Next Article in Journal
AI-Assisted Circuit Digital Twin Reproducing Ultrasound Waves in Human Tissues
Next Article in Special Issue
Full-Topology Real-Time Simulation Modeling Method and the Application in Super-Synchronous Oscillation Analysis of Large-Scale Offshore Wind Farms
Previous Article in Journal
RASC: Region-Aware Self-Calibration for Dense 2D Sensor Arrays
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Active Resonance Suppression Strategy for Hybrid Multi-Infeed HVDC Receiving-End Grid with LCC and MMC

1
State Grid Zhejiang Electric Power Co., Ltd., Research Institute, Hangzhou 310014, China
2
College of Electrical Engineering, Zhejiang University, Hangzhou 310027, China
*
Author to whom correspondence should be addressed.
Electronics 2026, 15(12), 2725; https://doi.org/10.3390/electronics15122725
Submission received: 25 May 2026 / Revised: 15 June 2026 / Accepted: 18 June 2026 / Published: 20 June 2026
(This article belongs to the Special Issue Advanced Power Conversion Technologies for Smart Grids)

Abstract

As renewable energy is increasingly integrated via high-voltage direct current (HVDC) transmission, hybrid multi-infeed receiving-end grids containing both line-commutated converters (LCC) and modular multilevel converters (MMC) have become common, and wideband resonance problems in power-electronized networks are growing more prominent. This paper proposes an active resonance analysis and suppression strategy for such systems. First, a wideband current source converter model and a wideband voltage source converter model are adopted to describe the LCC and MMC, respectively, and a positive-sequence s-domain model of the system is established. A two-stage s-domain nodal admittance matrix method is then applied to efficiently determine the wideband resonance modes and the corresponding mode shape eigenvectors. A dual criterion combining the matching degree between resonance frequencies and LCC characteristic harmonics with the modal damping ratio identifies high-risk resonance modes. On this basis, an active damping strategy that realizes a parallel virtual resistance on the AC side through MMC supplementary control is proposed, together with a quantitative design method for the virtual conductance. At the control implementation level, a modulation wave reconstruction bypass injection scheme superimposes the high-frequency damping command directly in the αβ stationary reference frame, thereby bypassing the PI controller and reducing the amplitude attenuation and phase distortion caused by the high-frequency limitation of the integral path. PSCAD/EMTDC simulation results on an IEEE 9-bus test system demonstrate that the proposed strategy effectively suppresses resonance amplification and wideband power oscillations excited by LCC characteristic harmonics without affecting the fundamental power transmission.

1. Introduction

Driven by the “dual carbon” target (carbon peak and carbon neutrality), large-scale renewable generation is increasingly delivered to receiving-end power grids via HVDC transmission. The eastern China power grid has evolved into a highly power-electronized configuration featuring multiple DC infeeds and AC/DC hybridization [1]. In this context, the coexistence of line-commutated converters (LCC) and modular multilevel converters (MMC) introduces more complex dynamic behavior, and the resulting wideband oscillations and harmonic resonance have become critical threats to secure system operation [2,3]. Recent converter studies have also shown that modulation strategy, harmonic ripple, and switching-frequency constraints can substantially affect converter-side harmonic behavior [4], which further motivates a network-level resonance analysis framework for hybrid AC/DC receiving-end grids.
Many wideband oscillation events have been reported in power-electronized power grids. For instance, subsynchronous oscillations in the range of 3–10 Hz occurred in the Guyuan area of North China [5,6]; harmonic amplification in electrical networks can be interpreted through modal harmonic analysis [7]; and high-frequency oscillations from hundreds to thousands of Hz have been observed in flexible DC projects and MMC-HVDC systems under weak grids [8]. These cases indicate that the resonance characteristics of power grids cover a wide frequency band from subsynchronous to high frequencies, rooted in the dynamic interaction between converter control systems and grid impedance [5,6].
Regarding the oscillation mechanism, two main explanations are commonly discussed. One is the “negative resistance” explanation, which attributes oscillation growth to a converter impedance whose real part becomes negative in certain frequency bands because of control interaction and delay effects [9,10]. This explanation has been useful for interpreting some source–load impedance interactions. However, when it is used as the sole mechanism for large-scale power-electronized grids, it may reduce the system to a local impedance pair and overlook weakly damped network modes distributed over many buses. Therefore, the present paper does not use negative resistance as the theoretical basis for wideband oscillation analysis; it is treated as a related converter impedance viewpoint rather than as the mechanism adopted here.
The second is the “harmonic amplification” mechanism, which explains wideband oscillations from the perspective of network resonance [7]. According to this theory, the observed wideband oscillations are forced harmonic responses amplified by weakly damped resonance modes inherent in the grid. The core arguments include: (1) power electronic devices can be represented by wideband voltage source or current source converter models, where converter nonlinearities are reflected by harmonic voltage or current sources and the harmonic order can be regarded as a continuous variable; (2) the positive-sequence network model is generally applicable for balanced harmonic amplification analysis; (3) actual power grids have relatively small resistive components, and weakly damped resonance modes generally exist; (4) the resonance peak voltage is inversely proportional to the modal damping ratio; (5) the voltage distribution at the resonance frequency is described by the mode shape eigenvector corresponding to the zero eigenvalue of the s-domain nodal admittance matrix.
Regarding resonance stability analysis methods, the classical state-space eigenvalue analysis [11,12] is widely used but encounters difficulties in modeling high-proportion power electronic systems, including high order and inability to handle distributed-parameter components [13]. Impedance-based frequency-domain analysis has therefore gained considerable attention [14,15,16], and references [3,8,17] applied it to frequency-domain stability analysis of voltage source converters and MMC-HVDC systems, respectively. However, conventional impedance methods generally focus on point-to-point stability and cannot capture the multi-modal oscillation characteristics of the entire network and the participation levels of different components.
The s-domain nodal admittance matrix method provides an effective approach to address the above problems. References [18,19] applied it to the modal analysis of complex systems, and frequency-dependent network components can also be represented in the s domain [20]. Its theoretical foundation, proved in [21], states that the s-domain loop impedance determinant, the s-domain nodal admittance determinant, and the characteristic polynomial of the state equation of a linear time-invariant network share the same non-zero zeros. Therefore, grid resonance modes can be uniformly expressed as the zeros of det ( Y node ( s ) ) , where the real part corresponds to damping and the imaginary part to oscillation frequency. On this basis, two-stage s-domain nodal-admittance calculation and frequency-domain modal analysis methods can be used to obtain resonance frequencies, damping ratios, mode shape eigenvectors, and component sensitivity indices [5,7,18,19].
Most existing studies are limited to pure AC systems or single-converter configurations. In LCC-MMC hybrid multi-infeed receiving-end systems, however, the analytical difficulty is higher because the two converter types play different roles in the same resonance path: 12-pulse LCCs continuously inject characteristic harmonic currents such as the 11th and 13th orders, whereas MMCs connected close to the resonance area can be used as controllable voltage source converters but may exhibit high-frequency phase lag due to digital delays and finite current-loop bandwidth. The practical challenge is therefore not only to calculate the resonance modes, but also to link the mode shape eigenvectors, LCC harmonic excitation frequencies, and MMC controllable locations into a controller design procedure. The wideband resonance problems caused by these combined effects still lack systematic investigation. In particular, how to use the resonance structure information obtained from the s-domain nodal admittance matrix to guide the design of MMC active damping controllers still lacks a complete methodological framework.
For resonance suppression, passive filters are bulky, have fixed tuning characteristics, and are sensitive to parameter deviations; active power filters require additional hardware with limited capacity. Virtual impedance (active damping) control emulates a desired impedance through supplementary control without extra hardware to enhance system damping, and has attracted considerable attention in recent years [22,23]. However, when high-frequency damping commands are introduced into the PI vector current inner loop, the integral path introduces amplitude attenuation and phase shift at high frequencies, causing the actual injected damping to deviate substantially from the design target.
Based on the above background, this paper proposes an active resonance suppression strategy for LCC-MMC hybrid multi-infeed receiving-end systems. The main contributions include:
  • LCC wideband current source model and MMC wideband voltage source model are adopted to establish the positive-sequence s-domain model of the system, and the two-stage s-domain nodal admittance matrix method is used to efficiently determine wideband resonance modes and mode shape eigenvectors;
  • By combining the matching degree of LCC characteristic harmonics with the modal damping ratio, a high-risk resonance mode identification criterion is formulated, providing clear targets for active suppression;
  • A modulation wave bypass injection control architecture is proposed to separate the high-frequency damping channel from the fundamental vector control channel. The method reduces PI-loop attenuation and phase lag at the target frequencies, while its open-loop damping frequency implementation is treated with explicit current/modulation limits and discussed as a robustness limitation.

2. S-Domain Nodal Admittance Matrix Method

2.1. Theoretical Basis

The method used in this paper is a frequency-domain resonance modal analysis method based on wideband converter source equivalents and the positive-sequence s-domain network. Converter switching, commutation overlap, capacitor voltage balancing, and digital implementation details are not ignored physically; their externally observed effect on the AC network is represented by harmonic voltage or current source behavior together with the equivalent high-frequency path of the converter. Therefore, the calculated modes should be interpreted as resonance modes of the harmonic network that amplify converter-generated harmonic excitations. The detailed nonlinear switching and control behavior is retained in the PSCAD/EMTDC model in Section 6, which verifies whether the active damping controller designed from the modal information suppresses the resulting harmonic amplification.
It was proved in [21] that for a linear time-invariant network, the s-domain loop impedance matrix determinant det ( Z loop ( s ) ) , the s-domain nodal admittance matrix determinant det ( Y node ( s ) ) , and the characteristic polynomial of the system state equation det ( s I A ) have the same non-zero zeros. The resonance modes of a power network, i.e., the eigenroots of the system state equation, are equivalent to the zeros of det ( Y node ( s ) ) , with the real part being the damping factor and the imaginary part being the resonance angular frequency.
Based on this theorem, the s-domain nodal voltage equation can be written as
Y node ( s ) V node ( s ) = I node ( s )
where V node ( s ) is the s-domain nodal voltage vector and I node ( s ) is the s-domain nodal injection current vector. This method naturally supports distributed-parameter and frequency-dependent components and is an effective means for analyzing wideband resonance stability in complex power grids.

2.2. Two-Stage Resonance Mode Calculation Method

To avoid the difficulty of directly solving the zeros of a high-order s-domain matrix determinant, this paper uses a two-stage s-domain nodal admittance matrix resonance mode calculation method developed from the modal harmonic analysis framework in [5,7,18,19].

2.2.1. Stage 1: Resonance Frequencies and Mode Shape Eigenvectors of the Undamped Network

Ignoring all resistive (conductance) parameters of the system yields an undamped network, where the eigenroots degenerate to purely imaginary numbers s i = j ω i , and the s-domain nodal admittance matrix becomes
Y node ( j ω i ) = j B node ( j ω i )
where B node is the real symmetric nodal susceptance matrix. Since s i is an eigenroot, det ( B node ( j ω i ) ) = 0 must hold. By scanning det ( B node ( j 2 π f ) ) over the target frequency band [ f st , f end ] with a certain step, zero-crossings can be detected by checking the sign change of the product between adjacent frequency points, and linear interpolation yields the undamped resonance frequency f i .
For the i-th resonance mode, QR decomposition is performed on B node ( j ω i ) to extract the right eigenvector M 1 = [ m 1 , , m n ] T corresponding to the zero eigenvalue, which is the mode shape eigenvector of this mode and is normalized to a maximum magnitude of 1. The mode shape eigenvector describes the relative amplitude and phase relationship of voltages at each node at the resonance frequency. The node k * with the largest magnitude is both the best observable node and the best controllable node for this mode, representing the optimal injection location for active damping control.

2.2.2. Stage 2: Identification of Damped Eigenroots Using the Test Signal Method

In the complete system with all damping components considered, let the best controllable and observable node of the i-th mode be k * . A unit test current is injected at this node, and the current division ratio η shunt ( s ) of a parallel branch connected to it is calculated. From Cramer’s rule, the transfer function between the test injection and any selected branch current can be written as a ratio between a cofactor polynomial of Y node ( s ) and det ( Y node ( s ) ) . Hence, after canceling any common factors that are not observable from the selected branch, the denominator of η shunt ( s ) contains the zeros of det ( Y node ( s ) ) that participate in the measured response. The proportionality factor is frequency-dependent only through numerator/cofactor terms and does not change the local pole locations used for modal estimation.
Select five frequency points within ±3% of the undamped resonance frequency f i , calculate the current division ratio, and perform fitting with a second-order rational fraction:
η shunt ( s ) b 2 s 2 + b 1 s + b 0 s 2 + a 1 s + a 0
The second-order approximation assumes that the target mode is locally dominant and that other modes are sufficiently far away in frequency or weakly observable at node k * . This assumption is checked by using the Stage-1 scan to confirm mode separation and by comparing the fitted resonance frequency with the harmonic peaks observed in PSCAD/EMTDC. If two modes overlap within the fitting band, the fitting order or the frequency window must be increased. Solving the denominator polynomial yields the eigenroot s i = σ i ± j ω i of this mode, from which the resonance frequency f i = ω i / ( 2 π ) and the damping ratio can be calculated as
ζ i = | σ i | σ i 2 + ω i 2
The core advantage of the two-stage method is that it reduces the originally two-dimensional zero search in the s-plane to a one-dimensional scan along the imaginary axis, followed by rational fraction fitting within a narrow neighborhood. Each stage employs well-established sinusoidal steady-state circuit analysis techniques, significantly reducing the computational burden.

3. S-Domain Modeling of Hybrid Multi-Infeed HVDC Receiving-End System

3.1. System Structure

Based on a modified IEEE 9-bus topology, this paper constructs a hybrid multi-infeed HVDC receiving-end system containing LCC and MMC, as shown in Figure 1. The MMC-HVDC is connected to bus 7, the LCC-HVDC to bus 8, the fundamental frequency is 50 Hz, and the AC rated voltage of the main network buses is 500 kV (line-to-line, RMS). The converter coupling transformers are included in the converter equivalent impedance branches rather than drawn as separate ideal transformer symbols in Figure 1. The AC transmission branches are represented by coupled π sections in PSCAD/EMTDC; their positive- and zero-sequence unit-length parameters and physical line lengths are listed in Section 6.1. The parallel operation of the two converter technologies enhances transmission capacity and control flexibility but also introduces differentiated harmonic sources and impedance characteristics, complicating the wideband resonance problem.
To simulate the scenario of an improperly configured passive filter bank in a real receiving-end grid, a triple-tuned filter is installed at bus 8 (the LCC connection point), as shown in Figure 1. Such a filter introduces additional resonance paths in the network and can trigger or aggravate resonance phenomena when its tuning frequencies coincide with or lie close to specific system modes. The filter adopts a ladder structure with three internal nodes designated as 10 (FT1), 11 (FT2), and 12 (FT3) in the network model; in Figure 1, FT1, FT2, and FT3 denote these internal filter nodes rather than additional AC buses. The three branches are tuned to 150 Hz, 1200 Hz, and 1850 Hz, respectively, and their detailed parameters are given in Section 6.1.

3.2. Wideband Converter Models

For the hybrid multi-infeed receiving-end system, power electronic devices are represented by wideband converter models [7]. Due to background harmonics, dead-time effects, commutation overlap, sampling delay, and modulation effects, the output voltage or current is not strictly sinusoidal and may contain a broad harmonic spectrum. The converter models used here are therefore steady operating point equivalents for resonance analysis: they preserve the dominant harmonic source behavior and the high-frequency impedance seen by the AC network, while the detailed nonlinear switching and control states are retained in the PSCAD/EMTDC verification model. Under this interpretation, the harmonic order h can be treated as a continuous variable greater than 1.

3.2.1. MMC Wideband Voltage Source Converter Model

The capacitor voltage balancing of MMC submodules adopts a sorting algorithm. Although the synthesized internal voltage is not strictly periodic, the harmonic voltage content is extremely low under the studied operating condition. Therefore, the MMC is modeled as a wideband voltage source converter. The equivalent internal voltage mainly contains the fundamental component, and harmonic voltages are neglected in the resonance mode calculation. The equivalent internal impedance Z MMC ( s ) is determined by the leakage inductance L T and resistance R T of the coupling transformer, as well as the arm reactor L arm and resistance R arm . This equivalent impedance does not imply that MMC internal nonlinear dynamics are absent; it means that their effect on the external high-frequency AC path is represented by the dominant passive branch plus the explicitly modeled digital control delay in the supplementary damping channel. For the high-frequency AC side path, the upper and lower arms are in parallel; thus
Z MMC ( s ) = R link + s L link
where R link = R T + R arm / 2 , L link = L T + L arm / 2 .

3.2.2. LCC Wideband Current Source Converter Model

Due to the inherent commutation process, a 12-pulse LCC injects characteristic harmonic currents into the AC side mainly at orders 12 k ± 1 ( k = 1 , 2 , ), such as the 11th (550 Hz), 13th (650 Hz), 23rd (1150 Hz), and 25th (1250 Hz). This follows from the two six-pulse bridges of a 12-pulse converter, whose phase-shifted transformer connection cancels the 5th and 7th harmonics and leaves the characteristic AC-side harmonics at n p ± 1 with pulse number p = 12. Non-characteristic harmonics can still appear under unbalanced voltage, firing-angle asymmetry, commutation failure, or control saturation; these components are outside the balanced positive-sequence screening model but are considered in the discussion of applicability. The amplitudes of the 11th and 13th characteristic harmonic currents are significant in the studied case and constitute the main harmonic excitation source in the hybrid multi-infeed receiving-end system. Therefore, the LCC is modeled as a wideband current source converter for the resonance mode calculation.

3.3. Establishment of the Positive-Sequence S-Domain Model

The positive-sequence network s-domain impedance model of the system is built according to the following source-equivalence principles for harmonic network modal calculation, consistent with Thevenin and Norton source-equivalence theorems:
(1)
Independent voltage sources (such as the MMC fundamental internal voltage, with negligible harmonic content) are replaced by short circuits;
(2)
Independent current sources (LCC harmonic current sources) are replaced by open circuits;
(3)
The LCC converter as a whole is treated as an open circuit in the positive-sequence network.
After the above equivalence, bus 7 presents the MMC equivalent impedance Z MMC ( s ) to ground; bus 8 (LCC connection point) retains only the line connections to the AC system. In this wideband source-equivalent framework, converter nonlinearities are expressed through harmonic voltage/current source spectra and through the high-frequency equivalent path seen from the AC side. No negative-resistance element is introduced into the modal network; resonance risk is evaluated from the proximity between harmonic excitation frequencies and weakly damped network modes. The s-domain admittances of each branch are established as follows: for a series resistance-inductance branch,
Y R L ( s ) = 1 R + s L
and for a parallel capacitor branch,
Y C ( s ) = s C
Equation (7) is the lossless form of a capacitor branch. In practical filters, dielectric loss and equivalent series resistance can be included by replacing the ideal capacitor with an R-C or R-L-C branch and stamping the corresponding admittance into Y node ( s ) . In the present case, the dominant damping of the studied high-risk mode is determined by the filter resistors and network/converter equivalent resistances; neglecting small capacitor losses therefore gives a conservative estimate of weak damping. If the capacitor loss resistance is known, it can be directly included without changing the proposed analysis procedure.
Following the rules for building the nodal admittance matrix, the s-domain admittances of all branches are assembled into the corresponding positions, resulting in the s-domain nodal admittance matrix Y node ( s ) of the hybrid multi-infeed receiving-end system. The order of this matrix equals the number of effective network nodes. In particular, the three internal nodes of the triple-tuned filter are treated as additional network nodes, and their series and parallel branch admittances are stamped into the matrix following the same rules as Equations (6) and (7). This matrix fully preserves the network topology and the frequency characteristics of the components, laying the foundation for subsequent resonance modal analysis.
The above model is a balanced positive-sequence model. Negative-sequence and zero-sequence resonances may be excited by unbalanced faults, asymmetric harmonic injections, transformer zero-sequence paths, or unequal phase impedances. The present paper focuses on the balanced characteristic-harmonic resonance caused by the LCC in normal operation, while protection-level unbalanced fault resonance is outside the present modeling scope.

4. System Resonance Modal Analysis

4.1. Identification of High-Risk Resonance Modes

Because the harmonic voltage content in the MMC wideband voltage source model is extremely low, the harmonic excitation of the system mainly originates from the LCC characteristic harmonic currents. When the frequency of a resonance mode is close to an LCC characteristic harmonic frequency and its damping ratio is relatively low, the characteristic harmonic current injected by the LCC will be significantly amplified through the weakly damped resonance mode of the grid network, leading to a high-risk oscillation scenario.
Considering both frequency proximity and modal damping, this paper defines engineering screening conditions for high-risk resonance modes as follows:
  • Condition 1 (Frequency proximity criterion): The deviation between the resonance frequency f i and any LCC characteristic harmonic frequency f char satisfies | f i f char | / f char 10 % ;
  • Condition 2 (Weak damping criterion): The modal damping ratio ζ i < 5 % .
The 10% band is selected to cover practical resonance peak broadening and modal frequency drift caused by operating condition changes, and the 5% damping ratio threshold follows the common engineering practice that modes below this level require damping improvement or close monitoring. These thresholds are not intended to create an absolute safe/unsafe boundary. A mode slightly outside the 10% band, or a mode with ζ i slightly above 5%, may still require evaluation if the injected harmonic current is large, the resonance peak is broad, or the mode shape eigenvector indicates high participation at converter buses. Therefore, a resonance mode that simultaneously satisfies both conditions is identified as high-risk and must be prioritized for suppression measures, while neighboring modes are retained as monitoring targets.

4.2. Mode Shape Eigenvector Analysis

The mode shape eigenvector M 1 of a high-risk resonance mode provides the relative distribution pattern of voltage amplification across nodes at that frequency. At the resonance frequency ω i , the harmonic voltage magnitude at node j is approximately
| V j ( j ω i ) | | m j | · | U mode 1 | .
Therefore, the node k * with the largest shape magnitude ( | m k * | = 1 ) experiences the most significant harmonic voltage amplification and is also the optimal location for active control injection to improve the damping of that mode. When the MMC connection point (bus 7) coincides with or is adjacent to k * , the MMC can be directly used to implement active damping control.

5. Active Resonance Suppression Strategy Based on MMC Virtual Damping

This paper proposes an active damping strategy in which MMC supplementary control emulates a parallel virtual resistance at the target resonance frequency. The fundamental power transmission of the MMC remains governed by the outer loop and the PI vector current inner loop; the additional active damping channel is designed to operate without interfering with power transfer at the fundamental frequency.
At the target resonance frequency f r = ω r / ( 2 π ) , the MMC is controlled to emulate a virtual parallel resistance R v to the external network, such that when a harmonic voltage disturbance Δ u r at frequency ω r appears at the PCC, the MMC actively injects an in-phase harmonic current Δ i r = Δ u r / R v . This is equivalent to connecting a positive real conductance G v = 1 / R v in parallel at the resonance node, thereby increasing the effective conductance at that frequency, raising the modal damping ratio, and suppressing resonance amplification.
The virtual resistance is selected through an offline modal-sensitivity procedure. First, candidate values of R v are inserted as a shunt conductance at the MMC bus in Y node ( s ) . Second, the two-stage modal calculation is repeated to obtain the damping ratio of the target mode. Third, values that satisfy the damping requirement but exceed converter harmonic current margin are rejected. A smaller R v produces stronger damping but increases the required harmonic current and modulation margin; a larger R v reduces converter stress but may leave insufficient damping. The selected value should therefore satisfy
ζ target 5 % , I damp , max = U harm , max R v I MMC , margin ,
where U harm , max is the expected maximum harmonic voltage magnitude at the PCC and I MMC , margin is the available harmonic current capacity after fundamental power operation is considered. The voltage and current quantities in this constraint should use a consistent RMS or peak basis; in the sensitivity table below, the measured RMS harmonic voltage is converted to peak current for a conservative current stress estimate. The detailed sensitivity analysis and practical adaptive-tuning logic are given in the following subsections.

5.1. Virtual Resistance Sensitivity Analysis and Design Trade-Offs

To quantify the design trade-off of R v , the candidate values from to 10 Ω are inserted as a shunt conductance at the MMC bus, and the two-stage modal calculation described in Section 2 is repeated. The undamped modal frequencies and mode shape eigenvectors are kept unchanged because a purely resistive shunt does not modify the susceptance matrix used in Stage 1. The damped roots, however, vary with the virtual conductance G v = 1 / R v . Table 1 summarizes the results for the dominant high-risk mode and the adjacent non-target mode.
The sensitivity results show three features. First, adding virtual conductance substantially increases the damping ratio of Mode #2 from 0.64% to well above the engineering threshold of 5% for all finite candidate values. Second, reducing R v does not provide unlimited benefit: although the conductance becomes larger, the damped root moves away from the original 11th–13th harmonic band, and the estimated peak damping current increases from 0.386 kA at 100 Ω to 3.862 kA at 10 Ω. Third, the same shunt conductance also affects the non-target Mode #3 because Bus7 has a non-negligible mode shape magnitude of 0.4461 in that mode. Moderate values improve Mode #3 damping, whereas excessively small R v increases converter stress and weakens the improvement of the adjacent mode.
Therefore, the admissible virtual resistance interval is determined by both the converter margin and the modal-damping requirement:
R v [ R v , min , R v , max ] , R v , min = U harm , max I MMC , margin ,
where R v , max is the largest value that still satisfies ζ target 5 % in the modal-sensitivity scan. The lower bound should be recalculated for each project using the actual harmonic current and modulation margins of the MMC. In the studied case, the range around 35–50 Ω provides a balanced compromise: Mode #2 damping is increased to 31.15–38.49%, the estimated peak damping current remains about 0.77–1.10 kA, and Mode #3 is also improved without forcing an excessive shift of the modal root. Thus, R v = 35 Ω is selected for the subsequent PSCAD/EMTDC verification because it gives a large target-mode damping margin while remaining within the supplementary-control margin.

5.2. Modulation Wave Reconstruction Bypass Injection Architecture

If the high-frequency damping current command is directly fed into the MMC’s PI vector current inner loop, inherent difficulties arise: the integral term K i / s provides nearly zero gain for high-frequency signals, and although the proportional term K p can respond, the overall PI closed-loop bandwidth is limited at high frequencies, inevitably introducing amplitude attenuation and phase lag. This causes the actually injected high-frequency current to deviate significantly in both magnitude and phase from the desired damping quantity; in particular, the phase deviation from the purely resistive target can severely degrade the damping effect or even exacerbate resonance in extreme cases.
To avoid routing the damping command through the low-bandwidth integral path, this paper proposes a modulation wave reconstruction bypass injection architecture (referred to hereafter as the bypass injection method), with the control block diagram shown in Figure 2. This control strategy retains the PI controller to focus on tracking the fundamental current in the dq frame (the DC quantity it excels at), while the high-frequency damping command bypasses the PI controller and is directly injected at the modulation wave level in the αβ stationary reference frame. This architecture separates the fundamental vector control channel and the high-frequency damping control channel in the frequency domain, reducing mutual interference. It should be emphasized, however, that the bypass channel is not a closed current loop at the resonance frequency. Therefore, it does not guarantee exact tracking of the commanded damping current. In practice, PCC voltage feedback, nominal delay compensation, conservative virtual resistance selection, and converter current/modulation limiting are used to keep the injected current within a positive damping operating region, but dead time, DC voltage ripple, and residual nonlinearities may reduce or distort the realized damping conductance. The proposed method should therefore be interpreted as an approximate positive damping implementation rather than an ideal regulated virtual resistance.

5.3. Implementation Steps of Bypass Injection Method

5.3.1. Extraction of Target-Frequency Harmonic Voltage

Measure the three-phase voltages u abc at the PCC, apply Clarke transformation to obtain u α β , and then extract the target harmonic component using a second-order band-pass filter (BPF) centered at ω r :
u α β , ω r ( s ) = H BPF ( s ) · u α β ( s )
H BPF ( s ) = ω b s s 2 + ω b s + ω r 2
where ω b is the filter bandwidth, typically chosen as ω b = ( 0.05 0.10 ) ω r to balance selectivity and response speed. A narrower bandwidth improves separation between adjacent harmonics but slows the response and makes the channel more sensitive to modal frequency drift; a wider bandwidth improves robustness to frequency drift but may introduce unwanted inter-harmonic components and noise. It can be verified that H BPF ( j ω r ) = 1 , i.e., the gain is 1 and the phase shift is 0 at the center frequency, enabling distortion-free extraction.

5.3.2. Phase Compensation for Digital Delay

The MMC digital control system has a total delay of approximately 1.5 T s , which produces a phase lag φ d = 1.5 T s ω r at the target frequency ω r . This value represents the nominal delay caused by sampling, calculation, and modulation update; in practice, the effective delay may vary slightly with digital implementation and modulation constraints. To ensure that the injected harmonic current is in phase with the PCC harmonic voltage as closely as possible (purely resistive response), a lead compensation is applied to the BPF output:
u α , ω r comp u β , ω r comp = cos φ d sin φ d sin φ d cos φ d u α , ω r u β , ω r .

5.3.3. Generation of Damping Current Command

According to the virtual parallel resistance equivalent principle, when harmonic voltage u α β , ω r comp appears at the PCC, the MMC reference is designed to absorb (with the current flowing into the converter taken as positive) a damping current
i α , damp * i β , damp * = G v u α , ω r comp u β , ω r comp = 1 R v u α , ω r comp u β , ω r comp .

5.3.4. Current-to-Voltage Command Conversion

Since the damping control is injected at the modulation voltage level after the PI output, the current command needs to be converted into an equivalent voltage command. In the vicinity of ω r , the effective gain of the PI controller can be approximated by the proportional gain K p (the integral term contribution is negligible); therefore, K p is used for the conversion:
v α , damp * v β , damp * = K p i α , damp * i β , damp * .

5.3.5. Modulation Wave Reconstruction (Bypass Injection)

The MMC outer loop and PI inner loop output the fundamental voltage commands V d , PI and V q , PI in the dq frame, which are transformed to the αβ frame via inverse Park transformation to obtain V α , PI and V β , PI . Before NLM modulation, the fundamental modulation voltage and the damping voltage command are directly superimposed in the αβ frame:
V α , final * V β , final * = V α , PI V β , PI v α , damp * v β , damp * .
The physical meaning of the minus sign is: when the PCC harmonic voltage perturbs positively, the MMC output modulation voltage is reduced, inducing harmonic current to flow from the AC grid into the MMC. If implementation delays and nonlinearities are sufficiently compensated or bounded, the resulting current component is approximately in phase with the PCC harmonic voltage, so the MMC behaves as a positive conductance that absorbs harmonic energy at the resonance node. Because this high-frequency current is not directly regulated by a closed current loop, the realized conductance must be checked by EMT simulation and constrained by current and modulation limits.
The core advantage of the bypass injection method is that the high-frequency damping channel bypasses the PI controller; the PI controller focuses on zero-steady-state-error tracking of the dq-axis fundamental current, and the two channels are separated in the frequency domain. This reduces the amplitude attenuation and phase distortion caused by high-frequency signals passing through the integral path, but it also means that damping frequency current regulation is open-loop. To avoid excessive or incorrectly phased harmonic injection, the practical implementation should include a damping current limiter, a modulation index limiter, online monitoring of the extracted harmonic current phase, and blocking logic under severe unbalanced faults or converter saturation. A fully closed-loop correction of damping frequency current deviations caused by dead time, DC voltage ripple, and converter nonlinearities is beyond the scope of this paper and is identified as future work.

5.4. Multi-Mode Resonance Simultaneous Suppression Scheme

When multiple high-risk resonance modes exist simultaneously in the system (target frequencies ω r , 1 , ω r , 2 , , ω r , N ), independent BPFs can be designed for each target frequency (center frequency ω r , k , bandwidth ω b , k independently tuned), generating respective damping voltage commands v α β , damp , k * . These commands are linearly superimposed in the αβ frame and then injected simultaneously:
V α , final * V β , final * = V α , PI V β , PI k = 1 N v α , damp , k * v β , damp , k * .
Each BPF has a gain of 1 at its own center frequency and a gain of approximately zero at other target frequencies; therefore, the frequency-domain coupling between different damping channels is minimal when the target frequencies are well separated and the BPF bandwidths do not overlap. Equation (17) realizes simultaneous suppression of multiple high-risk resonance modes. In the present verification, the damping channels are configured for the high-risk modes associated with the 11th and 13th LCC characteristic harmonics.

5.5. Adaptive Tuning of Virtual Conductance in Practical Applications

For practical systems with operating condition changes, the fixed offline value of R v can be used as the initial value and then updated online within the admissible interval in Equation (10). The dominant resonance frequency can be identified from PCC harmonic voltage/current measurements by a sliding-window FFT, or by an adaptive notch filter whose center frequency tracks the peak harmonic component. The modal damping trend can be estimated from the decay rate of the extracted oscillatory component after a disturbance or from the local slope of the frequency response around the identified resonance peak.
After the dominant mode is identified, the virtual conductance can be updated by either a lookup table or a recursive rule. In the lookup table method, offline modal scans similar to Table 1 are prepared for representative grid strength and power flow conditions; the controller selects the smallest conductance that satisfies the target damping ratio and then applies interpolation between operating points. In the recursive method, G v is increased step by step when the estimated damping ratio is below the target value and decreased when the damping margin is sufficient and the converter harmonic current margin becomes tight. The update should be slower than the BPF settling process, so that the damping channel does not chase measurement noise or transient estimation errors.
The adaptive loop is constrained by protection limits. The commanded damping current is saturated according to I MMC , margin , the modulation voltage command is limited by the available modulation index, and the channel is blocked when the identified resonance frequency moves outside the BPF tuning range, when severe unbalanced faults occur, or when converter saturation is detected. Under these limits, adaptive tuning changes only the positive conductance magnitude in the selected frequency band, while the bypass-injection phase compensation maintains an approximately resistive response. This provides a practical way to retune the damping strength for different resonance modes without altering the fundamental MMC power control loop, but it is not a substitute for closed-loop correction of damping frequency current deviations.

6. Simulation Verification

6.1. Simulation System Parameter Settings

On the PSCAD/EMTDC platform, the hybrid multi-infeed receiving-end IEEE 9-bus test system shown in Figure 1 is built. The main parameters of the system are listed in Table 2, Table 3, Table 4 and Table 5. The AC transmission branches use PSCAD coupled π sections, with a fundamental frequency of 50 Hz and a rated line-to-line voltage of 500 kV. The inverter-side converter of LCC-HVDC is connected to bus 8, adopting a 12-pulse configuration with a DC rated voltage of 800 kV and a rated active power of 2000 MW. The inverter-side MMC-HVDC is connected to bus 7, with an AC rated voltage of 525 kV, a DC rated voltage of 800 kV, a rated power of 2000 MW, and a control period T s = 50 μs. The MMC equivalent resistance is 1.5 Ω, the transformer equivalent inductance is 0.04785 H, the arm inductance is 0.1608 H, and the total equivalent inductance is 0.1864 H.

6.2. Resonance Modal Analysis and High-Risk Mode Identification

Using the two-stage s-domain nodal admittance matrix method, a wideband resonance mode scan is performed on the system of Figure 1, and the calculation results are shown in Table 6. The system exhibits three main resonance modes in this frequency band, denoted as #1, #2, and #3.
Mode #1 has a resonance frequency of 147.76 Hz, which is close to the first tuning point (150 Hz) of the triple-tuned filters (FT1–FT3). Its maximum shape node is the filter internal node FT1, while the shape magnitudes of the main network nodes (Bus1–Bus9) are all below 0.022, indicating a local resonance confined within the filter branch and not posing a system-wide risk.
Mode #2 has a resonance frequency of 581.31 Hz, lying between the LCC’s 11th (550 Hz) and 13th (650 Hz) characteristic harmonics, with an extremely low damping ratio of 0.64%. The mode shape eigenvector shows that the LCC connection point (Bus8) and the MMC connection point (Bus7) have magnitudes as high as 1.0000 and 0.9875, respectively, both being core areas of voltage amplification. This indicates that once the LCC injects the 11th or 13th harmonic current, strong harmonic voltage amplification will be excited at Bus7 and Bus8 and propagated throughout the network. Therefore, Mode #2 is identified as the primary high-risk resonance mode, and Bus8 or Bus7 is the optimal location for implementing active damping.
Mode #3 has a resonance frequency of 798.85 Hz with a damping ratio as low as 0.52%, but its frequency deviates significantly from the LCC characteristic harmonics (e.g., 23rd at 1150 Hz). Moreover, the maximum shape node is Bus4, while the shape magnitudes at the DC feed-in nodes Bus7 and Bus8 are relatively small (0.45–0.56). The risk of being directly excited by LCC characteristic harmonics is relatively low, and this mode does not require immediate suppression but warrants monitoring.
The harmonic voltage and current amplitudes at buses 1 to 9 obtained from PSCAD simulation are shown in Table 7 and Table 8, respectively. The simulation data further corroborates the above analysis: the 11th harmonic voltages at Bus7 and Bus8 reach 27.31 kV and 33.20 kV, respectively, and the 13th harmonic voltages reach 11.98 kV and 10.13 kV, far exceeding the levels in non-resonant frequency bands. This verifies that the extremely weak damping of Mode #2 causes significant amplification of LCC characteristic harmonics. Therefore, Bus8 and Bus7 are taken as priority implementation nodes for active damping control, with the suppression strategy focused on Mode #2.

6.3. Active Damping Control Effectiveness Verification

Based on the s-domain nodal admittance matrix analysis and the virtual resistance sensitivity results in Table 1, the MMC connection node Bus7 is configured with virtual damping control, making it equivalent to a parallel resistance R v = 35 Ω at the 11th harmonic frequency. This raises the damping ratio of Mode #2 from 0.64% to 38.49%. Considering that the resonance mode may shift after the virtual impedance control is applied, the same control parameters are also deployed at the 13th harmonic frequency to cover the main injection bands of LCC characteristic harmonics. After applying active damping, the system resonance modes obtained from s-domain analysis are shown in Table 9.
It can be seen that the originally high-risk Mode #2 is effectively suppressed: its resonance frequency shifts from 581.31 Hz to 643.22 Hz, and the damping ratio increases from 0.64% to 38.49% (approximately 60 times), far exceeding the engineering requirement of ζ 5 % . Notably, the damping ratio of Mode #3 is also raised from 0.52% to 6.39%, even though this mode was not directly targeted. This improvement arises because Bus7 has a non-negligible mode shape magnitude of 0.4461 in Mode #3; the virtual conductance G v = 1 / R v shunted at Bus7 increases the overall system dissipation and benefits all modes in which Bus7 participates.
It is worth noting that the mode shape eigenvectors in Table 9 remain identical to those in Table 6. This is because the virtual parallel resistance acts as a shunt admittance to ground at Bus7, which modifies only the self-admittance (diagonal) element of Y node ( s ) at that node. According to the two-stage method, the mode shape eigenvectors are extracted from the susceptance matrix B node in Stage 1, which is unaffected by purely resistive shunts. Physically, the damping control does not alter the network’s reactive power flow paths, and the relative voltage distribution pattern is therefore preserved. To further verify the performance, time-domain simulations are conducted in PSCAD/EMTDC. The simulation sequence is as follows: at t = 2 s, characteristic harmonic currents containing the 11th and 13th orders are injected at the LCC connection node Bus8; at t = 4 s, the proposed active damping control is activated. Figure 3 shows the three-phase voltage waveforms at buses 1–9 without active damping control, and Figure 4 shows the corresponding waveforms with active damping control. In these figures, the horizontal axis is time in seconds and the vertical axis is phase voltage in kV.
After the active damping control is enabled, the harmonic voltage and current amplitudes at buses 1 to 9 are shown in Table 10 and Table 11. From the simulation results:
  • t = 2∼4 s (before control): the 11th harmonic voltages at Bus8 and Bus7 reach 33.20 kV and 27.31 kV, respectively, while the 13th harmonic voltages reach 10.13 kV and 11.98 kV, indicating severe harmonic amplification;
  • t > 4 s (after control): the 11th harmonic voltage at Bus8 drops to 10.27 kV (69.1% reduction) and at Bus7 to 3.34 kV (87.8% reduction); the 13th harmonic voltage at Bus8 decreases to 1.68 kV (83.4% reduction) and at Bus7 to 5.57 kV (53.5% reduction).
Comparing the fundamental current data before and after control shows that the fundamental currents in each branch change very little (deviation less than 0.1%), and the active power at the PCC remains stable. This confirms that the proposed bypass injection architecture effectively separates the high-frequency damping channel from the fundamental vector control channel: the PI controller concentrates on zero-steady-state-error tracking of the fundamental, while the high-frequency damping command bypasses the PI controller and is superimposed directly on the modulation wave. The two channels work cooperatively with little mutual interference, suppressing the target resonance without affecting the normal power transmission of the MMC.
In summary, the simulation results verify the following: (1) the virtual resistance value R v = 35 Ω, selected from the modal-sensitivity trade-off in Table 1, substantially improves the damping of the high-risk resonance mode while maintaining a bounded damping current demand; (2) the bypass injection architecture realizes an approximate virtual resistance characteristic, so that the MMC behaves as a positive damping conductance for harmonic energy absorption at the target frequency without disturbing fundamental power transmission; and (3) the simultaneous suppression scheme for the 11th and 13th harmonics is effective in the studied case, with independently tuned channels and minimal cross-coupling.

7. Conclusions

This paper addresses the wideband resonance problem of hybrid multi-infeed HVDC receiving-end grids containing LCC and MMC and proposes a systematic active resonance analysis and suppression strategy based on the s-domain nodal admittance matrix method and MMC active damping control. The main conclusions are as follows:
  • Based on the LCC wideband current source model and the MMC wideband voltage source model, the positive-sequence s-domain model of the system is established. The two-stage s-domain nodal admittance matrix method efficiently determines the wideband resonance modes and mode shape eigenvectors of the hybrid multi-infeed receiving-end system. This method directly supports harmonic amplification analysis in balanced networks and naturally accommodates distributed-parameter and frequency-dependent components.
  • The high-risk resonance mode identification method, which uses the matching degree between resonance frequency and LCC characteristic harmonics together with the modal damping ratio as a dual criterion, accurately identifies the high-risk modes that require priority suppression, providing clear direction for the active suppression strategy.
  • The proposed modulation wave bypass injection architecture separates the fundamental vector control channel from the high-frequency damping control channel in the frequency domain. The PI controller focuses on fundamental zero-steady-state-error tracking, while the high-frequency damping command bypasses the PI and is directly injected at the modulation wave level in the αβ frame. This reduces the amplitude attenuation and phase distortion caused by high-frequency signals passing through the integral path. Because the damping frequency current is not closed-loop regulated, the method realizes an approximate positive damping conductance whose effectiveness depends on delay compensation, current/modulation limiting, and EMT verification.
  • The multi-BPF parallel superposition scheme achieves simultaneous suppression of multiple high-risk resonance modes with minimal cross-channel coupling. Each channel features strong frequency selectivity and independently tunable parameters, and the architecture can be readily extended to accommodate additional target frequencies.
Future research will explore closed-loop or observer-assisted correction of damping frequency current deviations caused by dead time, DC voltage ripple, and converter nonlinearities; online adaptive tuning of active damping parameters to accommodate resonance mode drift under varying operating conditions; sequence-coupled or phase-domain resonance under unbalanced disturbances; additional BPF channels for higher LCC characteristic harmonics such as the 23rd and 25th orders and for inter-harmonics from renewable energy converters; and distributed active damping strategies with coordinated multiple-MMC architectures. These extensions must account for narrower allowable filter bandwidth at higher frequencies, larger phase compensation sensitivity to digital delay, higher measurement noise amplification, limited converter harmonic current margin, and the stability of potential high-frequency current feedback loops.

Author Contributions

Conceptualization, W.H. and Y.H.; methodology, W.H. and C.Z.; software, C.Z. and T.H.; validation, G.W.; formal analysis, C.Z.; investigation, G.W. and T.H.; resources, Y.H.; writing—original draft preparation, W.H.; writing—review and editing, W.H., C.Z. and Y.H.; visualization, C.Z. and T.H.; supervision, Y.H.; project administration, Y.H.; funding acquisition, Y.H. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Science and Technology Project of State Grid Zhejiang Electric Power Co., Ltd. (Grant: B311DS25Z013).

Data Availability Statement

The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.

Conflicts of Interest

Authors Wen Hua and Chengming Zhang were employed by the company State Grid Zhejiang Electric Power Co., Ltd. Research Institute. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

Appendix A. Full Harmonic Data Before and After Control

This appendix provides the complete harmonic voltage and current data for all buses, covering harmonic orders 1–20.

Appendix A.1. Harmonic Voltages Before Control

Table A1. Full harmonic voltage amplitudes at each node before control.
Table A1. Full harmonic voltage amplitudes at each node before control.
OrderU1 (kV)U2 (kV)U3 (kV)U4 (kV)U5 (kV)U6 (kV)U7 (kV)U8 (kV)U9 (kV)
1295.1112293.9695293.9853295.1895294.4582293.7622293.5644291.8973293.4247
20.0171090.0172850.0086180.0228670.0201880.0139040.0385050.0315740.017513
30.0231740.0337860.0159000.0337580.0350810.0273250.0868930.1160760.046037
40.0191290.0203310.0101510.0250050.0239940.0155430.0443020.0391240.020570
50.0229050.0224120.0140730.0307140.0262290.0193860.0467600.0597890.028414
60.0215400.0221210.0108510.0284020.0268360.0171280.0462230.0383510.021681
70.0307130.0408960.0223480.0417880.0446510.0345940.0902320.0830850.043064
80.0317570.0227300.0147200.0418010.0327710.0237330.0480280.0453370.028092
90.0553720.0470030.0271750.0750230.0628430.0446360.1058520.1082820.056947
100.0659060.0402420.0267080.0864970.0641610.0435670.0845430.0822140.050537
1118.0881513.1571010.1997224.0737119.6657515.8679227.3081233.2000019.69266
120.3459580.1947030.1468700.4543300.3399280.2360280.3965570.4257340.279562
1316.530626.0585934.49077221.2816814.165637.83514711.9761810.131798.366051
140.0881630.0394020.0296730.1138820.0738420.0475080.0826120.0839010.055011
150.0988380.0401520.0258580.1230330.0710040.0431400.0922780.0994340.055134
160.1094120.0350580.0191570.1337600.0475620.0225450.0641530.0801920.034022
170.0765180.0386930.0251170.0907170.0329340.0242870.0633020.0920260.040422
180.0268830.0140860.0116530.0331960.0208680.0155690.0246350.0372380.020905
190.0249760.0190710.0133430.0309130.0217660.0170560.0318970.0377010.023060
200.0168080.0148190.0106440.0211920.0237730.0146230.0238450.0257910.017353
Note: All values are phase voltage RMS in kV.

Appendix A.2. Harmonic Currents Before Control

Table A2. Full harmonic current amplitudes at each node before control.
Table A2. Full harmonic current amplitudes at each node before control.
OrderI0 (kA)I1 (kA)I2 (kA)I3 (kA)I4 (kA)I5 (kA)I6 (kA)I7 (kA)I8 (kA)I9 (kA)
12.5419360.9113162.4375691.9728930.9170080.4316880.5057542.4511141.7422521.986680
20.0011310.0002220.0010040.0004140.0002130.0009250.0001510.0009760.0014020.000401
30.0028320.0003730.0016690.0007730.0003260.0015480.0001590.0016020.0028540.000741
40.0004540.0001920.0007250.0002850.0001470.0006650.0001580.0006600.0009150.000264
50.0011500.0002060.0006320.0003690.0001520.0005660.0001590.0005430.0011030.000316
60.0002600.0001820.0004980.0002200.0001050.0004360.0001580.0003850.0005550.000161
70.0007340.0003130.0009560.0004820.0002170.0008420.0002050.0007450.0013000.000396
80.0001620.0002380.0004320.0002359.93 × 10−50.0003620.0002370.0003070.0004890.000152
90.0002800.0003810.0007490.0004210.0001790.0005910.0003890.0004310.0008050.000266
100.0003730.0004200.0006470.0003870.0001630.0004950.0004730.0003210.0007140.000231
110.1634860.1314050.1911760.1482070.0548800.1344240.1252600.0810110.2515510.080388
120.0003400.0023250.0026370.0019770.0007440.0016910.0025910.0008990.0023860.000925
130.1037290.1016870.0745030.0552410.0206830.0359360.1274160.0166080.0192390.020822
140.0003740.0005470.0005330.0004150.0001580.0003280.0006520.0001720.0004330.000184
150.0005750.0005380.0004880.0003260.0001000.0004230.0006780.0001410.0005070.000131
169.68 × 10−50.0005720.0003870.0002170.0001020.0004620.0007610.0001210.0006288.43 × 10−5
170.0004740.0003990.0003860.0002420.0001100.0004260.0005010.0001590.0004978.65 × 10−5
180.0001120.0001470.0001860.0001445.39 × 10−50.0001740.0001868.41 × 10−50.0002035.88 × 10−5
190.0002590.0001470.0001990.0001484.55 × 10−50.0001830.0001910.0001050.0001915.36 × 10−5
207.08 × 10−50.0001170.0001480.0001144.15 × 10−50.0001230.0001349.47 × 10−50.0001565.99 × 10−5
Note: All values are phase current RMS in kA.

Appendix A.3. Harmonic Voltages After Control

Table A3. Full harmonic voltage amplitudes at each node after control.
Table A3. Full harmonic voltage amplitudes at each node after control.
OrderU1 (kV)U2 (kV)U3 (kV)U4 (kV)U5 (kV)U6 (kV)U7 (kV)U8 (kV)U9 (kV)
1295.1054293.9778293.9869295.1823294.4589293.7644293.5851291.9163293.4298
20.0106970.0149290.0066980.0138350.0135430.0095440.0323010.0239320.012770
30.0139780.0236910.0077660.0182630.0214840.0157700.0389340.0804970.028457
40.0132720.0179230.0073870.0178880.0197000.0118470.0407010.0300960.015372
50.0240930.0316040.0153930.0327640.0357280.0207950.0731680.0807380.035220
60.0189700.0235130.0100260.0253290.0248640.0154330.0524400.0384460.020376
70.0240000.0346700.0155700.0324780.0365870.0238940.0753990.0596580.030376
80.0256720.0298490.0132840.0343240.0332180.0214370.0614890.0464220.026012
90.0377700.0463170.0217870.0487790.0521810.0320990.0883820.0594450.037871
100.0437450.0404710.0214180.0582800.0537170.0339960.0843260.0710700.042220
113.8689791.6104083.0008225.1485093.2391014.4986933.34188210.274705.793026
120.1849370.1036820.0781170.2422180.1816730.1258260.2116650.2245020.148343
134.7705542.8168740.6990096.1413314.9860571.3794175.5664811.6788531.301675
140.0519580.0176990.0153310.0651960.0392280.0266740.0377920.0449810.030353
150.1069060.0299900.0136120.1376980.0464370.0230930.0731970.0760970.032132
160.0928600.0323630.0149040.1126630.0356310.0156780.0593540.0669460.026091
170.0649580.0269080.0246050.0773280.0279930.0252330.0456590.0859180.040468
180.0276590.0129870.0114190.0335170.0150040.0151870.0210860.0344430.018946
190.0178060.0146520.0129640.0209700.0167430.0159130.0235210.0345460.022869
200.0137770.0135210.0094350.0168120.0184840.0120030.0200160.0201350.014977
Note: All values are phase voltage RMS in kV.

Appendix A.4. Harmonic Currents After Control

Table A4. Full harmonic current amplitudes at each node after control.
Table A4. Full harmonic current amplitudes at each node after control.
OrderI0 (kA)I1 (kA)I2 (kA)I3 (kA)I4 (kA)I5 (kA)I6 (kA)I7 (kA)I8 (kA)I9 (kA)
12.5433510.9116432.4386171.9735630.9172520.4324710.5056682.4519911.7434221.987267
20.0007810.0002040.0009390.0003760.0001920.0008729.02 × 10−50.0009120.0012980.000360
30.0030340.0002440.0012100.0003230.0002290.0011590.0001750.0011560.0013760.000318
40.0003220.0001670.0006940.0002480.0001370.0006458.87 × 10−50.0006300.0007850.000221
50.0014420.0002980.0009940.0005020.0002270.0008830.0001510.0008310.0016310.000455
60.0001410.0001640.0005890.0002440.0001240.0005260.0001250.0004840.0006810.000198
70.0007430.0002500.0007950.0003340.0001700.0007010.0001540.0006180.0009310.000264
80.0001390.0002030.0005150.0002360.0001140.0004460.0001660.0003690.0005670.000168
90.0003740.0003180.0007960.0003760.0001790.0006620.0002640.0004920.0007780.000252
100.0002700.0003220.0006160.0003290.0001480.0004800.0003110.0003020.0006090.000193
110.1710590.0280740.0233830.0435950.0117180.0115650.0216720.0098120.0844560.023643
120.0003280.0012370.0014050.0010450.0003920.0009080.0013870.0004850.0012540.000495
130.1229540.0293400.0346930.0085850.0059700.0235060.0395450.0078920.0194380.003261
140.0002150.0003070.0002380.0001896.28 × 10−50.0001980.0003960.0001080.0002568.18 × 10−5
150.0002990.0005810.0003520.0001625.67 × 10−50.0004310.0007439.03 × 10−50.0005646.32 × 10−5
160.0001020.0004690.0003710.0001528.95 × 10−50.0004620.0006458.33 × 10−50.0005864.77 × 10−5
170.0002510.0003130.0002670.0002398.57 × 10−50.0002910.0004209.29 × 10−50.0004565.20 × 10−5
189.38 × 10−50.0001450.0001420.0001153.99 × 10−50.0001330.0001827.62 × 10−50.0001884.44 × 10−5
190.0001750.0001020.0001650.0001414.70 × 10−50.0001570.0001358.33 × 10−50.0001694.67 × 10−5
208.15 × 10−57.47 × 10−50.0001408.45 × 10−53.36 × 10−50.0001290.0001038.51 × 10−50.0001294.17 × 10−5
Note: All values are phase current RMS in kA.

References

  1. Tan, Z.; Chen, K.; Ju, L.; Liu, P.; Zhang, C. Issues and solutions of China’s generation resource utilization based on sustainable development. J. Mod. Power Syst. Clean Energy 2016, 4, 147–160. [Google Scholar] [CrossRef]
  2. Enslin, J.H.R.; Heskes, P.J.M. Harmonic interaction between a large number of distributed power inverters and the distribution network. IEEE Trans. Power Electron. 2004, 19, 1586–1593. [Google Scholar] [CrossRef]
  3. Wang, X.; Blaabjerg, F.; Wu, W. Modeling and analysis of harmonic stability in an AC power-electronics-based power system. IEEE Trans. Power Electron. 2014, 29, 6421–6432. [Google Scholar] [CrossRef]
  4. Zhu, G.; Dong, J.; Grazian, F.; Bauer, P. A Hybrid Modulation Scheme for Efficiency Optimization and Ripple Reduction in Secondary-Side Controlled Wireless Power Transfer Systems. IEEE Trans. Transp. Electrif. 2024, 11, 6840–6853. [Google Scholar] [CrossRef]
  5. Zhan, Y.; Xie, X.; Liu, H.; Liu, H.; Li, Y. Frequency-domain modal analysis of the oscillatory stability of power systems with high-penetration renewables. IEEE Trans. Sustain. Energy 2019, 10, 1534–1543. [Google Scholar] [CrossRef]
  6. Liu, H.; Xie, X.; Gao, X.; Liu, H.; Li, Y. Stability analysis of SSR in multiple wind farms connected to series-compensated systems using impedance network model. IEEE Trans. Power Syst. 2018, 33, 3118–3128. [Google Scholar] [CrossRef]
  7. Xu, Z. Analysis of Wideband Oscillation Mechanism and Suppression Technology Based on C-Type Damping Filter. Energies 2026, 19, 943. [Google Scholar] [CrossRef]
  8. Lyu, J.; Cai, X.; Molinas, M. Frequency domain stability analysis of MMC-based HVDC for wind farm integration. IEEE J. Emerg. Sel. Top. Power Electron. 2016, 4, 141–151. [Google Scholar] [CrossRef]
  9. Harnefors, L.; Bongiorno, M.; Lundberg, S. Input-admittance calculation and shaping for controlled voltage-source converters. IEEE Trans. Ind. Electron. 2007, 54, 3323–3334. [Google Scholar] [CrossRef]
  10. Miao, Z. Impedance-model-based SSR analysis for type 3 wind generator and series-compensated network. IEEE Trans. Energy Convers. 2012, 27, 984–991. [Google Scholar] [CrossRef]
  11. Kundur, P. Power System Stability and Control; McGraw-Hill: New York, NY, USA, 1994; ISBN 9780070359581. [Google Scholar]
  12. Fan, L.; Zhu, C.; Miao, Z.; Hu, M. Modal analysis of a DFIG-based wind farm interfaced with a series compensated network. IEEE Trans. Energy Convers. 2011, 26, 1010–1020. [Google Scholar] [CrossRef]
  13. Wang, X.; Harnefors, L.; Blaabjerg, F. Unified impedance model of grid-connected voltage-source converters. IEEE Trans. Power Electron. 2018, 33, 1775–1787. [Google Scholar] [CrossRef]
  14. Sun, J. Impedance-based stability criterion for grid-connected inverters. IEEE Trans. Power Electron. 2011, 26, 3075–3078. [Google Scholar] [CrossRef]
  15. Cespedes, M.; Sun, J. Impedance modeling and analysis of grid-connected voltage-source converters. IEEE Trans. Power Electron. 2014, 29, 1254–1261. [Google Scholar] [CrossRef]
  16. Wen, B.; Boroyevich, D.; Burgos, R.; Mattavelli, P.; Shen, Z. Analysis of D-Q small-signal impedance of grid-tied inverters. IEEE Trans. Power Electron. 2016, 31, 675–687. [Google Scholar] [CrossRef]
  17. Khazaei, J.; Beza, M.; Bongiorno, M. Impedance analysis of modular multi-level converters connected to weak AC grids. IEEE Trans. Power Syst. 2018, 33, 4015–4025. [Google Scholar] [CrossRef]
  18. Semlyen, A.I. S-domain methodology for assessing the small signal stability of complex systems in nonsinusoidal steady state. IEEE Trans. Power Syst. 1999, 14, 132–137. [Google Scholar] [CrossRef]
  19. Gomes, S.; Martins, N.; Portela, C. Modal analysis applied to s-domain models of AC networks. In Proceedings of the IEEE Power Engineering Society Winter Meeting, Columbus, OH, USA, 28 January–1 February 2001; IEEE: New York, NY, USA, 2001; pp. 1305–1310. [Google Scholar] [CrossRef]
  20. Marti, J.R. Accurate modelling of frequency-dependent transmission lines in electromagnetic transient simulations. IEEE Trans. Power Appar. Syst. 1982, PAS-101, 147–157. [Google Scholar] [CrossRef]
  21. Balabanian, N.; Bickart, T.A. Electrical Network Theory; Wiley: New York, NY, USA, 1969; ISBN 9780471045762. [Google Scholar]
  22. Wang, X.; Blaabjerg, F.; Liserre, M.; Chen, Z.; He, J.; Li, Y. An active damper for stabilizing power-electronics-based AC systems. IEEE Trans. Power Electron. 2014, 29, 3318–3329. [Google Scholar] [CrossRef]
  23. Turner, R.; Walton, S.; Duke, R. Stability and bandwidth implications of digitally controlled grid-connected parallel inverters. IEEE Trans. Ind. Electron. 2010, 57, 3685–3694. [Google Scholar] [CrossRef]
Figure 1. Structure of the hybrid multi-infeed HVDC receiving-end test system.
Figure 1. Structure of the hybrid multi-infeed HVDC receiving-end test system.
Electronics 15 02725 g001
Figure 2. Control block diagram of the modulation wave bypass injection architecture.
Figure 2. Control block diagram of the modulation wave bypass injection architecture.
Electronics 15 02725 g002
Figure 3. Three-phase voltage waveforms at buses 1–9 without active damping control (vertical axis: phase voltage in kV; horizontal axis: time in s).
Figure 3. Three-phase voltage waveforms at buses 1–9 without active damping control (vertical axis: phase voltage in kV; horizontal axis: time in s).
Electronics 15 02725 g003
Figure 4. Three-phase voltage waveforms at buses 1–9 with active damping control (vertical axis: phase voltage in kV; horizontal axis: time in s).
Figure 4. Three-phase voltage waveforms at buses 1–9 with active damping control (vertical axis: phase voltage in kV; horizontal axis: time in s).
Electronics 15 02725 g004
Table 1. Sensitivity of the dominant resonance modes to virtual resistance.
Table 1. Sensitivity of the dominant resonance modes to virtual resistance.
R v (Ω)Mode #2 f r (Hz)Mode #2 ζ (%) I damp , max (kA)Mode #3 ζ (%)
581.310.640.52
100576.2715.560.3865.26
50585.5431.150.7729.99
35643.2238.491.1036.39
25757.5135.301.5454.28
15878.1021.872.5752.78
10907.1614.563.8622.08
Note: I damp , max is estimated as 2 U harm , max / R v , where U harm , max = 27.31 kV is the largest pre-control Bus7 phase-voltage RMS value among the 11th and 13th harmonics.
Table 2. Main parameters of the test system.
Table 2. Main parameters of the test system.
ParameterValue
AC system rated voltage500 kV
AC network base power100 MVA
Frequency50 Hz
LCC-HVDC rated DC voltage800 kV
LCC-HVDC rated power2000 MW
LCC converter type12-pulse
MMC-HVDC AC rated voltage525 kV
MMC-HVDC DC rated voltage800 kV
MMC-HVDC rated power2000 MW
MMC control period T s 50 μs
MMC equivalent resistance Rlink1.5 Ω
Transformer equivalent inductance L T 0.04785 H
Arm inductance L arm 0.1608 H
Total equivalent inductance L link 0.1864 H
Table 3. Voltage source equivalent parameters of the modified IEEE 9-bus system.
Table 3. Voltage source equivalent parameters of the modified IEEE 9-bus system.
ParameterG1/Bus1G2/Bus2G3/Bus3
Voltage source phase angle (deg)13.411.912.7
Series resistance (Ω)1.250.6250.625
Series inductance (mH)39.819.919.9
Table 4. PSCAD coupled-π line unit-length parameters and line lengths.
Table 4. PSCAD coupled-π line unit-length parameters and line lengths.
Unit-Length ParameterR1 (Ω/m)L1 (H/m)C1 (F/m)R0 (Ω/m)L0 (H/m)C0 (F/m)
Value0.0196 × 10−30.8780 × 10−60.01313 × 10−60.1522 × 10−32.2840 × 10−60.009879 × 10−6
LineB2–B7B7–B8B8–B9B9–B3B7–B5B9–B6B4–B5B4–B6B4–B1
Length (m)60,00030,00030,00050,00070,00010,00070,00080,00040,000
Note: R1, L1, and C1 are positive-sequence parameters; R0, L0, and C0 are zero-sequence parameters. The positive-sequence parameters are used in the balanced s-domain model, while the zero-sequence parameters are retained in the PSCAD coupled-π line model.
Table 5. Parameters of the triple-tuned filter at bus 8.
Table 5. Parameters of the triple-tuned filter at bus 8.
Branch 1Branch 2Branch 3
R f 1 1500 Ω R f 2 400 Ω R f 3 106 Ω
L f 1 8.047 mH L f 2 126.556 mH L f 3 1.608 mH
C f 1 1.57929 μF C f 2 7.29461 μF C f 3 7.76831 μF
Table 6. Resonance modes of the hybrid multi-infeed receiving-end system before control.
Table 6. Resonance modes of the hybrid multi-infeed receiving-end system before control.
Parameter#1#2#3
Frequency (Hz)147.76581.31798.85
Damping ratio (%)14.760.640.52
Mode shape eigenvector
Bus1−0.00370.67810.8257
Bus2−0.00630.4798−0.2470
Bus3−0.00490.3245−0.0964
Bus4−0.00530.89721.0000
Bus5−0.00610.73490.2949
Bus6−0.00730.5152−0.0316
Bus7 (MMC)−0.01450.9875−0.4461
Bus8 (LCC)−0.02181.0000−0.5553
Bus9−0.01010.6227−0.1681
FT11.00000.03400.1242
FT20.98850.1911−0.0912
FT30.0023−0.03740.0625
Table 7. Harmonic voltage amplitudes at each node before control (key orders).
Table 7. Harmonic voltage amplitudes at each node before control (key orders).
Orderf (Hz)U1U2U3U4U5U6U7U8U9
1st (fund.)50295.11293.97293.99295.19294.46293.76293.56291.90293.42
11th55018.0913.1610.2024.0719.6715.8727.3133.2019.69
13th65016.536.064.4921.2814.177.8411.9810.138.37
16th8000.110.040.020.130.050.020.060.080.03
Note: All values are phase voltage RMS in kV. Full harmonic order data are provided in Table A1 (Appendix A).
Table 8. Harmonic current amplitudes at each node before control (key orders).
Table 8. Harmonic current amplitudes at each node before control (key orders).
Orderf (Hz)I0I1I2I3I4I5I6I7I8I9
1st (fund.)502.5420.9112.4381.9730.9170.4320.5062.4511.7421.987
11th5500.1630.1310.1910.1480.0550.1340.1250.0810.2520.080
13th6500.1040.1020.0750.0550.0210.0360.1270.0170.0190.021
16th8009.7 × 10−55.7 × 10−43.9 × 10−42.2 × 10−41.0 × 10−44.6 × 10−47.6 × 10−41.2 × 10−46.3 × 10−48.4 × 10−5
Note: All values are phase current RMS in kA. Full harmonic order data are provided in Table A2 (Appendix A).
Table 9. Resonance modes of the system after applying active damping.
Table 9. Resonance modes of the system after applying active damping.
Parameter#1#2#3
Frequency (Hz)147.74643.22705.14
Damping ratio (%)14.7638.496.39
Mode shape eigenvector
Bus1−0.00370.67810.8257
Bus2−0.00630.4798−0.2470
Bus3−0.00490.3245−0.0964
Bus4−0.00530.89721.0000
Bus5−0.00610.73490.2949
Bus6−0.00730.5152−0.0316
Bus7 (MMC)−0.01450.9875−0.4461
Bus8 (LCC)−0.02181.0000−0.5553
Bus9−0.01010.6227−0.1681
FT11.00000.03400.1242
FT20.98850.1911−0.0912
FT30.0023−0.03740.0625
Table 10. Harmonic voltage amplitudes at each node after control (key orders).
Table 10. Harmonic voltage amplitudes at each node after control (key orders).
Orderf (Hz)U1U2U3U4U5U6U7U8U9
1st (fund.)50295.11293.98293.99295.18294.46293.76293.59291.92293.43
11th5503.871.613.005.153.244.503.3410.275.79
13th6504.772.820.706.144.991.385.571.681.30
16th8000.090.030.020.110.040.020.060.070.03
Note: All values are phase voltage RMS in kV. Full harmonic order data are provided in Table A3 (Appendix A).
Table 11. Harmonic current amplitudes at each node after control (key orders).
Table 11. Harmonic current amplitudes at each node after control (key orders).
Orderf (Hz)I0I1I2I3I4I5I6I7I8I9
1st (fund.)502.5430.9122.4391.9740.9170.4320.5062.4521.7431.987
11th5500.1710.0280.0230.0440.0120.0120.0220.0100.0840.024
13th6500.1230.0290.0350.0090.0060.0240.0400.0080.0190.003
16th8001.0 × 10−44.7 × 10−43.7 × 10−41.5 × 10−49.0 × 10−54.6 × 10−46.5 × 10−48.3 × 10−55.9 × 10−44.8 × 10−5
Note: All values are phase current RMS in kA. Full harmonic order data are provided in Table A4 (Appendix A).
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Hua, W.; Zhang, C.; Hou, T.; Wang, G.; Huang, Y. Active Resonance Suppression Strategy for Hybrid Multi-Infeed HVDC Receiving-End Grid with LCC and MMC. Electronics 2026, 15, 2725. https://doi.org/10.3390/electronics15122725

AMA Style

Hua W, Zhang C, Hou T, Wang G, Huang Y. Active Resonance Suppression Strategy for Hybrid Multi-Infeed HVDC Receiving-End Grid with LCC and MMC. Electronics. 2026; 15(12):2725. https://doi.org/10.3390/electronics15122725

Chicago/Turabian Style

Hua, Wen, Chengming Zhang, Tian Hou, Guoteng Wang, and Ying Huang. 2026. "Active Resonance Suppression Strategy for Hybrid Multi-Infeed HVDC Receiving-End Grid with LCC and MMC" Electronics 15, no. 12: 2725. https://doi.org/10.3390/electronics15122725

APA Style

Hua, W., Zhang, C., Hou, T., Wang, G., & Huang, Y. (2026). Active Resonance Suppression Strategy for Hybrid Multi-Infeed HVDC Receiving-End Grid with LCC and MMC. Electronics, 15(12), 2725. https://doi.org/10.3390/electronics15122725

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop