1. Introduction
According to the Statistical Office of the Republic of Slovenia (SURS) [
1], households’ final energy consumption in 2024 was 12,016 GWh, representing 22% of the country’s total final energy consumption. A total of 59% (7032 GWh) of the final energy in households is used for space heating, with biomass being the most widespread source at 49%, followed by extra-light fuel oil at 13%, electricity at 11%, natural gas at 9%, district heat at 9%, and ambient heat at 8%. The share of the latter has been growing steadily since 2012, when it was 1%.
A heat pump is a device that utilises ambient heat with additional work in the form of electricity to satisfy heating demand. Heat pumps can utilise heat from ambient air, water, or the ground. According to the European Commission’s climate target, nearly 60 million heat pumps are expected to be installed in the EU by 2030 [
2]. However, air-source heat pumps (ASHPs) exhibit reduced efficiency and thermal output at low outdoor air temperatures, precisely when heating demand peaks. Moreover, real operational data from Central Europe indicate that 17% of ASHPs do not meet existing efficiency standards, and approximately 10% of the systems are oversized [
3].
Figure 1 illustrates the yearly distribution of outdoor air temperature at a specific location, indicating how many days per year the daily mean air temperature is at or below a given value. The area between this curve and the effective indoor temperature represents heating degree days (
), measured in K day. A heating system can consist of a single unit that independently supplies the heating load (
Figure 1a), operating in monovalent mode. However, a bivalent heating system includes both a primary and an auxiliary unit. The auxiliary unit can provide the entire heating load below certain outdoor air temperatures in bivalent alternate operation (
Figure 1b), or it can supply part of the heating load in bivalent parallel operation (
Figure 1c).
A heat pump in a bivalent heating system, often referred to as a hybrid heat pump (HHP), can be supported by various auxiliary heating systems, including solar thermal collectors [
4], hybrid photovoltaic–thermal solar collectors [
5], district heating [
6], biomass boilers [
7], and, most commonly, a condensing gas boiler. HHPs provide substantial value in cold climates by reducing peak electricity costs [
8] and can contribute to the energy flexibility of a building by enabling load shifting from the heat pump to the auxiliary unit in response to grid necessity [
9]. Alternatively, dual-source heat pumps can combine two renewable heat sources, such as outdoor air and ground, to improve operational flexibility and overcome limitations associated with a single heat source [
10].
Systems supported by a condensing gas boiler have been most widely studied numerically in various contexts, including single-family houses [
11,
12,
13,
14,
15,
16], multi-family buildings [
17,
18], and office/commercial buildings [
19]. The primary objective in most research has been to evaluate reductions in primary energy consumption, operating costs, and greenhouse gas (GHG) emissions compared to conventional condensing gas boilers. For sensitivity analysis, parameters such as system configurations, climatic conditions, control strategies, electricity generation carbon intensity, and energy prices are typically considered.
Numerical analysis of bivalent parallel–alternate operation of an ASHP and a gas boiler was conducted by Klein et al. [
11] for both unrenovated (389 W/K) and renovated (222 W/K) single-family buildings in Germany. Their study concluded that a HHP can reduce primary energy consumption by up to 12% in unrenovated buildings and 26% in renovated buildings when an undersized heat pump is used, compared to heating exclusively with a condensing gas boiler.
Bonomolo et al. [
12] analysed the impact of different climatic conditions on the environmental and economic performance of a HHP operating in parallel–alternate mode. They proposed a control strategy based on a
threshold below which the gas boiler is activated. In a mild climate (Palermo), a monovalent heat pump reduced CO
2 emissions by 40% compared to a gas boiler, while in a moderate climate (Milano), a 25% reduction was achieved with a HHP and a
switching threshold of 2.3. Similarly, Tihana et al. [
13] investigated the operation of a HHP supported by a gas boiler under economic and ecological control strategies, demonstrating that the preferred heat source and switching conditions depend on energy prices and the CO
2 emission intensity of electricity production.
Di Perna et al. [
14] experimentally evaluated the
of an ASHP as a function of outdoor air temperature and humidity to account for the
reduction caused by defrosting, as well as the efficiency of a condensing gas boiler at different heat loads, in their numerical study of a HHP.
Research by Saffari et al. [
15] indicates that HHPs and monovalent ASHPs significantly improve efficiency over conventional boilers, with HHPs achieving slightly higher primary energy savings (50–72%) than monovalent ASHPs (45–70%). In deep retrofit scenarios, HHP systems reduced the carbon footprint by 74%, compared to 68% for monovalent ASHPs. While full building retrofits did not yield a positive 20-year net present value, both heat pump types offered positive returns on investment when installed alongside thermal upgrades. HHP systems generally provide lower operating costs by leveraging gas under low ambient temperatures to avoid reduced electrical efficiency and high electricity costs.
GHG emissions associated with heating a theoretical house with an ASHP under three different operating modes (monovalent, bivalent parallel, and bivalent alternate) and using three different auxiliary energy types (natural gas, biomass, and an electric heater) were numerically analysed by Buday [
16]. Three different fixed carbon intensities of electricity production (307.5 g CO
2 eq./kWh, 35.6 g CO
2 eq./kWh, and 861.1 g CO
2 eq./kWh) were considered. They showed that with low and moderate carbon intensity of electricity production, all operating modes reduced GHG emissions compared to gas combustion, while for high electricity emission factors, heating provided by the gas boiler resulted in lower GHG emissions.
A comparative analysis of residential hybrid heat pumps in Italy and Spain [
20] revealed that their economic and environmental effectiveness is highly dependent on national energy prices and the electricity generation mix. In Spain, HHP systems can achieve operational cost savings of up to 50% and carbon emission reductions of up to 60% compared to a condensing boiler alone. In Italy, these benefits are more modest: limited to 20% for costs and 30% for emissions. That study also warned about the importance of heat pump size. To maintain high seasonal performance, the system should operate as much as possible at high capacity ratios, even if this means reducing the share of the heating load provided by the ASHP.
Beccali et al. [
21] reviewed 38 case studies involving hybrid heat pumps assisted by natural gas boilers published between 2016 and 2022. They identified two primary control strategies: rule-based control (RBC) and model predictive control (MPC). Both strategies were used equally often in the studied cases. RBC is simpler to implement but offers limited flexibility, while MPC offers greater optimisation potential at the cost of increased computational and hardware complexity. The choice of strategy depends on several factors, including climatic conditions (e.g., outdoor air temperature), local energy tariffs, signal processing, and the optimisation objective (e.g., minimising costs, CO
2 emissions, or primary energy consumption).
An autoregressive forecasting model for short-term hourly heat demand was developed and applied by Bizzarri et al. [
22] to determine the optimal operating mode of a hybrid heat pump system, aiming to minimise total operating costs. In non-renovated buildings, the MPC strategy achieved up to 20% lower operating costs compared to standard commercial control methods. In renovated buildings, the performance gap between MPC and commercial control was notably smaller due to reduced thermal variability.
An LCA comparison of a HHP and a condensing gas boiler [
23] showed that the HHP reduces GHG emissions by 30%. The environmental impact was lower in most categories for the HHP than for the gas boiler, except for human toxicity, water depletion, and metal depletion.
In all the mentioned studies, yearly average electricity production emission factors were used. However, average emission factors do not reflect the temporal variability of the electricity mix. During periods of high electricity demand, more carbon-intensive generation technologies may be dispatched, leading to higher actual GHG emissions than estimated using annual averages. Therefore, time-dependent emission factors should be considered when evaluating different HHP operating strategies [
24].
Biomass-assisted HHPs have received limited attention in the literature. Buday et al. [
16] showed that their environmental performance strongly depends on the carbon intensity of electricity production and the selected operating mode. Uche et al. [
7] demonstrated that appropriate system configuration and control can reduce operating costs and GHG emissions, while in a subsequent study, Uche et al. [
25] found that sizing the heat pump to approximately 60–70% of the peak heating demand provides the best balance between operating cost and environmental performance. A recent review of residential biomass heating technologies also highlighted the potential of biomass-assisted hybrid heat pumps while emphasising the limited number of available studies [
26].
Reducing peak power demand plays a crucial role in in maintaining the reliability of low-voltage grids in the current age with the deployment of residential low-carbon technologies, such as heat pumps, electric vehicles, photovoltaic (PV) systems, and battery storage. Higher electrification levels can lead to transformer overloading and voltage violations, requiring costly grid reinforcement. In Germany, grid reinforcement can be avoided if a 40–60% share of HHPs is achieved or if 60–80% of buildings are renovated [
27]. The potential of peak demand reduction by a bivalent operation of a HHP was identified by Cholewa et al. [
28], who suggested that the heat pump should cover from 70% to 90% of the peak heating demand, while the remaining 10% to 30% is covered by the peak heat source.
Aim and Scope
Based on the literature review, the research question of this study is whether the bivalent partially parallel (parallel–alternate) operation of a HHP supported by a biomass pellet boiler in a single-family residential building can reduce operating costs and GHG emissions compared to a monovalent ASHP. It was motivated by a gap in the research on HHPs supported by biomass boilers pointed out by Uche et al. [
25]. In contrast to extensively studied gas-assisted HHPs, the techno-economic and environmental performance of biomass-assisted HHPs remains scarcely investigated. These authors have stated that such a HHP can ensure sustainable heating with the use of local energy sources in rural areas. Even though those areas are usually not associated with poor air quality, temperature inversion in wintertime can increase the level of air pollution caused by biomass combustion [
29]. Wood smoke exposure has been associated with adverse health effects, including decreased lung function, increased susceptibility to respiratory infections, worsening of asthma symptoms, and potential cardiovascular impacts, due to systemic responses triggered by inhaled particles [
30]. Therefore, this study also investigates the potential of HHPs for particulate matter (with a diameter of 10
m or smaller—
) emission reduction compared to a monovalent biomass boiler, an environmental aspect that has received limited attention in previous HHP studies.
The analysis specifically targets buildings that have not yet undergone energy efficiency renovations but are already equipped with a biomass boiler. In retrofit scenarios where an ASHP is added, the existing biomass boiler can serve as an auxiliary heating unit. Consequently, investment costs are excluded from this assessment. Roccatello et al. [
31] indicated that in such buildings, hybrid heating systems could be a viable solution for increasing energy efficiency. Furthermore, buildings in rural areas were identified as having greater potential for energy savings compared to buildings in urban areas, driven by their ageing building stock and higher levels of energy poverty [
32].
A rule-based control strategy for switching between the ASHP and biomass boiler was developed to determine the optimal cut-off temperature by minimising operating costs under the new electricity distribution tariff methodology. The resulting operation is additionally evaluated using time-dependent electricity production emission factors and PM10 emissions from biomass combustion. The objective of this study is not to precisely model heating demand in an existing building, but rather to evaluate the performance of bivalent heating across a wide range of climatic conditions and building types. Consequently, the model incorporates hourly outdoor air temperature data from 23 representative locations across Slovenia, capturing the country’s diverse climatic conditions. This enables a spatial analysis of how regional climate influences the effectiveness of bivalent ASHP operation. The results were visualised using Geographic Information System (GIS) tools to identify areas where bivalent operation offers significant advantages over monovalent ASHP systems.
The main contributions of this study are the development and validation of a modelling framework for identifying the cost-optimal operation of a biomass-assisted HHP; the combined assessment of operating costs, time-dependent GHG emissions, and PM10 emissions under the new electricity distribution tariff methodology; and the generalisation of the results across different building heat-loss characteristics and climatic conditions with spatial analysis. This approach enables the economic and environmental suitability of biomass-assisted bivalent heating to be assessed at both the building and regional levels.
3. Results and Discussion
This section first presents the validation of the developed model against measured electricity consumption. The validated model is then used to evaluate the operating costs and GHG and PM10 emissions of the bivalent heating system in comparison with monovalent ASHP and biomass boiler operation. Finally, the influence of climatic conditions and building heat-loss characteristics is analysed, and the potential PM10 emission reduction is evaluated spatially across Slovenia.
3.1. Model Validation
Figure 5 presents the measured electricity consumption (expressed as daily mean power) for 2024, alongside the modelled electricity consumption for the same period and the corresponding daily mean outdoor air temperature. Modelled consumption consists of corrected historical consumption without an ASHP, combined with modelled ASHP consumption. The uncertainty band for energy consumption is shown only for the modelled values during the heating season, as described in
Section 2.4.1. The total yearly measured and modelled electricity consumption was 14,502 kWh and 14,113 kWh, respectively, resulting in a deviation of less than 2.7%, as over- and underpredictions partially cancelled out over time. Nevertheless, during the heating season, 66% of measurements fell within the model’s uncertainty band, supporting the predictive adequacy of the model. Notable deviations occurred at the beginning and end of the heating season, which can be attributed to discrepancies between the actual start and end dates of heating operation and those defined by the model. Additionally, supplementary heating provided by the ASHP at the end of April is evident in the figure and corresponds to lower outdoor air temperatures during that period, even though it is outside the heating season.
However, this validation has certain limitations; due to the lack of synchronisation between PV production and grid exchange data, the validation was performed using daily averages rather than 15 min values, so short-term variations could not be directly validated. In addition, non-heating electricity consumption in 2024 was estimated from corrected 2022 data rather than measured separately, introducing additional uncertainty into the validation.
3.2. Relative Savings of Bivalent Heating System
The analysis was conducted for 23 locations and seven total heat loss coefficients. The results are presented as relative operating costs and relative GHG emission reduction compared to a monovalent ASHP, and PM
10 emissions in comparison to the monovalent operation of a biomass boiler. These were evaluated separately for electricity consumption, biomass consumption, and overall energy consumption.
Figure 6 displays the results for a building in Rateče, assuming a specified
and excess power factor. Relative costs and GHG emissions were shown as functions of the cut-off temperature in the bivalent heating system. At temperatures above 15 °C, no heating was required, so a cut-off temperature of 15 °C corresponds to heating exclusively with the biomass pellet boiler. In this case, replacing the biomass boiler with an ASHP resulted in a reduction in overall energy costs of 18% and a GHG emission reduction of 50%. Further reductions were achieved through bivalent operation of the ASHP and biomass boiler. The lowest operating costs occurred at
−5.5 °C, yielding an additional 4.8% cost saving relative to monovalent ASHP operation. The GHG emission reduction of the bivalent system at minimal operating costs was 20%. However, an inappropriately selected switching temperature could result in increased energy costs. Specifically, switching temperatures above 0 °C used for cost optimisation may lead to worse performance than monovalent ASHP operation.
Table 4 compares results obtained using different excess power factors,
, for the case described above. An increase in the excess power factor did not lead to an increase in total energy costs and therefore did not affect the relative savings of bivalent operation. This outcome is partly due to the structure of the new methodology, where the agreed capacity for each time slot is defined based on the same electricity consumption being analysed.
Therefore, this study has several limitations from the perspective of operating costs:
Agreed capacity was calculated based on the same electricity consumption as used in the analysis. In practice, it is determined from peak loads in the previous winter; if the previous winter was unusually cold, excess capacity costs may increase. However, a separate analysis using historical climatic data showed cost reductions of a similar magnitude to those obtained for the corresponding
range in
Figure 7.
Operating costs and GHG and PM10 emissions were estimated under the assumption of optimal agreed capacity, whereas real-world consumers may not optimise this value precisely.
Cut-off temperatures were derived under the assumption of optimal agreed capacity; if the actual agreed capacity is overestimated, the savings from bivalent operation could be higher.
Additionally constant biomass boiler efficiency and PM10 emission factors were assumed. In real bivalent operation, boiler efficiency and particulate emissions may vary with part-load operation and during start-up and shutdown periods. These transient effects are not captured by the present model and may therefore lead to an overestimation of the calculated PM10 emission reductions.
Figure 7 presents relative energy cost savings and GHG emission reductions in the bivalent heating system compared to monovalent operation of an ASHP, calculated at the optimal switching temperature. The results are shown for both insulated (100 W/K) and uninsulated (350 W/K) single-family buildings across the 23 analysed locations. A second-order polynomial function was fitted to represent the dependence of savings on the heating degree day value. For
values lower than the positive root of the fitted function, savings were assumed to be 0%. The complete set of fitted functions for each analysed
is provided in
Appendix B. The fitted polynomial functions and their coefficients are specific to the analysed Slovenian context, including electricity tariff structure, energy prices, and emission factors. Therefore, the coefficients should not be applied directly to other countries or regions; application of the methodology elsewhere requires re-simulation using local input data and subsequent determination of new fitting coefficients.
In general, GHG emission reductions are approximately three times higher than operating cost savings, and both increase with . As expected, relative savings are lower for insulated buildings than for uninsulated buildings because of their lower heating demand. The results show that bivalent heating does not reduce operating costs below values of 2737 K day and 2561 K day for insulated and uninsulated buildings, respectively. Furthermore, for values around 3000 K day, corresponding to most of the analysed locations, operating cost savings are marginal for insulated buildings but reach up to 5% for uninsulated buildings. Even though the bivalent heating system does not reduce operating costs significantly for these locations, GHG emissions can be reduced by up to 10% for insulated buildings and up to 20% for uninsulated buildings.
Figure 8 shows absolute PM
10 emission reductions and relative operating cost savings of the HHP compared to a monovalent biomass boiler. For most locations, the HHP can reduce operating costs by up to 15% for insulated and up to 25% for uninsulated buildings. In colder locations, the savings are similar, which can be attributed to the lower share of heating provided by the ASHP. For most analysed locations where the HHP reduces operating costs, yearly PM
10 emissions can be reduced by 4–7 kg for insulated buildings and by 15–21 kg for an uninsulated single-family building.
Figure 9 displays the spatial distribution of yearly PM
10 emission reduction per single-family building resulting from the bivalent operation of a HHP compared to monovalent heating with a biomass boiler. The data covers the area of Slovenia at a spatial resolution of 1 km × 1 km. In the south-western coastal area, a PM
10 emission reduction of 0 kg is proposed, as the bivalent operation of HHP systems is not economically feasible under these climatic conditions.
The greatest reductions, reaching up to 25 kg, are observed in the yellow-coloured areas corresponding to the Alpine mountain regions and peaks, which are largely unpopulated. However, in populated Alpine valleys and the Dinaric plateaus, where heating degree days vary between 4000 K day and 5500 K day, the bivalent operation of the HHP can reduce PM10 emissions by 15–20 kg. Most populated areas in Slovenia are cities located in lowland basins with a milder climate, where heating degree days range from 2500 K day to 3000 K day, and the bivalent operation of the HHP can still reduce emissions by more than 10 kg. However, energy infrastructure in cities is more developed and diverse, making district heating or natural gas more convenient. In contrast, the spatial analysis shows that in rural areas in the south and west, as well as in the northern Alpine valleys, where biomass is a reliable local heating source, yearly PM10 emissions can be reduced by up to 15 kg for one single-family building.
Compared with previous studies, which have predominantly focused on gas-assisted hybrid heat pumps and optimised energy use, operating costs, and GHG emissions, the present model provides a more comprehensive assessment by simultaneously considering temperature-dependent ASHP performance, building heat-loss characteristics, capacity-based electricity tariffs, time-dependent electricity carbon intensity, and PM10 emissions from biomass combustion. Its validation against measured electricity consumption and application across a wide range of climatic and building conditions further strengthen its practical relevance. Although the current rule-based approach is less flexible than model predictive control, its relatively low computational complexity and transparent optimisation of the switching temperature make it suitable for adaptation to in loco operational optimisation. Coupled with measured building data and short-term weather, tariff, carbon-intensity, and potentially air-quality forecasts, the model could dynamically optimise heat pump and biomass boiler operation according to economic, grid, or environmental objectives.
4. Conclusions
In this study, the economic and environmental performance of a bivalent ASHP–biomass boiler system was evaluated for the retrofit of existing single-family buildings equipped with biomass boilers. A model was developed to determine the cost-optimal cut-off temperature while accounting for a new electricity distribution cost methodology. The analysis covered 23 locations across Slovenia and different building heat-loss characteristics, enabling the influence of climatic conditions and building demand to be assessed. The proposed methodology is intended as a general framework for evaluating the feasibility of hybrid heat pump systems rather than for detailed modelling of a specific building. It can be applied using hourly climatic data and different total heat loss coefficients, and can therefore support assessments across various building types, sizes, and climatic regions.
Compared with a monovalent ASHP, bivalent operation can reduce operating costs by up to approximately 10%, while GHG emission reductions can exceed 30% under colder climatic conditions. Compared with monovalent biomass heating, operating cost reductions of up to approximately 15% for insulated buildings and 25% for uninsulated buildings were obtained, while annual PM10 emissions can typically be reduced by 4–7 kg and 15–21 kg per building, respectively. The spatial analysis indicates the greatest practical potential in colder rural areas and Alpine valleys, where reductions of approximately 15–20 kg in PM10 per building and year can be achieved. These findings show that retaining an existing biomass boiler as an auxiliary heat source can facilitate heat pump deployment while reducing operating costs, limiting peak electricity demand, and substantially decreasing local particulate emissions.
The proposed approach extends previous assessments of hybrid heat pumps by jointly considering operating costs, grid-related tariffs, time-dependent GHG emissions, and local PM10 emissions across different climatic conditions and building heat-loss characteristics. The present control strategy is optimised with respect to annual operating costs, while GHG and PM10 emissions are evaluated as resulting performance indicators. Consequently, the cost-optimal switching temperature does not necessarily represent the environmentally optimal operating point, particularly during winter temperature inversions when reduced atmospheric dispersion can increase local PM10 concentrations. Future work should therefore investigate multi-objective and predictive control strategies that consider operating costs, peak electricity demand, GHG emissions, and PM10 emissions simultaneously and could prioritise ASHP operation during periods of unfavourable air-quality conditions. Pilot-scale validation should additionally account for transient biomass boiler operation and associated emissions.