Next Article in Journal
Digitization of Museum Objects and the Semantic Gap
Previous Article in Journal
Dynamic Response of Marzocco by Donatello to Seismic Excitation
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Lateral Confinement Reinforcement of Timber Under Perpendicular-to-Grain Compression

by
Jose Ramón Aira-Zunzunegui
1,* and
Laura Gonzalo-Calderón
2
1
Department of Architectural Construction and Technology, Escuela Técnica Superior de Arquitectura, Universidad Politécnica de Madrid, Avda. Juan de Herrera, 4, 28040 Madrid, Spain
2
Department of Structures and Building Physics, Escuela Técnica Superior de Arquitectura, Universidad Politécnica de Madrid, Avda. Juan de Herrera, 4, 28040 Madrid, Spain
*
Author to whom correspondence should be addressed.
Heritage 2025, 8(9), 368; https://doi.org/10.3390/heritage8090368
Submission received: 17 July 2025 / Revised: 29 August 2025 / Accepted: 2 September 2025 / Published: 5 September 2025
(This article belongs to the Section Architectural Heritage)

Abstract

One of the most common issues encountered in the rehabilitation of timber-structured buildings is the crushing of elements subjected to compression perpendicular to the grain. This crushing results in differential settlements that decrease comfort and, in some cases, compromise the habitability of the building. This study analyzed a reinforcement method involving the lateral confinement of timber members using two metallic side plates. Experimental tests were conducted with various configurations of the bolts used to fix the plates. In addition, several finite element models were developed and validated to extend the scope of the analysis virtually. An initial reinforcement proposal was examined, in which the metal plates were allowed to move vertically with the wood’s deformation. This setup achieved only a 26% reduction in deformation. Subsequently, an enhanced reinforcement system was tested, wherein the plates were anchored to the lower vertical stud, preventing their vertical movement. This configuration significantly enhanced performance, achieving maximum deformation reductions of up to 53%. Finally, in the improved reinforcement system, the load distribution among the bolts was analyzed to support their structural design.

1. Introduction

The crushing of elements subjected to compression perpendicular to the grain is a prevalent issue encountered during the rehabilitation of existing buildings with heavy timber-framed walls. This phenomenon typically manifests in sill plates and capitals due to the concentration of stresses at their intersections with the vertical studs, both upper and lower, as illustrated in Figure 1.
Figure 2 illustrates real-life instances of this pathology in existing buildings in Madrid.
The issue of compression perpendicular to the grain in timber is not exclusive to existing buildings; it also affects new constructions, as demonstrated by several recent studies [1,2,3]. With the increasing use of timber in construction and the growing height of timber buildings, addressing the problem of wood crushing is essential to prevent differential settlements that could compromise the building’s habitability and stability. Therefore, it is crucial to address this issue during the design phase, prior to the building’s commissioning.
In recent years, several research projects have been conducted to provide reinforcement solutions for new construction based on the use of elements that directly support compressive stresses. For instance, metal components such as structural screws or glued-in rods [4,5,6,7,8,9], plates [10], and even densified wood dowels have been utilized [11,12,13].
The behavior of timber under compression perpendicular to the grain is complex and non-intuitive. Unlike failures due to tensile or shear stresses, which often lead to brittle collapse, compression perpendicular to the grain typically results in a ductile failure mode characterized by progressive deformation rather than immediate structural collapse. This behavior is commonly represented by a three-segment stress–strain curve [14,15,16,17] with a very marked central phase of plastic deformation (Figure 3):
A.
Elastic segment: wood displays elastic behavior, which remains linear over the entire range except at the terminal segment.
B.
Plastic segment: buckling of the cell walls and thus yielding of the fibres with macroscopically evident crushing under a small load increase.
C.
Hardening segment: the cell walls break, occupying the empty cell lumen, causing the fibres to accumulate and densify, thereby increasing the strength of the whole. The increase in strength continues until the fibres finally break under compression (around 225 MPa for Picea abies [18]).
Although the compression of wood may not lead to structural collapse, it significantly impacts the building’s habitability by substantially reducing its comfort levels. For instance, it is common for the supports of floor slabs over timber-framed facades to have lower elevations compared to those over brick masonry facades, resulting in floor unevenness within the dwelling.
In previous laboratory tests involving compression perpendicular to the grain, it has been observed that wood experiences slight swelling at the center of the load application area, as shown in Figure 4. Building upon this phenomenon, the present study focuses on investigating the effects of lateral confinement on elements subjected to perpendicular compression, aiming to design reinforcements that mitigate wood crushing.
This lateral bulging has also been observed by other researchers, who have highlighted the influence of the growth ring arrangement on the deformed shape of the specimen [19]. Additionally, experiments have been conducted on perpendicular compression, laterally confining the specimen to understand the behavior of wood under axial, biaxial, and triaxial compression [20]. These studies have confirmed that lateral confinement reduces deformation and enhances the recovery of the specimen’s initial shape once the load is removed.
The reinforcement approach examined in this study represents a novel method not previously proposed for new construction projects. Traditionally, direct installation of pin-like elements, either metallic or wooden, is considered more effective for bearing localized compressive forces. However, lateral confinement may prove beneficial in rehabilitation projects where affected timber components are inaccessible from their upper and lower faces, as illustrated in Figure 2.

2. Materials and Methods

During the experimental phase, several reinforcement solutions were proposed, wherein the confinement of the specimens was achieved using 2 metal plates arranged laterally and connected by metal bolts. Perpendicular compression tests were conducted with varying bolt configurations.

2.1. Materials

A total of 12 glued laminated timber specimens measuring 120 × 120 × 360 mm were used, along with metal plates of 100 × 100 × 10 mm perforated with 10 mm diameter holes, 160 mm long steel bolts with a 10 mm diameter, 10 mm diameter nuts, and 10 mm diameter washers, as shown in Figure 5. All specimens were made of new timber, specifically spruce (Picea abies (L.) H. Karst), with a strength class of GL24h, as defined by standard EN 14080 [21]. The metal plates were made of S 235 JR steel, and the bolts were of steel grade 10.9.

2.2. Methods

A total of 12 destructive mechanical tests were tested in the laboratory with 4 different configurations to identify which one allowed the least crushing, with 3 tests conducted for each configuration. The first configuration was without reinforcement (C90SR), meaning no lateral plates were used to confine the specimen. The second configuration involved confining the specimen with 2 lateral metal plates joined by a single central bolt (C90RC). In the third configuration, the lateral metal plates were connected using 2 bolts placed in a horizontal line at a distance of twice the diameter from the edge (from centre of hole to edge, 20 mm) (C90RH). Finally, in the fourth configuration, the metal plates were joined with 2 bolts placed in a vertical line at a distance of twice the diameter (20 mm) from the edge (C90RV), as shown in Figure 6.
The bolt nuts were tightened until the metal plate came into contact with the wood, meaning that no pre-compression was applied to the wood in the direction perpendicular to the grain, as this could significantly affect the results.
The load was applied uniformly distributed on the upper metal plate in the negative vertical axis direction (downward), with a constant movement of the load head until failure was reached at 300 ± 120 s, in accordance with EN 408 [22]. The lower plate was embedded across its entire surface, while the upper plate could only move vertically along the axis (without rotation). The vertical displacement of the movable head was recorded using a Linear Variable Displacement Transducer (LVDT) attached to it.
Once the experimental phase was completed, a 3D model of each perpendicular compression test was developed using Dlubal RFEM software (version 5.34) for finite element (FE) numerical analysis. The goal was to create an FE model that accurately represents the experimental reality, allowing for an increased number of virtual tests. To validate the models, the crushing experienced by the specimen in the load range of 0.1–0.4 Fmax was calculated, as this is the reference range with linear-elastic behavior used in the standard [22]. Since the tests indicated that the maximum load was approximately 70 kN, the reference range of 7–28 kN was used.
In order for the finite element model to accurately represent the experimental behavior it is essential to properly define the material properties. Wood is an anisotropic material that is commonly considered as orthotropic, to simplify its analysis, with the following three orthotropic directions: longitudinal (L), radial (R), and tangential (T). To characterize the behavior of an orthotropic material in the linear-elastic range, it is necessary to define 12 elastic constants: 3 Young’s moduli: EL, ER and ET; 3 shear moduli: GLR, GLT and GRT; and 6 Poisson’s ratios: ʋLR, ʋLT, ʋRT, ʋTR, ʋRL, ʋTL. Of the 12 elastic constants, only 9 are independent; the remaining constants can be determined through known mathematical expressions derived from stress symmetry.
The stiffness values of the material (Young’s modulus and shear modulus) were obtained directly from the EN 14080 [21] standard for the strength class GL24h. Since the standard does not provide Poisson’s ratios, these were taken from the Wood Handbook [23] for Sitka spruce wood. Accordingly, the values used in the 3D finite element model were as follows:
  • EL: 11,500 MPa, ER: 300 MPa, ET: 300 MPa
  • GLR: 650 MPa, GLT: 650 MPa, GRT: 65 MPa
  • ʋLR: 0.372, ʋLT: 0.467, ʋRT: 0.435
  • ʋRL: 0.010, ʋTL: 0.012, ʋTR: 0.435
The mesh density of the finite element model was defined such that the edge length of the finite elements was 10 mm. Additionally, the software was instructed to automatically select either quadrilateral or triangular elements to optimize the element shape and avoid excessive distortion.
Once the FE models were validated, virtual tests were conducted by examining different bolt arrangements and quantities: with 4 bolts in 2 vertical rows, with 6 bolts in 3 vertical rows, and with 9 bolts in 3 vertical rows, as shown in Figure 7. In all configurations, the outer bolts were positioned so that their centers were located at a distance of twice the diameter from the edge (from the center of the hole to edge, 20 mm). The remaining bolts, the interior ones, were evenly distributed within the remaining space.
In the initial reinforcement proposal, the vertical displacement of the lateral plates was considered to occur simultaneously with the crushing of the wood. To improve the performance of the initial reinforcement, a second reinforcement was virtually tested, which prevented the lateral plates from descending. For this, it was assumed that the plates were fixed to the lower stud. The implementation of this improved reinforcement in the field would be feasible without significant difficulties. To account for this mechanical behavior in the FE models, a new displacement constraint was introduced, which consisted of preventing downward movement in the Z direction of the lateral plates.
Furthermore, it is worth noting that some reinforcements have been observed, such as the one shown in Figure 8, consisting of placing a metal plate on the exterior that directly connects the upper stud with the lower one. This reinforcement allows the load transfer from the upper stud to occur directly to the lower stud without the capital (or the sill plate) having to work in perpendicular compression. It is an effective reinforcement, but it is not always feasible to implement, especially when it requires penetrating intermediate floors. The second reinforcement proposed in this study would only connect the capital (or the sill plate) with the lower stud using lateral metal plates.

3. Results and Discussions

3.1. Initial Reinforcement

Figure 9 presents comparative graphs between the three reinforcement configurations and the unreinforced arrangement, derived from the experimental results of the destructive tests. The x-axis shows the displacement (or crushing) of the wood in millimeters, while the y-axis indicates the applied load in kilonewtons (kN).
It is observed that the central reinforcement slightly increases the stiffness by raising the slope of the elastic segment (segment A). The horizontal reinforcement similarly enhances the stiffness in segment A and also increases the load-bearing capacity by surpassing the load value of the unreinforced configuration. Finally, the vertical reinforcement is clearly the most effective of all, as it significantly improves both stiffness and strength.
The failure mode of the wood was similar across all tests, as shown in Figure 10. As the test progressed, the load head compressed the wood in the perpendicular direction until the longitudinal fibers fractured (by shear) and then continued compressing in the perpendicular direction until the material was fully plastified and densified.
The metal plates demonstrated sufficient thickness to prevent significant deformations during the tests. In contrast, the metal bolts exhibited different behaviors depending on the type of test. In the tests with central reinforcement (C90RC) and horizontal reinforcement (C90RH), the bolts operated exclusively in tension by preventing the separation of the metal plates. The position of the bolts along the specimen’s axis allowed the upper and lower compressions to be balanced without inducing any bending in the bolts (after the tests, the bolts could be manually removed from the holes without effort). However, in the tests with vertical reinforcement (C90RV), the bolts primarily experienced bending. The load transmitted from the end of the specimen, where the bolt was located, was greater than that from the opposite, more distant end, which was attenuated; this caused the bolt to bend. The upper bolt experienced a positive moment (concave deformation), while the lower bolt experienced a negative moment (convex deformation), as shown in Figure 11. This behavior was evident because the bolts were completely bent after the test (making manual recovery impossible).
The behavior of the bolts adequately explains the graphs shown in Figure 9. Thus, with 2 bolts arranged horizontally, the performance was expected to improve compared to a single bolt; however, this improvement was practically imperceptible because sufficiently thick plates were used. In other words, the metal plates experienced the stresses from the wood as it attempted to deform transversely, but they hardly deformed at all. Using thinner plates would likely have made the difference in crushing between the two types of tests more evident. On the other hand, with the vertical arrangement of the bolts, the crushing was less because the bolts provided additional stiffness (their own flexural rigidity) by working together with the wood.
To validate the FE models, the strains recorded during the experimental tests were compared with those computed by the software within the load interval of 0.1–0.4 Fmax (7–28 kN). The obtained results are presented in Table 1.
It is observed that, as previously discussed, the best configuration tested in the laboratory is C90RV, achieving a reduction in crushing of up to 20% compared to the unreinforced specimen, as shown in Figure 10. Comparing the numerically obtained values with the experimental results indicates that the finite element models exhibit crushings similar to those observed in reality. Furthermore, the percentage of improvement observed when transitioning from one configuration to the next is also quite similar. The minor discrepancies found are due to the stiffness values incorporated into the numerical models correspond to a GL24h class; however, due to the heterogeneity typically present in wood, the properties of the specimens used do not precisely match these normalized stiffness values. Therefore, it can be concluded that the developed models have sufficient accuracy to reliably conduct virtual testing.
In Table 1, the crush values obtained from the virtual tests of configurations C904P, C906P, and C909P are also presented. The reduction in crushing continues to increase when transitioning between configurations, from 11% in C90RC up to 26% in C909P.
The reinforcements carried out by other researchers on new construction (using pin-like elements arranged parallel to the load) achieved much greater stiffness increases [6]. For example, by using 6 metal screws with a length 10 times their diameter, a 55% reduction in deformation was observed in the linear-elastic segment.
Therefore, from a practical standpoint, the reduction achieved with the initial reinforcement appears insufficient to justify the high number of bolts required for this type of reinforcement. In other words, the proposed reinforcement to reduce wood crushing through confinement perpendicular to the grain is ineffective.

3.2. Enhanced Reinforcement

After confirming that the initial reinforcement, with its various configurations, did not significantly reduce wood crushing through confinement, an improved version of this reinforcement was proposed. The enhancement consisted simply of preventing the side plates from descending with the wood crushing. To achieve this, it was necessary for the plates to be continuous with the lower stud, thereby preventing their vertical displacement. An example of this solution is shown in Figure 12.
This reinforcement aimed to directly activate the bending action of the bolts, regardless of their position, thereby ensuring that the stiffness of the reinforcement was shared between the lateral confinement of the wood and the bending of the metal bolts, as shown in Figure 13.
In the FE models the improved reinforcement was simulated by adding a restriction to the vertical movement of the lateral plates. Specifically, vertical movement was prevented exclusively at the lower surface of the lateral plates to allow for possible bulging when confining the wood. The results are shown in Table 2.
It was observed that the improved reinforcement performed significantly better than the initial reinforcement, as it allowed for a reduction in crushing of up to 53% (in configuration C909P). Additionally, the configurations with 4 and 6 bolts already achieved a substantial reduction in crushing of 46% and 50%, respectively. These values are closer to those obtained in other studies for reinforcements in new construction [6].
Deriving a mathematical equation that relates to the crush reduction achieved for each configuration is challenging. This difficulty arises from the fact that not all configurations have the same number of bolts aligned with the direction of load application, i.e., the vertical axis. Nonetheless, it would be feasible to establish such a relationship for configurations C90RV, C904P, and C906P, as all of them feature two bolts (one at each end) aligned with the vertical load direction. Configuration C90RV has one line of two vertical bolts at the ends, configuration C904P has two lines of two bolts each, and configuration C906P has three lines of two bolts each. Thus, a relationship can be established between the reduction in bearing deformation and the number of lines (each consisting of two vertical bolts located at the ends), using the following logarithmic equation (Equation (1)). To do so, a simple regression analysis was performed for this purpose, yielding a coefficient of determination of R2 = 0.998.
Crush reduction (%) = 10.989·ln (nº vertical lines with 2 bolts at the ends) + 38.103
On the other hand, in order to advance the practical application of the results, a simple methodology was developed to size the bolts (in the improved reinforcement) for any type of geometry with proportions similar to those in this study, as shown in Table 3. To do this, the actual load (Qreal) applied to each bolt in the FE models was obtained and compared with the load corresponding to its tributary area (Qtrib). The goal was to equalize both loads, for which a multiplying coefficient called kload was determined. Thus, when designing a reinforcement, it would be sufficient to multiply kload by Qtrib to obtain Qreal, which is the load used to size the bolts, as expressed in Equation (2).
Qreal = kload·Qtrib
As previously mentioned, Qreal was obtained from the FE models. Specifically, the maximum deflection of each bolt was measured, and subsequently, Qreal was obtained by Equation (3) (elastic equation for a beam with fixed ends under a uniformly distributed load).
Qreal = f·384·E·I/L4
where Qreal is the load acting on the bolt in N/mm, f is the deflection at the center of the span in mm, E is the elastic modulus of the bolt in N/mm2 (210,000 N/mm2), I is the moment of inertia of the bolt in mm4 (491 mm4), and L is the length of the bolt in mm (120 mm).
On the other hand, Qtrib was calculated directly considering the tributary area of the bolt. With a diameter of 10 mm and a length of 120 mm, the tributary area is 10 × 120 = 1200 mm2. Since the total area where the load is applied is 120 × 120 = 14,400 mm2, and the applied load is 28,000 N, Qtrib is obtained using the expression: (1200/14,400) × 28,000 = 2333 N. Per unit length, this results in 2333/120 = 19.44 N/mm.
For example, if one wishes to size a bolt in the upper row within the C906P reinforcement configuration that receives a total load of 40,000 kN applied over an area of 100 × 100 mm, the following approach would be used. Considering bolts with a diameter of 8 mm and a length of 100 mm, Qtrib is calculated as (8 × 100)/(100 × 100) × 40,000/100 = 32 N/mm. To obtain Qreal, simply apply Equation (2): 1.87 × 32 = 59.84 N/mm.
As observed in Table 3, the load factor kload for the upper bolts is greater than one, which would increase the load considered in the calculation, while for the lower bolts it is less than one. Since it is common to use bolts of the same diameter throughout, the diameter of the upper bolts would be used, as they are more heavily loaded.
Finally, by comparing Table 2 and Table 3, it is possible to identify the most suitable configuration, that is, the one that allows for the greatest reduction in wood crushing while also avoiding the use of numerous bolts and ensuring that they are not excessively loaded. In this regard, the C904P configuration appears to be the most optimized, as it reduces crushing by 46% and uses only 4 bolts.

4. Conclusions

The feasibility of reducing the crushing of compressed wood pieces in the direction perpendicular to the grain through confinement with lateral metal plates was analyzed. Destructive mechanical tests were conducted with different reinforcement arrangements: unreinforced (C90SR), reinforcement with lateral plates secured by a single central bolt (C90RC), with 2 horizontal central bolts (C90RV), and with 2 vertical central bolts (C90RV). Additionally, several finite element (FE) models were designed to extend the experimental campaign virtually by simulating the placement of 4, 6, and 9 bolts.
With the initial reinforcement proposed, the results showed a reduction in crushing of only 20%, 23%, and 26% with the placement of 4, 6, and 9 bolts, respectively. When comparing these values to other types of reinforcement, such as the use of pin-like elements arranged in the load direction, it indicated that the effectiveness of the reinforcement was quite limited.
In order to improve the performance of the initial reinforcement, an enhanced reinforcement was designed. This consisted simply in preventing the vertical displacement of the side plates, for which they were considered fixed to the lower stud. In the initial reinforcement, this displacement occurred jointly with the crushing of the wood. The performance of the enhanced reinforcement increased significantly, achieving a reduction in wood crushing of 46%, 50%, and 53% with the installation of 4, 6, and 9 bolts, respectively. Finally, taking into account the amount of material used, the most suitable configuration would be C904P, which uses only 4 bolts.
Additionally, for the configurations studied in the enhanced reinforcement, the load distribution among the bolts was analyzed to facilitate their design. As a result, a multiplication factor was obtained that allows determining the actual load carried by each bolt based on its position.
It can be concluded that this work presents a simple solution to reduce the crushing of wood components placed on-site, where access to the top and bottom faces is not possible. In new construction, it is more appropriate to use pin-like elements, as demonstrated by previously published research in the scientific literature. An additive model combining both reinforcement methods could improve the results; however, this would be the subject of analysis in future research. In this context, the economic cost of using a large number of reinforcement elements should be considered.
The experimental tests were conducted on pieces that were not previously compressed. In components placed on-site, already pre-crushed by perpendicular compression, the effectiveness of the lateral confinement reinforcement is likely to be lower. In the future, the experimental testing campaign will be expanded to include reclaimed wood with varying degrees of crushing, in order to adjust the results of this research, also considering the influence of the species, the density or number of bolts, their size and arrangement. Moreover, the influence of the adhesives used in the manufacture of glulam could be analyzed, as recent research has demonstrated that the adhesives used in Laminated Veneer Lumber (LVL) production can significantly contribute to enhancing its strength in aspects that are not typically considered in the structural verifications [24].

Author Contributions

Conceptualization, J.R.A.-Z. and L.G.-C.; methodology, J.R.A.-Z. and L.G.-C.; software, J.R.A.-Z.; validation, J.R.A.-Z. and L.G.-C.; formal analysis, J.R.A.-Z. and L.G.-C.; investigation, J.R.A.-Z. and L.G.-C.; resources, J.R.A.-Z.; data curation, J.R.A.-Z.; writing—original draft preparation, J.R.A.-Z. and L.G.-C.; writing—review and editing, J.R.A.-Z. and L.G.-C.; visualization, J.R.A.-Z. and L.G.-C.; supervision, J.R.A.-Z. and L.G.-C.; project administration, J.R.A.-Z.; funding acquisition, J.R.A.-Z. All authors have read and agreed to the published version of the manuscript.

Funding

This research received no external funding.

Acknowledgments

The authors would like to express their gratitude to Miguel Luengo Escacena for his collaboration in the preparation and execution of the mechanical tests, to Enrique Nuere Matauco for generously sharing his expertise and raising the issue addressed in this work, and to Dlubal Software GmbH.

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

The following abbreviations are used in this manuscript:
FEFinite Element
LVDTLinear Variable Displacement Transducer
LVLLaminated Veneer Lumber

References

  1. Leijten, A.J.M.; Franke, S.; Quenneville, P.; Gupta, R. Bearing Strength Capacity of Continuous Supported Timber Beams: Unified Approach for Test Methods and Structural Design Codes. J. Struct. Eng. 2012, 138, 266–272. [Google Scholar] [CrossRef][Green Version]
  2. Hassan, K.A.; Hussain, T.; Arman, K. Compression Perpendicular to Grain in Timber-Bearing Strength for a Sill Plate. Master’s Thesis, Linnaeus University, Växjö, Sweden, 2014. [Google Scholar]
  3. Brol, J.; Kubica, J.; Weglorz, M. The Problem of Compressive Strength in Direction Perpendicular to the Grains on Example of Tests of the Load-Bearing Capacity of the Continuously Supported Timber-Frame Sill Plates. Materials 2020, 13, 1160. [Google Scholar] [CrossRef] [PubMed]
  4. Dietsch, P.; Brandner, R. Self-tapping screws and threaded rods as reinforcement for structural timber elements-A state-of-the-art report. Constr. Build. Mater. 2015, 97, 78–89. [Google Scholar] [CrossRef]
  5. Harte, A.M.; Dietsch, P. Reinforcement of Timber Structures: A State-of-the-Art Report; Shaker Verlag GmbH: Düren, Germany, 2015. [Google Scholar]
  6. Dietsch, P.; Rodemeier, S.; Blaß, H.J. Transmission of perpendicular to grain forces using self-tapping screws. In Proceedings of the INTER International Conference on Timber Engineering Research, Tacoma, WA, USA, 26–29 August 2019. [Google Scholar]
  7. Aloisio, A.; Ussher, E.; Fragiacomo, M.; Tomasi, R. Capacity models for timber under compression perpendicular to grain with screw reinforcement. Eur. J. Wood Wood Prod. 2023, 81, 633–654. [Google Scholar] [CrossRef]
  8. Tomasi, R.; Aloisio, A.; Hånde, E.A.; Thunberg, K.R.; Ussher, E. Experimental investigation on screw reinforcement of timber members under compression perpendicular to the grain. Eng. Struct. 2023, 275, 115163. [Google Scholar] [CrossRef]
  9. Kanagaki, D.; Totsuka, M.; Hirashima, T.; Kato, H. Reinforcement for compression perpendicular to grain in column-base and -beam joints using partially threaded and fully threaded screws. Eng. Struct. 2025, 324, 119334. [Google Scholar] [CrossRef]
  10. Alinoori, F.; Moshiri, F.; Sharafi, P.; Samali, B. Reinforcement methods for compression perpendicular to grain in top/bottom plates of light timber frames. Constr. Build. Mater. 2020, 231, 116377. [Google Scholar] [CrossRef]
  11. O’Ceallaigh, C.; Conway, M.; Mehra, S.; Harte, A.M. Modified wood as compression reinforcement of timber perpendicular to the grain. In Proceedings of the WCTE 20-21, Santiago, Chile, 9–12 August 2021. [Google Scholar]
  12. Conway, M.; Mehra, S.; Harte, A.M.; O’Ceallaigh, C. Densified wood dowel reinforcement of timber perpendicular to the grain: A pilot study. J. Struct. Integr. Maint. 2021, 6, 177–186. [Google Scholar] [CrossRef]
  13. O’Ceallaigh, C.; Conway, M.; Mehra, S.; Harte, A.M. Numerical Investigation of Reinforcement of Timber Elements in Compression Perpendicular to the Grain using Densified Wood Dowels. Constr. Build. Mater. 2021, 288, 122990. [Google Scholar] [CrossRef]
  14. Verbist, M.; Branco, J.M.; Nunes, L. Characterization of the Mechanical Performance in Compression Perpendicular to the Grain of Insect-Deteriorated Timber. Buildings 2020, 10, 14. [Google Scholar] [CrossRef]
  15. Pasca, D.P.; Massaro, F.M.; De Santis, Y.; Stamatopoulos, H.; Ljungdahl, J.; Aloisio, A. Deformation level and specimen geometry in compression perpendicular to the grain of solid timber, GLT and CLT timber products. Eng. Struct. 2024, 321, 118972. [Google Scholar] [CrossRef]
  16. Adibaskoro, T.; Sołowski, W.; Hostikka, S. Experimental dataset for the macro-scale compression of Norway Spruce perpendicular to grain direction. Data Brief 2022, 40, 107742. [Google Scholar] [CrossRef] [PubMed]
  17. Li, W.; Zhang, Z.; Wang, X.; Mei, C.; Van Acker, J.; Van den Bulcke, J. Understanding the effect of growth ring orientation on the compressive strength perpendicular to the grain of thermally treated wood. Wood Sci. Technol. 2021, 55, 1439–1456. [Google Scholar] [CrossRef]
  18. Adusumalli, R.B.; Raghavan, R.; Ghisleni, R.; Zimmermann, T.; Michler, J. Deformation and failure mechanism of secondary cell wall in Spruce late wood. Appl. Phys. A Mater. Sci. Process. 2010, 100, 447–452. [Google Scholar] [CrossRef]
  19. Wu, G.F.; Sun, J.C.; Fu, F.; Ren, H.Q. Review of mechanical behavior of wood under compression load perpendicular-to-grain. Chin. J. Wood Sci. Technol. 2022, 36, 1–8. [Google Scholar] [CrossRef]
  20. Zhong, Y.; Wu, G.; Fu, F.; Shen, Y.; Sun, J.; Ren, H.; Guo, J. A novel constitutive model for the porosity related super-large deformation and anisotropic behavior of wood under perpendicular to grain compression. Wood Sci. Technol. 2022, 56, 553–571. [Google Scholar] [CrossRef]
  21. EN 14080; Timber Structures—Glued Laminated Timber and glued Solid Timber—Requirements. European Committee for Standarization (CEN): Brussels, Belgium, 2013.
  22. EN 408:2010+A1; Timber Structures—Structural Timber and Glued Laminated Timber—Determination of Some Physical and Mechanical Properties. European Committee for Standardization (CEN): Brussels, Belgium, 2012.
  23. Kretschmann, D.E. Chapter 5: Mechanical properties of wood. In Wood Handbook: Wood as an Engineering Material; General technical Report FPL-GTR-190; United States Department of Agriculture (USDA), Forest Product Laboratory: Madison, WI, USA, 2010. [Google Scholar]
  24. Sudo, R.; Miyamoto, K.; Ido, H. Quantitative assessment of adhesive effects on partial and full compressive strength of LVL in the edge-wise direction. J. Wood Sci. 2025, 71, 19. [Google Scholar] [CrossRef]
Figure 1. Concentration of compressive stress perpendicular to the grain areas in timber-frame wall.
Figure 1. Concentration of compressive stress perpendicular to the grain areas in timber-frame wall.
Heritage 08 00368 g001
Figure 2. Examples of perpendicular compression crushing in real buildings. Left: Building at 6 Tesoro Street, crushing of the capital due to lower stud. Right: Building at 6 Tesoro Street, crushing of the capital due to lower stud and of the sill plate due to upper stud.
Figure 2. Examples of perpendicular compression crushing in real buildings. Left: Building at 6 Tesoro Street, crushing of the capital due to lower stud. Right: Building at 6 Tesoro Street, crushing of the capital due to lower stud and of the sill plate due to upper stud.
Heritage 08 00368 g002
Figure 3. Diagram of wood behavior under perpendicular compression.
Figure 3. Diagram of wood behavior under perpendicular compression.
Heritage 08 00368 g003
Figure 4. Lateral bulging of wood after perpendicular compression test (the red arrow indicates the direction of the widening cross-section).
Figure 4. Lateral bulging of wood after perpendicular compression test (the red arrow indicates the direction of the widening cross-section).
Heritage 08 00368 g004
Figure 5. Material for performing perpendicular compression tests.
Figure 5. Material for performing perpendicular compression tests.
Heritage 08 00368 g005
Figure 6. Perpendicular compression tests. From top to bottom: C90SR, C90RC, C90RH, C90RV.
Figure 6. Perpendicular compression tests. From top to bottom: C90SR, C90RC, C90RH, C90RV.
Heritage 08 00368 g006aHeritage 08 00368 g006b
Figure 7. Finite element models: C90SR, C90RC, C90RH, C90RV, C904P, C906P, and C909P. Metal elements are represented in blue, wood specimens in orange. The wood grain direction is the X direction, while the load application direction is the Z direction (downward).
Figure 7. Finite element models: C90SR, C90RC, C90RH, C90RV, C904P, C906P, and C909P. Metal elements are represented in blue, wood specimens in orange. The wood grain direction is the X direction, while the load application direction is the Z direction (downward).
Heritage 08 00368 g007
Figure 8. Building at 86 Alcalá Street. Reinforcement using an external plate that directly connects the upper and lower studs.
Figure 8. Building at 86 Alcalá Street. Reinforcement using an external plate that directly connects the upper and lower studs.
Heritage 08 00368 g008
Figure 9. Comparative graphs of perpendicular compression tests with central reinforcement (C90RC), horizontal reinforcement (C90RH), and vertical reinforcement (C90RV) arrangements, compared to the unreinforced arrangement (C90SR).
Figure 9. Comparative graphs of perpendicular compression tests with central reinforcement (C90RC), horizontal reinforcement (C90RH), and vertical reinforcement (C90RV) arrangements, compared to the unreinforced arrangement (C90SR).
Heritage 08 00368 g009aHeritage 08 00368 g009b
Figure 10. Wood failure mode.
Figure 10. Wood failure mode.
Heritage 08 00368 g010
Figure 11. Vertical displacement (in mm) of the metal elements in the C90RV configuration under a distributed load of 28 kN on the top plate (×40 zoom). The C90TV configuration in this figure is the same as in Figure 7, but in this case, the wooden piece has been hidden to better observe the deformation of the metal elements.
Figure 11. Vertical displacement (in mm) of the metal elements in the C90RV configuration under a distributed load of 28 kN on the top plate (×40 zoom). The C90TV configuration in this figure is the same as in Figure 7, but in this case, the wooden piece has been hidden to better observe the deformation of the metal elements.
Heritage 08 00368 g011
Figure 12. Enhanced reinforcement.
Figure 12. Enhanced reinforcement.
Heritage 08 00368 g012
Figure 13. Vertical displacement (in mm) of the metal elements in the C909P configuration under a distributed load of 28 kN on the top plate (×40 zoom). The C909P configuration in this figure is the same as in Figure 7, but in this case, the wooden piece has been hidden to better observe the deformation of the metal elements.
Figure 13. Vertical displacement (in mm) of the metal elements in the C909P configuration under a distributed load of 28 kN on the top plate (×40 zoom). The C909P configuration in this figure is the same as in Figure 7, but in this case, the wooden piece has been hidden to better observe the deformation of the metal elements.
Heritage 08 00368 g013
Table 1. Reduction in crushing (within linear-elastic range) achieved with the initial reinforcement.
Table 1. Reduction in crushing (within linear-elastic range) achieved with the initial reinforcement.
Test TypeExperimental Results (Side Plates No Fixed to the Lower Column)FE Results (Side Plates No Fixed to the Lower Column)
crushing (mm)crush reduction (%)crushing (mm)crush reduction (%)
C90SR0.495---0.415---
C90RC0.439110.36712
C90RH0.436120.36213
C90RV0.394200.34118
C904P------0.33020
C906P------0.31823
C909P------0.30926
Table 2. Reduction in crushing (within linear-elastic range) achieved with the enhanced reinforcement.
Table 2. Reduction in crushing (within linear-elastic range) achieved with the enhanced reinforcement.
Test TypeFE Results (Side Plates Fixed to the Lower Stud)
crushing (mm)crush reduction (%)
C90SR0.415---
C90RC0.28731
C90RH0.26935
C90RV0.25638
C904P0.22646
C906P0.20850
C909P0.19353
Table 3. Load multiplier factor, kload, for bolt sizing in the enhanced reinforcement.
Table 3. Load multiplier factor, kload, for bolt sizing in the enhanced reinforcement.
C90RCC90RHC90RVC904PC906PC909P
Central boltBoth
bolts
Upper boltLower boltUpper boltsLower boltsUpper boltsLower boltsUpper boltsCentral boltsLower bolts
f (mm)0.1780.1620.2510.0750.2130.0660.1900.0500.1620.0860.050
Qreal (N/mm)33.9830.9347.9114.3240.6612.6036.279.5430.9316.429.54
Qtrib (N/mm)19.4419.4419.4419.4419.4419.4419.4419.4419.4419.4419.44
kload1.751.592.460.742.090.651.870.491.590.840.49
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Aira-Zunzunegui, J.R.; Gonzalo-Calderón, L. Lateral Confinement Reinforcement of Timber Under Perpendicular-to-Grain Compression. Heritage 2025, 8, 368. https://doi.org/10.3390/heritage8090368

AMA Style

Aira-Zunzunegui JR, Gonzalo-Calderón L. Lateral Confinement Reinforcement of Timber Under Perpendicular-to-Grain Compression. Heritage. 2025; 8(9):368. https://doi.org/10.3390/heritage8090368

Chicago/Turabian Style

Aira-Zunzunegui, Jose Ramón, and Laura Gonzalo-Calderón. 2025. "Lateral Confinement Reinforcement of Timber Under Perpendicular-to-Grain Compression" Heritage 8, no. 9: 368. https://doi.org/10.3390/heritage8090368

APA Style

Aira-Zunzunegui, J. R., & Gonzalo-Calderón, L. (2025). Lateral Confinement Reinforcement of Timber Under Perpendicular-to-Grain Compression. Heritage, 8(9), 368. https://doi.org/10.3390/heritage8090368

Article Metrics

Back to TopTop