Figure 1.
Classification of power system stability: classical and extended categories.
Figure 1.
Classification of power system stability: classical and extended categories.
Figure 2.
Control scheme for GFM control.
Figure 2.
Control scheme for GFM control.
Figure 3.
Droop control with LPFs and proportional gains: filtered (P/Q) deviations adjust frequency and voltage references.
Figure 3.
Droop control with LPFs and proportional gains: filtered (P/Q) deviations adjust frequency and voltage references.
Figure 4.
Block diagram of virtual synchronous machine (VSM) control showing virtual inertia, damping, and power–frequency dynamics.
Figure 4.
Block diagram of virtual synchronous machine (VSM) control showing virtual inertia, damping, and power–frequency dynamics.
Figure 5.
Synchronverter control structure with active power (frequency) and reactive power (voltage) loops.
Figure 5.
Synchronverter control structure with active power (frequency) and reactive power (voltage) loops.
Figure 6.
IEEE 39-bus New England test system single-line diagram.
Figure 6.
IEEE 39-bus New England test system single-line diagram.
Figure 7.
Dominant eigenvalues of the synchronous machine (SM) baseline. Most oscillatory modes lie within the 0.1–2 Hz band with relatively high damping.
Figure 7.
Dominant eigenvalues of the synchronous machine (SM) baseline. Most oscillatory modes lie within the 0.1–2 Hz band with relatively high damping.
Figure 8.
Dominant eigenvalues of the 100% grid-forming inverter (GFM) replacement. Several modes shift to higher frequencies (up to 10–12 Hz) and exhibit lower damping compared to the SM case.
Figure 8.
Dominant eigenvalues of the 100% grid-forming inverter (GFM) replacement. Several modes shift to higher frequencies (up to 10–12 Hz) and exhibit lower damping compared to the SM case.
Figure 9.
Fault-initiated separation of the IEEE 39-bus system. A 3 fault is applied on Line 25–26 at 12.15 sand cleared at 12.30 s. Subsequent line openings at 17–18 (35.30 s), 4–14 (38.30 s), and 6–11 (40.20 s) complete the controlled split into Zone 1 and Zone 2. Icons indicate GFM converter placements.
Figure 9.
Fault-initiated separation of the IEEE 39-bus system. A 3 fault is applied on Line 25–26 at 12.15 sand cleared at 12.30 s. Subsequent line openings at 17–18 (35.30 s), 4–14 (38.30 s), and 6–11 (40.20 s) complete the controlled split into Zone 1 and Zone 2. Icons indicate GFM converter placements.
Figure 10.
(a) SM baseline; (b) GFM inverter. Bus voltage trajectories for the fault-initiated separation (GFM case). Colored traces show generator bus voltages (G01–G10). Dashed vertical lines mark the fault clearing at 12.30 s and the system split at 40.20 s. Dashed horizontal lines indicate the operational acceptance band [0.9, 1.1] p.u.
Figure 10.
(a) SM baseline; (b) GFM inverter. Bus voltage trajectories for the fault-initiated separation (GFM case). Colored traces show generator bus voltages (G01–G10). Dashed vertical lines mark the fault clearing at 12.30 s and the system split at 40.20 s. Dashed horizontal lines indicate the operational acceptance band [0.9, 1.1] p.u.
Figure 11.
System frequency trajectories for (a) synchronous machine baseline using and (b) 100% GFM case using . Gray: Zone 1; Orange: Zone 2; Green: global before split.
Figure 11.
System frequency trajectories for (a) synchronous machine baseline using and (b) 100% GFM case using . Gray: Zone 1; Orange: Zone 2; Green: global before split.
Figure 12.
(a) Zone 1 (under-frequency). (b) Zone 2 (over-frequency). Frequency trajectories for fixed and varying .
Figure 12.
(a) Zone 1 (under-frequency). (b) Zone 2 (over-frequency). Frequency trajectories for fixed and varying .
Figure 13.
(a) Zone 1 (under-frequency). (b) Zone 2 (over-frequency). Frequency trajectories for fixed and varying .
Figure 13.
(a) Zone 1 (under-frequency). (b) Zone 2 (over-frequency). Frequency trajectories for fixed and varying .
Figure 14.
(a) Zone 1 (under-frequency). (b) Zone 2 (over-frequency). Frequency trajectories for fixed and varying .
Figure 14.
(a) Zone 1 (under-frequency). (b) Zone 2 (over-frequency). Frequency trajectories for fixed and varying .
Figure 15.
(a) Zone 1 (under-frequency). (b) Zone 2 (over-frequency). Frequency trajectories for fixed and varying .
Figure 15.
(a) Zone 1 (under-frequency). (b) Zone 2 (over-frequency). Frequency trajectories for fixed and varying .
Figure 16.
Maximum RoCoF in Zone 1 (under-frequency island) across the grid.
Figure 16.
Maximum RoCoF in Zone 1 (under-frequency island) across the grid.
Figure 17.
Maximum RoCoF in Zone 2 (over-frequency island) across the grid.
Figure 17.
Maximum RoCoF in Zone 2 (over-frequency island) across the grid.
Figure 18.
Maximum frequency drop (nadir) in Zone 1 across the grid.
Figure 18.
Maximum frequency drop (nadir) in Zone 1 across the grid.
Figure 19.
Maximum frequency overshoot in Zone 2 across the grid.
Figure 19.
Maximum frequency overshoot in Zone 2 across the grid.
Figure 20.
Settling time in Zone 1 (under-frequency island) across .
Figure 20.
Settling time in Zone 1 (under-frequency island) across .
Figure 21.
Settling time in Zone 2 (over-frequency island) across .
Figure 21.
Settling time in Zone 2 (over-frequency island) across .
Table 1.
Load demand in the IEEE-39 bus system.
Table 1.
Load demand in the IEEE-39 bus system.
| Load | Bus | P (MW) | Q (Mvar) |
|---|
| L03 | 03 | 322.0 | 2.4 |
| L04 | 04 | 500.0 | 184.0 |
| L07 | 07 | 233.8 | 84.0 |
| L08 | 08 | 522.0 | 176.0 |
| L12 | 12 | 7.5 | 88.0 |
| L15 | 15 | 320.0 | 153.0 |
| L16 | 16 | 329.0 | 32.3 |
| L18 | 18 | 158.0 | 30.0 |
| L20 | 20 | 628.0 | 103.0 |
| L21 | 21 | 274.0 | 115.0 |
| L23 | 23 | 247.5 | 84.6 |
| L24 | 24 | 308.6 | −92.2 |
| L25 | 25 | 224.0 | 47.2 |
| L26 | 26 | 139.0 | 17.0 |
| L27 | 27 | 281.0 | 75.5 |
| L28 | 28 | 206.0 | 27.6 |
| L29 | 29 | 283.5 | 26.9 |
| L31 | 31 | 9.2 | 4.6 |
| L39 | 39 | 1104.0 | 250.0 |
Table 2.
Generator data in the IEEE-39 bus system.
Table 2.
Generator data in the IEEE-39 bus system.
| Gen | (MVA) | H (s) | (p.u.) | (p.u.) | (p.u.) | (p.u.) | (p.u.) |
|---|
| G01 | 10,000 | 5.000 | 0.0000 | 0.6000 | 0.8000 | 2.0000 | 1.9000 |
| G02 | 700 | 3.030 | 0.0000 | 0.4879 | 1.1900 | 2.0650 | 1.9740 |
| G03 | 800 | 3.580 | 0.0000 | 0.4248 | 0.0700 | 1.9960 | 1.8960 |
| G04 | 800 | 2.860 | 0.0000 | 0.3488 | 1.3280 | 2.0960 | 2.0640 |
| G05 | 300 | 2.600 | 0.0000 | 0.3960 | 0.4980 | 2.0100 | 1.8600 |
| G06 | 800 | 3.480 | 0.0000 | 0.4000 | 0.6512 | 2.0320 | 1.9280 |
| G07 | 700 | 2.640 | 0.0000 | 0.4030 | 1.3020 | 2.0650 | 2.0440 |
| G08 | 700 | 2.430 | 0.0000 | 0.3990 | 0.6377 | 2.0300 | 1.9600 |
| G09 | 1000 | 3.450 | 0.0000 | 0.5700 | 0.5870 | 2.1600 | 2.0500 |
| G10 | 1000 | 4.200 | 0.0000 | 0.3100 | — | 1.0000 | 0.6900 |
Table 3.
Replacement map (100% GFM) and preserved operating points.
Table 3.
Replacement map (100% GFM) and preserved operating points.
| Gen | Bus | Bus Type | Ctrl | (MVA) | (MW) | (p.u.) |
|---|
| G01 | 39 | PV | Droop | 10,000 | 1000.0 | 1.0300 |
| G02 | 31 | Slack | VSM | 700 | — | 0.9820 |
| G03 | 32 | PV | SyncV | 800 | 650.0 | 0.9831 |
| G04 | 33 | PV | Droop | 800 | 632.0 | 0.9972 |
| G05 | 34 | PV | SyncV | 300 | 508.0 | 1.0123 |
| G06 | 35 | PV | Droop | 800 | 650.0 | 1.0493 |
| G07 | 36 | PV | SyncV | 700 | 560.0 | 1.0635 |
| G08 | 37 | PV | SyncV | 700 | 540.0 | 1.0278 |
| G09 | 38 | PV | Droop | 1000 | 830.0 | 1.0265 |
| G10 | 30 | PV | SyncV | 1000 | 250.0 | 1.0475 |
Table 4.
Controller parameters of the grid-forming inverters.
Table 4.
Controller parameters of the grid-forming inverters.
| Droop-GFM (G01, G04, G06, G09) |
|---|
| P-Droop () | G01 = 5%, G04 = 8%, G06 = 7%, G09 = 3% |
| Q-Droop () | 5% (all) |
| Power Meas. LPF () | 0.05 s |
| Voltage Meas. LPF () | 0.01 s |
| Voltage-loop Gains () | 0.01 |
| Voltage Regulation Point | POI (mode = 1) |
| Virtual Synchronous Machine (VSM, G02) |
| Virtual Inertia (H) | 3 s |
| Damping () | 100 |
| Damping Filter () | 6 rad/s |
| Voltage Setpoint LPF | 0.003 s |
| Under-voltage Logic | ; linear reduction enabled |
| Overload Limiter | Gain = 0.1, LPF = 0.0025 s |
| Active Power Limits | , |
| Synchronverter (G03, G05, G07, G08, G10) |
| Virtual Inertia (H) | 3 s |
| Damping () | 100 |
| Reactive Droop () | 20 |
| Voltage-loop Gain () | 1000 (G03–G05–G07–G08); 1200 (G10) |
Table 5.
Aggregated voltage quality metrics (percentiles across buses; all result values expressed per unit).
Table 5.
Aggregated voltage quality metrics (percentiles across buses; all result values expressed per unit).
| | SM | 100% GFM |
|---|
| Retained Voltage (FRT, 12.15–12.30 s) |
| p05 | 0.524 | 0.686 |
| p50 | 0.771 | 0.900 |
| p95 | 0.973 | 0.987 |
| Worst | 0.524 (G08) | 0.686 (G08) |
| Post-fault (12.35–13.35 s) |
| Overshoot p.u. p95 | 0.100 | 0.000 |
| IVD p50 | 0.036 | 0.019 |
| Worst | 0.310 (G09) | 1.000 |
| Post-split 1 s (40.25–41.25 s) |
| Overshoot p.u. p95 | 0.009 | 0.000 |
| IVD p50 | 0.050 | 0.017 |
| Worst | 0.200 (G07) | 1.000 |
| Post-split 10 s (40.25–50.25 s) |
| Overshoot p.u. p95 | 0.009 | 0.000 |
| IVD p50 | 0.032 | 0.020 |
| Worst | 0.920 (G07) | 1.000 |
Table 6.
Computed frequency metrics (late window 180–200 s). Values are reported for the global pre-split system and for Zone 1 and Zone 2 after islanding. is the offset from 50 Hz (+overshoot, −drop).
Table 6.
Computed frequency metrics (late window 180–200 s). Values are reported for the global pre-split system and for Zone 1 and Zone 2 after islanding. is the offset from 50 Hz (+overshoot, −drop).
| Region | Case | [Hz] | [Hz] | Nadir [Hz] | Peak [Hz] | | Max RoCoF [Hz/s] |
|---|
| Global | SM | n/a | n/a | 49.995 | 50.207 | n/a | 0.259 |
| | GFM | n/a | n/a | 49.925 | 50.116 | n/a | 0.140 |
| Zone 1 | SM | 46.746 | (drop) | n/a | n/a | 0.016 | 0.318 |
| | GFM | 49.899 | (drop) | n/a | n/a | 0.098 | 0.083 |
| Zone 2 | SM | 51.856 | (overshoot) | n/a | n/a | 0.133 | 0.788 |
| | GFM | 50.173 | (overshoot) | n/a | n/a | 0.026 | 0.173 |
Table 7.
Percentage improvement or deterioration in frequency metrics when varying the damping (20→120) and inertia H (2→12). Positive values indicate improvement (reduced magnitude of the metric), while negative values denote worsening.
Table 7.
Percentage improvement or deterioration in frequency metrics when varying the damping (20→120) and inertia H (2→12). Positive values indicate improvement (reduced magnitude of the metric), while negative values denote worsening.
| Metric | Units | | |
|---|
| Z1 Frequency drop | Hz | +9.82% | +6.77% |
| Z2 Frequency overshoot | Hz | +13.39% | +52.09% |
| Z1 Min RoCoF | Hz/s | +65.12% | +26.74% |
| Z2 Max RoCoF | Hz/s | +76.26% | +13.23% |
| Z1 Settling time | s | −3.39% | −4.98% |
| Z2 Settling time | s | −41.69% | +76.36% |