Real Air-Conditioning Performance of Ejector Refrigerator Based Air-Conditioner Powered by Low Temperature Heat Source

by
Tongchana Thongtip
1 and
Natthawut Ruangtrakoon
2,*
1
Thermal and Fluid Laboratory (TFL), Department of Teacher Training in Mechanical Engineering, King Mongkut’s University of Technology North Bangkok, 1518, Bang Sue, Bangkok 10800, Thailand
2
Department of Mechanical Engineering, School of Engineering, King Mongkut’s Institute of Technology Ladkrabang, Bangkok 10520, Thailand
*
Author to whom correspondence should be addressed.
Energies 2021, 14(3), 711; https://doi.org/10.3390/en14030711
Submission received: 8 December 2020 / Revised: 4 January 2021 / Accepted: 8 January 2021 / Published: 30 January 2021

Abstract

In this present work, the air-conditioning test performance of an ejector refrigerator-based air-conditioner (ERAC) was proposed. The ERAC was operated as the water chiller to produce the cooling load up to 4.5 kW. The chilled water temperature was later supplied to the fan-coil unit for producing the thermal comfort condition. The cooling water used to cool the condenser was achieved from the cooling tower which was operated under the hot and humid ambient. This is to demonstrate the feasibility of using the ERAC in real working conditions. The cooling load supplied to the air-conditioned space was applied by the air heater. The ERAC could efficiently be operated to produce the thermal comfort condition which was driven by the hot water temperature (Thot) of 90–98 °C. The system performance could vary with the heat source temperatures, cooling load, primary nozzle, and air-conditioned space temperature. The optimal performance was determined when varying the Thot, and, hence, the optimal Thot was indicated. The optimal Thot varied significantly with variations in the working condition. The test results demonstrated high potential to further using the ejector refrigeration system in the actual air conditioning application.
Keywords: ejector refrigeration system; air-conditioning; thermal comfort; low grade heat utilization ejector refrigeration system; air-conditioning; thermal comfort; low grade heat utilization

Share and Cite

MDPI and ACS Style

Thongtip, T.; Ruangtrakoon, N. Real Air-Conditioning Performance of Ejector Refrigerator Based Air-Conditioner Powered by Low Temperature Heat Source. Energies 2021, 14, 711. https://doi.org/10.3390/en14030711

AMA Style

Thongtip T, Ruangtrakoon N. Real Air-Conditioning Performance of Ejector Refrigerator Based Air-Conditioner Powered by Low Temperature Heat Source. Energies. 2021; 14(3):711. https://doi.org/10.3390/en14030711

Chicago/Turabian Style

Thongtip, Tongchana, and Natthawut Ruangtrakoon. 2021. "Real Air-Conditioning Performance of Ejector Refrigerator Based Air-Conditioner Powered by Low Temperature Heat Source" Energies 14, no. 3: 711. https://doi.org/10.3390/en14030711

APA Style

Thongtip, T., & Ruangtrakoon, N. (2021). Real Air-Conditioning Performance of Ejector Refrigerator Based Air-Conditioner Powered by Low Temperature Heat Source. Energies, 14(3), 711. https://doi.org/10.3390/en14030711

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.