1. Introduction
People spent more than 90% of their time in different indoor environments, such as offices, homes, care centers, schools, universities, shopping centers, etc. Indoor environmental quality (IEQ) is critical to human health, well-being, and work efficiency [
1]. In particular, students spend one-third of their time every day in classrooms and school buildings. For children aged 7–14 years living in Organization for Economic Co-operation and Development countries, they spent nearly 7000 h in school classrooms [
2]. Indoor air quality (IAQ) problems would not only lead to long-term and short-term health problems for students, but also affect students’ learning efficiency and teachers’ teaching quality. IAQ management is critical in classrooms where students spend most of their time [
3,
4]. Therefore, researchers and scholars have been more and more interested in this microenvironment [
5,
6].
Carbon dioxide (CO
2) is a normal trace component in the atmosphere at about 400 ppm [
7]. However, CO
2 concentration in closed or poorly ventilated environments is often higher than natural levels due to human metabolism [
8]. Scholars agree that CO
2 concentration is not only regarded as representative of ventilation, but also counted as a key pollutant affecting indoor environmental quality and occupant health [
9]. Therefore, exploring optimal CO
2 concentration levels is crucial for the well-being and productivity of occupants in enclosed spaces [
10]. Branco’s research results show that the limit value of the ICC of 1000 ppm has been accepted worldwide, according to the recommendations of the World Health Organization (WHO Region, 2000) and the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE Standard 62) [
11]. Satish U et al. [
12] found that, when the ICC increased from 600 ppm to 1000 ppm, most people’s decision-making measures decreased slightly, but when the indoor concentration increased to 2500 ppm, they decreased significantly. The result showed that the performance of the MATB task decreased significantly when the CO
2 concentration increased from 1500 ppm to 3500 ppm [
10]. In addition, some researchers found that a high CO
2 concentration in the classroom not only made it difficult for students to concentrate, reducing their learn efficiency, but also affected the work status of teachers. It was easy for teachers and students to develop health problems in the environment. Cumulative damage could lead to more serious consequences in the long term. D.G. Shendell et al. [
13] found that, for every 1000 ppm CO
2 concentration increase in classrooms, the relative increase in student absenteeism was 10–20%. The study also showed that participants’ performance was negatively affected by exposure to a lack of learning at 2700 ppm CO
2 relative to the 830 ppm participants, and that people who were already sleep deprived might be more susceptible to the effects of CO
2 in enclosed spaces [
14].
In addition, good thermal comfort was also associated with improved human productivity, concentration, performance, and well-being [
5]. Owing to the special requirements of educational buildings in the aspects of high personal density, young age, and more sedentary activities, the determination of classroom environment design parameters should also be fully considered regarding its impact on thermal comfort and learning performance [
15,
16,
17]. The recommended values of current thermal environment design parameters in the specification, such as indoor temperature, could not be used directly to guide classroom environment design [
18]. Recently, some researchers [
19] suggested that modest reductions in classroom air temperatures, i.e., when the temperature was decreased from 25 °C to 20 °C (77 °F to 68 °F), improved student academic performance. Performance improved on both numerical and language-based tasks that required concentration and logical thinking. Jingjiang et al. [
18] showed that the classroom temperature range was 13.0–15.0 °C to meet the thermal demands in Chinese students’ classrooms compared with the indoor temperature range recommended by the Chinese regulations in winter. Therefore, exploring the impact of indoor and outdoor pollutants in classrooms on IAQ and how to achieve good IAQ with low energy consumption was crucial for the health and sustainable development of teachers and students. In order to improve IAQ and supply fresh air, different regulations had been put forward for different indoor requirements [
20,
21].
Recently, natural ventilation and mechanical ventilation are two methods to provide indoor fresh air. For colleges, previous educational building research mainly focused on the overall composition of the campus and the design of the external environment; the indoor environment design mainly focused on sound insulation and lighting, but insufficient consideration was given to the IAQ and thermal environment. Moreover, due to the early design of public buildings in colleges and the uncertainty of the number of users, mechanical ventilation was basically not set up, and natural ventilation was mainly used instead. The effect of natural ventilation on improving indoor air quality attracted the extensive attention of researchers [
22,
23]. Good natural ventilation could improve the thermal comfort of the classroom and reduce the ICC [
24]. Natural ventilation does not require the installation of fresh air equipment, and outdoor air only needed to be introduced through an external window. Therefore, natural ventilation became the most commonly used fresh air supply method. Efforts were made to improve the IAQ and thermal comfort with low or no energy consumption by natural ventilation [
22,
23,
25]. Jie Gao et al. [
26] found that, in the heating season, the automatic operation of windows had a significant impact on CO
2 concentration and classroom temperature. The perception of the indoor environment was more positive in a classroom ventilated by automatically operated windows and exhaust fans. This classroom reported fewer symptoms than others.
Nowadays, for the simulation of building ventilation and pollutant transport, a multizone model is simulated with computational fluid dynamics (CFD) software to obtain precise flow fields and precision in a certain region. However, CFD simulations faced a formidable challenge; the performing high-fidelity CFD simulations were time-consuming. Therefore, it was impractical for scenarios that required extensive CFD execution [
27]. Multizone models had the advantage of being shorter than CFD simulations. Many multizone models (such as CONTAM, COMIS, and the Modelica model established by the multizone approach [
28]) were widely used to study pollutant transport [
29,
30,
31,
32]. Multizone models could also be coupled with other platforms to obtain more accurate flow fields and parameter values in a specific space. M. Justo Alonso et al. [
33] developed a coupled building model for energy, airflow, and pollutant transport to analyze different strategies for controlling supply and return air recirculation rates, including the use of the Demand Controlled Ventilation (DCV) strategy, which uses collaborative simulations between EnergyPlus and CONTAM. Zuo et al. [
29,
34] integrated FFD with Modelica for coupled simulations of indoor airflow, HVAC control, and building envelope heat transfer. Coupled simulations could simulate the dynamic interactions between indoor environments with stratified air and the building envelope faster than real time [
34]. The Buildings Library developed by Wetter et al. [
35] had greatly facilitated simulations on four Modelica platforms by other researchers in the field of the building environment. Fu et al. [
36] studied the energy consumption of a data center using the Modelica building library. The simulation results showed potential energy savings of up to 24% by addressing identified control-related issues and optimizing supply air temperature. Because of the ease of being established on the Modelica simulation platform, new models and control modules were also widely used in the research on heating [
29], ventilation [
24], heat transfer [
37], heat storage [
38], and energy systems [
39,
40], etc.
Moreover, according to the 2021 education statistics released by China’s Ministry of Education, there were 529,300 schools at all levels and of all types in China, 291 million students in school, and the average education duration was 10.9 years and still rising. Obviously, Chinese people were spending more and more time in the classroom. According to the current China classroom ventilation situation, most classrooms have no basic ventilation facilities and only rely on manual window opening to improve indoor air quality. Too little manual window opening resulted in indoor CO2 far higher than the limit of classroom air quality standard, which seriously affected students’ learning efficiency and was harmful to students’ health. Also, too much manual window opening would increase the load of fresh air, waste energy, and decrease indoor thermal comfort, affecting the learning efficiency of indoor students. It was urgent to improve the ventilation methods of school classrooms, maintaining indoor thermal comfort and reducing ICC at a low cost of energy consumption so as to ensure students’ physical and mental health and learning efficiency in the classroom.
Thus, this paper established a Modelica model, considering the student’s learning efficiency and the energy cost, to explore the relationship between winter indoor air quality, thermal comfort, and fresh air energy consumption in colleges by different ventilation methods, and some suggestions were provided for the selection of fresh air systems in college classrooms.
3. Results and Discussion
For the indoor design temperature of classrooms, international organizations, countries, and regions established standards based on the theory of thermal comfort research, such as those of the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) [
47], the Chartered Institution of Building Services Engineers, the International Standards Organization (ISO) [
48], and the Association of European Operational Research Societies [
49], as well as relevant standards in various countries and industries. The specific temperatures corresponding to the comfortable zone in each standard are shown in
Table 7. The evaluation standard for the indoor environmental parameters of Chinese buildings, named the Design Code for Heating Ventilation and Air Conditioning of Civil Buildings (GB 50736-2012) [
20], stipulated that the minimum design temperature to ensure the comfort of the indoor thermal environment of buildings was 18 °C.
However, due to the fact that the current research methods and evaluation models of thermal comfort are mainly based on the average comfort level of adults in the whole society, and for the particularity of the educational building group, the high individual density, the young age, and the differences between the thermal comfort requirements of students in a classroom and those of adults, the above standards cannot be fully applicable in Chinese universities.
A school building is mainly for student learning, and because of this special function, the determination of classroom environment design parameters should also fully account for their impact on thermal comfort and learning performance [
18]. According to the previous study [
18], the classroom temperature range required to meet the thermal demand of Chinese students was 13.0–15.0 °C and the learning efficiency of students reached the highest at 13.5 °C compared with the indoor temperature range in winter recommended by the current standard in China.
As a result, in this subsection, the simulation results of the ICC, indoor temperature, and fresh air energy consumption in the classroom are discussed. At the same time, the energy consumption results under different design temperatures are compared and analyzed. The usage of air conditioners in classrooms in winter is discussed in this paper. The influence of indoor air quality and thermal comfort in the classroom is discussed under these three different ventilation methods (FWM, SCM, ACM), as the design temperature
T1 = 18 °C, in
Section 3.1. While, in
Section 3.2, the influence of the above three ventilation methods on the air quality of the classroom is discussed when the design temperature
T2 = 13.5 °C. In
Section 3.3, the effect of three different ventilation methods, the heat production of air conditioning, and total fresh air energy consumption under different design temperatures are analyzed. Considering air quality, thermal comfort, and fresh air energy consumption, the optimal ventilation strategy based on learning efficiency is given.
3.1. The Effect on IAQ and Thermal Comfort Based on the Regulations
In this subsection, according to the Design Code for Heating Ventilation and Air Conditioning of Civil Buildings (GB 50736-2012), the indoor temperature parameter of the classroom is set to 18 °C. The influence of indoor air quality and thermal comfort in the classroom under these three different ventilation methods are researched in this section.
3.1.1. The Effect of the Fixed Window-Opening Method
When the window was closed, indoor and outdoor air were only exchanged through the window gap, and the rate of indoor CO
2 production was far higher than the rate of CO
2 entering the room from the outside.
Figure 10 shows the trend of the ICC under FWM with 0%, 20%, 40%, 60%, 80%, and 100% opening in winter. When the window-opening ratio was fixed at 0%, the ICC exceeded 1000 ppm at 8:07, as shown in
Figure 10a. The ICC exceeded 3000 ppm at 8:29. At the end of the first lesson, the ICC reached 8720 ppm. At the beginning of the second lesson, the ICC dropped below 8591 ppm. But, at the end of the second lesson, the indoor CO
2 reached a maximum of 20,355 ppm. During the whole class time, the duration time for the ICC to exceed 1000 ppm was 233.50 min, which occupied 97.29% of the whole class time. Moreover, the duration time when the ICC exceeded 3000 ppm was 211.08 min, which occupied 87.95%. As shown in
Figure 10b–f, the results showed that, when the window-opening ratio was fixed at 20%, the ICC exceeded 1000 ppm at 8:08. The ICC reached 1370 ppm at 9:35. The ICC dropped below 553 ppm at 9:55. Meanwhile, the ICC reached the peak of 1594 ppm at 12:20. The time occupied 93.19% of the whole study period when the CO
2 concentration in the classroom exceeded 1000 ppm, and it did not exceed 3000 ppm. When the window-opening ratio was fixed at 40%, 60%, 80%, and 100%, the ICC would not exceed 1000 ppm during the whole time. As shown in
Figure 11, with the increase in window-opening ratio, the average and maximum CO
2 concentration in the classroom would decrease, but the average hourly air change (ACH) would increase. During the whole class time, with six fixed window-opening ratios (0%, 20%, 40%, 60%, 80%, and 100%), the average ICCs in the classroom were 10,642 ppm, 1360 ppm, 900 ppm, 757 ppm, 684 ppm, and 633 ppm, respectively, and the maximum ICCs were 20355 ppm, 1594 ppm, 976 ppm, 770 ppm, 692 ppm, and 640 ppm, respectively. The ACH was 0.0267, 3.1291, 6.2953, 8.9500, 11.3997, and 13.9428, respectively. As shown in
Figure 12, when the fixed window-opening ratios were 0% and 20%, the indoor temperature of the classroom would reach the set value of 18 ± 0.1 °C at 8:17 and 8:23, respectively. The capacity of indoor air conditioner to handle air load was reduced due to the break time. When the window-opening ratio increased again, the air conditioner was unable to handle the fresh air load, resulting in a certain degree of decline in indoor temperature. After the second class, the indoor temperature rose again after the air conditioning capacity recovered to the peak. Moreover, if the window-opening ratio increased to 60% or above again, the indoor temperature would not reach 18 °C during the whole calculation time. When the window-opening ratios were 60%, 80%, and 100%, the maximum indoor temperatures of the classroom were 17.90 °C, 15.79 °C, and 14.30 °C, respectively.
3.1.2. The Effect of the Switch Control Method
According to
Section 2.3, the SCM was supposed to be set a fixed value. When the indoor CO
2 exceeded 1000 ppm, the switch would open to control the window-opening ratio at the set value. As mentioned above, the ICC could not be controlled below 1000 ppm under the FWM with 20% opening. However, when the fixed window-opening ratio was 40%, the ICC could be well controlled. Thus, 40% was selected as the fixed window-opening ratio of the SCM.
Figure 13 shows the trend of the ICC in the classroom under the SCM. It could be seen that the overall concentration in the classroom was below 1000 ppm. During whole class time, the duration time when the ICC exceeded 1000 ppm was 7.33 min, accounting for 3.01%. According to the simulation results, as shown in
Figure 14, the average ICC in the first lesson was 898 ppm, the maximum concentration was 1014 ppm, and the average ACH was 6.06. At the same time, the average ICC in the second lesson was 927 ppm, the maximum concentration was 994 ppm, and the average ACH was 6.15. The average ICC of the two classes was 914 ppm, which did not exceed the limit of the classroom air quality standard, and the maximum value occurred at 8:10 in the first class. As shown in
Figure 15, the switch was opened at 8:07, and the window-opening ratio of the classroom was fixed to 40% at 9:33. Then, the switch was closed, and the classroom window was completely closed. At 10:00, the switch was opened again. Meanwhile, the indoor temperature in the classroom reached the set value at 9:46. Then, from 10:00 to 10:27, the indoor temperature dropped slightly, higher than 17.5 °C, and then remained at 18 ± 0.1 °C. The average indoor temperature during the first class was 14.47 °C, and it was 17.95 °C during the second class, and the average indoor temperature of both classes was 16.58 °C. In the whole class time, the time for the indoor temperature to reach the set value was 123 min, accounting for 51.25%. In addition, the temperature in the first classroom would not reach the set value any more, and the indoor air had no good thermal comfort.
3.1.3. The Effect of the Automatic Control Method
Compared with the SCM, the window-opening ratio was not a set fixed value when the ACM was adopted. When the indoor CO
2 exceeded 1000 ppm, the window would open automatically, and the window-opening ratio would be time-variant.
Figure 16 shows the trend of the ICC in the classroom under the ACM. It could be seen that the overall concentration of the classroom could always be maintained below 1000 ppm. During class time, the time interval when the ICC exceeded 1000 ppm was only 9.33 min, accounting for 3.89%. According to the simulation results, as shown in
Figure 17, the average ICC in the first lesson was 977 ppm, the maximum concentration was 1006 ppm, and the average ACH was 5.10. At the same time, the average ICC in the second lesson was 1000 ppm, the maximum concentration was 1004 ppm, and the average ACH was 5.58. The average ICC of the two classes was 991 ppm, which did not exceed the limit of the classroom air quality standard, and the maximum value occurred at 8:07 in the first class. As shown in
Figure 18, at 8:07, the window would open automatically and last for 96 min. After that, the window would keep closed for 20 min and then keep open until the end. In the whole class time, the average window-opening ratio was 33.49%. At the same time, the indoor temperature in the classroom reached the set value of 18 °C at 8:51, and then remained at 18 ± 0.1 °C. The average indoor temperature of the first class was 15.65 °C, it was 18 °C in the second class, and the average indoor temperature of both classes was 17.07 °C. In the whole class time, the time interval for the indoor temperature to reach the set value was 193.33 min, accounting for 80%.
3.1.4. The Effect of Indoor Average CO2 Concentration and Temperature
The average ICC of the first class and the second class of the above eight ventilation methods and the proportion of time when the temperature reached the standard in the whole calculation time are shown in
Figure 19. Wherein, A~F were different window-opening ratios of FWM (0%, 20%, 40%, 60%, 80%, 100%), respectively. It can be seen from
Figure 20 that, when the classroom was ventilated by the FWM with 0% or 20% opening, the ICC was higher than the limit value of the classroom air quality standard, which seriously affected students’ learning efficiency and was harmful to students’ health. When the classroom was ventilated by the FWM with 40% opening or more, the air temperature could not be controlled at the set value of 18 ± 0.1 °C. The indoor air had no good thermal comfort and wasted a lot of energy. In general, the FWM in the classroom was not recommended in this paper, while both the SCM and ACM could maintain the average ICC of the two classes below 1000 ppm. It can be seen from
Figure 20 that the ACM had a better thermal comfort than the SCM; thus, the ACM was recommended when considering indoor air quality and thermal comfort.
3.2. The Analysis of IAQ and Thermal Comfort Based on Learning Efficiency
Based on the temperature point of the highest learning efficiency studied by Jingjiang et al. [
18], the design temperature was 13.5 °C. In this subsection, the indoor air temperature, CO
2 concentration, and fresh air energy consumption of the three ventilation methods were compared and analyzed.
When the FWM was adopted, the CO2 concentration with 0% opening or 20% opening and the fresh air energy consumption with 60% opening or 80% opening were both too high, which were obviously unsuitable. Therefore, in this subsection, 40% opening by the FWM was selected to conduct the simulation. In the simulation process, it was found that the original SCM with 40% opening had no obvious positive effects on reducing the ICC, so the SCM with 50% opening was selected to conduct the simulation analysis together.
3.2.1. The Effect of the ICC
In this subsection, the four different ventilation methods were simulated and the results were analyzed, namely, the FWM with 40% opening, the SCM with 40% opening, the SCM with 50% opening, and the ACM. As shown in
Figure 20, during the whole class time, their corresponding average ICCs were 985 ppm, 1003 ppm, 883 ppm, and 991 ppm, respectively. Furthermore, the highest concentrations were 1154 ppm, 1154 ppm, 987 ppm, and 1002 ppm, respectively. The duration time with the CO
2 concentrations of more than 1000 ppm accounted for 58.52%, 48.26%, 0.03%, and 2.22% of the whole class time. Only the SCM with 50% opening and the ACM could ensure an acceptable CO
2 concentration in the classroom.
3.2.2. Indoor Temperature
Meanwhile, as shown in
Figure 21, it took 1200, 1140, 1760, and 1120 s to reach the set indoor temperature value by the above different ventilation methods, respectively. Except the fact that the SCM with 50% opening produced a small vibration in the first five minutes of the break time, the four ventilation methods could always control the indoor temperature at the set value of 13.5 ± 0.1 °C. It could be observed that the four different ventilation methods could control the indoor temperature at the set value well.
3.2.3. Comparison of Indoor Average CO2 Concentration and Temperature
The average ICC of the first class and the second class of the above four ventilation methods and the proportion of time when the temperature reached the standard in the whole calculation time are shown in
Figure 22. It can be seen from
Figure 23 that the average CO
2 concentration in the second class was higher than the limit value of the classroom air quality standard when the classroom was ventilated with the FMW with 40% opening and the SCM with 40% opening. When the SCM with 50% opening was adopted, the thermal comfort of indoor air was worse than the other three methods. Therefore, when the design temperature was 13.5 °C, the ACM was recommended.
3.3. Analysis of Fresh Air Energy Consumption
In this subsection, the changes in the heating capacity of classroom air conditioning and the total energy consumption of fresh air under different design temperatures and three different ventilation methods were compared and analyzed.
3.3.1. Heating Capacity of Air Conditioning under the Temperature 18 °C
It could be concluded from
Section 3.1.1 that, when the design temperature was 18 °C and the FWM was adopted, the window-opening ratio value of 40% could be selected to ensure a satisfactory CO
2 concentration. The heating capacity of air conditioning under the design temperature 18 °C for the three ventilation methods, which were the FWM with 40% opening, the SCM with 40% opening, and the ACM, was compared in this subsection. According to
Figure 23, when the window-opening ratio was fixed at 40%, from 8:00 to 10:30, the air conditioner maintained the maximum heating capacity, which was 5460 W/s, and then gradually decreased. In the whole morning, the average heating capacity of the air conditioner was 4838.83 W/s. When the SCM with 40% opening was adopted, the air conditioner maintained the maximum heating capacity and started to drop at 9:44. At 10:00, the heating capacity of the air conditioner recovered to the highest value again, and gradually decreased at 10:26. In the whole morning, the average heating capacity of the air conditioner was 4555.41 W/s. When the ACM was adopted, the air conditioner maintained the maximum heating capacity at 8:48 and started to decrease. Then, after a brief shock, the heating capacity of the air conditioner began to decrease continuously. Due to the absence of a CO
2 source in the room during the break at 9:35, the window was completely closed, and the spatiotemporal modulated heat suddenly dropped to 0. The heating capacity of the air conditioner recovered to the maximum heating capacity of 5460 W/s again after a short shock at 9:55. After 80 s, it gradually decreased after a short shock. In the whole morning, the average heating capacity of the air conditioner was 4001.50 W/s.
3.3.2. Heating Capacity of Air Conditioning under the Temperature of 13.5 °C
According to the analysis in
Section 3.2, the ventilation methods that could be used to effectively control the ICC were the SCM with 50% opening and the ACM. The heating capacity of air conditioning under design temperature 13.5 °C for the three ventilation methods, which were the FWM with 40% opening, the SCM with 50% opening, and the ACM, was compared in this subsection. It can be seen from
Figure 24 that, when the window-opening ratio was fixed at 40%, the maximum heating capacity of the air conditioner was 5460 W/s, from 8:00 to 8:19, and then gradually decreased. There were no students in the room during the break at 9:35, which caused the heat loss of the human body to become zero, resulting in a sharp rise in the building heat load. Moreover, the window-opening ratio did not change, so the heating capacity of the air conditioner suddenly increased to the highest, and then gradually decreased. At 9:55, the class started again, the building heat load decreased, and the heating capacity of the air conditioner suddenly decreased. After a period of shock, it continued to decline. In the whole morning, the average heating capacity of the air conditioner was 2499.65 W/s. When the SCM with 50% opening was adopted, the air conditioner maintained the maximum heating capacity and started to drop at 8:28. Owing to the break time, at 9:35, the heating capacity of the air conditioner recovered to the highest value, and dropped rapidly at 9:39. After 0.67 min, the heating capacity of the air conditioner dropped to 0, then reached the peak for 1.33 min. After that, it dropped to 0 again. At 9:46, the heating capacity of the air conditioner rose slowly until 9:55, then suddenly dropped to 0 again and lasted for 4.50 min. The heating capacity of the air conditioner rose rapidly at 10:00 and then decreased slowly. The reason why the heat load of the air conditioner would temporarily be 0 after the second class was the time lag of the SCM. After the second class began, the window had not been opened under the control of the switch, while the students’ heat dissipation could meet the heat load requirements of the classroom. In the whole morning, the average heating capacity of the air conditioner was 3023.37 W/s. When the ACM was adopted, the trend of air conditioning heat load was basically consistent with the ACM in
Section 3.3.1. At the beginning, the air conditioner maintained the maximum heating capacity until 8:17. After a short shock, the heating capacity of the air conditioner started to decrease continuously. The heating capacity of the air conditioner suddenly dropped to 0 at 9:55. After 3.33 min, the heating capacity of the air conditioner kept rising. At 9:55, the heating capacity of the air conditioner decreased gradually after another 20 min shock. In the whole morning, the average heating capacity of the air conditioner was 2137.87 W/s.
3.3.3. Comparison of Energy Consumption under the Design Temperatures
The fresh air energy consumption of the three ventilation methods (the FWM with 40% opening, the SCM with 40% opening, and the ACM under the design temperatures of 18 °C and 13.5 °C) throughout the morning is shown in
Figure 25. When the set temperature was 18 °C, the total fresh air energy consumption of the FWM, SCM, and ACM was 6.81, 6.42, and 5.63
, respectively. Under the FWM and SCM, the energy consumption of fresh air was 20.96% and 14.03% higher than that of the ACM, respectively. At a temperature of 13.5 °C, the total fresh air energy consumption of the FWM, SCM, and ACM was 3.52, 3.13, and 3.01
, respectively. Under the FWM and SCM, the energy consumption of fresh air was 16.94% and 3.99% more than that of the ACM, respectively. At the same time, when the design temperature was reduced from 18 °C to 13.5 °C, the total fresh air energy consumption was reduced by 48.38%, 51.26%, and 46.58%, respectively, by using the FWM, SCM, and ACM. Therefore, the natural ventilation system that automatically controlled the window-opening ratio to provide fresh air for the classroom was recommended to reduce the indoor design temperature of the classroom.