Next Article in Journal
New Interval Improved Fuzzy Partitions Fuzzy C-Means Clustering Algorithms under Different Distance Measures for Symbolic Interval Data Analysis
Next Article in Special Issue
Impulse Characteristics of Soil Treated with Enhancement Materials and Various Moisture Contents
Previous Article in Journal
A Malware Detection Framework Based on Semantic Information of Behavioral Features
Previous Article in Special Issue
Electromagnetic Fields from Cloud-to-Cloud Horizontal Lightning Channel on Perfect Conducting Soil: Induced Potentials in Flying Aircraft
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Research on Lightning Overvoltage Protection of Line-Adjacent Pipelines Based on Solid-State Decoupling

1
State Grid Hubei Power Supply Limited Company Ezhou Power Supply Company, Ezhou 436000, China
2
School of Electrical and Electronic Engineering, Shandong University of Technology, Zibo 255000, China
*
Author to whom correspondence should be addressed.
Appl. Sci. 2023, 13(22), 12529; https://doi.org/10.3390/app132212529
Submission received: 12 September 2023 / Revised: 27 October 2023 / Accepted: 8 November 2023 / Published: 20 November 2023

Abstract

:
Existing transmission lines and pipelines are frequently crossed and erected in parallel, meaning that if lightning strikes a wire and causes insulator flashovers, the resulting lightning current will spread through the grounding of the tower where the flashover insulator is located. This dispersion of current can lead to overvoltage effects on nearby pipelines. This study performs simulation calculations to analyze the overvoltage experienced by pipelines due to the dispersion of grounding current from the tower. Furthermore, this paper proposes a method for protecting the pipeline from such an overvoltage. Firstly, the lightning transient calculation model of a transmission line tower is constructed using the electromagnetic transient software ATP-EMTP 5.5. The model calculates the effects of lightning peak currents and soil resistivity on the distribution characteristics of lightning current in the tower, specifically in the area where the flashover insulator is located. Subsequently, a calculation model of the tower grounding grid–natural gas pipeline is developed, taking into account the distribution characteristics of lightning current in the tower. This model analyzes the impact of lightning peak currents, soil resistivity, and pipeline spacing on pipeline overvoltage. Finally, the effectiveness of the solid-state decoupler in mitigating lightning overvoltage in the pipeline is verified. The results demonstrate a positive correlation between the lightning current entering the tower grounding grid through the flashover insulator and the lightning current distribution characteristics. The solid-state decoupling device proves to be effective in reducing the voltage of the pipeline insulation layer, and the simulation results provide the optimal laying length of the bare copper wire.

1. Introduction

Since the national “new infrastructure” and other development strategies were put forward, in which the “energy Internet” has become an important form of construction, the “West–East Gas Transmission”, “West-to-East Electricity Transmission”, and other national cross-regional energy transmission projects have been implemented, effectively alleviating China’s energy load center distribution imbalance and other issues to a great extent, to meet the social development needs of electricity, oil and natural gas, and other energy forms [1]. However, the new infrastructure also faces many problems, for example, to save land area, electricity, oil and gas, and other energy supply facilities often use the “shared corridor” construction method, leading to the inevitable formation of natural gas pipelines, electric power overhead line crossovers, and so on, which cause “two lines and one land” electromagnetic interference problems that are gradually becoming larger concerns [2,3]. When the overhead power conductor suffers a lightning strike, the lightning current in the intruding conductor will generate a space-alternating electromagnetic field around the conductor such that the adjacent pipeline, due to inductive coupling, produces a pipeline overvoltage [4,5]. If the lightning current makes the line insulator flashover, the lightning current will be scattered along the surface of the flashover insulator through the tower grounding grid such that the adjacent pipeline, due to resistive coupling, produces a pipeline overvoltage [6,7,8]. Furthermore, due to the existence of resistive coupling and the pipeline insulation layer’s potential difference, the safe operation of the pipeline has been threatened; thus, research into the overvoltage protection of the transmission line adjacent to the pipeline is of great significance.
Protection for the transmission line near the natural gas pipeline mainly includes two aspects: the first concerns protection for the DC transmission line, research into the DC leakage current near the natural gas pipeline, and metal layer corrosion research to determine some measures to slow down or inhibit the metal layer corrosion; the second concerns the normal operation of the overhead line, research into grounding faults, and how a lightning strike near the natural gas pipeline induces overvoltage through studying some measures to reduce the magnitude of the pipeline overvoltage.
Lucca Giovanni studied the effect of pipe insulation coating breakage on electromagnetic interference between transmission lines and pipelines and proposed a law stating that the resistance of pipe insulation to soil decreases over time [9]. Mo Bingyu et al. used Maxwell’s system of equations to derive the pipeline-induced electromotive force originating from the AC transmission line; established the pipeline equivalent circuit; analyzed the electromagnetic coupling to the neighboring underground pipelines during the steady-state operation of the AC transmission line; and, combined with a practical case, proposed a measurement method that can be corrected to the pipeline–ground potential distribution at the same moment [10]. Based on the influence of the pipeline coating resistance on the pipeline characteristic impedance, M. Rabbani concluded that the smaller the impedance, the smaller the induced voltage on the pipeline; conversely, the greater the impedance of the coating, the greater the voltage difference between the pipeline and the coating [11]. G.T. Quickel, by characterizing accidentally perforated pipes, concluded that the cause of the pipe perforation is a high-voltage arcing discharge from the pipe wall to the ground, which is mainly due to lightning strikes or the occurrence of ground faults in the overhead lines, and proposed three methods for protecting the insulation joint of the pipeline [12].
A significant amount of research has been conducted both domestically and internationally on protecting natural gas pipelines from electromagnetic interference caused by overhead lines. This research primarily focuses on two aspects: steady-state interference protection and lightning overvoltage protection. Currently, solid-state decouplers are commonly used for steady-state interference protection, while limited research has been performed on lightning overvoltage protection for pipelines. This paper aims to investigate the impact of grounded, scattered lightning currents on nearby natural gas pipelines and assess the effectiveness of solid-state decouplers in reducing the voltage endured by the pipeline’s insulating layer. The simulation results are then used to determine the optimal length for laying bare copper wire, as presented in the provided equation.

2. Simulation Model and Parameters

2.1. Line Tower Model and Parameters

In order to study the impact of lightning strikes more accurately on overhead conductors regarding the overvoltage of natural gas pipelines in the vicinity, it is essential to calculate the distribution of lightning current between overhead lines and towers after a lightning strike. For this study, a 500 kV overhead line is selected and the frequency-dependent JMarti line model in ATP-EMTP is utilized to determine the line parameters [13,14]. The relevant parameters for the overhead conductor and lightning line can be found in Table 1. The line insulators consist of 28 glass insulators of type U210BP/170, and voltage-controlled switches are employed to model these insulators in ATP-EMTP [15,16].
The tower mode chosen for this study is a more realistic equidistributed, multi-wave impedance tower model, and the tower is taken to be a ZB4 wine-glass-type linear tower. The structure of the power pole tower is illustrated in Figure 1.

2.2. Modeling and Parameterization of Tower Grounding Grids and Natural Gas Pipelines

In the actual project of power overhead line tower grounding grid structure, various types are used. The most commonly used type is the box with a ray type grounding grid. For this study, a typical grounding grid is selected, with a diameter of Φ = 16 mm and a buried depth of h1 = 0.8 m, using galvanized round steel as the material. As shown in Figure 2, the length of grounding grid box is 15 m and the length of the extended ray is 20 m. The angle between the extension ray and the box extension line is α = 45°. When calculating the distribution of lightning current, it is sufficient to model it as a grounding resistance.
The selection of the natural gas pipeline is based on a standard, exemplified by the cross-section of the pipeline shown in Figure 3. The pipe insulation layer material used is 3PE, with the specific parameters provided in Table 2.
To investigate the effects of overvoltage on a natural gas pipeline at a cross-crossing after a lightning strike on the conductor, causing flashover of the line insulator and resulting in ground scattering current, a simplified model of the T0, TR1 tower grounding grid and the natural gas pipeline (as depicted in Figure 4b) is established using COMSOL Multiphysics 5.6 simulation software. The length of the natural gas pipeline (lp) is 400 m, and both sides of the pipeline and the T0, TR1 tower grounding grid have a pendant angle of (β). Both sides of the pipeline are treated with grounding, and the burial depth (h2) is 2 m.

3. Calculation of Lightning Current Distribution Characteristics

3.1. The Influence of Lightning Peak Current

ATP-EMTP is utilized to establish the transmission tower line model. Figure 4a depicts its relative position. The lightning current is modeled using a double exponential model with a waveform parameter of 2.6/50 μs. The lightning stroke point occurs at the A-phase conductor in the center of the T0 and TR1 spans. With a soil resistivity of ρ = 1000 Ω m, the simulation results indicate that the lightning withstand level of shielding failure for a 500 kV overhead line is 24.18 kA. It is observed that when the amplitude of the lightning current is below 24.18 kA, the majority of the lightning current flows through the overhead conductor. Keeping other simulation parameters constant, the lightning peak current (I0) is varied to 5 kA, 30 kA, 35 kA, 40 kA, 45 kA, and 50 kA to assess its impact on the lightning current distribution after line insulator flashover. Figure 5 illustrates the lightning current distribution at the T0 and TR1 towers.
According to the results shown in Figure 5, it is observed that when the amplitude of the lightning current exceeds 24.18 kA, the line insulators of T0 and TR1 towers experience flashover. This occurs because the lightning strike point is located at the center of the overhead wire span between T0 and TR1 towers. As a result, the lightning current is dispersed into the ground through the T0 and TR1 tower grounding grid. Moreover, as the amplitude of the lightning current increases, the current flowing through the T0 and TR1 tower grounding grid also gradually increases. Consequently, the overvoltage issue of the T0 and TR1 tower grounding current affecting the adjacent pipeline needs to be taken into consideration.

3.2. The Influence of Soil Resistivity

The distribution of lightning current after the flashover of line insulators is studied by varying the soil resistivity ρ. The lightning peak current I0 is fixed at 50 kA. The different values of soil resistivity considered are 200 Ω m, 500 Ω m, 800 Ω m, 1000 Ω m, 1200 Ω m, and 1500 Ω m. Figure 6 illustrates the lightning current distribution for T0 and TR1 towers.
The results indicate that as soil resistivity increases, the mine current entering the tower through T0 and TR1 decreases. Additionally, the waveform and amplitude of the mine current entering the tower through T0 and TR1 remain the same. This phenomenon occurs because, following a line insulator flashover, the increase in soil resistivity leads to an increase in the grounding resistance of the tower grounding grid. This increase in resistance partially obstructs the flow of lightning current into the ground through the tower grounding grid. Simultaneously, the increase in soil resistivity also hampers the flow of lightning current through the tower grounding grid into the surrounding soil area.

4. Analysis of Pipeline Overvoltage under the Action of Multi-Tower Flow

When the power overhead conductor is struck by lightning, the lightning current can cause the line insulator to flashover. In this situation, the lightning current disperses along the surface of the flashover insulator through the tower grounding grid. Due to the presence of resistive coupling, the potential of the soil area near the grounding grid and the steel layer of the adjacent pipeline will increase. As a result, there will be a potential difference between the soil area near the pipeline and the steel layer of the pipeline, leading to a potential difference in the insulating layer. In this paper, based on the ATP-EMTP simulation results, the mine current of T0 and TR1 tower grounding grid is introduced into the COMSOL model.
When the lightning impulse current disperses through the tower grounding grid, it will cause a nearby rise in ground potential. The equation for calculating the potential Vt is shown in Equation (1):
V t = k × i t × R
where k is the impact coefficient, it is the current into the mine through the tower, and R is the tower grounding resistance.
Without considering the tower foundation, the grounding resistance R of the power tower can be calculated according to term Equation (2) when the grounding device is a box extension shape.
R = ρ 2 π L ln L 2 h d + A t
In term Equation (2), L = 4(lga + lg1), where lga and lg1 are the length of the frame and the epitaxial ray, respectively; h is the buried depth of grounding device; d is the diameter of the grounding body; and At = 1.76.
The ground potential Vt near the grounding grid will increase due to the dispersion of lightning current. However, as the distance from the grounding grid increases, the ground potential will gradually decrease. The equation for calculating the ground potential rise caused by resistive coupling at a point outside the insulating layer of a gas pipeline is represented by Equation (3).
V x = V t r e r e + x
In Equation (3), x is the distance from the point to the tower grounding device and re is the radius of the equivalent hemispherical grounding body of the tower. Its re calculation term equation is shown in term Equation (4).
r e = L ln L 2 h d + A t
The theoretical term equation suggests that the lightning overvoltage of gas pipelines is influenced by factors such as the spacing between pipelines, the amplitude of lightning current, and soil parameters. Therefore, a simulation analysis will be conducted to examine these influencing factors.

4.1. The Influence of Lightning Peak Current

In order to investigate the impact of lightning peak current on lightning overvoltage of natural gas pipelines at the cross-crossing under the influence of lightning stroke conductor, certain parameters were fixed: soil resistivity (ρ) of 1000 Ω·m, spacing between pipelines (dgp1) of 40 m, and cross angle (β) of 0°. Lightning peak currents of 25 kA, 30 kA, 35 kA, 40 kA, 45 kA, and 50 kA were sequentially selected. The lightning current waveforms of T0 and TR1 tower grounding grids under different lightning peak currents were imported into COMSOL Multiphysics. Figure 5 illustrates these waveforms. The lightning overvoltage amplitude of natural gas pipelines at the cross-crossing of overhead lines is depicted in Figure 7. Figure 8 presents the potential height distribution of the tower grounding grid and crossing natural gas pipeline under different lightning peak currents.
Based on the results shown in Figure 7a, it can be observed that as the lightning peak current increases, both the induced voltage amplitude of the metal layer and the induced voltage amplitude of the insulation layer of the natural gas pipeline also increase. Specifically, when the lightning peak current is raised from 25 kA to 50 kA, the induced voltage amplitude of the metal layer rises from 22.61 kV to 42.25 kV, while the induced voltage amplitude of the insulation layer increases from 25.55 kV to 47.56 kV. Similarly, Figure 7b illustrates a similar trend in the voltage amplitude of the pipeline insulation layer with respect to the lightning peak current. In this case, as the lightning peak current increases from 25 kA to 50 kA, the voltage amplitude of the pipeline insulation layer increases from 3.46 kV to 7.23 kV, representing a significant increase of 108.96%.
The reason for studying the variation law mentioned above is that as the amplitude of the lightning current increases, the current flowing into the earth through the tower also increases. This, in turn, leads to an increase in the potential of the tower grounding grid and the surrounding soil, under the same soil resistivity. Consequently, the resistive coupling effect of the gas pipeline is aggravated. Equation (1) demonstrates that this rise in potential will cause the nearby ground potential to increase, resulting in a larger potential difference between the outer insulation layer and the metal layer of the pipeline. Thus, it is evident that the amplitude of the lightning current directly influences the voltage amplitude of the pipeline insulation layer.
Based on the results shown in Figure 8, it is evident that the potential height of the T0, TR1 tower grounding grid and the surrounding soil increases significantly with the increase in lightning peak current. This can be attributed to the increased flow of scattered lightning through the tower grounding grid. When the soil resistivity remains constant, the potential of both the tower grounding grid and the surrounding soil increases, thereby exacerbating the resistive coupling effect on the natural gas pipeline. At the same time, it can be obviously seen that the potential height at the center of the natural gas pipeline is significantly higher than the potential height at both ends of the natural gas pipeline.

4.2. The Influence of Soil Resistivity

In order to investigate the impact of soil resistivity on the overvoltage of natural gas pipelines at the cross-crossing during lightning strikes, several parameters were set as follows: the lightning peak current (I0) was fixed at 50 kA, the distance between the “tube-line” (dgp1) was set to 40 m, and the cross angle of the “tube-line” (β) was 0°. The soil resistivity (ρ) was varied, with values of 200 Ω·m, 500 Ω·m, 800 Ω·m, 1000 Ω·m, 1200 Ω·m, and 1500 Ω·m being selected sequentially. The current waveform of the lightning current passing through the T0 and TR1 tower grounding grid under different soil resistivity conditions is shown in Figure 6. The resulting lightning overvoltage amplitude of the natural gas pipeline at the cross-crossing is presented in Figure 9. Additionally, Figure 10 illustrates the potential distribution of the tower grounding grid and the natural gas pipeline at the cross-crossing for different soil resistivity values.
According to Figure 9a, it can be observed that the induced voltage of the metal layer and insulation layer of the natural gas pipeline increases as the soil resistivity increases. When the soil resistivity increases from 200 Ω·m to 1500 Ω·m, the induced electric potential amplitude of the natural gas pipeline and the induced voltage amplitude of the insulation layer increase from 9.68 kV and 13.07 kV to 59.63 kV and 64.80 kV, respectively. This represents an increase of 516.01% and 395.79% for the induced electric potential amplitude and induced voltage amplitude, respectively. The results in Figure 9b demonstrate that as soil resistivity increases, the pressure resistance of the pipeline insulation layer gradually increases. However, after reaching a certain point, the increase in pressure resistance becomes less pronounced. For instance, when the soil resistivity increases from 200 Ω·m to 1000 Ω·m, the withstand voltage of the insulating layer increases from 4.25 kV to 7.23 kV, representing a 70.12% increase. On the other hand, when the soil resistivity increases from 1000 Ω·m to 1500 Ω·m, the withstand voltage of the insulating layer only increases from 7.23 kV to 7.35 kV, resulting in a mere 1.66% increase.
The reason for studying the variation law mentioned above is that an increase in soil resistivity can impede the spreading of the tower grounding grid to the surrounding soil. As a result, the mine current is more likely to spread towards the far end of the extension ray, leading to an increase in the effective spreading area of the tower grounding grid and the soil potential near the grounding grid. This, in turn, exacerbates the impact of the tower grounding grid on the gas pipeline. When the soil resistivity prevents the tower grounding grid from dispersing into the surrounding soil, the induced voltage and withstand voltage of the metal layer and insulating layer of the gas pipeline increase. Conversely, when the mine current decreases, the induced voltage and withstand voltage of the metal layer and insulating layer of the gas pipeline decrease. Therefore, the interaction of these two factors causes the induced voltage and withstand voltage of the metal layer and insulating layer of the gas pipeline to exhibit an upward trend.
Figure 10 illustrates that an increase in soil resistivity obstructs the spread of the tower grounding grid box into the surrounding soil. Consequently, the mine current tends to spread towards the far end of the extension ray such that the effective spreading area of the tower grounding grid and the soil potential near the grounding grid will increase, which will lead to the aggravation of the influence of the tower grounding grid on the natural gas pipeline.

4.3. The Influence of “Tube-Line” Spacing

The study investigates the impact of different “tube” spacings (dgp1) on the overvoltage of a natural gas pipeline when subjected to lightning strikes. The fixed soil resistivity (ρ) is 1000 Ω·m and the lightning peak current (I0) is 50 kA. The “tube” cross angle (β) is 0°. The “tube” spacing options considered are 40 m, 50 m, 60 m, 70 m, 80 m, and 90 m. Figure 11 illustrates the amplitude of lightning-induced overvoltage on the natural gas pipeline at the intersection. Figure 12 shows the distribution of potential height for the tower grounding grid and the intersecting natural gas pipeline under different “pipeline” spacings.
Based on the findings of Figure 11a, it was observed that as the spacing between pipelines increases, the induced electric potential of both the metal layer and the insulation layer of the natural gas pipeline decreases. Specifically, when the pipeline spacing increases from 40 m to 90 m, the induced voltage of the metal layer decreases from 42.25 kV to 30.96 kV and the induced voltage of the insulating layer decreases from 47.56 kV to 32.37 kV; these reductions correspond to a decrease of 26.72% and 31.94%, respectively. Figure 11b illustrates that the withstand electric potential of the pipeline insulation layer gradually decreases with the increase in pipeline spacing. However, as the spacing continues to increase, the voltage drop trend of the insulation layer becomes more gradual. For instance, when the spacing increases from 40 m to 70 m, the withstand voltage of the insulating layer decreases from 7.23 kV to 2.53 kV, a decrease of 65.01%. When the spacing further increases from 70 m to 90 m, the withstand voltage of the insulating layer decreases from 2.53 kV to 1.91 kV, representing a decrease of only 24.51%.
The reason for studying the variation law mentioned above is that the pipeline’s center is closer to the tower grounding grid and the effective dispersion area of the tower grounding grid. This proximity causes a more significant impact of the tower grounding grid dispersion on the center of the pipeline. When the spacing between the pipeline and the tower is small, the center of the pipeline is more affected by the dispersion of the tower grounding grid at both ends. As a result, the induced voltage curve along the insulation layer becomes more prominent. However, when the spacing between the pipeline and the tower increases within a certain range, the difference in the impact of the tower grounding grid dispersion on the center of the pipeline and the two ends reduces. Consequently, the overall curve of the induced voltage along the insulation layer becomes relatively flat.
Figure 12 demonstrates that altering the “tube-line” spacing dgp1 does not impact the potential height distribution of the grounding grid and the surrounding soil area. In order to ensure that the lightning current components of the scattered current through the T0 and TR1 tower grounding grids are approximately equal, the vertical distance between the natural gas pipeline and the T0 and TR1 tower grounding grids can be adjusted by changing the “tube-line” spacing dgp1. This adjustment will affect the extent to which the scattered current from the T0 and TR1 grounding grids impacts the natural gas pipeline. Consequently, a minimum value of pipeline overvoltage can be achieved in this scenario.

5. Pipeline Overvoltage Protection Based on Solid-State Decoupler

The solid-state decoupler is a product designed to protect against AC/DC interference. It combines embedded current drainage, surge protection, and AC decoupling, and has a high capacity for breaking impact currents. Internally, it typically consists of capacitors, thyristors (or diodes), and surge protection devices connected in parallel. Figure 13 illustrates the appearance and internal circuitry of the solid-state decoupler, while Table 3 provides its technical parameters.
This section aims to decrease the electric potential of the pipeline insulation layer by utilizing the specific wiring method of the solid-state decoupler. It also seeks to validate the solid-state decoupler’s ability to reduce the voltage of the pipeline insulation layer through modeling and simulation. Figure 14a illustrates the simulation diagram. In this setup, a bare copper wire is placed parallel to the natural gas pipeline, with a distance of 1m between them. The length of the bare copper wire is determined based on the current dispersion characteristics of the tower grounding grid. In order to save cost and avoid excessive design, the laying length of bare copper wire pl1 is defined as shown in Figure 14b. The calculation term equation of laying length of bare copper wire is shown in term Equation (1). In this section, pl1 = 0 m indicates that there are no protective measures for natural gas pipelines.
p l 1 = 2 × d g p 1 0.5 × l g a + l g a
In term Equation (5), pl1 is the length of bare copper wire laying, dgp1 is the “tube-line” spacing, and lga is the length of the epitaxial ray.
To evaluate the effectiveness of the method, a simulation model is created using COMSOL Multiphysics simulation software, as illustrated in Figure 14a. The aim is to analyze the impact of varying laying lengths of bare copper wire (pl1) on the resistive coupling overvoltage of natural gas pipelines at the cross-crossing. The simulation parameters used are as follows: lightning peak current (I0) = 50 kA, soil resistivity (ρ) = 1000 Ω·m, spacing between the tube and the line (dgp1) = 40 m, length of the epitaxial ray (lg1 = lg2 = 20 m), commutation angle (α) = 45°, and cross angle between the tube and the line (β) = 0°. The laying lengths of bare copper wire considered are pl1 = 0 m, 30 m, 40 m, 50 m, 80 m, and 200 m. Figure 15 depicts the overvoltage amplitude of natural gas pipelines under different lengths of bare copper wire, as determined through simulation calculations.
According to the results shown in Figure 15, as the length of the bare copper wire increases, the induced voltage of the metal layer of the natural gas pipeline also increases gradually, while the voltage of the pipeline insulation layer decreases gradually. This phenomenon occurs because the solid-state decoupler causes an instantaneous short-circuit between the bare copper wire and the pipeline when subjected to lightning impulse current. The soil potential in the area where the bare copper wire is located is much higher than the induced voltage of the pipeline metal layer, leading to an increase in the induced voltage of the pipeline metal layer during the short-circuiting process. On the other hand, the induced electric potential of the pipeline insulation layer remains relatively stable and fluctuates within a certain range, which can be disregarded. The withstand electric potential of the insulation layer depends on the difference between the induced voltage of the pipeline insulation layer and the metal layer. Therefore, when the induced voltage of the insulation layer changes slightly and the induced electric potential of the metal layer continues to increase, the withstand voltage of the insulation layer gradually decreases.
When the bare copper wire length (pl1) is 0 m, the induced voltage amplitude of the metal layer of the natural gas pipeline is 42.25 kV and the voltage amplitude of the insulating layer is 7.23 kV. When the bare copper wire length is 80 m, the induced voltage amplitude of the metal layer of the natural gas pipeline is 43.43 kV and the voltage amplitude of the insulating layer is 5.45 kV. Similarly, when the bare copper wire length is 200 m, the induced voltage amplitude of the metal layer of the natural gas pipeline is 43.59 kV and the voltage amplitude of the insulating layer is 5.39 kV. It can be observed that increasing the length of the bare copper wire from 0 m to 80 m results in a decrease in the withstand voltage of the pipeline insulation layer from 7.23 kV to 5.45 kV, representing a decrease of 24.62%. However, when the length increases from 80 m to 200 m, the withstand voltage of the pipeline insulation layer decreases only slightly from 5.45 kV to 5.39 kV, representing a decrease of 1.10%.
To better understand the impact of the external bare copper wire of the solid-state decoupling device on the overvoltage of the natural gas pipeline, in close proximity, we focused our research on the central section of the tower grounding grid. This section, which is perpendicular to the natural gas pipeline, was chosen as the research path. Figure 16 illustrates this selection, with a research path length (lr) of 400 m and depth (h3) = 2 m. By conducting simulation calculations, we obtained the soil potential change curve for the path under different lengths of the bare copper wire (pl1), as depicted in Figure 17.
Figure 17 demonstrates that the implementation of solid-state decoupling primarily alters the soil potential surrounding the bare copper wire and the pipeline location. However, it has minimal impact on the soil potential of the tower grounding grid and other regions. As the length of the bare copper wire increases, the soil potential around it gradually decreases. Conversely, the soil potential at the pipeline position exhibits a gradual increase.
The subsequent increase of 120 m of bare copper wire has minimal impact on reducing the voltage of the pipeline insulation layer. Therefore, increasing the length of the bare copper wire does not improve the overvoltage protection effect of the pipeline. In practical engineering, it is more economical and convenient to determine the length of the bare copper wire according to Figure 14b. The detailed calculation term equation is shown in term Equation (5).

6. Conclusions

The current research on overvoltage of adjacent pipelines caused by lightning strikes on overhead lines only focuses on the situation of lightning strikes on towers. When a lightning strike occurs on the conductor and causes the insulator to flashover, there is grounding scattered current on both sides of the lightning strike point. This scattered lightning current can also generate pipeline overvoltage on the natural gas pipeline at the intersection. Additionally, to prevent excessive design of pipeline overvoltage protection measures, this paper presents the optimal length term equation of bare copper wire for a solid-state decoupling device. The conclusions of this study are as follows:
(1)
As the lightning peak current increases, there is an upward trend observed in the induced voltage of the metal layer, the induced voltage of the insulation layer, and the withstand voltage of the insulation layer in natural gas pipelines. Specifically, when the lightning peak current increases from 25 kA to 50 kA, the withstand electric potential of the insulation layer increases by 108.96%.
(2)
The induced voltage of the metal layer, the induced voltage of the insulating layer, and the withstand electric potential of the insulating layer of the natural gas pipeline exhibit an upward trend with increasing soil resistivity. As the soil resistivity increases from 200 Ω m to 1500 Ω m, the electric potential of the insulating layer increases by 72.94%.
(3)
As the spacing between the “pipeline” increases, the induced voltage of the metal layer, the induced electric potential of the insulating layer, and the withstand electric potential of the insulating layer of the natural gas pipeline gradually decrease.
(4)
In situations where there is scattered lightning current in the ground, the voltage of the pipeline’s insulation layer can be reduced by using a solid-state decoupling device, a bare copper wire, and a specific connection mode. When the length of the bare copper wire is increased from 0 m to 80 m, the voltage amplitude of the pipeline’s insulation layer decreases by 1.78 kV.

Author Contributions

Conceptualization, W.L. and Z.J.; methodology, Y.H. and H.T.; software, H.T.; validation, H.T. and W.L.; formal analysis, Y.H.; investigation, X.S. and Y.H.; resources, X.S.; data curation, Y.H.; writing—original draft preparation, H.T.; writing—review and editing, Y.H.; visualization and supervision, J.X. and W.S.; project administration, Y.W.; funding acquisition, Z.J. All authors have read and agreed to the published version of the manuscript.

Funding

This project is supported by the State Grid Hubei Electric Power Co., Ltd. Science and technology project. grant number (B315F0222836).

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The data presented in this study are available in article.

Acknowledgments

The authors would like to express sincere thanks to the Science and Technology Research Institute, National Oil and Natural Gas Pipeline Network Group Company Limited, and CNPC Engineering Materials Research Institute Co., Ltd., State Key Laboratory of Service Behavior and Structural Safety of Petroleum Pipe and Equipment Materials.

Conflicts of Interest

The authors declare that they have no known competing financial interests or personal relationships that could have appeared to influence the work reported in this paper. Wei Liu, Zhipeng Jiang, Xiaole Su, Jie Xiong, Wei Su and Yi Wang are employee of State Grid Hubei Power Supply Limited Company Ezhou Power Supply Company, who provided funding and teachnical support for the work. The funder had no role in the design of the study; in the collection, analysis, or interpretation of data, in the writing of the manuscript, or in the decision to publish the results.

References

  1. Huang, W.; Zhou, S.; Sun, C.; Mo, B.; Han, M.; Kang, J.; Luo, Y.; Wu, S.; Jing, H. Research on Electromagnetic Interference of AC Transmission Line to Adjacent Buried Pipeline Under Transient States. Proc. CSEE 2021, 41, 275–285. [Google Scholar]
  2. Wang, C.; Liang, X.; Freschi, F. Investigation of Factors Affecting Induced Voltages on Underground Pipelines Due to Inductive Coupling with Nearby Transmission Lines. IEEE Trans. Ind. Appl. 2020, 56, 1266–1274. [Google Scholar] [CrossRef]
  3. Zhang, B.; Cao, F.; Zeng, R.; He, J.; Meng, X.; Liao, Y.; Li, R. DC Current Distribution in Both AC Power Grids and Pipelines Near HVDC Grounding Electrode Considering Their Interaction. IEEE Trans. Power Deliv. 2019, 34, 2240–2247. [Google Scholar] [CrossRef]
  4. Yong, J.; Zhu, Z.; Wang, X. Investigating the Overhead Line Caused Harmonic Induction on Pipeline: Evaluation Method and Impact Factors. Proc. CSEE 2021, 41, 3130–3138. [Google Scholar]
  5. Wan, B.; Xie, H.; Zhang, X.; Wu, X. Fan L. Influence of Lightning Strike to UHV AC Double-circuit Tower on Oil or Gas Pipelines. High Volt. Eng. 2009, 35, 1812–1817. [Google Scholar]
  6. Czarnywojtek, P.; Machczynski, W. Wave propagation effects induced in transmission pipelines by EMI from power lines. Eletr. Eng. 2018, 100, 1739–1747. [Google Scholar] [CrossRef]
  7. Wu, X.; Zhang, H.; Karady, G. Transient analysis of inductive induced voltage between power line and nearby pipeline. Int. J. Electr. Power Energy Syst. 2017, 84, 47–54. [Google Scholar] [CrossRef]
  8. Popoli, A.; Cristofolini, A.; Sandrolini, L. A numerical model for the calculation of electromagnetic interference from power lines on nonparallel underground pipelines. Math. Comput. Simulatio 2021, 183, 221–233. [Google Scholar] [CrossRef]
  9. Lucca, G. Electromagnetic interference from power lines on pipelines: Influence of pipe insulating coating degradation. Intenational Ransactions Electr. Energy Syst. 2016, 26, 2699–2712. [Google Scholar] [CrossRef]
  10. Mo, B.; Huang, W.; Zhou, S.; Wei, J.; Luo, Y.; Kang, J.; Sun, T.; Guo, G. Case Studies of the Electromagnetic Influence of AC Transmission Lines on the Adjacent Buried Oil/gas Pipeline Under Steady State. Proc. CSEE 2020, 40, 6035–6044. [Google Scholar]
  11. Rabbani, M.; Oo, A. Electromagnetic effect of lightning return stroke to buried energy pipelines. Energy Procedia 2019, 160, 467–474. [Google Scholar] [CrossRef]
  12. Quickel, G.T.; Beavers, J.A. Pipeline Failure Results from Lightning Strike: Act of Mother Nature? J. Fail. Anal. Prev. 2011, 11, 227–232. [Google Scholar] [CrossRef]
  13. An, N.; Peng, Y.; Ai, X.; Huang, G.; Shi, Y.; Zhang, M. Electromagnetic Effects on Underground Oil/Gas Pipeline of the Lightning Strike on EHV AC Transmission Line. High Volt. Eng. 2012, 38, 2881–2888. [Google Scholar]
  14. Huangfu, Y.P.; Wang, S.H.; Tao, X. Transient Lightning Impulse Performance Analysis for Composite Transmission Line Tower. IEEE Trans. Electromagn. Compat. 2015, 57, 1103–1111. [Google Scholar] [CrossRef]
  15. Ametani, A.; Triruttanapiruk, N.; Yamamoto, K.; Baba, Y.; Rachidi, F. Impedance and Admittance Formulas for a Multistair Model of Transmission Towers. IEEE Trans. Electromagn. Compat. 2020, 62, 2491–2502. [Google Scholar] [CrossRef]
  16. Datsios, Z.G.; Mikropoulos, P.N.; Tsovilis, T.E. Effects of Lightning Channel Equivalent Impedance on Lightning Performance of Overhead Transmission Lines. IEEE Trans. Electromagn. Compat. 2019, 61, 623–630. [Google Scholar] [CrossRef]
Figure 1. The tower model and parameters used in ATP-EMTP software are calculated. (a) Tower model. (b) Electric power tower structure.
Figure 1. The tower model and parameters used in ATP-EMTP software are calculated. (a) Tower model. (b) Electric power tower structure.
Applsci 13 12529 g001
Figure 2. Tower grounding grid structure. (a) Lightning current dispersion path. (b) Tower grounding grid structure.
Figure 2. Tower grounding grid structure. (a) Lightning current dispersion path. (b) Tower grounding grid structure.
Applsci 13 12529 g002
Figure 3. Natural gas pipeline profile and construction site. (a) Natural gas pipeline section diagram. (b) Natural gas pipeline construction site.
Figure 3. Natural gas pipeline profile and construction site. (a) Natural gas pipeline section diagram. (b) Natural gas pipeline construction site.
Applsci 13 12529 g003
Figure 4. Simulation diagram of tower grounding grid and pipeline. (a) Schematic diagram of lightning conductor. (b) Top view of tower grounding grid and natural gas pipeline.
Figure 4. Simulation diagram of tower grounding grid and pipeline. (a) Schematic diagram of lightning conductor. (b) Top view of tower grounding grid and natural gas pipeline.
Applsci 13 12529 g004
Figure 5. The influence of lightning peak current on the lightning current distribution of T0 and TR1 towers.
Figure 5. The influence of lightning peak current on the lightning current distribution of T0 and TR1 towers.
Applsci 13 12529 g005
Figure 6. The influence of soil resistivity on lightning current distribution of T0 and TR1 towers.
Figure 6. The influence of soil resistivity on lightning current distribution of T0 and TR1 towers.
Applsci 13 12529 g006
Figure 7. The influence of lightning peak current on the overvoltage of natural gas pipelines at cross-crossings. (a) Induced voltage amplitude of metal layer and insulation layer of pipeline. (b) Voltage amplitude of pipeline insulation layer.
Figure 7. The influence of lightning peak current on the overvoltage of natural gas pipelines at cross-crossings. (a) Induced voltage amplitude of metal layer and insulation layer of pipeline. (b) Voltage amplitude of pipeline insulation layer.
Applsci 13 12529 g007
Figure 8. The potential height distribution of tower grounding grid and natural gas pipeline at cross-crossing under different lightning amplitudes. (a) I0 = 25 kA. (b) I0 = 30 kA. (c) I0 = 40 kA. (d) I0 = 50 kA.
Figure 8. The potential height distribution of tower grounding grid and natural gas pipeline at cross-crossing under different lightning amplitudes. (a) I0 = 25 kA. (b) I0 = 30 kA. (c) I0 = 40 kA. (d) I0 = 50 kA.
Applsci 13 12529 g008
Figure 9. The influence of soil resistivity on overvoltage of natural gas pipeline at cross-crossing. (a) Induced voltage amplitude of metal layer and insulation layer of pipeline. (b) Voltage amplitude of pipeline insulation layer.
Figure 9. The influence of soil resistivity on overvoltage of natural gas pipeline at cross-crossing. (a) Induced voltage amplitude of metal layer and insulation layer of pipeline. (b) Voltage amplitude of pipeline insulation layer.
Applsci 13 12529 g009
Figure 10. Potential distribution of tower grounding grid and natural gas pipeline at cross-crossing under different soil resistivity.
Figure 10. Potential distribution of tower grounding grid and natural gas pipeline at cross-crossing under different soil resistivity.
Applsci 13 12529 g010
Figure 11. Influence of “pipeline” spacing on overvoltage of natural gas pipeline at cross-crossing. (a) Induced voltage amplitude of metal layer and insulation layer of pipeline. (b) Voltage amplitude of pipeline insulation layer.
Figure 11. Influence of “pipeline” spacing on overvoltage of natural gas pipeline at cross-crossing. (a) Induced voltage amplitude of metal layer and insulation layer of pipeline. (b) Voltage amplitude of pipeline insulation layer.
Applsci 13 12529 g011
Figure 12. The potential height distribution of tower grounding grid and natural gas pipeline at cross-crossing under different “pipeline” spacings. (a) dgp1 = 40 m. (b) dgp1 = 50 m. (c) dgp1 = 70 m. (d) dgp1 = 80 m.
Figure 12. The potential height distribution of tower grounding grid and natural gas pipeline at cross-crossing under different “pipeline” spacings. (a) dgp1 = 40 m. (b) dgp1 = 50 m. (c) dgp1 = 70 m. (d) dgp1 = 80 m.
Applsci 13 12529 g012
Figure 13. Solid-state decoupler. (a) Physical images. (b) Circuit diagram in thyristor mode.
Figure 13. Solid-state decoupler. (a) Physical images. (b) Circuit diagram in thyristor mode.
Applsci 13 12529 g013
Figure 14. Solid-state decoupler wiring diagram. (a) Simulation diagram. (b) Bare copper wire length diagram.
Figure 14. Solid-state decoupler wiring diagram. (a) Simulation diagram. (b) Bare copper wire length diagram.
Applsci 13 12529 g014
Figure 15. Influence of bare copper wire length on overvoltage of natural gas pipeline. (a) Induced voltage amplitude of metal layer and insulation layer of pipeline. (b) Voltage amplitude of pipeline insulation layer.
Figure 15. Influence of bare copper wire length on overvoltage of natural gas pipeline. (a) Induced voltage amplitude of metal layer and insulation layer of pipeline. (b) Voltage amplitude of pipeline insulation layer.
Applsci 13 12529 g015
Figure 16. Research path top view.
Figure 16. Research path top view.
Applsci 13 12529 g016
Figure 17. The influence curve of bare copper wire length on soil potential in the research path.
Figure 17. The influence curve of bare copper wire length on soil potential in the research path.
Applsci 13 12529 g017
Table 1. Parameters of conductors and lightning conductors.
Table 1. Parameters of conductors and lightning conductors.
Model NumbersOutside Diameter/mmDC Resistance/(Ω·km−1)Fission Number
LGJ-400/3526.820.073894
JLB20A-8011.41.07880
Table 2. Pipeline parameters.
Table 2. Pipeline parameters.
Parameter NameNumerical Value
Outside diameter/mm429
Steel thickness/mm9.5
Insulation thickness/mm3
Table 3. Related technical parameters of solid-state decoupler.
Table 3. Related technical parameters of solid-state decoupler.
DC Leakage/mA≤1mAIsolation Voltage/V+2/−2 or +1/−3, etc.Impact Flow Capacity/(8/20 μs)/kA100
Steady-state alternating current/A45Working temperature/°C−45~60Protection level≥IP65
Fault current (AC-rms/power frequency/30 cycle wave)/A≥3500
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Liu, W.; Hu, Y.; Tian, H.; Jiang, Z.; Su, X.; Xiong, J.; Su, W.; Wang, Y. Research on Lightning Overvoltage Protection of Line-Adjacent Pipelines Based on Solid-State Decoupling. Appl. Sci. 2023, 13, 12529. https://doi.org/10.3390/app132212529

AMA Style

Liu W, Hu Y, Tian H, Jiang Z, Su X, Xiong J, Su W, Wang Y. Research on Lightning Overvoltage Protection of Line-Adjacent Pipelines Based on Solid-State Decoupling. Applied Sciences. 2023; 13(22):12529. https://doi.org/10.3390/app132212529

Chicago/Turabian Style

Liu, Wei, Yuanchao Hu, Haipeng Tian, Zhipeng Jiang, Xiaole Su, Jie Xiong, Wei Su, and Yi Wang. 2023. "Research on Lightning Overvoltage Protection of Line-Adjacent Pipelines Based on Solid-State Decoupling" Applied Sciences 13, no. 22: 12529. https://doi.org/10.3390/app132212529

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop