1. Introduction
The total energy end use has dramatically increased in the past few decades, and buildings, accounting for 40% of such use, represent the largest energy-consuming sector [
1]. The national implementation of the EU Directives led to a strong impulse to improve the energy performance in the building sector through different policies and actions [
2]. One of them is the introduction of the Nearly Zero-Energy Buildings (NZEB), defined as buildings with a very high-energy performance where the nearly zero or very low amount of energy demand should be covered almost entirely by renewable energy sources produced on-site or nearby [
2], and adopted as the construction standard in all EU countries. The NZEB target is set for new buildings and buildings subjected to deep renovation. The latter represents the major challenge to meet the energy and environment targets, because of the poor energy performance of the existing building stock [
3]. The educational buildings represent an important segment of this stock, being responsible for high energy uses, and it is also necessary to provide adequate Indoor Environmental Quality (IEQ) for pupils and students [
4,
5]. The relevance of the topic is highlighted by several EU projects dealing with the deep energy renovation of school buildings [
6,
7,
8,
9,
10].
Several studies dealt with NZEB and low-energy performance school buildings. Hong et al. [
11] developed a decision support model to maintain and improve elementary electric energy consumption of school facilities, combining genetic algorithms and neural networks. Fiaschi et al. [
12] reported an energy analysis of public buildings (including schools) discussing possible retrofitting strategies from energy and economic perspectives. Raatikainen et al. [
13] carried out a study on six school buildings built in different periods, analyzing different days and different operative hours to evaluate the trends of electricity and district heating costs. Muñoz et al. [
14] calculated the overall primary energy consumption of a new educational building during its whole lifespan according to the Life Cycle Energy Assessment (LCEA) method, concluding that the building did not satisfy NZEB requirements despite being designed as a low-energy building. Borrelli et al. [
15] studied the heating system of an NZEB educational building in Belgium during the winter period; they implemented a building model validated with measured field data in order to optimize its control strategies.
Many NZEB studies focused on the energy performance and cost-effectiveness [
16]; nevertheless, pursuing adequate IEQ levels affects the building energy demand [
17,
18,
19]. Providing IEQ at minimum energy cost is a challenging task for building designers [
20,
21], since poor air quality and thermal comfort make human beings more vulnerable to disease [
22,
23,
24,
25]. IEQ is critical in school buildings, where pupils spend around 25% of their time [
26]; furthermore, more than 50% of schoolchildren are affected by allergies or asthma [
27]. Poor IEQ affects also the productivity and performance of students and teachers [
28,
29]. For the mentioned reasons, research on the relation among occupants’ productivity, energy efficiency and IEQ in school buildings was carried out [
30]. Perez and Capeluto [
31] found complex interdependences among different design parameters, which affect the energy use in school buildings; the study focused on a hot–humid climate, to provide specific design guidelines. Energy performance and air quality in a new school building were investigated by experimental and numerical analyses in [
32]; the study explored the correlation between heat recovery ventilation and heat pump energy conservation, analyzing the displacement ventilation system and its thermal stratification. Allab et al. [
33] analyzed a French university campus, adapting and implementing an energy audit protocol with indoor climate issues; the objective was to have a full picture of the building behavior, including its operating conditions. Hameem et al. [
34] developed a unified protocol for Post-Occupational Evaluations and Measurements (POE + M) of critical IEQ variables in school facilities. Bogdanovica et al. [
35] analyzed the CO
2 concentration in a secondary school in Latvia, coupling measurement and a pupil survey; they observed an inverse correlation between the CO
2 concentration level and the pupils’ performance. The impact of the COVID-19 pandemic measures on thermal comfort and IAQ conditions in Mediterranean classrooms was studied in [
36]. The environmental monitoring carried out before and during the pandemic in two classrooms demonstrated that the “emergency” ventilation protocols provided good IAQ conditions with a decrease in CO
2 concentrations; conversely, effects on thermal discomfort conditions were also registered.
The operational performance of NZEBs is a topic under investigation, as documented in [
37,
38]. POE on NZEBs located in Germany, Austria, Switzerland and the Netherlands evidenced a low comfort satisfaction related to IAQ and indoor temperature in summer [
39]. The same result was obtained in a POE study performed in a low-energy building located in Italy [
40], which evidenced how NZEB requirements do not always guarantee adequate indoor conditions. Trofimova et al. [
41] investigated a Zero-Carbon Building (ZCB) in China to estimate occupants’ comfort; although results showed a general satisfaction with the environmental conditions, around half of the occupants experienced some sick building syndrome consequences.
The main causes of low IEQ levels can be summarized as follows: poor design of heating, cooling, ventilation and air conditioning (HVAC) systems [
39,
40,
41,
42]; excessively high level of thermal insulation in the building envelope [
42,
43,
44,
45]; incorrect design and application of passive technologies and strategies [
39,
40,
44,
45].
Building renovation is an important subject in Italy, since more than 50% of existing school buildings were built before 1970 [
46]. A significant number of Italian schools present substantial structural hazards, which is a critical issue in a country characterized by a high seismic risk, and they were built without any energy conservation measures [
47]. In Italian schools, space heating accounts for 80–90% of total energy end use, while active cooling systems are not installed, since schools are closed in summer. Mechanical ventilation systems, also, are seldom installed in existing schools because it was not the current practice at the time that most schools were built, and because several constraints apply in building renovation: noise control, structure of the building, significant additional cost. National policy requirements present high energy and environmental targets, including deep energy renovation of buildings [
48]. Relevant measures regard the upgrade of the building envelope, for both air tightness and thermal insulation, as well as the improvement of the heating systems’ efficiency; conversely, aspects related to indoor comfort and quality are seldom taken into account.
The main objective of the present study is to qualitatively and quantitatively assess the indoor environmental quality changes in school buildings undergoing NZEB targeted renovation, starting from the preliminary analyses carried out by the authors in [
49]. The study is carried out by numerical analyses focusing on the energy performance, thermal comfort and air quality issues, as well as on the contribution of passive cooling solutions to contrast the indoor overheating risk.
2. Materials and Methods
The methodology adopted to achieve the paper’s aim is structured as follows:
Identification of relevant parameters and indicators to describe thermal comfort and IAQ in the built environment;
Definition of the reference building (RB) considering the thermal characteristics of the envelope, the climatic conditions, the operational settings and the occupancy profile;
Definition of the RB variants, taking into account the Italian NZEB requirements, as well as the selected passive strategies and techniques to improve the indoor conditions;
Assessment of the energy performance of the RB before and after renovation, focusing on the use of space heating;
Assessment of the IEQ before and after the building renovation, evaluating and comparing the relevant indicators.
The numerical analyses focused on two crucial aspects for NEZB-targeted energy retrofit:
The energy performance assessment by applying the Italian standards, methodologies and tools.
The IEQ evaluation, here focused on the indoor thermal comfort and IAQ, assessed by analyses in transient regime, able to accurately reproduce the indoor environment of the buildings. According to the literature review, Italian schools do not have active cooling; hence, the thermal comfort analysis is performed during the off-heating period, when the building is in thermal free-floating conditions and the overheating risk is higher. The IAQ analysis is performed for the whole year, hence with the heating system on and off.
In order to fix boundary conditions to a wide and complex topic, the following limitation applies to the present study:
The analyses of the energy performances and the passive cooling technologies are focused on the building envelope, according to the current renovation measures and the building energy use in school buildings. Therefore, the technologies related to active and renewable energy systems were not taken into account, although they will play a crucial role in the future, thanks to their integration at district and community level.
The space heating system efficiency is not considered, since it would influence additional parameters not directly related to the paper topic. The other energy uses (domestic hot water, electricity for auxiliary and lighting systems) are not analyzed, since they are correlated to the energy measures here treated and have no relation with IEQ.
2.1. Identification of the Relevant Indicators
The building energy performance is expressed in terms of specific energy use (kWh/m2), which normalizes the energy used by the building to its useful area. The indicator chosen for this study is the net energy use, defined as the amount of energy supply needed to keep the building at the temperature set point (20 °C in winter), without taking into account the energy losses of the energy system. This choice was made to focus on the envelope performance, without introducing other variables not strictly related to the objective of the study.
Environmental quality is a complex field to investigate. The term sick building syndrome (SBS) was introduced by the World Health Organization (WHO) to describe the technical aspects related to the design of HVAC systems. SBS is generally used to characterize an indoor built environment equipped with HVAC systems where occupants suffer from illness symptoms due to poor IAQ. Different design standards were implemented in order to reach the requirements for both efficient energy systems and healthy environments [
50].
The level of indoor carbon dioxide (CO
2) is considered the main indicator to understand and assess the IAQ in the built environment [
51,
52], and its evolution is analyzed for the whole year. The operative temperature is identified as the main parameter to assess the thermal comfort conditions in buildings naturally ventilated and in thermal free-floating conditions during the off-heating period [
53]. The procedure and performance target for both analyses were carried out during the building occupation hours according to the relevant standard [
53].
2.2. Identification of Relevant Climatic Zones
The analyses were carried out in three Italian cities, characterized by different climatic conditions, to represent the heterogeneity of the Italian territory. The main characteristics of the chosen locations are as follows:
Milan—North Italy (lat. 45°37′ N, long. 08°44′ E): this location belongs to the Cfa class (humid subtropical climate) in the Köppen climate classification, characterized by hot, humid summers and cold, foggy winters.
Rome—Central Italy (lat. 41°48′ N, long. 12°14′ E): this location belongs to the Csa class (dry summer subtropical climate, often referred to as Mediterranean) in the Köppen climate classification, characterized by mild winters and warm to hot summers.
Palermo—South Italy (lat. 38°11′ N, long. 13°06′ E): this location also belongs to the Csa class, with temperatures consistently higher than Rome (around 3 °C as annual average).
Other climatic and operational data, as standardized in the national building code, are summarized in
Table 1 [
54]. The heating degree days (HDDs) are calculated considering a base temperature of 20 °C; no equivalent indicator exists for the cooling season.
2.3. Definition of the Reference Building
The building was modeled according to recurring characteristics of Italian schools: three floors, classrooms oriented along one side and corridor on the other, services and stairs at one extreme of the corridor. The plan of a typical floor is presented in
Figure 1. The classrooms are of the same size, and their main geometric data are: net area 50 m
2; room height 3.2 m; two identical windows of around 5 m
2 each (20% window to floor ratio, standard value in Italian classrooms).
The opaque components of this reference building (RB) envelope are not thermally insulated; the windows have an aluminum frame without thermal break and a single glass unit, with a solar factor of 0.85. Thermal transmittance values of the facade components are the same for the three climatic zones, assuming that the school was built before the introduction of the energy saving legislation. The values are summarized in the first column of
Table 2. Internal shading devices are mounted for daylight control, and their shading factor is 0.8 (in a 0–1 range, where 0 is no shading); no shadings are installed on the windows in the corridors.
As previously indicated, the building is equipped with a heating system but no active cooling systems are installed. The manual opening of the windows provides natural ventilation; this is the usual solution used in Italian school buildings, and it is applied to RB and its variants. Concerning the ventilation rate, Italian standards define the Air Changes per Hour (ACH) requirements according to building use [
55]. The rates indicated for schools are largely overestimated with respect to real conditions in buildings ventilated by manual window opening. ACH was also calculated implementing a realistic operational schedule for window opening: 10 minutes per hour and 30 additional minutes during the morning break at 10:30; full details can be found in
Section 3.2.
Other operational data used in the numerical analyses are:
A typical yearly schedule was considered for the building opening: Italian schools usually open on 10 September and close on 10 June. This implies that the teaching hours during the off-heating season are 546, 648 and 918 in Milan, Rome and Palermo, respectively.
2.4. Definition of the Building Variants
The initial RB variant is the NZEB configuration, characterized by a very high thermal insulation. U-values of the different components change as a function of the climatic zone, as defined in the relevant Italian standard [
59]. Windows are made of aluminum with thermal-break frames and double glazing units with a low-emissivity coating (0.6 solar factor). U-values of such components are reported in
Table 2.
The technologies and strategies implemented in the building variants to improve the indoor environment conditions were selected from a cost-effectiveness perspective, since other solutions would require a significant additional budget. The solutions identified are:
Solar-protection devices to reduce solar gains and improve thermal comfort during the off-heating season; the device has a shading factor of 0.8. It is assumed that the shading devices are moveable, according to current practices, and are activated only during the off-heating season. In winter, only the internal shading is activated for daylighting purposes. The external shading systems are not activated; thus, they do not affect the heating energy performance.
The nighttime ventilative cooling to reduce the indoor temperature, discharge the thermal mass at night and improve the thermal comfort during classes in the morning in the off-heating season. The strategy, hence, does not affect the energy performance in winter. Ventilation rates are set to 3 ACH from 21:00 to 07:00 a.m. This solution is analyzed in combination with the previous one.
Several window opening profiles are analyzed to assess the impact on IAQ during the occupation hours for the whole year.
Concerning the first mitigation solution, it has to be noted that the installation of the shading system affects the daylight availability in classrooms. The topic is relevant and has been explored in several studies [
60,
61]; however, it is beyond the scope of the present paper.
4. Results and Discussion
4.1. Energy Performance
The energy performance results of the RB and NZEB variant for the three cities and to the four building orientations are summarized in
Table 3 and
Table 4. The results refer to the ACH values defined by the national standards (
Table 3) and are based on the real operating conditions (
Table 4), respectively.
The results highlight the direct dependence of the energy performance versus the climate conditions. The orientation averaged net energy is 211.5, 125.5 and 71.5 kWh/m2 for Milan, Rome and Palermo, respectively, with ACH = 1.4−1. Despite the significant differences in absolute terms, the relative savings are similar, ranging from 69% in Milan to 74% in Palermo. The relative variation in the energy performance as a function of the orientation falls within 10% compared to the average value for the same climate and thermal insulation level.
Reducing the natural ventilation from theoretical (1.4 h−1) to effective (0.3 h−1) values led to 25–28% energy savings; thus, the average net energy for the existing building decreased to 157.5, 90.5 and 52.3 kWh/m2 for Milan, Rome and Palermo, respectively. The effective ventilation emphasizes the high impact of the transmission losses on the energy performance; in fact, the relative savings after the energy renovation are in the range of 88–92%.
4.2. Overheating Risk Assessment
The first set of results refers to the average operative temperature during the occupancy hours of the off-heating period, and it is summarized in
Table 5. The absolute operative temperatures are reported for the existing classrooms, while the temperature increase with respect to RB is reported for the other configurations. The RB results do not present significant differences between the intermediate rooms and the top floor, with 0.23 and 0.15 °C being the operative temperature difference for Milan/Rome and Palermo, respectively. The NZEB renovation causes a rise in the orientation-averaged operative temperature by 6.3, 5.2 and 4.9 °C for Milan, Rome and Palermo, respectively. The difference depends on the thermal insulation levels required for envelope components, which are proportional to the severity of the climate. Thus, the lower U-values in Milan lead to a higher overheating risk during the mild and warm seasons. The peak temperature rise is recorded in Milan: 6.8 °C for the north room on the second floor. It should be noted that the average operative temperature is always above 28.9 °C in all cases but the case of the north-oriented, first-floor classroom in Milan, scoring 28.3 °C. These figures provide a clear picture of the overheating risk in NZEB, uniquely designed to achieve energy conservation in winter.
The external solar protection devices installed on the NZEB building (NZEB + shad) cause a reduction in the average operative temperature by 3.0, 2.8 and 2.5 °C compared to the standard case in Milan, Rome and Palermo, respectively. The impact is lower (1.2–1.8 °C) on the north-oriented classrooms, because of the lower solar load on such facades. The combination of ventilative cooling and solar shading (NZEB + shad + vent) greatly improves the response of the NZEB; in fact, the average operative temperature is close to RB, the differences being in the range of −0.1–0.6 °C for the three cities.
An exemplary case of the indoor operative and external air temperature evolution versus time is plotted in
Figure 2. It refers to the case of Rome, for an east-oriented classroom, for an entire week from 1 to 7 May. The temperature profiles are similar, but the different building configurations lead to a vertical shift in the curves. Despite mild outdoor temperatures, the operative temperature reaches 30 °C for the NZEB case and it is around 5–6 °C higher than the non-insulated configurations, peaking at 7 °C at nighttime. The NZEB configuration with external solar protection exhibits intermediate performance compared to the two previous case, while the natural ventilative cooling during the night provides a significant mitigation of the thermal conditions, with the temperature profile aligned to that of RB.
The impact of solar gains through the roof on the thermal comfort was assessed analyzing the operative temperature differences calculated at the top floor and at the intermediate level. The frequency distribution plot of
Figure 3 presents the exemplary case of the south-oriented classroom in Milan. The operative difference is lower than 0.5 and 0.8 °C in more than 50% and 90% of the observation period, respectively. Similar results were achieved for other building configurations; thus, they are not presented here for brevity. This result shows that temperature differences among floors were often negligible. For such reasons, further elaboration on the operative temperature is presented for the classroom at the intermediate floor, as representative of all the classrooms with the same orientation. The role of the roof, as a source of heat in classrooms, is reintroduced again for the discomfort analysis.
Figure 4 shows the influence of the orientation on the overheating risk for different building configurations. The three cities produced similar results; hence, the case of Milan is presented as exemplary. The north-orientated classroom is the coolest for the RB case, with the operative temperature below 26 °C (OP_26) in 77% of the period, because of the low solar gains through windows. Conversely, the east-oriented classroom is the warmest (OP_26 in 62%) because of the solar irradiation through the windows during the morning teaching hours. South and west rooms have a quasi-identical profile, due to similar irradiation conditions during the off-heating season; the calculated OP_26 is 71% and 70%, respectively. Indoor operative temperatures rise significantly for the NZEB, but the trend does not compare to the RB case; hence, it is not presented here for brevity. The trend changes instead for the NZEB + shad; in fact, the south-oriented classrooms are cooler than north-facing ones, the operative temperature being below 28 °C (OP_28) in 73% and 67% of the observation period, respectively. This phenomenon is explained by the temperature increase in the unshaded south-oriented corridor, which, in turn, warms up the north-oriented classrooms. This behavior is also observed for the west classrooms, whose performance is very close to that of the east-oriented classrooms, with OP_28 at, respectively, 59% and 56%. The same trend is observed for NZEB + shad + vent configuration, but the differences are smaller compared to the previous case, i.e., the hours with the operative temperature below 26 °C are in the range of 70% (east)–80% (south) for all cases.
The final analysis is carried out to correlate the indoor operative temperatures and the thermal discomfort occurrence, according to the procedure defined in the relevant standard [
53]. The discomfort hours are those in which the operative temperature falls outside of the acceptance range, the latter being a function of the daily mean running outdoor temperature and the user category. Category II, which refers to a normal level of comfort in new and renovated buildings, was applied in the present study. The results are expressed in relative terms to facilitate a comparison among the off-season periods in the selected cities.
The results for Milan are reported in
Figure 5 and they show that the second floor (classroom below the roof) is more exposed to thermal discomfort than the intermediate classroom. The difference in discomfort hours is in the range of 3–6% for all the configurations but the NZEB + shad; this is explained by the effective control of the solar loads on the first floor, while the upper classroom is affected by the solar gains through the roof as well. Regarding the impact of the façade orientation, it is observed that the north classroom causes fewer discomfort hours, at 9–11%, than the orientations’ average; this value drops to 0–3% for the configurations equipped with solar shading. Comparing the building configurations, the highest differences were recorded between RB and NZEB, in fact. The discomfort hours rise from 14% to 88% of the period, highlighting the deterioration of thermal conditions because of the NZEB renovation. The shading systems reduce the discomfort hours to 51%, which is a significant figure in any case. Solar gains are only part of the thermal load; thus, it is also important to cool down air and structures to mitigate the indoor environment. The night ventilation, coupled with solar protection, fulfills the objective and ensures that discomfort hours remain below 5%, improving the RB indoor conditions.
Figure 6 presents the results of the discomfort hours obtained for the RB located in Rome. The top-floor classroom has 3–8% more discomfort hours than the room below; the difference rises to 15% for the NZEB-shad case. The north is the most comfortable orientation in RB, with 9% discomfort hours compared to 21% of the orientation average. The solar shading systems are most effective in the south-oriented classroom (discomfort hours 12% lower than the average), since this orientation is the most affected by solar gains in the intermediate season. These results prove the relevant impact of solar gains in the mild Mediterranean climate and the need to implement solar control strategies on transparent and opaque components as well. Comparing the different configurations, the discomfort hours are 21% for the existing RB and the indoor microclimate is improved (10% discomfort hours) in the case of building renovation with solar protection and night ventilative cooling. NZEB either equipped without or with solar protection leads to extremely poor thermal conditions, with 98% and 66% of discomfort hours, respectively.
Figure 7 reports the Palermo results. The high irradiance levels and ambient temperatures typical of South Italy lead to significant discomfort conditions in all the building configurations. The discomfort hours account for around 40% of the period for RB, and no significant differences are observed between the two floors. The results show a strong dependence on the orientation, e.g., RB in the south-oriented classroom has almost twice the discomfort hours (50%) of the north-oriented one (27%). The benefit of solar protection devices in the NZEB south-oriented rooms is not relevant in this case (5% with respect to average), because the high temperature is the driving force behind overheating in Palermo. Comparing the different configurations, the lowest average discomfort hours were calculated for NZEB + shad + vent (35%), 5% less than the existing RB. Extremely poor thermal conditions were observed for the NZEB configurations, either with or without solar protection systems, which led to 80% and 98% discomfort hours, respectively.
4.3. Indoor Air Quality Assessment
Preliminary calculations showed that the CO
2 concentration does not depend on the classroom floor. It was also found that the CO
2 concentration slightly changes with the climatic zone and the building configuration, since it is mainly a function of the gas produced by the occupants inside the built environment. Aggregate results are presented in
Table 6, where the average concentrations are presented for three cities, four building configurations and two orientations, south and east. The high CO
2 concentration levels in the occupied classrooms are in agreement with the data provided by the field survey [
58]. These values are not acceptable according to the relevant standard [
53], which sets the CO
2 concentration limit to 1200 ppm.
The frequency distribution of CO
2 concentration in the south-oriented classroom in Rome is selected as an exemplary case, and it is plotted for the different building configurations in
Figure 8. The maximum CO
2 concentration is above 4000 ppm in all cases, while levels above 2800 ppm are reached in around 40% of hours. Concentrations below 2000 ppm are calculated for around 20% of the period, and they are mainly recorded during the morning break hour, when windows are kept open for a longer period of time. Concentrations below the relevant standard requirements (1200 ppm) are achieved for between 16% and 18% of the hours only.
In general, the effect of the energy renovation has a small positive impact (reduction of between 6% and 9% in CO2 concentration with respect to the average values), because the increase in the indoor air temperature in the NZEB configuration creates favorable conditions for natural ventilation. The concentration is variable for the NZEB with external shading, ranging from a 4% reduction for the south classroom in Milan to a 1% rise in Rome. The night ventilation and consequent lower temperatures lead to an increase in the gas concentration, ranging from 2% in south classrooms in Palermo up to 9% in Rome.
An additional set of calculations were carried out to verify under which conditions the natural ventilation is sufficient to provide adequate IAQ. The results are presented in
Figure 9 and refer to the NZEB + shad. The results are expressed as a function of a progressive increase in the window opening time per hour—that is, the increase in the air exchange rate. The trend and the absolute values are very similar for the reference cities, in accordance with the previous results. According to these outcomes, acceptable CO
2 concentration levels might be achieved with window openings of longer than 30 min per hour. This option is not realistic because of the evident implications, such as the cold air inlet in winter and the noise from outside during teaching hours.
5. Conclusions
This study investigated the impact of deep energy retrofit on the IEQ in a reference school building for different climates in Italy. A typical school building was accurately modeled, and several geographic and operating configurations were analyzed. The energy simulations demonstrated that the net energy use for space heating might decrease from 68% to 82% in the case of an NZEB retrofit, with the highest and lowest relative savings achieved in Palermo and Milan, respectively. Calculations in the transient regime were performed to assess the indoor air and thermal quality; the results evidenced a serious worsening of the environmental conditions during the off-heating season, which is the period most exposed to overheating. A relevant increase in the average operative temperature was calculated, ranging from 4.5 °C of the east-oriented first-floor classroom in Palermo to 7.1 °C in the west-oriented second-floor classroom in Milan. The thermal comfort analysis showed that existing buildings are in the comfort range for the majority of the time in Milan and Rome, but only 60% of the period in Palermo. Conversely, the NZEB renovation leads to discomfort conditions for most of the teaching hours at all latitudes, and the application of external protection devices confirms the risk for 50–80% of the period. The combined effect of solar shading and night ventilation reduces the overheating risk to a lower level compared to the existing configuration (from 5% in Milan to 35% in Palermo). CO2 concentration analyses showed that the Indoor Air Quality is ensured in neither existing buildings nor in retrofitted ones when ventilation is provided by window opening. Average concentrations above 2000 ppm were calculated for all the configurations and acceptable values might be reached only with unsustainable window opening times during classes.
The study thus demonstrated the poor IEQ in school buildings. The situation is particularly dangerous in warmer climates: the case of Palermo clearly proves that thermal comfort conditions are not provided for a significant part of the year, even in non-insulated buildings. The use of additional passive solutions, as phase change materials and advanced ground coupled ventilation, might be envisaged, even if such technologies will significantly increase the renovation costs. Recent developments in the positive energy districts and energy communities provide new perspectives on the shared energy generation by renewables, exchange and use among buildings. The use of an active cooling system might be acceptable and sustainable in school buildings within these scenarios, in which the energy use might be optimized through proper management at district level.
It is, finally, advised that the deep energy retrofit actions should include measures aimed at preserving and improving the thermal comfort and the air quality conditions, even if they might not provide benefits from a life cycle cost perspective, assuming that the health and comfort of pupils and students are beyond economic issues. This implies a rethinking of the renovation process, often considered as a simple technological effort, where a multi-objective approach to the building design provides a healthier and comfortable built environment, besides a very high energy target.