 to 21.21 MW, reduces COP from 1.543 to 1.524. The additional heat supplied to the water circuit increases steam production from 10.65 to 10.93 kg s
−1; however, the fixed superheater duty then supplies less heat per kilogram, lowering steam delivery temperature by 4.28 K. Within the investigated pressure range, a higher discharge pressure, therefore, increases steam production at the expense of COP and steam temperature, so its selection requires considering the required steam flow and temperature together.
3.3. Effects of Make-Up Water Temperature and Circulating-Water Flow
The water-side cases retain the baseline CO
2 states and approximately the same gas-cooler duties, so
Figure 7 shows how water temperature and circulation affect steam production without changing the CO
2-cycle conditions. Increasing the make-up water temperature from 16 to 24 °C raises the mixed-water inlet temperature from 109.09 to 110.93 °C and the gas-cooler-B outlet temperature from 278.56 to 280.03 °C. The higher outlet-water enthalpy increases the fraction converted to steam at the fixed separator pressure, raising steam flow from approximately 10.72 to 10.86 kg s
−1. Since the superheater still supplies 3.60 MW, however, the heat supplied per kilogram of steam decreases and the delivery temperature falls by 2.03 K. Thus, under the specified gas-cooler duties, preheating the make-up water increases steam production rather than the final steam temperature.
Increasing the total circulating-water flow from 36 to 52 kg s−1 changes steam production by only approximately 0.05 kg s−1, while the flash fraction decreases from 29.97% to 20.85%. Most of the additional water, therefore, remains liquid after flashing and returns to the water heater. As approximately the same gas-cooler-B duty is distributed over a larger mass flow, the enthalpy increase per kilogram decreases and the outlet temperature falls from 282.50 to 243.77 °C. The greater proportion of hot recycled liquid also raises the mixed-water inlet temperature from 108.98 to 120.45 °C, so the temperature rise across the heater becomes smaller. A higher circulation rate, consequently, increases the degree of subcooling at the heater outlet but provides little additional steam, indicating that circulation should be selected with regard to the liquid state before throttling and the temperature differences within the heater.
Water pressure and circulation affect the liquid state through different mechanisms, since higher pressure raises the saturation temperature, whereas higher flow reduces the enthalpy increase per kilogram at a fixed heating duty. At an outlet pressure of 6.98 MPa, the lowest-flow case of 36 kg s−1 reaches 282.50 °C and remains approximately 3.14 K below saturation; the larger flows provide greater subcooling without a comparable increase in steam production. To check the relationship between water heating and flashing, the separated steam flow is also calculated from the water enthalpy before throttling and the saturated-state enthalpies at the separator pressure. Using independent REFPROP properties, this calculation agrees with the reported steam flows within 0.005 kg s−1 for all 20 cases.
3.4. Heat-Exchanger Temperature Differences and Exergy Destruction
The baseline profiles in
Figure 5 identify a minimum temperature difference of approximately 12 K inside gas cooler B, at about 18 MW of cumulative heat transfer, or approximately three-fifths of the total duty. This value is smaller than the terminal differences of 33.58 and 20.00 K because the temperatures of high-pressure CO
2 and liquid water change at different rates along the exchanger. A check based only on the terminal temperatures would, therefore, overestimate the smallest temperature difference available for heat transfer, even when the total duty satisfies the overall energy balance. Gas cooler B, thus, requires an internal temperature-profile assessment in addition to the inlet and outlet state calculations.
Gas cooler A and the recuperator differ from gas cooler B in that their smallest displayed temperature differences occur at the hot-inlet/cold-outlet end, with values of 36.44 and 32.50 K, respectively. All displayed points in the three baseline profiles, therefore, exceed the 5 K reference value. For the parameter cases, the evaporator checks are based on terminal temperatures, whereas the internal temperature profiles of the gas coolers and recuperator are evaluated for the baseline.
Non-isentropic compression accounts for approximately 27.0% of the estimated total exergy destruction of 12.81 MW, followed by the water throttling valve and flash separator at 18.7% and the CO
2 valve at 17.1%, as shown in
Figure 8. The compressor requires more work than an isentropic process, whereas the valves reduce pressure without recovering work; improving compressor efficiency and reducing throttling losses, therefore, address different sources of irreversibility. Changes to the water- or CO
2-pressure levels would, nevertheless, need to preserve the required steam-generation conditions and the single-phase expander outlet. The recuperator, which accounts for approximately 7.7% of total exergy destruction, also affects the work of both machines, as demonstrated by the suction-temperature analysis in
Section 3.2. Its performance must, consequently, be assessed through the resulting cycle power consumption, as well as the exergy destroyed within the exchanger itself.
Although the source water releases 11.64 MW of heat, its temperature is close to the 25 °C reference environment, resulting in a thermal exergy decrease of only approximately 0.46 MW. Electrical work, consequently, provides most of the total exergy input of 21.56 MW, which includes compressor power minus expander power, recycle-pump power and the source-water exergy decrease. The net increase in exergy from make-up water to delivered steam is approximately 8.76 MW, corresponding to an exergy efficiency of 40.6%. Since source-water pumping and make-up water pressurization are excluded, a comparison with another system would require the same treatment of auxiliary electricity and identical steam-delivery conditions.
5. Conclusions
This study evaluates the use of low-temperature CAES cooling water in a recuperated CO2 heat pump for industrial steam generation near 300 °C. The steady-state calculations lead to the following findings:
Cooling water supplied at 50 °C and returned at 25 °C provides 11.64 MW, equivalent to 12.8% of the CAES cooling duty. With saturated-liquid recycling, the baseline produces 10.79 kg s−1 of steam at 0.40 MPa and 303.33 °C and supplies 31.96 MW of heat, giving a COP of 1.533 at a net cycle power input of 20.85 MW, excluding pumping. The water-heater outlet remains 6.35 K below saturation and the CO2 expander outlet remains single-phase, so water flashing and formation of the two-phase CO2 mixture occur in their respective downstream throttling processes.
Increasing compressor suction temperature from 94.5 to 100.5 °C raises discharge temperature by 7.81 K but reduces COP from 1.550 to 1.520, because net power input increases proportionally more than heating duty as compressor power rises and expander power falls. Although steam production increases, the fixed superheater duty supplies less heat per kilogram, causing steam delivery temperature to decrease despite the higher CO2 discharge temperature. Recuperation must, therefore, be evaluated by its combined effects on heat output and machine powers, rather than the discharge-temperature increase alone.
An increase in the discharge pressure from 25.6 to 26.4 MPa increases steam production but reduces COP, from 1.543 to 1.524, and lowers the steam temperature by 4.28 K at the fixed superheater duty. In the separate water-circulation analysis, increasing the flow from 36 to 52 kg s−1 reduces the flash fraction from 29.97% to 20.85% while producing only approximately 0.05 kg s−1 of additional steam. Since most of the additional circulating water is recycled as liquid, circulation should be selected to maintain subcooled heating and sufficient heat-transfer temperature differences rather than increased solely to raise steam output.
All displayed points in the three baseline counterflow profiles exceed the 5 K reference value, although the internal minimum of approximately 12 K in gas cooler B is smaller than either terminal temperature difference. Compression and water throttling with flash separation account for approximately 27.0% and 18.7% of total exergy destruction, respectively, identifying compressor efficiency and pressure reduction as important considerations alongside heat-exchanger temperature matching. Together, these results support the thermodynamic assessment of CAES waste-heat recovery for industrial steam generation, while equipment testing and dynamic validation remain necessary before implementation.