1. Introduction
Permafrost regions support major transportation corridors in high-latitude and high-altitude cold regions. Because ice–water phase composition, pore-water migration and soil stiffness change rapidly near the freezing point, permafrost is sensitive to climate warming and engineering disturbance [
1,
2,
3,
4]. These changes can cause active-layer deepening, thaw settlement, frost heave, pavement cracking and slope deformation [
2,
5,
6]. Wide asphalt embankments are especially vulnerable because dark pavements absorb solar radiation and the embankment body stores heat across a large cross-section. Slope-aspect differences further promote uneven heat input, making long-term frozen-ground protection a central construction problem in permafrost regions [
7,
8,
9].
To limit heat transfer into underlying permafrost, engineering has adopted several cooling measures. Crushed-rock revetments and berms enhance cold-season convective cooling, ventilation ducts promote air circulation, insulation layers reduce downward heat flux and sunshades modify surface energy balance [
10,
11,
12,
13,
14,
15]. Two-phase closed thermosyphons (TPCTs) have been widely used as active heat-transfer devices that transfer heat from the ground to the atmosphere [
16,
17,
18,
19]. As shown in
Figure 1, the buried evaporator absorbs ground heat, vapor transports heat upward inside TPCTs, the condenser releases heat to ambient air, and condensate returns to the evaporator by gravity [
16,
19]. In practice, these measures are combined because each controls a different part of the embankment-ground energy pathway [
15,
20,
21]. In wide asphalt embankments, however, residual weak zones may remain near shoulders or slope toes because heat accumulation, water migration and slope-aspect effects interact [
8,
9,
22].
TPCT embankments have been studied as field-scale measures for slowing ground warming and reducing thaw-related deformation. Long-term monitoring shows that TPCTs operate mainly during the cold season, form low-temperature zones around evaporators and raise or maintain the permafrost table [
17,
18,
19]. Part of this cooling can persist through the warm season and accumulate over multiple years in wide asphalt embankments. Embankment response, however, is not governed by vertical heat extraction alone. Pavement heat storage, slope aspect and embankment geometry also redistribute heat laterally, creating uneven cooling across the road section [
8,
9,
23,
24]. Field observations and simulations link this uneven thermal field to uplifted 0 °C isotherms, convex permafrost tables and lateral temperature gradients [
22,
25]. These features can induce differential frost heave or thaw settlement [
5,
8,
22]. In inclined TPCT embankments, they may concentrate tensile stress on the pavement and promote longitudinal cracking [
22,
26]. Thus, TPCT system design must consider not only ground cooling but also whether the cooling field is compatible with the cross-sectional thermal and deformation pattern of the embankment.
TPCT performance is controlled by both device-scale heat transfer and embankment-scale thermal regulation. Air temperature, boundary conditions, pipe geometry, inclination, burial depth and evaporator position control the operating period, heat-extraction depth and cooling range [
16,
18,
19,
27,
28,
29,
30]. Semiconductor-assisted cooling has been explored to extend TPCT operation into the warm season, while lower ambient temperatures in high-latitude regions can increase cooling capacity without auxiliary refrigeration [
31,
32]. At the embankment scale, layout optimization has focused on reducing lateral thermal imbalance caused by slope aspect and pavement heat storage [
8,
9]. Bilateral TPCT arrangements provide more balanced cooling than unilateral, although sunny-shaded asymmetry persists [
25,
33]. L-shaped TPCTs and TPCT-insulation composite embankments extend cooling toward the embankment center and slope zones, but field evidence shows limited operating duration, persistent sunny-side warming and cracking when protection does not span the full cross-section [
20,
21,
34]. Recent horizontal and self-adaptive horizontal TPCTs redistribute cooling along the embankment, reducing lateral temperature contrasts, smoothing isotherms and increasing heat release relative to inclined layouts [
34,
35,
36,
37]. Targeted arrays with variable-inclination evaporators have been used to cool localized warm zones in embankment–bridge transition sections by forming cold cores and raising the permafrost table [
38]. These studies show that climate forcing, TPCT-scale design and embankment layout jointly control TPCT performance. For wide asphalt embankments, the unresolved issue is whether a layout can preserve laterally continuous frozen ground under asymmetric heat input [
8,
26,
39]. Assessing this issue requires layout-level indicators, including lateral temperature uniformity, volumetric ice content, operating duration and cumulative cooling capacity.
This study evaluates how different TPCT layouts regulate the hydrothermal state of a wide asphalt embankment in a permafrost region under climate warming. A three-dimensional hydrothermal model is used to compare an embankment without TPCTs, a conventional inclined two-phase closed thermosyphon (CIT) layout and a base-arranged novel horizontal two-phase closed thermosyphon (NHT) layout. The analysis first characterizes degradation in the unprotected embankment and then examines how the two TPCT layouts affect temperature distribution, volumetric ice content, maximum thaw depth, operating duration and cumulative cooling capacity. By linking these indicators, this study assesses the ability of each layout to maintain frozen-state continuity and cross-sectional temperature uniformity, providing a basis for TPCT layout selection in wide asphalt embankments in permafrost regions.
2. Materials and Methods
Figure 2 summarizes the research workflow, including model inputs, hydrothermal model construction, initialization, validation, scenario simulation, indicator extraction and performance assessment. After natural ground validation, field monitoring data were used as indirect checks.
2.1. Geometry
In the model coordinate system, x, y and z denote the transverse, longitudinal and vertical directions, respectively, and the natural ground surface is set at z = 0.
Figure 3 shows the embankment cross-section, along-road computational unit and two TPCT layouts. The embankment has a 13 m crest width, a 3 m height and a side–slope ratio of 1:1.5. To reduce lateral boundary effects, the natural ground extends 39 m outward from both slope toes. The domain comprises embankment fill above the natural ground and three foundation layers: silty clay from 0 to 2 m, sub-clay from 2 to 8 m and weathered mudstone from 8 to 30 m. Layer-specific thermal and hydraulic parameters were assigned to represent differences in heat transfer, moisture migration and frozen-state evolution. A 0.1 m thick XPS insulation layer was placed 2 m above the embankment.
The CIT and NHT cases used identical pipe dimensions, evaporator and condenser lengths, condenser-fin parameters and computational-unit length but differed in evaporator orientation, installation position and cooling coverage. The CIT was inserted at 45° from below the XPS layer near the shoulder, whereas the NHT was placed horizontally along the embankment base. Both TPCTs had outer and inner diameters of 0.089 m and 0.08 m, a 10.5 m evaporator and a 2.5 m condenser. The condenser-fin height, thickness and spacing were 2.5 cm, 0.1 cm and 1 cm, respectively.
The 45° inclined TPCT was selected as a representative conventional layout used in previous engineering applications and laboratory studies [
33,
34]. This arrangement allows the evaporator to extend from the shoulder region toward the lower central part of the embankment and strengthen deep cooling beneath the embankment. Changing the inclination angle would alter evaporator burial depth, lateral coverage and cooling-field geometry. Therefore, this comparison is interpreted as a layout-level comparison rather than an optimization of inclination angle.
2.2. Design Rationale and Experimental Basis of the NHT Layout
A laboratory-scale straight TPCT was tested experimentally to examine whether guided gas–liquid circulation could sustain heat transfer with a horizontal evaporator. The test system is shown in
Figure 4a,b. Constant-temperature baths independently controlled the evaporator and condenser temperatures. Inside the TPCT, gas and liquid guide tubes separated vapor transport from condensate return (
Figure 4c). A sealed separator was installed at the bottom of the condenser to maintain a liquid head and guide condensate return. The TPCT was tested at an inclination angle of 0° under different condenser-section temperatures. Each condition was repeated twice, and the heat flow rate was calculated from the stable 10 min average after steady heat transfer was reached. The TPCT maintained an effective heat flow rate at 0°, and the heat flow rate increased as the condenser-section temperature decreased (
Figure 4d). The fitted correlations in
Figure 4d were obtained from the mean values of the two repeated measurements at each condenser-section temperature. Compared with previously reported horizontal TPCTs that use wick structures, liquid collectors, and return lines for condensate redistribution, the present phase-separated design uses gas-guide and liquid-guide tubes together with a sealed separator to separate vapor transport from condensate return [
34,
36]. These data support horizontal operation and phase-separated circulation but were not used to calibrate the field-scale numerical model. The TPCT dimensions and test parameters are provided in
Appendix A.
2.3. Governing Equations
In the hydrothermal model, temperature and unfrozen-water content were selected as the primary solution variables. Liquid-water migration was driven by unfrozen-water content gradients, temperature gradients and gravity, whereas ice was treated as immobile.
2.3.1. Coupled Hydrothermal Equations for Soil
Heat transfer in the soil–water–ice system was described as transient conduction with ice–water phase change. Based on energy conservation, the governing heat-transfer equation is expressed as [
11,
40]:
where
T is soil temperature (°C);
t is time (s);
x,
y and
z are spatial coordinates (m);
Ce is the apparent equivalent volumetric heat capacity (J m
−3 K
−1); and
λe is the equivalent thermal conductivity (W m
−1 K
−1).
Pore-water freezing and thawing were treated as continuous transitions over a finite phase-change interval. A smoothed step function was used to avoid abrupt changes in thermal properties near the freezing temperature:
H is a smoothed function, Tf is the characteristic freezing temperature of the soil (°C), and ΔT is the phase-change smoothing interval (K), set to 0.5 K. Hf represents the local frozen-state fraction within the phase-change interval centered at Tf.
Soil thermal properties were updated according to the frozen-state fraction. In the apparent heat-capacity method, the equivalent volumetric heat capacity includes sensible heat storage and latent heat release. The equivalent thermal conductivity includes conductive heat transfer and latent-heat redistribution associated with unfrozen-water migration [
4,
33]:
where
Cu and
Cf are the specific heat capacities of thawed and frozen soil, respectively (J kg
−1 K
−1); ρ
s is the dry density (kg m
−3); L is the latent heat of ice–water phase change (J kg
−1); ρ
w is the density of water (kg m
−3);
λu and
λf are the thermal conductivities of thawed and frozen soil, respectively (W m
−1 K
−1);
Dw represents moisture diffusion associated with the unfrozen-water content gradient (m
2 s
−1); and
θu is the unfrozen-water content (m
3 m
−3).
In frozen soil, only liquid unfrozen water was assumed to migrate, whereas ice remained immobile. The moisture mass-conservation equation is written as [
11,
33]:
where
θi is the volumetric ice content (m
3 m
−3);
ρi and
ρw are the densities of ice and water, respectively (kg m
−3); and
qwx,
qwy and
qwz are the liquid-water flux components in the x, y and z directions, respectively (m s
−1).
Liquid-water flux was driven by gradients in unfrozen-water content and temperature, with gravity included in the vertical direction:
where
DT represents temperature-gradient-driven moisture diffusion, and
Kw is the hydraulic conductivity (m s
−1). The units of
Dw and
DT are m
2 s
−1 and m
2 s
−1 K
−1, respectively.
Under frozen conditions, adsorption on soil-particle surfaces and physicochemical effects retain part of the pore water in an unfrozen state. The temperature-dependent unfrozen-water content was described by an empirical relation [
41]:
where
θr is the residual volumetric water content (m
3 m
−3),
θtot is the total volumetric water content (m
3 m
−3), and
a1 and
b1 are empirical parameters for the unfrozen-water characteristic curve.
During freezing, ice formation reduces liquid-water pathways and decreases hydraulic conductivity and moisture diffusivity. The freezing-impedance effect was described by empirical functions of volumetric ice content [
33,
42,
43]:
where
a2 and
a3 are empirical coefficients for hydraulic conductivity and water diffusivity, respectively.
Equations (1)–(9) constitute the hydrothermal model for the soil domain. Temperature controls ice–water phase transformation and the associated thermal and moisture-migration parameters. Unfrozen-water migration and phase change update the unfrozen-water content, freezing state and latent-heat effects. All symbols and physical meanings are summarized in
Appendix C.
2.3.2. Equivalent Heat-Transfer Model for TPCTs
To avoid numerical instability caused by resolving internal two-phase flow in long-term embankment-scale simulations, TPCT heat transfer was represented by an equivalent thermal-resistance method. Because the condenser was not explicitly resolved in the model, the equivalent resistance was treated as a lumped system resistance that includes pipe-wall conduction, internal phase-change heat transfer and condenser-air heat exchange. The same equivalent-resistance framework was used for the CIT and NHT cases to isolate layout-scale effects related to evaporator position and cooling coverage. The cooling effect was applied as an equivalent heat-absorption flux at the evaporator boundary:
where
λe is the equivalent thermal conductivity of soil (W m
−1 K
−1), n
TPCT is the outward normal of the evaporator boundary, and q
TPCT is the equivalent heat flux absorbed from the soil by the evaporator segment (W m
−2).
TPCT operation was controlled by the effective temperature difference between the evaporator and ambient air. A smooth activation function was used to represent start-up and shut-down:
where
Son is the TPCT activation factor;
Tevap is the mean wall temperature of the evaporator (°C);
Tair is the ambient air temperature (°C); ΔT
start is the TPCT start-up temperature difference (K), set to 1 K; and ΔT
on is the start-up smoothing interval (K).
The heat-transfer power of a single TPCT was calculated from the effective evaporator-air temperature difference and the equivalent total thermal resistance. It was then converted into an equivalent heat-absorption flux on the evaporator boundary [
28,
29,
30]:
where
QTPCT is the heat-transfer power of TPCT (W), A
eo is the outer heat-exchange area of the evaporator (m
2), R
TPCT is the equivalent total thermal resistance (K W
−1), and
qTPCT is the equivalent evaporator heat flux (W m
−2).
The equivalent total thermal resistance was decomposed into pipe-wall conduction, internal phase-change heat transfer and condenser-side air convection:
where R
ew and R
cw are the wall conduction resistances of the evaporator and condenser, respectively; R
ei and R
ci are the phase-change resistances in evaporator and condenser, respectively; and R
co is the convective resistance between the condenser outer surface and ambient air. All resistance terms have units of K W
−1.
The individual thermal-resistance components can be expressed as:
where λ
TPCT is the thermal conductivity of the pipe wall (W m
−1 K
−1); L
e and L
c are the evaporator and condenser lengths, respectively (m); d
o and d
i are the outer and inner pipe diameters, respectively (m); α
e, α
c and α
a are the evaporator-side boiling, condenser-side condensation and condenser-air convective heat-transfer coefficients, respectively (W m
−2 K
−1); and A
e, A
c and A
f are the corresponding evaporator inner, condenser inner and finned condenser outer heat-exchange areas, respectively (m
2).
Equations (10)–(14) couple the TPCT with the soil temperature field. This formulation supports layout-level comparison but does not resolve inclination-dependent internal two-phase-flow resistance. It also excludes long-term device ageing, including environmental corrosion, non-condensable gas formation and leakage caused by external damage, which may influence field-scale thermal resistance during multi-decade service.
2.4. Boundary Conditions and Material Parameters
Solar radiation, wind speed, air temperature and surface materials impose different thermal conditions on the natural ground, embankment slopes and asphalt pavement. Equivalent surface-temperature boundaries were prescribed to represent these periodic surface-temperature variations [
20,
33,
44]:
where
Ts is the equivalent surface temperature (°C),
T0 is the annual mean surface temperature (°C),
A is the annual temperature amplitude (°C), and φ is the initial phase (rad). ΔT
air is the prescribed climate-warming rate for the study region (°C yr
−1), set to 0.052 °C yr
−1.
Equivalent surface-temperature boundaries were used to represent surface-material, slope-aspect and regional-warming effects. Asphalt pavement was assigned a higher annual mean surface temperature than natural ground, and the sunny slope a higher value than the shaded slope. The parameters in
Table 1 were derived from Beiluhe station monitoring data and previous Qinghai–Tibet Plateau embankment studies [
25,
33,
34], with annual mean temperature and amplitude integrating air temperature, radiation, wind-driven convection and surface properties. The warming rate of 0.052 °C yr
−1 was applied as a regional high-altitude permafrost-corridor scenario for three cases [
45]. The south-facing and north-facing slopes represent the traditional sunny-shaded contrast for an east–west road in the Northern Hemisphere; other orientations can be assessed by interpolating or recalculating equivalent surface-temperature parameters according to slope azimuth and local radiation-meteorological conditions.
The lateral boundaries (DK-FL) were set as zero normal-flux boundaries, and an upward geothermal heat flux of 0.03 W m
−2 was applied at the bottom boundary (KL). The XPS insulation layer was excluded from the moisture-field calculation. Parameters in
Table 2 and
Table 3 were obtained from field investigation, laboratory tests and hydrothermal parameters for the study region [
25,
33,
34]. The water, ice and residual-water contents are expressed as relative volumetric contents (m
3 m
−3).
Before embankment construction, the natural ground was simulated without climate warming until a quasi-steady hydrothermal state was obtained. This state provided the initial temperature and moisture fields for the soil domain. The embankment fill was initialized from its initial saturation and surface thermal condition. Climate-warming surface-temperature boundaries were then applied to three cases.
Local mesh refinement was applied in the TPCT–soil contact zone, embankment and shallow foundation. The maximum element size was 0.1 m at the TPCT–soil contact boundary, 0.25 m in the embankment region, 0.1 m in the silty clay layer and 0.15 m in the sub-clay layer. The weathered mudstone layer used a graded mesh with a maximum element size of 1 m and a growth ratio of 3. Quadratic Lagrange elements were adopted, and the final model contained approximately 5.36 × 105 degrees of freedom. The transient solver used a maximum time step of 1 d and a relative tolerance of 1 × 10−4.
Model reliability was checked using natural ground validation, mesh sensitivity and time-step sensitivity. The quasi-steady natural ground temperature profile was compared with field observations. Mesh refinement produced a maximum-thaw-depth difference of 0.04 m at the sunny-side slope toe. The 1 d and 0.1 d maximum time steps produced small differences in TPCT heat-flux-density response, with maximum deviations of 0.96 W m−2 on the sunny side and 1.10 W m−2 on the shaded side. The laboratory horizontal-TPCT test supported the feasibility of NHT operation, but was not used to validate the embankment-scale cooling simulation.