Next Article in Journal
Effects of Bioavailability and Microbial Community on the Degradation of Atrazine in Sewage Sludge Biochar-Amended Soils
Previous Article in Journal
Impact of Daylight Saving Time on Energy Consumption in Higher Education Institutions: A Case Study of Portugal and Spain
Previous Article in Special Issue
Critical Node Identification for Cyber–Physical Power Distribution Systems Based on Complex Network Theory: A Real Case Study
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Sensorless Compensation of DC-Link Current Pulsations in Energy Storage Systems

by
Dariusz Zieliński
1,*,
Maciej Rudawski
1,* and
K. Gopakumar
2
1
Department of Electrical Drives and Machines, Faculty of Electrical Engineering and Computer Science, Lublin University of Technology, 20-618 Lublin, Poland
2
Department of Electronics Systems Engineering, Indian Institute of Science, Bangalore 560012, India
*
Authors to whom correspondence should be addressed.
Energies 2025, 18(12), 3153; https://doi.org/10.3390/en18123153
Submission received: 5 May 2025 / Revised: 31 May 2025 / Accepted: 12 June 2025 / Published: 16 June 2025

Abstract

:
This study addresses the problem of DC-link current pulsations in four-wire AC/DC converters with energy storage operating under unbalanced load conditions. A sensorless compensation algorithm based on AC-side voltage and current measurements is proposed, eliminating the need for additional sensors. The algorithm incorporates a Second Order Generalized Integrator (SOGI) filter for accurate detection and compensation of the pulsating component. Experimental validation under severe asymmetry confirmed the method’s effectiveness. In case 1, the AC component of the DC-link current was reduced from 7 A to 1.4 A and, in case 2, from 3 A to 0.5 A. Corresponding FFT analysis showed a reduction in relative amplitude from 240% to 21.5% and from 264% to 22%, respectively. In an asymmetrical charging scenario (case 3), the AC component was reduced from 2.5 A to nearly 0 A, corresponding to a decrease from 42% to 4.9% in the FFT spectrum. These results demonstrate that the proposed method enables stable converter operation even under deep phase current imbalances, significantly improving energy storage reliability and utility grid performance.

1. Introduction

The fourth generation of AC/DC converters has introduced significant advancements, providing new opportunities for reliable and efficient operation of microgrids. This generation of converters enables the independent control of the current in each phase of the AC/DC inverter, addressing many challenges associated with microgrid asymmetry [1]. This functionality is achieved through two fundamental modifications to the classical three-phase three-wire control system. The first improvement involves extending the topology by incorporating an additional passive or active leg and effectively introducing a fourth wire into the system [2,3]. The choice between a passive or active solution depends on application-specific requirements, including the level of current asymmetry and the desired power output of the converter [4]. The second enhancement involves transforming the traditional three-phase vector control [5] into three independent single-phase control algorithms [6]. Alternatively, vector control combined with symmetrical component decomposition can be utilized to manage the current components independently [7]. These innovations facilitate voltage symmetrization in microgrids by enabling the injection of independently controlled phase currents through an AC/DC four-wire converter [8]. For example, in [9], the theoretical foundations for compensating unbalanced power in four-wire networks were established, focusing on decomposing to symmetrical power components. In [10], the authors proposed a triple-loop control strategy to address voltage unbalance in four-wire inverters with split capacitors, achieving reliable voltage stabilization under asymmetrical loading. Although this approach mitigates voltage asymmetry within the microgrid, it simultaneously transfers the asymmetry problem to the DC link of the AC/DC converter [11,12]. The asymmetrical injection or withdrawal of currents introduces additional challenges in managing the DC link, necessitating further technical solutions to address the resulting issues.
When asymmetry is introduced in the system, such as when one phase draws energy from the grid while the other two deliver energy, the sum of the time-variant components no longer equals zero [13,14]. This imbalance causes power pulsations to appear in the DC link. The presence of a high AC component in the DC link is particularly undesirable, as it leads to increased losses in the balancing module, thereby reducing the overall efficiency and reliability of the system [15,16]. These challenges underscore the importance of developing effective solutions to mitigate the adverse effects of asymmetry on DC-link performance.
The study presented in [14] introduced a method for canceling pulsations in a DC-link by directly measuring the pulsation current. This approach, which leverages a resonant algorithm, is fast and accurate. However, this solution increases the inductance between the energy storage and the DC link of the power converter, leading to higher costs. In addition, it requires an ADC measurement channel and an AC and DC transducer, which adds complexity to the system.
In [17], an optimized phase-shift modulation strategy was introduced to reduce harmonic stress on the DC-link capacitor in cascaded converters. By adjusting the carrier phase shift between modulated signals, DC-link current distortion was minimized, improving efficiency and capacitor lifespan. However, precise phase synchronization is required, adding control complexity.
An adaptive active capacitor converter was proposed in [18] to enhance the stability of cascaded DC power-supply systems. Pulsations in the DC link were reduced using a nonisolated DC/DC converter. This solution is particularly effective in applications with unstable DC-link voltages. For systems in which electrochemical energy storage is directly connected to the DC link, voltage pulsations are inherently compensated for by the energy storage current. However, the high AC component of the current periodically charges and discharges energy, leading to increased energy losses and potentially reducing the lifespan of the storage system [13]. These limitations highlight the need for further optimization to mitigate DC-link pulsations.
Recent studies have also explored the performance of various four-leg inverter topologies under unbalanced load conditions. Study [19] conducted a comparative analysis of two-level and three-level inverters employing model predictive control (MPC), demonstrating that the three-level four-leg inverter topology offers superior performance in terms of current total harmonic distortion (THD), leakage current, and DC-link voltage stability, especially in applications requiring asymmetrical operation such as wave energy converters. These findings underline the importance of inverter design choices in managing asymmetry and maintaining energy quality.
To overcome this problem, in this study, researchers proposed a novel solution based on shifting the pulsation problem from a DC link to a supercapacitor. The key innovation lies in the sensorless current pulsation calculation algorithm, which requires only the measurement of voltages and currents on the AC side, which are already essential for the operation of the inverter. This significantly simplifies the overall system by eliminating the requirement for additional sensors or measurement channels dedicated to the DC link. Moreover, the algorithm incorporates an SOGI filter in its structure, allowing for the precise and rapid determination of the pulsation current on the DC bus, which further enhances its effectiveness. The proposed approach, implemented using a bidirectional DC/DC buck–boost converter, not only enhances the reliability of the power converter but also reduces the system complexity and cost.
This article is organized into several sections to present the proposed solution and its validation. Section 2 describes the methodology for calculating DC-link pulsations in an AC/DC converter. Section 3 introduces the system topology and the laboratory test bench used for validation. Section 4 and Section 5 presents the experimental results, followed by a discussion of the findings and the main conclusions. This structured format ensured clarity and facilitated the application of the proposed solution in technical practice.

2. Materials and Methods

The main components of the AC–DC four-wire converter are the current and voltage sensors placed in each phase. These sensors enable the calculation of the instantaneous AC and DC components of the DC-link current based on three-phase instantaneous currents and the grid voltage synchronization angle. This capability is crucial for analyzing the behavior of the DC-link current, particularly under asymmetrical operating conditions, where current imbalances in the network can introduce fluctuations in the DC link. The behavior of the DC-link current in an AC/DC converter under such asymmetrical conditions can be mathematically described. The magnitude of the AC component of the DC-link current I d c A C as a function of the magnitude of the AC component of the neutral wire current I n can be expressed as follows:
I d c A C = V a , b , c 2 V D C I n ,
where Va,b,c is the phase RMS voltage, and VDC is the DC-link voltage.
The instantaneous value of the AC component can be further described as
I d c A C = I d c A C sin 2 ω t + φ n = V 1 2 V D C I n s i n ( 2 ω t + φ n ) ,
where φ n is the phase of neutral wire current.
If the efficiency of the inverter is neglected, Equation (1) can be used to approximate the power output in the DC link [14]. When the inverter operates with symmetric currents, the sum of the time-variant components from the three phases is zero, resulting in the absence of pulsations in the DC link.
The proposed method for sensorless calculation of the DC-link current, illustrated in Figure 1, is based on the Second Order Generalized Integrator algorithm (SOGI) [20], which serves as an effective quadrature signal generator offering robust filtering properties, particularly for suppressing harmonic distortions and DC offsets. This is achieved through its dual transfer functions:
α s = k ω s s 2 + k ω s + ω 2 ,
β s = k ω 2 s 2 + k ω s + ω 2 ,
where ω is the angular fundamental frequency, and k is the damping factor of the SOGI algorithm.
The first is a band-pass filter (3) for the in-phase signal, and the second is a low-pass filter with a 90° phase shift for the quadrature signal (4). These properties allow the SOGI to provide clean αβ components, which are fundamental for precisely calculating the DC-link current.
In the proposed algorithm, the SOGI filter is utilized to extract the positive- and negative-sequence components of the input current on the AC side of the converter. Based on symmetrical component decomposition theory, any unbalanced three-phase system can be represented as a combination of three separate three-phase systems, as described by Equation (5). The first two components correspond to balanced sequences rotating in opposite directions, whereas the third component represents a pulsating sequence with angular frequency ωt. This decomposition enables precise analysis and control of asymmetrical operating conditions in AC/DC conversion systems.
I a b c = I a I b I c = I + cos ω t cos ω t 2 π 3 cos ω t + 2 π 3 + I cos ω t cos ω t 2 π 3 cos ω t + 2 π 3 + I 0 cos ω t cos ω t cos ω t ,
where I+, I, and I0 are the magnitudes of currents of symmetrical components.
Additionally, it is possible to remove one of the equations by converting Equation (5) to the αβ reference system (6), where the Clarke transform is applied.
I α β = I α I β = I + cos ω t + + sin ω t + + + I cos ω t + sin ω t + ,
where ∅+ and ∅ are the phases of symmetrical components obtained from PLL loop of inverter.
Subsequently, the signal was split into two independent processing paths. One path is processed using the SOGI filter, which effectively suppresses unwanted components and isolates only the fundamental frequency component of the input signal. Both processed signals are then subjected to Park transformation, as defined in Equations (7) and (8), enabling their representation in a rotating reference frame for further analysis and control, where the phase reference angle is derived from the PLL of the converter.
The component I d q + is of particular interest because it is directly associated with the current pulsation on the DC link of the power inverter. Given that the signal processed through the SOGI filter retains only the fundamental frequency component, its d-axis projection corresponds to the DC component drawn from the inverter DC link. The resulting difference represents the AC component of the current drawn by the inverter from the DC link by subtracting this value from the double-axis component of the second signal.
I d q + = I d + ¯ I q + ¯ + i d + ~ i q + ~ = I + cos + sin + ¯ + I cos cos 2 ω t sin 2 ω t + I sin sin 2 ω t cos 2 ω t ~ ,
I d q = I d ¯ I q ¯ + i d ~ i q ~ = I + cos sin ¯ + I cos + cos 2 ω t sin 2 ω t + I sin + sin 2 ω t cos 2 ω t ~ .
Since the proposed algorithm relies solely on AC-side voltage and current measurements to estimate the DC-link current, a conversion of these quantities to the DC side is necessary. To enable this, a dedicated scaling mechanism was introduced in the algorithm to translate the magnitude of AC-side signals into their corresponding DC-side equivalents. This scaling coefficient, denoted as k D C in the algorithm diagram, is mathematically defined in Equation (9).
k D C = V d V D C d D C ,
where V D C is the DC-link voltage, d D C is the modulation index magnitude of the converter, and V d is the d-axis voltage component of the AC side of the converter.
All the variables utilized in the proposed algorithm are either directly measured or derived as part of the standard operation of the converter. The overall control structure of the system is illustrated in Figure 2. As shown in the diagram, the AC component compensator for the DC link operates without the need for additional measurement systems, relying solely on the signals already available from the inverter.
In the investigated system, an unisolated buck–boost converter integrated with a supercapacitor bank is employed to mitigate the AC component of the DC-link current. The implementation of this compensation system follows the schematic shown in Figure 3.

3. Results

The capability to compensate for pulsations on the DC link of the power inverter was evaluated using a dedicated laboratory test bench, as depicted in Figure 4. The control algorithm for the power modules, along with the sensorless AC current estimator, was developed in the MATLAB 2021B and Simulink environments and subsequently implemented on a Texas Instruments TMS320F28379D microcontroller through automatic code generation. The proposed algorithm does not incorporate closed-loop controllers and is therefore executed at the same frequency as the switching frequency of the AC/DC converter transistors. The experimental results indicate that the minimum execution frequency required for proper operation is at least 20 times the fundamental grid frequency of 50 Hz. Below this threshold, signal distortions emerge, negatively affecting the performance and quality of the compensation process. The output signal i d c A C generated by the proposed algorithm, which serves as the reference current signal, generated by the proposed algorithm, was produced via the DAC of the microcontroller and measured using an oscilloscope.
All measurements were conducted by initially operating the inverter under asymmetrical conditions without compensation on the DC link, followed by activation of the compensator. In both cases, the 100 Hz component was determined relative to the DC component. In addition, the instantaneous active and reactive power components were analyzed for each phase. To quantitatively assess the reduction in the AC component in the DC-link current, the measured current I d c A C was subjected to Fourier analysis using a tool available in the Specialized Power Systems library of the MATLAB environment. This analysis enabled the evaluation of whether the operation of the compensator introduces current oscillations into higher frequency ranges. The experimental results demonstrated that the increase in higher-order harmonics caused by the compensator is limited to the fifth harmonic of the 100 Hz component. For clarity of presentation, the spectral analysis was extended up to the tenth harmonic of this component.
A current-measurement transducer was integrated into the DC link of the AC/DC power converter, appropriately scaled, and connected to an oscilloscope for signal acquisition. This enabled a comparative analysis between the measured values and those determined by I d c A C . The key electrical parameters monitored during the experimental tests included I a , b , c , representing the three-phase output current from the AC/DC converter; V D C , denoting the voltage and current on the DC link; and I d c A C , corresponding to the compensation algorithm output. All measured signals were recorded using two synchronized oscilloscopes to ensure precise data acquisition. The Tektronix MSO5034B was used to measure currents on the AC side, while the Tektronix DPO5054B captured other signals. Power measurements were obtained from the converter controller via a 14-bit DAC connected directly to the oscilloscope. The experimental setup consisted of five primary components, and their respective parameters are listed in Table 1.
To mitigate the influence of the floating voltage of the capacitor on the measurement accuracy, a high-capacity capacitor was selected. Throughout all experimental scenarios, the AC/DC inverter operated under asymmetrical conditions while interfaced with the utility grid via a transformer with a voltage reduction ratio. The presence of significant asymmetry in system operation resulted in the generation of high-amplitude AC components on the DC link of the inverter. The laboratory testing procedure was divided into three distinct phases. The test scenarios were selected to represent the most challenging conditions in terms of DC-link current pulsation levels in order to evaluate the effectiveness of the proposed system under the most demanding and practically relevant operating modes. These include voltage balancing, reactive power compensation, and energy storage charging, which are of particular interest from both the user and grid perspectives:
  • Case 1: High current asymmetry: Two phases deliver active power to the grid ( P a , c = 3.2   k W ), while one phase draws active power from the grid ( P b = 3.2   k W ) , with no reactive power present ( Q a , b , c = 0   V a r ) (Figure 5);
  • Case 2: Phase c delivers active power to the grid ( P a = 3.2   k W ,   Q a = 0   V a r ) , phase b has no power exchange ( P b = 0   W ,   Q b = 0   V a r ) , and phase a supplies capacitive reactive power to the grid ( P c = 0   W ,   Q c = 4.2   k V a r ) (Figure 6);
  • Case 3: Current asymmetry during energy storage charging: All phases draw active power from the grid ( P a , b , c = [ 0.8   k W , 2.4   k W , 4   k W ] ) , with no reactive power present ( Q a , b , c = 0   V a r ) (Figure 7).
In case 1, as shown in Figure 5, the operation of the converter was analyzed in a scenario where the two phases functioned as active power compensators, while the third phase operated as a rectifier. The reactive power balance of the converter remains zero. The DC-link current I D C reaches an amplitude of 10 A and periodically crosses the zero value, indicating that the energy storage system undergoes continuous charging and discharging cycles at a frequency of 100 Hz. The ratio of the 100 Hz component to the DC component was determined to be 236%.
Upon activation of the compensating DC/DC converter, a significant reduction in the AC component amplitude was observed. Notably, the current waveform no longer intersects the x-axis, indicating effective suppression of pulsations. As a result, the ratio of the 100 Hz component to the DC component decreased to 21.5%.
In case 2, as shown in Figure 6, the converter operated under a high level of asymmetry. The first phase functioned as an active power compensator, the second phase did not exchange power with the grid, and the third phase functioned as a reactive power compensator. Under these conditions, the asymmetry of the DC link reached an amplitude similar to that observed in case 1, with a peak current of 10 A. The DC-link current also crossed the zero value and exhibited negative values, indicating the periodic charging and discharging of the energy storage system at 100 Hz. The 100 Hz component relative to the DC component was measured to be 264%.
Following activation of the compensating DC/DC converter, a significant reduction in the AC component of the DC-link current was achieved. The 100 Hz component was successfully reduced to 19%, while the total AC component content was minimized to 22%.
In case 3, as shown in Figure 7, the asymmetrical energy storage charging scenario was analyzed. All the phases of the converter operated as rectifiers, drawing active power from the grid in an asymmetrical manner. Under these conditions, the DC-link current pulsation reached an amplitude of 5 A without crossing the zero value. The 100 Hz component relative to the DC component was measured as 42%.
After activating the compensating DC/DC converter, a substantial reduction in the AC component of the DC-link current was achieved. The 100 Hz component was reduced to 2.4%, while the total AC component content decreased to 4.9%.
This represents a significant improvement, particularly when compared to the author’s previous work [13], in which a preliminary, simplified version of the algorithm was investigated. In that study, pulsation reduction of approximately 80% was achieved, lowering the DC-link current oscillation from 8 A to 1.5 A. However, the compensation strategy in that case relied on an isolated Dual Active Bridge (DAB) converter, which may have influenced the effectiveness of the algorithm. The influence of converter topology on compensation performance will be addressed in the author’s future research.

4. Discussion

This study investigated the issue of DC-link current pulsations in four-wire AC/DC converters with energy storage operating under asymmetrical load conditions. The motivation behind this research stems from the increasing role of microgrids in modern power systems, in which independent phase control is employed to mitigate voltage asymmetry. Although this method enhances microgrid performance, it simultaneously introduces DC-link current pulsations, which may adversely impact the efficiency and lifespan of energy storage systems.
Unlike other methods, the sensorless compensation algorithm proposed in this study eliminates the need for additional sensors by utilizing the existing voltage and current measurements on the AC side, which are already required for the operation of the converter. The algorithm incorporates an SOGI filter, enabling precise detection and compensation of pulsations without significantly increasing the system complexity. This innovative approach allows for the dynamic correction of DC-link current pulsations, thereby protecting the energy storage system.
In all tested scenarios, the magnitude of the AC component I D C A C was significantly reduced upon activating the compensator. Even under the most challenging conditions, where severe asymmetry caused the AC component to exceed the DC component, leading to alternating charging and discharging of the energy storage system, the proposed solution effectively mitigated these oscillations. After the compensator was enabled, the AC component was substantially reduced, and the issues of alternating charging and discharging were eliminated. This effect was particularly pronounced in cases 1 and 2, where the AC component prior to compensator activation reached 7 A and was subsequently reduced to approximately 1.4 A and, in case 2, where it decreased from 3 A to 0.5 A. The effectiveness of this reduction is further confirmed by the FFT analysis, which indicates that the relative amplitude of the AC component was reduced from 240% to 21.5% in case 1 and from 264% to 22% in Case 2.
The method proved to be effective across all operating modes of the converter, as confirmed by additional measurements in case 3, where the system was tested under asymmetrical energy storage charging conditions. In this case, the AC component on the DC link was reduced from 2.5 A to almost 0 A. In the FFT analysis, this corresponds to a reduction from 42% to 4.9%, demonstrating the robustness of the proposed approach even under significant phase current imbalance conditions.

5. Conclusions

The outcome of the authors’ work is a novel and innovative algorithm for compensating the AC component of the DC-link current in a power converter, which operates solely based on voltage and current measurements taken on the AC side of the converter. The proposed method for DC-link current pulsations was experimentally validated under highly asymmetrical load conditions. The results demonstrated significant reduction in the AC component in all tested cases, confirming the method’s effectiveness and robustness. By eliminating the need for additional sensors and leveraging existing measurements, the solution reduces both complexity and cost. The study highlights the potential of integrating such sensorless algorithms with DC/DC interfaces for improved energy storage performance and microgrid stability.
Future research endeavors will aim to expand the analyzed system by incorporating various DC/DC converter topologies, including isolated configurations, to further optimize the performance of the DC-link pulsation compensator. The current findings indicate that a non-isolated buck–boost converter effectively reduces AC oscillations on the DC link. However, in applications requiring greater flexibility in energy management, isolated DC/DC converter topologies, such as Dual Active Bridge (DAB) and Full-Bridge LLC, may offer additional advantages. The resonant operation mode of the Full-Bridge LLC converter has the potential to enhance the energy efficiency at higher switching frequencies. Moreover, galvanic isolation of the supercapacitor from the main energy storage system may improve the system safety by mitigating the direct influence of the low-impedance energy source on the energy storage unit. This could contribute to the reduction in uncontrolled current flows, thereby enhancing the system reliability. Planned experiments will compare different topologies in terms of pulsation compensation efficiency and their impact on power quality parameters.

Author Contributions

Conceptualization, D.Z.; Methodology, D.Z.; Software, M.R.; Validation, K.G.; Data curation, M.R.; Writing—original draft, M.R.; Writing—review & editing, K.G. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Data Availability Statement

The original contributions presented in the study are included in the article, further inquiries can be directed to the corresponding authors.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Stefańczak, B.; Zieliński, D. The Problem of the Influence of Phase Current Asymmetry and the Direction of Energy Flow on the Idle Current of a Transformer in Star-Delta Winding Configuration. Przegląd Elektrotech. 2022, 1, 69–74. [Google Scholar] [CrossRef]
  2. Wu, W.; Wang, D. An Optimal Voltage-Level Based Model Predictive Control Approach for Four-Level T-Type Nested Neutral Point Clamped Converter with Reduced Calculation Burden. IEEE Access 2019, 7, 87458–87468. [Google Scholar] [CrossRef]
  3. Soból, C.; Milczarek, A. Circulating Current Elimination in Parallel Operation of Non-Isolated AC-DC 4-Leg Converters. In Proceedings of the 2023 IEEE 17th International Conference on Compatibility, Power Electronics and Power Engineering (CPE-POWERENG), Tallinn, Estonia, 14–16 June 2023; pp. 1–6. [Google Scholar]
  4. Carreno, A.; Perez, M.; Baier, C.; Huang, A.; Rajendran, S.; Malinowski, M. Configurations, Power Topologies and Applications of Hybrid Distribution Transformers. Energies 2021, 14, 1215. [Google Scholar] [CrossRef]
  5. Lang, B.; Zhang, H.; Sun, L.; Wang, B.; Zheng, X. Design of Three Phase Grid-Connected Inverter Based on Grid-Voltage Oriented Control. In Proceedings of the 2019 Chinese Control Conference (CCC), Guangzhou, China, 27–30 July 2019; pp. 6525–6530. [Google Scholar]
  6. Kot, R.; Stynski, S.; Stepien, K.; Zaleski, J.; Malinowski, M. Simple Technique Reducing Leakage Current for H-Bridge Converter in Transformerless Photovoltaic Generation. J. Power Electron. 2016, 16, 153–162. [Google Scholar] [CrossRef]
  7. Marchgraber, J.; Gawlik, W. Dynamic Voltage Support of Converters during Grid Faults in Accordance with National Grid Code Requirements. Energies 2020, 13, 2484. [Google Scholar] [CrossRef]
  8. Stefańczak, B. Controlling a Four-Wire Three-Level Ac/Dc Converter with Independent Power Control in Every Phase. Inform. Autom. Pomiary W Gospod. Ochr. Śr. 2021, 11, 51–54. [Google Scholar] [CrossRef]
  9. Czarnecki, L.S.; Haley, P.M. Unbalanced Power in Four-Wire Systems and Its Reactive Compensation. IEEE Trans. Power Deliv. 2015, 30, 53–63. [Google Scholar] [CrossRef]
  10. Wu, F.; Miao, B.; Peng, S.; Li, M.; Wen, S. Analysis of the Mechanism and Control of the Unbalanced Operation of Three-Phase Four-Wire Inverters. Appl. Sci. 2023, 13, 12253. [Google Scholar] [CrossRef]
  11. Zieliński, D.; Stefańczak, B.; Jędrys, K. Phase-Independent Reactive Power Compensation Based on Four-Wire Power Converter in the Presence of Angular Asymmetry between Voltage Vectors. Energies 2022, 15, 497. [Google Scholar] [CrossRef]
  12. Piasecki, S.; Jasiński, M.; Milicua, A. Brief View on Control of Grid-interfacing AC-DC-AC Converter and Active Filter under Unbalanced and Distorted Voltage Conditions. COMPEL—Int. J. Comput. Math. Electr. Electron. Eng. 2011, 30, 351–373. [Google Scholar] [CrossRef]
  13. Fatyga, K.; Zieliński, D. Sensorless Current Pulsation Compensation in a Hybrid Energy Storage. Appl. Sci. 2023, 13, 2252. [Google Scholar] [CrossRef]
  14. Zieliński, D.; Fatyga, K. Attenuation of DC-Link Pulsation of a Four-Wire Inverter during Phase Unbalanced Current Operation. Appl. Sci. 2021, 11, 1322. [Google Scholar] [CrossRef]
  15. Milczarek, A.; Martinez-Caballero, L. Control Strategy of Hybrid Energy Storage System for High-Dynamic Load Changes. In Proceedings of the 2023 IEEE 17th International Conference on Compatibility, Power Electronics and Power Engineering (CPE-POWERENG), Tallinn, Estonia, 14–16 June 2023; pp. 1–5. [Google Scholar]
  16. Tang, H.; Kong, L.; Wang, Y. A Novel Analysis of the Influence of Zero-Axis Control on Neutral-Point Potential Self-Balancing of Three-Level Converters. Electronics 2024, 13, 4657. [Google Scholar] [CrossRef]
  17. Zhou, X.; Choy, W.J.; Alcaide, A.M.; Wang, S.; Guenter, S.; Leon, J.I.; Monopoli, V.G.; Franquelo, L.G.; Liserre, M.; Galea, M.; et al. Common DC-Link Capacitor Harmonic Current Minimization for Cascaded Converters by Optimized Phase-Shift Modulation. Energies 2023, 16, 2098. [Google Scholar] [CrossRef]
  18. Zhang, X.; Ruan, X.; Kim, H.; Tse, C.K. Adaptive Active Capacitor Converter for Improving Stability of Cascaded DC Power Supply System. IEEE Trans. Power Electron. 2013, 28, 1807–1816. [Google Scholar] [CrossRef]
  19. Roh, C. Performance Comparisons of Three-Phase/Four-Wire Model Predictive Control-Based DC/AC Inverters Capable of Asymmetric Operation for Wave Energy Converters. Energies 2022, 15, 2839. [Google Scholar] [CrossRef]
  20. Herrejón-Pintor, G.A.; Melgoza-Vázquez, E.; Chávez, J.D.J. A Modified SOGI-PLL with Adjustable Refiltering for Improved Stability and Reduced Response Time. Energies 2022, 15, 4253. [Google Scholar] [CrossRef]
Figure 1. The proposed sensorless algorithm utilizing the SOGI method and based on symmetrical component decomposition.
Figure 1. The proposed sensorless algorithm utilizing the SOGI method and based on symmetrical component decomposition.
Energies 18 03153 g001
Figure 2. The proposed method for eliminating DC-link pulsation without an additional current sensor.
Figure 2. The proposed method for eliminating DC-link pulsation without an additional current sensor.
Energies 18 03153 g002
Figure 3. Simplified diagram of the laboratory setup.
Figure 3. Simplified diagram of the laboratory setup.
Energies 18 03153 g003
Figure 4. Laboratory setup of the tested power converter.
Figure 4. Laboratory setup of the tested power converter.
Energies 18 03153 g004
Figure 5. Measurements performed in case 1: (a) AC-side currents of the inverter I a , b , c , (b) DC-side current of the inverter I D C , current of compensator I C M P , and AC component of DC-link I D C A C , (c) calculated active power on the AC side, (d) calculated reactive power on the AC side of the converter, (e) Fourier transform of the I D C with the compensator disabled, first order = 100 Hz, and (f) Fourier transform of the I D C with the compensator enabled, first order = 100 Hz.
Figure 5. Measurements performed in case 1: (a) AC-side currents of the inverter I a , b , c , (b) DC-side current of the inverter I D C , current of compensator I C M P , and AC component of DC-link I D C A C , (c) calculated active power on the AC side, (d) calculated reactive power on the AC side of the converter, (e) Fourier transform of the I D C with the compensator disabled, first order = 100 Hz, and (f) Fourier transform of the I D C with the compensator enabled, first order = 100 Hz.
Energies 18 03153 g005
Figure 6. Measurements performed in case 2: (a) AC-side currents of the inverter I a , b , c , (b) DC-side current of the inverter I D C , current of compensator I C M P , and AC current component of DC-link I D C A C , (c) calculated active power on the AC side, (d) calculated reactive power on the AC side of the converter, (e) Fourier transform of the I D C with the compensator disabled, first order = 100 Hz, and (f) Fourier transform of the I D C with the compensator enabled, first order = 100 Hz.
Figure 6. Measurements performed in case 2: (a) AC-side currents of the inverter I a , b , c , (b) DC-side current of the inverter I D C , current of compensator I C M P , and AC current component of DC-link I D C A C , (c) calculated active power on the AC side, (d) calculated reactive power on the AC side of the converter, (e) Fourier transform of the I D C with the compensator disabled, first order = 100 Hz, and (f) Fourier transform of the I D C with the compensator enabled, first order = 100 Hz.
Energies 18 03153 g006
Figure 7. Measurements performed in case 3: (a) AC-side currents of the inverter I a , b , c , (b) DC-side current of the inverter I D C , current of compensator I C M P , and AC current component of DC-link I D C A C , (c) calculated active power on the AC side, (d) calculated reactive power on the AC side of the converter, (e) Fourier transform of the I D C with the compensator disabled, first order = 100 Hz, and (f) Fourier transform of the I D C with the compensator enabled, first order = 100 Hz.
Figure 7. Measurements performed in case 3: (a) AC-side currents of the inverter I a , b , c , (b) DC-side current of the inverter I D C , current of compensator I C M P , and AC current component of DC-link I D C A C , (c) calculated active power on the AC side, (d) calculated reactive power on the AC side of the converter, (e) Fourier transform of the I D C with the compensator disabled, first order = 100 Hz, and (f) Fourier transform of the I D C with the compensator enabled, first order = 100 Hz.
Energies 18 03153 g007
Table 1. Parameters of the experimental setup.
Table 1. Parameters of the experimental setup.
Name of ModuleParameterValue
2-order LCL grid filterLCL components value0.2 mH, 10 uF, 1.2 mH
AC/DC three-level
power inverter
(3L-T-NPC)
Switching frequency
Topology
Control algorithm
Output power
AC-line voltage
Switching component
18 kHz
T-NPC
Multi-resonant
25 kVA
230 VAC RMS
SK80TMLI12F4
Energy Storage—NILARLit-ion module560–770 VDC
DC/DC buck–boost converterSwitching frequency
Input choke
Control technique
Switching component
40 kHz
0.3 mH
PWM with PI regulator
3× C3M0075120K
Supercapacitor—LSNominal voltage
Rated Capacity
500 VDC
10F
MeasurementsCurrent measurements
Voltage measurements
LEM CKSR 50-NP
LEM LV 25-P
DSPMicrocontrollerTMS320F28379D
Algorithm frequency18 kHz
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Zieliński, D.; Rudawski, M.; Gopakumar, K. Sensorless Compensation of DC-Link Current Pulsations in Energy Storage Systems. Energies 2025, 18, 3153. https://doi.org/10.3390/en18123153

AMA Style

Zieliński D, Rudawski M, Gopakumar K. Sensorless Compensation of DC-Link Current Pulsations in Energy Storage Systems. Energies. 2025; 18(12):3153. https://doi.org/10.3390/en18123153

Chicago/Turabian Style

Zieliński, Dariusz, Maciej Rudawski, and K. Gopakumar. 2025. "Sensorless Compensation of DC-Link Current Pulsations in Energy Storage Systems" Energies 18, no. 12: 3153. https://doi.org/10.3390/en18123153

APA Style

Zieliński, D., Rudawski, M., & Gopakumar, K. (2025). Sensorless Compensation of DC-Link Current Pulsations in Energy Storage Systems. Energies, 18(12), 3153. https://doi.org/10.3390/en18123153

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop