1. Introduction
With the ongoing global energy transition, the large-scale integration of renewable energy has become a key trend in the evolution of modern power systems [
1]. As one of the world’s largest markets for renewable energy deployment, China had, by the end of 2025, accumulated more than 1800 GW of installed wind and photovoltaic capacity, accounting for 47.3% of its total installed power generation capacity. At the same time, the installed capacity of newly deployed energy storage systems in operation nationwide reached 136 GW/351 GWh. New energy storage is therefore emerging as an important infrastructure for facilitating renewable energy integration and enhancing the regulation capability of power systems. Compared with electrochemical energy storage technologies, flywheel energy storage systems (FESSs) offer distinct advantages, including high power density, fast response, long cycle life, and environmental friendliness [
2,
3]. Accordingly, FESSs have shown considerable potential in high-frequency power regulation, short-term inertial support, and transient support during faults [
4,
5]. With the continued advancement of FESS demonstration projects and standardization efforts, grid-connected operation under complex grid-fault conditions—especially low-voltage ride-through (LVRT) capability—has become a key factor limiting the wider deployment of FESSs.
Existing LVRT studies mainly follow two technical routes, namely hardware-assisted methods and control-oriented methods [
6,
7]. Hardware-assisted methods usually introduce energy storage or dissipation units to buffer the energy impact during faults [
8,
9], whereas control-oriented methods improve converter capacity utilization by optimizing current allocation, reactive power support, and power regulation strategies [
10,
11]. Although these studies have provided useful theoretical and technical references for fault ride-through control, most of them focus on wind turbines or wind–storage hybrid systems, while specific investigations on coordinated control between the machine-side and grid-side converters of a standalone grid-connected FESS during faults remain limited. As the role of energy storage devices in fault support continues to expand, increasing attention has also been paid to their own grid-connected operating characteristics and LVRT control under voltage sag conditions [
12,
13]. Relevant studies indicate that research on energy storage is gradually extending from the ride-through control of the storage device itself to its participation in fault support and transient stability enhancement of external renewable energy systems [
14,
15].
Owing to its rapid power response and favorable transient-support characteristics, the FESS has recently attracted growing interest in fault ride-through studies of renewable-energy systems. Existing studies have shown that the FESS can enhance the transient stability and fault support capability of wind farms and renewable energy transmission systems [
16,
17]. Meanwhile, some researchers have started to investigate the grid-fault ride-through performance of standalone FESSs. Zhai et al. established an early grid-connected FESS model and proposed a basic ride-through control strategy for three-phase short-circuit faults, thereby verifying the feasibility of fault support by the FESS. However, their work mainly focused on symmetrical faults, with insufficient attention given to disturbance suppression under asymmetrical faults [
18]. On this basis, Zheng et al. further proposed an LVRT strategy based on coordinated machine-side and grid-side control, which is applicable to both symmetrical and asymmetrical faults and improves current tracking and reactive power support during faults. However, their study did not sufficiently address machine-side electromagnetic transients and torque impacts [
19]. To overcome this limitation, Sturm et al. investigated machine-side electromagnetic characteristics and suppressed torque shock and flux fluctuations during faults through resonant current control and flux regulation [
20]. At present, research on LVRT control of standalone FESSs is still at a developing stage. Existing studies mainly focus on validating basic fault-support capability and conventional coordination between the machine-side and grid-side converters. Further efforts are still needed to formulate the key issues under symmetrical and asymmetrical faults in a unified manner and to improve coordinated machine-side and grid-side control.
In summary, most existing LVRT schemes for standalone FESSs adopt a control mode that combines conventional closed-loop machine-side control with grid-side reactive power support. Under such schemes, machine-side power regulation mainly follows external commands passively, lacking active coordination and online reconstruction based on DC-side energy imbalance. Consequently, grid voltage faults can easily lead to active-power imbalance between the machine side and the grid side, resulting in DC-link overvoltage. In addition, although existing methods for asymmetrical faults have involved positive- and negative-sequence decoupling, current limiting, and power ripple suppression, relatively few studies have systematically addressed the coordination among double-frequency disturbance suppression, grid-current quality improvement, and converter capacity constraints from the perspective of grid-side current-loop disturbance rejection. Therefore, this paper investigates the coordinated LVRT control of a standalone grid-connected FESS under symmetrical and asymmetrical voltage sag faults. Based on the mathematical models of the machine-side and grid-side converters, the mechanisms of active-power imbalance between the machine side and the grid side, DC-link voltage fluctuation, and double-frequency disturbances caused by negative-sequence components during faults are analyzed, and a coordinated fault ride-through control framework for the machine-side and grid-side converters is established. Specifically, to cope with DC-side energy accumulation and DC-link overvoltage caused by reactive-power-priority support and constrained active-power output on the grid side under low-voltage faults, a coordinated regulation method based on cascaded limiting of DC-link voltage deviation is adopted on the machine side to restore the power balance between the machine side and the grid side and suppress DC-link overvoltage. Meanwhile, an improved linear active disturbance rejection control (LADRC) is introduced into the grid-side current inner loop. By optimizing the structure of the extended state observer, the observation and compensation capability for double-frequency disturbances is enhanced, thereby improving grid-current quality under asymmetrical faults. In this way, power rebalancing between the machine side and the grid side, DC-link voltage stabilization, and grid-current disturbance suppression are incorporated into a unified coordinated control objective.
The contributions of this study are summarized as follows:
- (1)
A coordinated LVRT control framework for the machine-side and grid-side converters is established for standalone grid-connected FESSs. Different from conventional control methods in which the machine-side power command mainly passively follows an external reference, the proposed framework takes the DC-side energy imbalance as the coordination criterion and introduces the DC-link voltage deviation into the regulation of the machine-side active-current command.
- (2)
An online reconstruction strategy for the machine-side active-current command based on cascaded limiting of DC-link voltage deviation is proposed. This strategy enables the machine-side converter to actively adjust its power response when the grid-side active-power output is constrained, thereby suppressing DC-link overvoltage or undervoltage and restoring the power balance between the machine side and the grid side.
- (3)
An improved LADRC-based grid-side current inner-loop control strategy is proposed for asymmetrical voltage sags. By optimizing the linear extended state observer (LESO) structure, the proposed method enhances the observation and compensation capability for the double-frequency disturbance caused by negative-sequence components, thereby improving grid-current quality and disturbance rejection performance.
Finally, hardware-in-the-loop (HIL) experiments are conducted to verify the effectiveness of the proposed coordinated control strategy in DC-link voltage stabilization, grid-current quality improvement, and LVRT performance enhancement.
2. Grid-Connected Topology and Steady-State Control of FESS
The grid-connected topology of the FESS is shown in
Figure 1. It mainly consists of a flywheel rotor, a permanent magnet synchronous machine (PMSM), a machine-side converter, a grid-side converter, a DC-link capacitor, and an LCL filter [
21]. The flywheel rotor is rigidly coupled to the shaft of the PMSM. The machine-side and grid-side converters form a back-to-back structure through the DC link, while the grid-side converter is connected to the AC grid through the LCL filter [
22]. According to the direction of power flow, the FESS can operate in two modes: charging and discharging. In the charging mode, the grid-side converter absorbs power from the AC grid and transfers it to the machine side through the DC link, driving the PMSM to accelerate the flywheel and store energy. In the discharging mode, the flywheel releases mechanical energy, which is delivered to the grid through the machine-side and grid-side converters [
23]. Under steady-state operation, the machine side is responsible for flywheel speed and electromagnetic power regulation, whereas the grid side is responsible for DC-link voltage stabilization and grid power control.
Under steady-state conditions, the machine-side converter adopts a rotor-flux-oriented vector control scheme. The q-axis current is used to regulate the electromagnetic torque and the charge/discharge power, while the d-axis current reference is set to
= 0. The dq-axis current inner loop of the machine-side converter employs a voltage control law with cross-coupling compensation and permanent-magnet back-EMF feedforward [
24], which can be expressed as:
where
and
are the d- and q-axis current references, respectively,
and
are the corresponding actual currents,
and
are the d- and q-axis inductances of the PMSM,
is the permanent-magnet flux linkage,
is the reference value of the electrical angular speed of the machine,
is the electrical angular speed of the machine, and
and
are the proportional and integral gains of the machine-side current inner loop. Under the condition of
= 0 and neglecting machine losses, the machine-side electromagnetic power can be written as:
which indicates that the machine-side active power is ultimately regulated through the q-axis current.
The grid-side converter adopts a double-loop control structure composed of an outer voltage loop and an inner current loop [
25]. The outer loop regulates the DC-link voltage and generates the active-current reference, while the inner current loop ensures fast tracking of the grid-current reference, thereby stabilizing the DC-link voltage and regulating the grid-side active and reactive power. In the grid-voltage-oriented synchronous rotating dq reference frame, the d- and q-axis voltage equations of the grid-side converter are given by:
where
is DC-link voltage reference,
and
are the d- and q-axis components of the grid voltage,
and
are the d- and q-axis components of the grid current reference,
and
are the d- and q-axis components of the grid current,
and
are the equivalent grid-side filter inductance and resistance, respectively, and
is the synchronous angular frequency. Accordingly, the active and reactive power delivered by the grid-side converter can be expressed as:
3. Conventional LVRT Control Strategy of FESS
When grid faults cause the point-of-common-coupling voltage to sag or swell, the FESS is still required to remain connected to the grid within the specified time and to provide the necessary reactive power support in accordance with fault ride-through requirements [
26,
27], so as to assist the grid voltage in recovering to a stable operating state.
During steady-state operation of the FESS, as shown in
Figure 1, the machine-side electromagnetic power
and the active power
delivered by the grid-side converter satisfy the energy balance relationship:
where
is the voltage across the DC-link capacitor, and
is the DC-link capacitance. When the machine-side power and grid-side power are balanced, i.e.,
, the DC-link voltage remains stable. During a grid voltage sag, if the FESS operates in the discharging mode, the power imbalance caused by the fault leads to an increase in the DC-link voltage; conversely, if the system operates in the charging mode, the power imbalance causes the DC-link voltage to decrease. Considering the voltage withstand capability of the converters and DC-link components, the upper and lower protection thresholds of the DC-link voltage are set to 1.1 pu and 0.9 pu of the rated value, respectively.
3.1. Machine-Side Control Strategy During Grid Voltage Faults
When the grid voltage sags, the active power output capability of the grid-side converter decreases, resulting in a transient imbalance between the machine-side electromagnetic power and the grid-side active power, which further causes DC-link voltage fluctuations [
28]. For a standalone FESS, the core objective of machine-side control during faults is to rebalance the power between the machine side and the grid side by regulating the electromagnetic power, thereby suppressing DC-link overvoltage. To this end, the machine-side converter adopts a power outer-loop and current inner-loop control strategy, as shown in
Figure 2.
According to the machine-side power relationship in
Section 2, under rotor-flux-oriented control and with
, the q-axis reference current of the machine side can be obtained from the output of the power outer loop as:
where
is the machine-side power reference,
and
are the proportional and integral gains of the power outer loop, respectively. It can be seen that the regulation of machine-side active power is ultimately achieved through the q-axis current reference command.
The machine-side controller parameters are tuned according to the bandwidth-separation principle of “fast tracking in the current inner loop and slow regulation in the power outer loop”. The current inner loop is designed using the pole-zero cancelation method. After voltage feedforward and cross-coupling compensation, the d- and q-axis current channels can be approximately regarded as first-order plants in the form of , where L and R denote the equivalent inductance and equivalent resistance of the corresponding axis, respectively. By matching the zero of the PI controller with the pole of the controlled plant, the proportional gain and integral gain can be determined as and , respectively, where is the desired current-loop bandwidth. The bandwidth of the power outer loop is set lower than that of the current inner loop. Its PI parameters are initially tuned according to the relationship between the electromagnetic power and the q-axis current, and are further verified and corrected through simulation and HIL experiments to ensure the dynamic response and smoothness of the power regulation process.
3.2. Grid-Side Control Strategy During Grid Voltage Faults
During steady-state operation, the grid-side converter adopts a grid-voltage-oriented vector control scheme to maintain the stability of the DC-link voltage. According to the grid-side power relationship in
Section 2, the d-axis current determines active power exchange, while the q-axis current determines reactive power output. Therefore, under LVRT conditions, the control of the grid-side converter is constrained not only by the energy balance requirement on the DC side of the system, but also by grid connection codes. The control scheme of the grid-side converter is shown in
Figure 3.
According to the voltage sag depth at the point of common coupling, the relationship between the reactive current required for voltage recovery and the voltage sag depth [
29,
30,
31] is given by:
where
is the per-unit voltage at the point of common coupling, and
is the rated current of the converter. When the voltage at the point of common coupling drops deeply, the converter capacity of the grid-side converter limits the active-current output, and the maximum allowable active-current reference can be expressed as:
where
is the maximum current magnitude allowed for the grid-side converter output. The DC-link voltage deviation is regulated by a PI controller to obtain the active-current reference
. The active-current limit
is calculated from (8), and the smaller one is selected as the active-current output command of the grid-side converter. When
, the DC-link voltage can be kept stable by the outer-loop control alone. When
, the active-power output of the grid-side converter is limited by the converter capacity. In this case, the DC-link voltage cannot be effectively restored by grid-side control alone; therefore, coordinated regulation between the machine-side and grid-side converters is required.
The tuning method of the grid-side PI controller parameters is similar to that of the machine-side controller. The PI parameters of the grid-side current inner loop are determined using a method that combines pole-zero cancelation and bandwidth design. The proportional and integral gains are initially selected according to the equivalent inductance , equivalent resistance , and desired current-loop bandwidth of the grid-side filter. After the current inner loop is stably tuned, the grid-side DC-link voltage outer loop is further designed with a bandwidth lower than that of the current inner loop, so as to avoid current shocks and DC-link voltage oscillations caused by overly rapid variations in the active-current reference generated by the outer loop. The final PI parameters are verified through simulation and HIL experiments by considering current limiting, DC-link voltage fluctuation, and the fault-switching process.
5. Experimental Validation
To verify the effectiveness of the proposed coordinated fault ride-through control strategy for the FESS based on DC-link voltage deviation control and the improved LADRC, a standalone grid-connected FESS model was established on a hardware-in-the-loop (HIL) experimental platform, as shown in
Figure 10. Experimental studies were carried out under two operating conditions: symmetrical and asymmetrical grid faults. Furthermore, conventional PI control, conventional LADRC, and the improved LADRC were employed to conduct a comparative analysis of the proposed LVRT scheme and the associated control strategies. The main system parameters are listed in
Table 1, where the upper and lower limits of the DC-link voltage are set to 1.1 pu and 0.9 pu, respectively.
The experimental validation was conducted on a HIL platform consisting of a host computer, an MT 8020 real-time simulator (ModelingTech, Shanghai, China), an MT 1070 rapid control prototyping (RCP) controller (ModelingTech, Shanghai, China), and an oscilloscope (Tektronix, Beaverton, OR, USA), as shown in
Figure 10. The overall configuration and signal flow of the HIL experimental platform are shown in
Figure 11. The main power circuit of the grid-connected flywheel energy storage system was implemented on the MT 8020 real-time simulator. The main circuit model was executed in real time with a fixed simulation step of 1 μs, which enables the fast switching dynamics of the power electronic converters and the transient characteristics under grid faults to be represented. The proposed control algorithm was implemented on the MT 1070 RCP controller. The controller receives the analog signals from the real-time simulator, performs real-time computation of the control law, and generates PWM signals that are fed back to the simulator to drive the power converters, thereby forming a closed-loop HIL configuration. In the experiments, the converter switching frequency was set to 10 kHz, and the control sampling frequency was also set to 10 kHz, corresponding to a control step of 100 μs. The signal acquisition, control computation, and data transmission processes were completed within one control sampling period. The analog signals were scaled to ±10 V and processed with 16-bit resolution. An oscilloscope was used to record key experimental waveforms, including the DC-link voltage, grid-side voltage, grid-side current, and power responses. The quality of the recorded signals and the reliability of subsequent quantitative analysis depend strongly on measurement-data quality and noise characteristics [
38,
39]. Compared with offline simulation, the HIL platform incorporates practical factors such as sampling, computation, interface transmission, and digital control implementation under real-time closed-loop conditions. Recent studies on HIL real-time simulation also indicate that this approach is suitable for evaluating the interaction among power-electronic plant models, controller hardware, and interface processes under closed-loop operating conditions [
40]. Therefore, it provides support for the real-time feasibility of the proposed LVRT control strategy and the reliability of the experimental results.
Although the improved LADRC has a more complex observer structure than conventional PI control, it does not involve online optimization, iterative calculation, or high-order matrix operations. Compared with the conventional LESO, only one proportional compensation branch is added in the disturbance-estimation feedback path, so the additional computational burden mainly consists of only a few multiplications and additions. Under the 10 kHz control sampling frequency used in the HIL experiment, the control-law calculation and PWM update can be completed within one control period. Therefore, the improved LADRC can meet the real-time implementation requirements of high-speed digital control systems.
The grid-side line-to-line voltage is set to 690 V according to the rated low-voltage AC-side voltage of the HIL experimental system and the MW-class grid-connected FESS converter. This voltage level matches the 1.0 MW power rating of the FESS and the current capacity of the grid-side converter, allowing the grid-side voltage, current, and power parameters to remain within a reasonable engineering range. Meanwhile, the 690 V line-to-line voltage is also used as a basic parameter for grid-side current reference calculation, converter capacity constraint, and current limiting during faults, and the main controller parameters are provided in
Appendix A.
As shown in
Figure 12a, the flywheel energy storage system (FESS) initially operates in the discharging mode at 650 kW. At
t = 0.5 s, the grid voltage drops to 40% of its rated value and recovers to normal at
t = 1.125 s after a duration of 0.625 s. It can be observed from
Figure 12b that during the voltage sag, the grid-side output current amplitude increases significantly, reaching a peak of approximately 1800 A, while the three-phase currents maintain good symmetry. As shown in
Figure 12c,d, the grid-side reactive power rapidly rises to about 450 kvar at
t = 0.5 s. Meanwhile, due to converter capacity constraints, the grid-side active power decreases from 600 kW to 400 kW. Because the machine-side output power exceeds the power delivered by the grid-side converter at the onset of the fault, a transient active power imbalance occurs, causing the DC-link voltage to rise rapidly. When the DC-link voltage reaches the preset upper threshold, the DVCRH exits saturation and takes over the regulation of the machine-side active-current command, as shown in
Figure 12e. Under its action, the machine-side power is rapidly reduced to approximately 400 kW, thereby re-establishing the power balance and stabilizing the DC-link voltage near 1650 V, as shown in
Figure 12f. During the voltage sag, the proposed coordinated control strategy promptly regulates the machine-side power and maintains DC-link voltage stability, thereby ensuring continuous LVRT operation.
Figure 13 presents the experimental results for an asymmetrical grid fault where the voltages of phases A and B drop to 20% of their rated values at t = 0.5 s, with all other operating parameters remaining identical to those in the symmetrical fault experiment. As shown in
Figure 13b, following the onset of the asymmetrical fault, the grid-side current increases briefly but maintains stability, with the three-phase currents reaching a steady state after approximately 25 ms. Observations from
Figure 13c,d indicate that the grid-side converter responds to the LVRT command during the voltage sag, leading to a rapid rise in reactive power and a constrained reduction in active power. However, due to the influence of the negative-sequence component in the grid voltage, pronounced double-frequency pulsations are superimposed on both the active and reactive powers. As illustrated in
Figure 13e, the machine-side output power decreases accordingly. Owing to the initial power imbalance, the DC-link voltage rises rapidly; once its average value reaches the preset upper safety threshold, the DVCRH exits saturation and takes over the regulation of the active-current command. Consequently, the average DC-link voltage is stabilized around 1650 V, as shown in
Figure 13f.
Figure 14 presents the fast Fourier transform (FFT)-based harmonic spectra of the grid-side voltage and current during the fault interval of 0.6–1.1 s. The voltage spectra are mainly concentrated at the 50 Hz fundamental component, while the high-order harmonic components are relatively small. This indicates that the voltage sag mainly changes the fundamental amplitude rather than introducing significant high-order harmonic distortion. Under both symmetrical and asymmetrical voltage sag conditions, the voltage THD values are lower than 0.01%, which is below the voltage THD limit specified in IEEE 519-2022 [
41]. As shown in
Figure 14b,d, the high-order harmonic components of the grid-side current remain at a low level under both symmetrical and asymmetrical voltage sag conditions, with maximum current THD values of 0.13% and 0.12%, respectively. The total demand distortion (TDD) was calculated using the rated line current of 836.74 A as the reference current, which was determined from the 1.0 MW rated power of the FESS and the 690 V grid-side line-to-line RMS voltage. Based on this reference current, the maximum current TDD values under symmetrical and asymmetrical voltage sag conditions are 0.20% and 0.18%, respectively, both of which are lower than the conservative 5% current TDD limit specified in IEEE 519-2022. These results indicate that the proposed control strategy can maintain good grid-side power quality during LVRT.
Figure 15 compares the grid-side d- and q-axis current responses under asymmetrical faults using conventional PI control, conventional LADRC, and the improved LADRC. It can be observed that, during the fault interval of 0.6–1.1 s, the peak-to-peak ripples of
and
under conventional PI control are 87.12 A and 77.00 A, respectively, while the corresponding RMS ripples are 24.18 A and 19.95 A. With conventional LADRC, the peak-to-peak ripples of
and
are reduced to 43.17 A and 41.49 A, respectively, and the RMS ripples are reduced to 10.33 A and 8.79 A, respectively. After adopting the improved LADRC, the peak-to-peak ripple and RMS ripple of
are further reduced to 34.35 A and 7.67 A, corresponding to reductions of 60.6% and 68.3% compared with conventional PI control, respectively. For
, the peak-to-peak ripple and RMS ripple under the improved LADRC are 53.22 A and 11.51 A, respectively, which are reduced by 30.9% and 42.3% compared with conventional PI control. Therefore, while maintaining a fast current-tracking response, the improved LADRC can significantly suppress the double-frequency ripple of the dq-axis currents and exhibits superior dynamic disturbance rejection capability.
Figure 16 further compares the output waveforms of the grid-side three-phase currents under conventional PI control and the improved LADRC during the asymmetrical voltage sag. Under conventional PI control, the three-phase grid currents exhibit obvious imbalance and distortion due to the double-frequency disturbance induced by the asymmetrical fault. In particular, the amplitudes of the phase-B and phase-C currents are approximately 1815 A and 1763 A, respectively, yielding a maximum interphase peak-current deviation of about 52 A. After adopting the improved LADRC, the peak currents of phases A, B, and C are approximately 1787.9 A, 1791.7 A, and 1787.1 A, respectively, and the maximum interphase peak-current deviation is reduced to about 4.57 A, corresponding to a reduction of approximately 91.2% compared with conventional PI control. Meanwhile, the maximum RMS deviation among the three-phase currents is only 3.33 A. Therefore, the improved LADRC can effectively suppress the interphase current imbalance and current distortion caused by the asymmetrical voltage sag, allowing the three-phase currents to maintain good symmetry and sinusoidal characteristics during the fault period, thereby improving the grid-current quality of the FESS during LVRT.
6. Conclusions
This study focuses on the LVRT capability of FESS and investigates the operating mechanism and control issues under symmetrical and asymmetrical grid-voltage sag conditions. The results show that, during low-voltage faults, the reactive-power-priority support of the grid-side converter compresses its active power output capability, thereby causing an active-power imbalance between the machine side and the grid side and resulting in DC-link voltage limit violations. Under asymmetrical faults, the negative-sequence component further induces double-frequency oscillations in the grid current and power, which weaken the transient stability and degrade the grid power quality of the system. To address these issues, a coordinated fault ride-through control framework for the machine-side and grid-side converters is established. On the machine side, a coordinated regulation strategy based on cascaded limiting of the DC-link voltage deviation is adopted to achieve the adaptive reconstruction of the active-current command. On the grid side, an improved LADRC is employed to enhance the observation and compensation of double-frequency disturbances. In this way, DC-link voltage stabilization, power rebalancing between the machine side and the grid side, and grid-side disturbance rejection are achieved in a coordinated manner.
Experimental results show that the proposed coordinated control strategy exhibits strong fault adaptability and dynamic coordination capability during LVRT. Under both symmetrical and asymmetrical voltage sags, the DC-link voltage can be stabilized at approximately 1650 V, indicating that the proposed strategy can effectively re-establish the power balance between the machine side and the grid side. Under symmetrical and asymmetrical voltage sag conditions, the voltage THD values are both lower than 0.01%, while the maximum grid-current THD values are 0.13% and 0.12%, respectively, with corresponding TDD values of 0.20% and 0.18%, indicating that the harmonic distortion of the grid current is effectively suppressed. Under asymmetrical faults, the improved LADRC reduces the RMS ripples of and by 68.3% and 42.3%, respectively, compared with conventional PI control, and reduces the maximum interphase peak-current deviation from approximately 52 A to 4.57 A, corresponding to a reduction of about 91.2%. Therefore, the proposed strategy shows good effectiveness in DC-link voltage stabilization, double-frequency disturbance suppression, and grid-current quality improvement.
At present, the operation of practical flywheel energy storage systems is constrained by factors such as mechanical stress, motor losses, temperature conditions, and energy capacity. However, the LVRT process in the experiments of this study lasts only 0.625 s and belongs to a short-term electrical transient process. Within this time scale, the influence of these slow dynamic physical factors on the proposed high-speed coordinated electrical control is relatively limited; therefore, they are not included in the current model. Future work will establish a multi-physics comprehensive model considering mechanical constraints, loss models, thermal characteristics, and capacity limitations, so as to further evaluate the comprehensive ride-through performance of FESSs under long-duration and consecutive fault conditions.