This section examines the topology of the grid-forming converter and, on the basis of the VSG control scheme, establishes a dynamic model that captures the coupled effects of virtual inertia and damping.
2.1. Principle of VSG Control
Before formulating the dynamic model of the GFM-VSG, the basic topology and control principle of the VSG-controlled grid-forming converter should first be clarified. This subsection aims to explain the fundamental operating mechanism of VSG control and clarify how the converter emulates the inertial and damping characteristics of a synchronous generator.
Figure 1 presents the basic topology of the studied VSG system and provides the structural basis for the subsequent analysis of the VSG control principle.
Figure 1 depicts the overall configuration of the VSG system, which mainly consists of a DC source, a voltage-source converter, an output filter, the grid, and the connected load.
In this topology,
represents the DC-side source, while
,
, and
correspond to the filter inductance, parasitic resistance, and filter capacitance, respectively, and PCC denotes the common coupling point. The converter current and voltage at the PCC are expressed by
and
. The VSG controller generates the internal electromotive-force magnitude and phase by emulating synchronous-generator rotor dynamics, so that virtual inertia and damping characteristics can be introduced [
13]. Meanwhile, the active power loop incorporates droop regulation through the governor-like mechanism shown in (1).
where
corresponds to the active-power reference, and
is the active power-frequency droop coefficient, hereinafter referred to as the droop coefficient.
The classical second-order swing equation of a synchronous generator can be expressed as follows [
27]:
where
and
denote the inertia constant and damping coefficient, respectively;
,
, and
denote the mechanical, electromagnetic, and damping torques, respectively;
and
refer to the mechanical and electromagnetic powers, respectively;
denotes the rated angular velocity, whereas
represents the actual angular velocity.
2.2. Dynamic Characteristic Analysis Considering the Coupled Effects of Inertia and Damping
Based on the small-signal dynamic analysis method for VSG systems, by combining (1) and (2), the relationship between system frequency and active power can be obtained as follows [
28]:
Equation (3) shows that the output active power of the VSG depends not only on the reference active power but also on the deviation between the actual angular velocity and its rated value.
To further analyze the dynamic behavior of the system, the resistance of the grid-forming converter is neglected, and (2) is linearized around the steady-state operating point. By further incorporating the power transfer equation of the system, as given in (4), one obtains:
Accordingly, the closed-loop transfer function from the input active power to the output active power can be expressed as follows:
where
denotes the synchronizing power coefficient.
By comparing the derived transfer function with the standard second-order form, the relationships among the characteristic angular frequency , the damping ratio , and the converter control parameters can be obtained as follows:
The settling time , which describes the time required for the system to return to steady-state operation, cannot be directly determined solely from the natural angular frequency and the damping ratio . Nevertheless, within a tolerance band of 2% to 5%, it can be approximately expressed as follows:
As indicated by (6), when the droop coefficient remains unchanged, the damping ratio is inversely related to the virtual inertia and directly related to the damping coefficient . In contrast, the settling time increases with and decreases with .
For the dynamic analysis in this section, the VSG is first operated with a load of 20 kW. At
, a sudden 10 kW reduction in active load is introduced. By fixing either
or
and varying the other parameter, the respective influence of virtual inertia and damping on the dynamic response of the system can be observed, as shown in
Figure 2.
The responses in
Figure 2 show that a larger virtual inertia reduces the immediate sensitivity of the converter to active-power disturbances and lowers the initial frequency gradient, which reflects stronger inertial buffering. The drawback is that the transient process becomes slower. When
remains fixed, increasing
lowers the damping ratio and makes the response more oscillatory, so the corresponding overshoot becomes larger and the oscillation duration is extended.
By contrast, increasing the damping coefficient within a reasonable range is effective for suppressing overshoot and accelerating oscillation decay. The settling process therefore becomes shorter. However, if is enlarged excessively, response flexibility deteriorates even though the stability margin is improved. These observations show that satisfactory dynamic behavior cannot be achieved by changing only one parameter independently, and coordinated adjustment of and is therefore required.
2.3. Adaptive Parameter Control Strategy
Based on the classical second-order motion equation, the following relationship can be established between the system frequency deviation and the rate of change of frequency:
As indicated by (8), virtual inertia exerts a more direct effect on the rate of frequency change, whereas the damping coefficient plays a more prominent role in determining the frequency deviation. An appropriate increase in both and helps reduce the frequency deviation and the rate of frequency variation, thereby improving the overall stability of the system. Therefore, when power disturbances occur, properly increasing these two parameters can effectively restrain both the amplitude and the growth rate of frequency fluctuations.
Nevertheless, fixed parameter settings cannot satisfy the distinct control requirements associated with different stages of the oscillatory process. Taking the transient response under a large disturbance as an example, the VSG output frequency curve shown in
Figure 3 can be divided into four dynamic regions, denoted as Regions I, II, III, and IV.
Region I: The output frequency of the VSG is higher than the reference value and , indicating that the frequency is still rising. Under this condition, . To quickly suppress the upward frequency trend and drive toward zero, the virtual inertia should be increased so as to strengthen inertial support and restrain the rapid frequency excursion. At the same time, the damping coefficient should also be increased to limit the overshoot during the transient process.
Region II: The output frequency remains above the reference value, whereas , which means that the rising trend has ended and the frequency has started to fall back. In this case, . Since the system has entered the recovery stage, should be reduced to accelerate the return of the frequency to its nominal value. Meanwhile, should be decreased appropriately to avoid an overly sluggish response that would weaken the recovery effect.
Regions III and IV: The parameter adjustment principles in these two regions follow the same logic as those in Regions I and II, respectively. Accordingly, the adaptive tuning rules for
and
throughout the disturbance-induced oscillation process are summarized in
Table 1, where the arrows ↑ and ↓ indicate an increase and a decrease in the corresponding parameter, respectively.
Based on the hierarchical regulation concept, frequency deviation and frequency slope are selected as the governing variables to construct the following piecewise adaptive regulation laws:
where
and
denote the steady-state values of virtual inertia and damping coefficient, respectively;
,
,
, and
are the adaptive coefficients associated with inertia regulation under disturbance conditions;
,
,
, and
are the corresponding coefficients for damping regulation; and
and
represent the thresholds for frequency deviation and frequency variation rate, respectively. In this study,
and
is set to 0.1 and
is set to 1.
2.4. Small-Signal and Lyapunov Stability Analysis
Since the adaptive parameters are updated in a discrete control manner, J and D can be regarded as frozen parameters within each control sampling interval for local small-signal analysis. To verify the stability of the proposed adaptive laws, a small-signal model is established around the steady-state operating point. Let the small-signal state vector be defined as
where
and
denote the small-signal deviations of the power angle and angular frequency, respectively. Considering the active power-frequency loop of the VSG, the small-signal dynamic equations can be written as
where
is the synchronizing power coefficient,
is the rated angular frequency, and
is the active power-frequency droop coefficient. Therefore, the corresponding state-space model is
The characteristic equation of the state matrix can be derived as
According to the Routh-Hurwitz stability criterion for a second-order system, the system is locally stable if all coefficients of the characteristic equation are positive. Therefore, the small-signal stability conditions are
The proposed adaptive laws adjust and according to the frequency deviation and RoCoF. As long as the adaptive parameters are constrained within positive bounded ranges, the above stability conditions can be satisfied during the regulation process.
To further verify the stability of the adaptive parameter regulation process, the following Lyapunov function is selected:
Since , , and , is positive definite. In the digital control implementation, and are updated according to the adaptive laws and are held constant within each control sampling interval. Therefore, the derivative of along the system trajectory is
Substituting the small-signal dynamic equations into the above expression gives
When , there is . According to the small-signal dynamic equation, further gives . Therefore, the equilibrium point is locally asymptotically stable.
Since the adaptive parameters are constrained by predefined upper and lower bounds, the updated values of and always satisfy and . Therefore, the state matrix remains Hurwitz during each sampling interval. The adaptive law changes only the numerical values of and , but does not alter the sign-definiteness of the damping and synchronizing terms. Hence, under the sample-and-hold implementation and bounded parameter constraints, the proposed adaptive regulation preserves the local small-signal stability of the VSG system.