Next Article in Journal
Damage Evaluation of RC Bridge Columns Subjected to Close-In Explosions Considering Failure Modes
Previous Article in Journal
The Uniaxial Compressive Constitutive Behavior and Mesoscopic Numerical Simulation of HPC Incorporating ASR Mitigation Measures After Ten Years of Alkali Solution Immersion
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Hygrothermal Performance of Exterior Wall Assemblies Under Wind-Driven Rain Across China’s Thermal Zones

1
Department of Architecture, Wuhan University, Wuhan 430072, China
2
Shanghai Research Institute of Building Sciences (China), Shanghai 200032, China
*
Authors to whom correspondence should be addressed.
Buildings 2025, 15(22), 4198; https://doi.org/10.3390/buildings15224198
Submission received: 10 October 2025 / Revised: 13 November 2025 / Accepted: 14 November 2025 / Published: 20 November 2025
(This article belongs to the Section Architectural Design, Urban Science, and Real Estate)

Abstract

Wind-driven rain (WDR) is recognized as a primary source of moisture intrusion in exterior wall assemblies. However, China’s national code for thermal design of wall assemblies predominantly relies on temperature criteria classified by thermal zones, with humidity-related impacts on building thermal performance remaining unconsidered. Thus, the influence of WDR on the hygrothermal performance of exterior wall assemblies necessitates systematic investigation. This study aims to explore variations in moisture resistance among different wall assemblies under WDR exposure and differences in hygrothermal performance of identical assemblies across designated thermal zones. To this end, the hygrothermal behavior of five typical insulated wall assembly types was evaluated across 21 representative cities spanning four major thermal zones in China. Results indicate significant disparities in the hygrothermal performance of wall assemblies under WDR across thermal zones: dryness rates decreased by an average of 100%, 93.33%, 44%, and 30% in Severe Cold, Cold, Hot Summer and Cold Winter, and Hot Summer and Warm Winter Zones, respectively. Furthermore, although certain wall assemblies eventually dried over time, the risk of mold growth persisted. Notably, wall assemblies with external EPS insulation exhibited high sensitivity to WDR, while self-insulated and internal insulation systems were also vulnerable to WDR in the Hot Summer and Warm Winter Zone. In conclusion, annual WDR exposure and U-value are key factors in designing wall assemblies for optimal hygrothermal performance.

1. Introduction

Wind-driven rain (WDR) is a phenomenon where raindrops are given a horizontal velocity component by the wind, causing them to fall in an inclined manner [1,2]. It represents a critical moisture source affecting the hygrothermal performance and long-term durability of building envelopes [3,4]. As one of the most critical external moisture loads on building envelopes, WDR directly governs the hygrothermal balance, surface wetting, and durability of exterior walls, particularly in climates with high wind exposure [5]. WDR significantly affects various aspects of building performance, including energy consumption, mechanical properties, and risks associated with moisture accumulation, such as mold growth and material degradation [6,7,8]. Recent studies have shown that neglecting WDR can lead to underestimation of surface moisture flux and long-term deterioration risks in simulation-based envelope analyses [9]. Moreover, the regional variability of WDR exposure, which depends on wind speed, rainfall intensity, and façade orientation, has been recognized as a dominant factor influencing envelope degradation and energy demand [10]. Consequently, accurate quantification and understanding of WDR impacts are essential prerequisites for climate-responsive envelope design and durability assessment [11].
WDR is one of the primary moisture sources affecting the hygrothermal performance and long-term durability of exterior walls [12,13]. WDR exposure quantification methods have been systematically reviewed, covering field measurements, semi-empirical models, and numerical simulation approaches [14]. These quantification methods are generally categorized into three types: (1) empirical and semi-empirical approaches that calculate exposure indices from meteorological data; (2) numerical models based on computational fluid dynamics (CFD) that simulate the airflow–raindrop interaction around building envelopes; and (3) coupled heat-air-moisture (HAM) transfer models used to predict moisture penetration and drying behavior inside multilayer wall systems. Among these, the ISO 15927-3 (2009) standard [15] provides a widely accepted framework for calculating the annual and extreme driving rain index from hourly wind and rainfall data, forming the basis for WDR evaluation across climatic regions. Early numerical studies, such as Choi [16] and Blocken and Carmeliet [17], established the fundamental principles for predicting raindrop trajectories and façade wetting intensity. Subsequent research enhanced model precision by integrating high-resolution CFD analyses with full-scale façade measurements [18]. With the development of HAM modeling, the WUFI® program, originally proposed by Künzel [19], has become a standard tool for dynamic simulation of hygrothermal processes under wind-driven rain exposure. Numerous studies have investigated the hygrothermal responses of different exterior wall assemblies under WDR exposure [20]. Palani et al. [21] validated WUFI predictions against field data for a cold-climate wall system, while Nath et al. [22] confirmed its accuracy for long-term mold growth assessment under temperate conditions. Dang et al. [13] further emphasized the influence of material vapor permeability and capillary absorption on HAM-based simulations. These validated modeling frameworks provide a solid foundation for quantitative assessment of WDR-induced moisture transport and have been increasingly applied in performance-based design and regional durability evaluation [23].
Significant progress has been made in quantifying WDR and assessing its hygrothermal impacts. A consensus acknowledges that the hygrothermal response of walls to WDR is a complex process involving the coupling of multiple factors, including climate, assembly design, and material properties [12,13]. Effective moisture management strategies, such as the use of ventilated rainscreens and capillary-active insulation, along with robust simulation models, are crucial for optimizing the performance and durability of wall assemblies in varying climates [10]. In recent years, research has shifted from single-climate analyses to comparative investigations across multiple climatic zones, aiming to understand how regional WDR variations influence wall performance and moisture risk. Huang et al. compared wall assemblies in twenty North American cities and demonstrated that neglecting WDR leads to underestimation of hygrothermal degradation [24]. Yu et al. analyzed public buildings across different Chinese climate zones using WUFI-Plus, showing that WDR-induced hygrothermal coupling reduced cooling demand in northern China while increasing it in southern regions [20]. Pakkala and Lahdensivu [10] examined Finnish climate zones and found that WDR loads are highest in coastal regions, with future increases projected under warming conditions. Dae and Cannon further predicted a general rise in WDR indices across Canadian climate regions, especially in western and northern areas, while Cornick and Dalgliesh demonstrated the conversion of rainfall observations into quantitative WDR data for simulation use [25,26,27,28]. These studies collectively reveal the climate-dependent and regionally differentiated nature of WDR impacts on hygrothermal performance.
Different wall assembly types exhibit varied hygrothermal responses under WDR exposure due to differences in material moisture storage, vapor permeability, and insulation configuration [10,11,28]. Previous studies have demonstrated that ventilated rainscreen façades and exterior insulation systems provide superior resistance to WDR-induced wetting compared with face-sealed claddings, particularly in hot–humid climates [29,30]. Capillary-active insulation systems have been shown to mitigate interstitial condensation and enhance drying potential under cyclic wetting conditions [13]. In contrast, highly insulated lightweight walls—such as deep-cavity wood-framed assemblies—are more vulnerable to moisture accumulation and mold growth when exposed to repeated wind-driven rain and imperfect detailing [31]. Recent investigations have also emphasized that material selection and surface finish significantly affect the wall’s response to WDR. Bastien and Winther-Gaasvig reported that driving rain combined with vapor diffusion strongly influences the overall thermal efficiency of hygroscopic envelopes, especially during prolonged wet seasons [32]. Similarly, Hamid and Wallentén highlighted that internally insulated masonry walls in cold climates are highly sensitive to moisture accumulation when exterior layers remain vapor-tight [33]. In parallel, material-oriented research has explored microstructural modifications and polymer-based composite designs to improve moisture resilience. For instance, Xian et al. developed a self-healing carbon nanotube/epoxy system that exhibited superior durability under cyclic hygrothermal stress, demonstrating material-level innovations that may inspire envelope performance enhancement under WDR exposure [34]. Experimental and simulation studies further confirmed that the absorption and drying behavior of finishing materials strongly depend on surface treatment and cumulative WDR exposure [35]. Collectively, these findings indicate that the interplay between assembly design, material properties, and climatic factors fundamentally governs moisture transport and durability performance under WDR. However, current research has predominantly examined either the performance of single-wall assemblies across multiple climates or different wall assemblies within the same climate zone, while comprehensive cross-comparisons encompassing multiple wall types and climatic conditions remain limited.
Beyond this research gap, another limitation exists in practical design, where the envelope design practice guided by the China National Code for Thermal Design of Civil Buildings (GB 50176–2016) predominantly relies on U-value criteria, while the effects of WDR-induced moisture accumulation are seldom considered in design evaluation [36]. As a result, the suitability of wall assemblies is often assessed only from the perspective of thermal insulation, neglecting the coupled influence of WDR and moisture transport on long-term durability. Moreover, existing comparative studies lack a unified evaluation framework that integrates both thermal and moisture performance under realistic WDR exposure, especially across different climatic zones. To address this gap, this study aims to establish a dual-dimensional analytical framework for systematically investigating the hygrothermal performance of wall assemblies across typical thermal zones in China. Specifically, it seeks to compare: (1) the performance of identical wall assembly types across different climate zones to reveal the conditioning role of climate; and (2) the performance of different wall assembly types within the same thermal zone to identify pathways for assembly optimization. All analyses will explicitly consider long-term WDR exposure as a core influencing factor.
In hygrothermal simulations, moisture content serves as the primary indicator of wall performance because it directly reflects the dynamic balance between wetting and drying under coupled heat–moisture transfer. The accumulation of moisture not only accelerates material degradation but also alters thermal conductivity and reduces insulation efficiency [21]. Moreover, WUFI simulations calculate transient moisture content across each material layer, making it a physically consistent and widely validated variable for assessing both hygrothermal behavior and long-term durability [19,37]. Therefore, this study adopts the mean moisture content of wall assemblies as the key quantitative indicator to evaluate their moisture resistance and drying potential under long-term WDR exposure across different thermal zones, and further quantifies the effects of WDR intensity and U-value on the variation in moisture content.

2. Research Methods

Current research on WDR and building envelopes typically adopts three main approaches: field measurements [38], computational fluid dynamics (CFD) simulations [11,16,17,18,31], and semi-empirical models [35,39,40,41,42], each with its own strengths and limitations [38,39,40,43]. In contrast, semi-empirical models enable faster calculations and have been continuously refined and calibrated over time [38,39,44,45], making them one of the most widely used approaches [15,40,41].
Simulation tools based on semi-empirical models include DELPHIN 5, COMSOL Multiphysics 6.3, DeST-Standard, and WUFI pro (6.7), among a total of 14 widely used hygrothermal modeling software packages. A comparative study of these 14 hygrothermal tools assessed their performance in predicting external wall surface temperatures, revealing that WUFI exhibited the highest accuracy in quantitative simulations of nighttime cooling effects [46]. A previous study validated WUFI’s performance across 15 North American cities, demonstrating that both climatic conditions, such as humidity and precipitation, and material properties, such as thermal conductivity and vapor diffusion resistance, affect wall moisture dynamics [24]. Another study further emphasized the impact of WDR-induced hygrothermal coupling on building energy use, affirming the relevance of dynamic simulation tools in moisture-related assessments [20]. Such precision in surface temperature prediction helps minimize errors in moisture analysis caused by inaccurate external temperature calculations. It must be acknowledged that existing studies have confirmed certain limitations in semi-empirical models, such as insufficient consideration of building width and wind-blocking effects [40]. Therefore, their applicability in scenarios with complex building geometries or airflow fields requires careful evaluation. However, since this study does not involve multiple complex building shapes or significant wind-blocking effects, the semi-empirical model can still be reasonably adopted for this study.

2.1. Weather Data and Location

The selection of meteorological datasets was guided by two key criteria. First, the study requires a full year of hourly meteorological data, including temperature, relative humidity, global radiation, wind direction, wind speed, and precipitation, with each variable comprising 8760 records. Among the currently accessible and budget-compliant datasets, the 2020 weather dataset from the European Center for Medium-Range Weather Forecasts (ECMWF) represents the most recent and authoritative source that fulfills these requirements. It has undergone rigorous validation and demonstrates high reliability [47].
Second, considerable emphasis was placed on the climatic typicality and long-term representativeness of the data. Although multi-year climate datasets such as the 1991–2020 China Surface Standard Climate Normals Dataset (CSCND, authoritative data from the China Meteorological Administration) exhibit strong long-term representativeness, they only provide annual or monthly averages, which are inadequate for hourly simulations. Therefore, to evaluate the climatic typicality and long-term representativeness of the station data, we quantified the statistical agreement between the monthly average precipitation from the ECMWF 2020 dataset and the 1991–2020 CSCND.
A coefficient of determination (R2) threshold of 0.7 was employed in the regression analysis to evaluate data consistency. This threshold aligns with the established convention in climate data validation studies, where an R2 ≥ 0.7 is widely adopted to indicate an acceptable level of agreement between datasets for subsequent modeling applications. In their study, “New procedure in developing adjustment algorithm for harmonizing historical climate datasets”, Komutunga indicated that an R2 > 0.5 (corresponding to a correlation coefficient R2 > 0.7) between simulated data and observed monthly rainfall can be considered indicative of a “strong and statistically significant linear relationship” [48]. Their study concluded that an R2 of 0.53–0.54 sufficiently accounts for a substantial portion of data variance, making it suitable for subsequent analysis. Building on this consensus and considering the need for higher data consistency in this study, we established a more stringent threshold of R2 ≥ 0.7. This ensures a stronger correlation between the ECMWF 2020 data and the 1991–2020 CSCND, thereby better supporting the quality requirements of input data for subsequent hygrothermal simulations. Among the 106 meteorological stations analyzed, 33 met the R2 ≥ 0.7 criterion. To ensure spatial distribution uniformity, 21 stations were selected as representative simulation locations according to China’s four thermal zones, with detailed parameters of the selected stations illustrated in Figure 1.

2.2. Simulation Setup

This study adopted WUFI Pro (version 6.7) for semi-empirical simulations. Developed by the Fraunhofer Institute in Germany, the software is based on the heat–air-moisture transfer (HAMT) model proposed by Künzel [19]. It comprehensively incorporates key climatic factors, such as material moisture content, WDR, solar radiation, longwave radiation, capillary transport, and summer condensation. WUFI Pro accurately simulates the transient hygrothermal performance of building components under natural climate conditions, supports simulations of standard cross-sections, and performs dynamic hygrothermal analyses in accordance with the DIN EN 15026 standard using real climatic data [49].

2.2.1. Boundary Conditions

Based on the 2020 hourly meteorological data from the ECMWF, this study adopted the WAC format to construct climate files for the required locations, as WUFI’s built-in weather database lacks meteorological stations in mainland China. The resulting outdoor boundary conditions comprise a full year of hourly data—including temperature, relative humidity, global radiation, wind direction, wind speed, and precipitation—with 8760 records for each variable across the 21 selected cities.
The indoor environmental conditions were derived using the algorithm specified in ASHRAE Standard 160 [35], which derives indoor thermal conditions from outdoor climate data. In this study, indoor design temperatures for heating and cooling were determined by comprehensively considering the thermal zoning characteristics of each city [50]. The on/off status of air conditioning systems was automatically controlled according to indoor temperature and humidity conditions to maintain the indoor environment within the target range. Indoor air movement also plays a critical role in heat and moisture transfer processes. Therefore, an appropriate airflow model was applied in the simulation, incorporating designated air change rates to reflect the potential influence of ventilation on the inner surface of the wall. Specifically, in Severe Cold and Cold Zones, the indoor heating temperature was set at 18 °C, with a design ventilation rate of 0.5 air changes per hour during the heating period. In the Hot Summer and Cold Winter Zone, the indoor design temperature was set to 18 °C for winter heating and 26 °C for summer cooling, with a design ventilation rate of 0.5 air changes per hour. In the Hot Summer and Warm Winter Zone, during summer air-conditioning operation, the indoor design temperature for living spaces is maintained at 26 °C, with a design ventilation rate of 1.0 air changes per hour.
In this study, a total of 68 simulation cases, each defined as a unique combination of one location and one wall type, were run for a period of four years with reference to a previous study [30].

2.2.2. Physical Model Setting

To evaluate the accuracy of the WUFI simulations in this study, we reproduced the study of the EPS internally insulated wall in Beijing from reference [51], using the moisture content data provided in that study as a validation benchmark. We strictly followed the wall construction, hygrothermal material parameters, and boundary conditions described in the literature to establish the corresponding physical model in WUFI Pro.
A key and unavoidable discrepancy lies in the fact that the original text does not specify the exact source and version of the Typical Meteorological Year data for Beijing used in their study. Due to the diversity of historical weather datasets, it was impossible to ensure the use of a climate file identical to that in the original study. Nevertheless, the simulated moisture content variation over time in the concrete layer of the wall showed a high degree of consistency with the data reported in the literature, both in dynamic trends and numerical magnitude, as shown in Figure 2. This demonstrates the robustness and reliability of the WUFI model and parameter settings adopted in this study.
The tested wall assemblies in this study are all thermal insulation types, including thin plastered EPS external insulation system (Type 1), rock wool external insulation system (Type 2), precast concrete sandwich insulation panel system (Type 3), autoclaved aerated concrete block self-insulation system (Type 4), and gypsum board-expanded polystyrene composite internal insulation system (Type 5). Since thermal insulation types are not suitable for mild climate zones, this study does not include locations in the mild climate zone.
For the same wall assembly type to be evaluated across different climate zones, the insulation layer thickness, however, requires adjustment to meet the specified thermal transmittance. Per the requirements outlined in the General Code for Energy Efficiency and Renewable Energy Application in Buildings (GB 55015-2021) [52], the maximum allowable U-values (W/(m2·K)) for external walls of residential buildings with three or more stories are 0.40, 0.45, 1.20, and 1.50 for the Severe Cold, Cold, Hot Summer and Cold Winter, and Hot Summer and Warm Winter Zones, respectively. All assemblies selected in this study comply with these criteria. The corresponding configurations and the thermophysical parameters of each wall assembly are summarized in Table 1 and Table 2.
Selected typical wall assembly types were precisely modeled as physical assemblies in WUFI Pro. These models detail the layer sequence, thickness of each layer, and specific material parameters, while consistently following a fixed indoor–outdoor orientation convention, where the left side represents the exterior and the right side represents the interior. The determination of the orientation and the calculation of WDR involve two steps. First, the direction with the maximum WDR is determined. The eight available orientations for exterior walls include the four cardinal directions (east, west, south, and north) and four intercardinal directions (northeast, northwest, southeast, southwest). The WDR for each orientation is then computed using Equation (1), with all eight directions included in the calculation.
R w d r = R h R 1 + R 2 U c o s ϴ
where the following applies: R w d r —total wind-driven rain amount (mm)
R h —rainfall intensity on the horizontal plane (mm/h)
R 1 —wind-driven rain coefficient related to roof eave inclination
R 2 —wind-driven rain coefficient dependent on wind speed
U —hourly average wind speed at a height of 10 m (m/s)
ϴ —angle between the wind direction and the wall surface normal.
The calculation of the annual WDR load (DR) in a single orientation for each location, as well as the WDR input data used in the simulation, employs the r b v index (kg/m2·h) proposed in ASHRAE Standard 160-2009. The indicator accounts for WDR deposition on exterior walls based on hourly meteorological data, incorporating hourly rainfall, hourly average wind speed, and adjusting for terrain, building height, and roof geometry as illustrated in Figure 1.
The specific calculation uses Equation (2) is as follows:
r b v = F E F D F L U c o s ϴ R h
where the following applies:
r b v —WDR deposition on the vertical wall surface, kg/(m2·h);
F E —rain exposure factor, taken as 1 (assuming building height < 10 m and moderately exposed conditions);
F D —rain deposition factor, taken as 0.5 (assuming a wall beneath a low-inclination eave);
F L —empirical constant, 0.2 kg·s/(m2·mm).
The grid size was set to 100 cells, indicating a relatively fine resolution. Monitoring points were defined within each material layer along the thickness direction. No additional sources of heat, moisture, or air exchange were introduced to isolate the effects of indoor and outdoor environments on wall performance. The simulation outputs included hourly data on moisture content and mold growth potential over the simulation period, providing a basis for performance evaluation.

2.3. Indicators for Evaluation

2.3.1. Moisture Content

In a simulation study for all test cases, the initial relative humidity and temperature of the wall assemblies were set to fixed values of 80% and 20 °C, respectively, throughout the entire model. This criterion indicates the ability of the wall assembly to dry out over time. The initial and final moisture contents for the entire assembly are evaluated for each wall over a 4-year period. If the final value at the end of the modeling period is less than the initial value, this means that the wall has the potential to dry out. The moisture content involved in the research also includes the total mean moisture content (TMC), the insulation layer mean moisture content (IMC), and the outermost layer mean moisture content (OMC).

2.3.2. Dryness Rate

This study employed dryness rate as the key indicator to assess the hygrothermal performance of wall assemblies. The dryness rate provides an intuitive measure of how well wall assemblies can release moisture over time under specific climatic conditions, which is crucial for evaluating the durability and long-term stability of building materials. This indicator has been used in previous studies on hygrothermal performance of external walls [30].
The dryness rate was calculated as the difference between the initial and final moisture content. A positive value indicates that the case has the capacity to dry over time under the specified climatic conditions. The dryness rate, expressed as a percentage of this moisture loss relative to the initial moisture content, represents the degree of drying achieved during the simulation period.
ρ = ω 1 ω 2 ω 1 × 100 %
where the following applies: ρ —dryness rate
ω 1 —initial moisture content, kg/m3
ω 2 —final moisture content, kg/m3

2.3.3. Mold Growth

Mold growth serves as a critical indicator for assessing both wall performance and indoor hygienic conditions [29,32]. It is particularly important in the context of adding insulation layers to historic buildings or during retrofitting projects [33]. In addition to affecting indoor air quality, mold growth can lead to physical degradation of wall assemblies. For example, organic acids secreted by mold can corrode concrete surfaces, causing unevenness, detachment of finishing layers, and deterioration of insulation materials. These effects may result in material softening, chalking, and ultimately a reduction in the service life of the building envelope [30].
Mold growth on interior wall surfaces is primarily influenced by surface temperature, relative humidity, and duration. In this study, the risk of mold growth was assessed using the bio-hygrothermal model integrated within the WUFI pro (6.7). This model, based on the theory of Sedlbauer [53], comprehensively considers the synergistic effects of different relative humidity levels and their duration within the temperature range of 0 °C to 50 °C on the germination of mold spores. The assessment thresholds are dynamically interrelated and not fixed values. WUFI simulations provide temperature–humidity scatter plots, where the x-axis represents temperature (°C) and the y-axis represents relative humidity (%). More importantly, the software’s mold analysis function directly outputs evaluation results based on these complex calculations. In this study, the simulation results for the interior surfaces of all wall assemblies were analyzed, and cases identified by the software as posing a mold growth risk were recorded accordingly [19].

2.3.4. U-Value

Exterior wall assemblies are commonly composed of porous materials due to their capacity to absorb and retain moisture [54,55]. Within these materials, moisture may exist in three phases, vapor, liquid, and ice, as a function of temperature, relative humidity, and pore structure. These interrelated factors contribute to the complexity of their hygrothermal behavior [56].
In dry conditions, wall assemblies exhibit low U-values, ensuring superior thermal insulation. However, upon moisture absorption, their thermal performance can deteriorate significantly, as changes in moisture content affect changes in the U-value, and vice versa [56]. This mutual influence between moisture transport and heat transfer reduces insulation capacity and may ultimately increase building energy consumption [57].
The HAMT within building envelopes is a complex process. Therefore, when analyzing the impact of wind-driven rain in different climatic zones and its effects on various wall assemblies, it is essential to incorporate the HAMT process. This is crucial for reducing building energy consumption, assessing and preventing moisture-related damage, improving indoor thermal comfort and hygiene, and optimizing the overall performance of envelope types [54,55,58].
The initial U-values of wall assembly types in each thermal zone were uniformly specified at the beginning of the calculation period, while the simulation process was dynamic. Therefore, in quantifying the effects of DR and U-value on moisture content, this study uses the hourly mean U-value of wall assemblies from the final year of the calculation period, ensuring that the results reflect the actual thermal transmittance characteristics of the envelope under long-term service conditions.

2.4. Statistical Analysis

To examine whether statistically significant differences in moisture content exist among the wall assembly types within each location, a comparative analysis was conducted using the hourly total moisture content from the final simulation year of each case. Since the moisture content data of all 68 wall cases exhibited a pronounced positive skew (skewness coefficients ranging from 0.39 to 4.93) and the sample size was large (n > 8760 per case), the Shapiro–Wilk normality test may be overly sensitive and potentially misleading in this context. In large samples, even minor deviations from normality can lead to statistically significant results (p < 0.001). Thus, the assumptions for parametric tests were not met, and nonparametric methods were employed in this study. Given that each location has two to five independent groups, i.e., wall assembly types, multiple group comparisons were conducted for each location (involving up to five wall types, corresponding to six pairwise comparisons). To control the false positive error rate (Family-Wise Error Rate, FWER) arising from multiple testing, the Bonferroni correction was applied. This method adjusts the significance threshold (α/m, where m is the number of tests) to ensure that the overall error rate does not exceed the predetermined level (e.g., α = 0.05) [59]. Specifically, the original α = 0.05 was adjusted to α = 0.0083 (0.05/6 ≈ 0.0083). This adjustment imposes a stricter criterion for determining statistical significance, thereby reducing the risk of false positives, though it may slightly increase the probability of false negatives.
In addition, to investigate the relationship between WDR load and wall moisture content, Spearman’s rank correlation analysis was performed using the TMC, IMC, and OMC as variables. This nonparametric method was selected because both WDR load and moisture content violated the assumption of bivariate normality and exhibited nonlinear relationships, allowing for the assessment of monotonic associations and their statistical significance.

2.5. Quantifying the Impact of Key Factors on Moisture Content

This study further employs a machine-learning approach, specifically the Random Forest Regression Model [60], combined with the Sobol Sensitivity Analysis [61]. A previous study has developed a machine-learning method for predicting wind-driven rain catch ratios on building façades and compared multiple algorithms [62]. Random Forest is an ensemble learning algorithm based on multiple decision trees, improving prediction accuracy and stability through voting mechanisms. Leveraging its robustness and resistance to overfitting, we employ the RF–Sobol framework to investigate the impact of DR (mm/a) and U-value (W/(m2·K)) on the annual average moisture content of the outermost layer of building structures, where the outermost layer refers to the insulation layer for external insulation system and the structural layer for non-external insulation systems. The research dataset consists of 68 samples, each derived from a single case, with input variables including construction type, DR (mm/a), and the mean U-value for the final year. The output variable is the annual average moisture content of the outermost layer (kg/m3).
During the modeling phase, wall assembly types were treated as a discrete categorical variable and input into the model using One-Hot encoding along with other continuous parameters. A random forest regression model containing 500 decision trees was constructed using Python (3.9)’s sklearn.ensemble library to characterize the relationship between input variables and moisture content. Model evaluation results showed an R2 of 0.978 for the training set and 0.947 for the test set, with a test set RMSE of 11.915 and MAE of 6.253, as shown in Figure 3. These results indicate good agreement between predicted and measured values, along with strong generalization ability. Therefore, this model can serve as a reliable surrogate model for subsequent sensitivity analysis.
In the sensitivity analysis phase, the Saltelli method from the SALib library [63] was used to generate sampling points within the parameter space. Predictions were made using the trained random forest model, followed by calculations of Sobol first-order sensitivity indices (S1) and total effect indices (ST). DR and mean U-value were continuously sampled across the five wall assembly types to explore the sensitivity characteristics of these two continuous variables under different construction systems.

3. Simulation Results and Discussions

3.1. Moisture Content Assessment

The results demonstrated that, in all locations, the moisture content of different wall assembly types exhibited statistically significant differences (p < 0.001), indicating that wall assemblies with identical initial U-values had significant differences in moisture content within the same location, and this pattern was consistent across all thermal zones. However, after applying the Bonferroni correction for multiple comparisons, only two pairs showed no significant difference: Type 1 vs. Type 4 in Fuding, and Type 1 vs. Type 3 in Taiyuan. Detailed results are presented in Table 3. Despite the more stringent significance threshold imposed by the Bonferroni correction (α = 0.0083), the key between-group differences reported in Table 3 remained statistically significant. This further supports the conclusion that moisture content fundamentally differs across wall types.
After a calculation period of four years, the moisture content within each layer of all the wall assemblies reached a steady state, exhibiting periodic fluctuations in response to seasonal climatic variations. The amplitude of these fluctuations varied across all wall assembly types due to differences in material properties. To clearly demonstrate the moisture content variation patterns of all wall assembly types across every location within each Thermal Zone during the final year, we selected two representative patterns for each zone, i.e., (a) universal pattern, depicting one representative location that demonstrates the universal moisture content variation trend typical of the thermal zone. (b) unique pattern, showing the location exhibiting distinct moisture content variation patterns or deviating from the universal trend.
In the Severe Cold and Cold Zones, three wall assemblies were simulated for each location, i.e., Type 1, Type 2, and Type 3. In all locations, Types 1 and 3 exhibited similar overall moisture content trends, with consistent seasonal fluctuations and relatively small variation ranges. In contrast, Type 2 consistently showed the highest overall moisture content in both climate zones.
Type 1 adopts an external insulation system using EPS board as the insulation layer; Type 2 adopts a sandwich insulation system with XPS board; and Type 3 is also an external insulation system, but with rock wool board. Regarding the thermal properties, the porosity (m3/m3) of the three insulation materials is similar, with values of 0.95, 0.95, and 0.967, respectively. The initial thermal conductivity [W/(m·K)] measures 0.040, 0.035, and 0.041, with Type 2 slightly lower. In comparison, the most significant difference lies in the water vapor diffusion resistance factor, which is 30, 100, and 1.3 for the three types, respectively, with Type 2 being markedly higher than the other two. This characteristic may account for the consistently higher overall moisture content observed in Type 2 compared to Types 1 and 3. Additionally, the peak moisture content in the Cold Zone was higher than that in the Severe Cold Zone, despite their initial moisture contents being within a similar range between 11 and 14 kg/m3. This difference may be attributed to the higher average DR in the Cold Zone locations, which reached 186.66 mm/a, compared with 67.73 mm/a in the Severe Cold Zone locations.
Notably, among all locations, all types performed the smallest seasonal fluctuations in total moisture content in Yushu (Figure 4 and Figure 5). This phenomenon suggests a relationship with the relative stability of humidity at this location. Across the 11 locations in the Severe Cold and Cold Zones, the overall standard deviation of relative humidity averaged 20.66%, with Yushu ranking second lowest at 16.18. Although Qingdao showed the lowest overall standard deviation of relative humidity at 15.99, its total moisture content still exhibited considerable fluctuations. The smaller variation in Yushu is likely attributable to its relatively low annual DR of 58.57 mm/a, compared with 86.62 mm/a in Qingdao.
For the Hot Summer and Cold Winter Zone, five wall assemblies were simulated in each location, i.e., Type 1, Type 2, Type 3, Type 4, and Type 5. Unlike in the Severe Cold and Cold Zone, Type 2 did not exhibit significantly higher moisture content compared to Type 1 and Type 3. These three types consistently maintained lower overall moisture levels compared to Type 4 and Type 5, with smaller seasonal fluctuations, while Type 4 and Type 5 showed larger amplitudes of variation.
Type 4 employs an autoclaved aerated concrete (AAC) self-insulation system without an additional insulation layer, and the AAC material has a density of 600 kg/m3. In contrast, Type 5 adopts an internal insulation system composed of gypsum board combined with EPS board. The insulation layer is positioned on the interior side, while the exterior side consists of concrete with a density of 2200 kg/m3. Notably, the results indicate that non-external insulation systems or wall assemblies featuring a high-density concrete layer on the exterior side are more susceptible to the influence of WDR. This phenomenon can be attributed to the concrete wall layer’s vapor diffusion resistance factor of 92, which prolongs moisture diffusion time and consequently leads to greater moisture accumulation.
However, in Fuding, the total moisture content of Type 4 was comparable to that of Types 1,2, and 3 and even recorded the lowest values during certain periods (Figure 6). This could stem from the fact that in Fuding, the overall standard deviation of relative humidity averaged 12.96, the lowest among the Hot Summer and Cold Winter Zone, while the DR was also the lowest at 142.90 mm/a. Thus, Type 4 is better suited to climatic conditions characterized by smaller relative humidity fluctuations and lower DR.
In the Hot Summer and Warm Winter Zone, two wall assembly types were simulated, i.e., Type 4 and Type 5. Generally, Type 5 consistently exhibited higher overall moisture content than Type 4 throughout the year. From the perspective of material layers, this difference is attributable to the vapor diffusion resistance factor of the autoclaved aerated concrete blocks in Type 4 being 8.3, which allows faster diffusion, whereas the concrete wall layer in Type 5 has a vapor diffusion resistance factor of 92, leading to longer diffusion times and greater moisture accumulation. However, in Fogang, Guangzhou, and Shantou, Type 4 may exhibit notably higher total moisture content than Type 5 during the summer period (Figure 7). This can be attributed to the relatively high mean relative humidity during June to September in these locations, with values of 84.43, 81.76, and 81.67, accompanied by smaller fluctuations, with standard deviations of 11.36, 12.12, and 8.93. By contrast, Fuzhou and Yuanmou showed lower mean relative humidity values of 77.73 and 63.92, but with larger fluctuations, with standard deviations of 14.81 and 17.85. A more pronounced difference was observed in the WDR load over the same period: Fogang, Guangzhou, and Shantou recorded 139.05, 174.93, and 121.96 mm/a, which were significantly higher than the values of 33.43 and 44.70 mm/a in Fuzhou and Yuanmou. These results indicate that Type 4 is more sensitive to WDR load. Consequently, under conditions of high WDR and high relative humidity, it tends to accumulate more moisture, resulting in higher overall moisture content compared with Type 5.
Further, even when the initial relative humidity of all wall assembly types is set at 80%, differences in insulation thickness for the same wall assembly type across thermal zones result in differences in initial moisture content. Therefore, when comparing the performance of the same wall assembly type in different thermal zones, more focus should be on the fluctuation pattern of moisture content changing rather than the absolute values of moisture content, as the fluctuation patterns reflect the adaptability of a given wall assembly type within a specific thermal zone.

3.2. Dryness Potential Assessment

The results of wall assembly dryness rates across climate zones reveal distinct drying performance patterns. Severe Cold, Cold, Hot Summer and Cold Winter, and Hot Summer and Warm Winter Zones exhibit significant differences in both the proportion of drying cases and the magnitude of dryness rates, as shown in Table 4.
In the Severe Cold Zone, all 18 cases demonstrated drying behavior, with final moisture contents consistently lower than initial values. Dryness rates ranged widely from 25.59% to 55.47%, with Type 1 (47.73%), Type 2 (30.46%), and Type 3 (48.27%) showing notable variation in average performance.
The Cold Zone presented a slightly lower drying incidence, with 14 out of 15 cases exhibiting drying behavior—the sole exception being Type 2 in Xuzhou. Dryness rates here were more modest (1.04% to 38.91%), and average values followed a descending order of Type 1 (29.53%), Type 3 (25.47%), and Type 2 (14.23%).
A notable contrast emerged in the Hot Summer and Cold Winter Zone, where only 11 out of 25 cases showed drying behavior. Dryness rates remained low (1.28% to 22.10%), with Type 1 (18.70%) and Type 3 (13.56%) outperforming Types 2, 4, and 5, which exhibited negligible or no drying (≤2.28%).
The Hot Summer and Warm Winter Zone showed the poorest drying performance, with merely three out of ten cases demonstrating drying behavior. Dryness rates ranged from 10.52% to 47.18%, though average values remained low at 13.56% for Type 4 and 2.10% for Type 5.
The percentage of cases exhibiting drying behavior decreased progressively from northern to southern climate zones at 100% in the Severe Cold Zone, 93.33% in the Cold Zone, 44% in the Hot Summer and Cold Winter Zone, and 30% in the Hot Summer and Warm Winter Zone. This climatic gradient reflects the influence of regional climate conditions on moisture dissipation within wall assemblies.
Results revealed pronounced differences in hygrothermal performance between wall assembly types across China’s four thermal zones under long-term WDR exposure. A clear north-to-south decreasing trend in drying capacity emerged, reflecting the combined effects of ambient temperature, relative humidity, and precipitation intensity.
In the Severe Cold and Cold Zones, Type 2 consistently showed higher moisture accumulation tendency with significantly lower dryness rates compared to Types 1 and 3. This pattern arises from the water vapor diffusion resistance factors, which were 30 for Type 1, 100 for Type 2, and 1.3 for Type 3, respectively. Type 2’s substantially higher resistance inhibits moisture release from its insulation layer under low-temperature conditions, thereby reducing drying efficiency.
In the Hot Summer and Cold Winter Zone, characterized by hot-humid summers, relatively cold winters, and large annual temperature fluctuations, Types 2, 4, and 5 generally exhibited low dryness rates, suggesting that external insulation systems, such as Types 1 and 3, are more suitable for this climate.
In the Hot Summer and Warm Winter Zone, although Type 4 performed marginally better than Type 5, approximately 70% of cases showed no drying behavior, indicating a need for additional moisture protection measures.
However, dryness rate alone provides only partial insight into suitability as an indicator. Among all cases, 69.1% exhibited satisfactory dryness rate, yet 19.1% still experienced persistent moisture accumulation with varying degrees of mold growth risk. Cases with relatively high dryness rates may still suffer thermal performance degradation or mold susceptibility. Conversely, when material properties and structural configurations are appropriately optimized, even cases with lower dryness rates can maintain acceptable indoor conditions. A comprehensive assessment should therefore include mold growth risk evaluation alongside dryness rate measurements.

3.3. Mold Growth Risk Assessment

In this study, mold growth risk was classified into four levels for 68 building cases: low risk, moderate risk, elevated risk, and high risk. A total of 49 cases (72.06% of the samples) fell within the low-risk category, indicating that the five representative wall assemblies generally demonstrate favorable hygrothermal adaptability across most thermal zones in China. The remaining 19 cases (27.94%) exhibited varying degrees of mold risk. Among these, nine cases failed to achieve drying, showing consistency between mold risk predictions and the calculated dryness rate. The other 10 cases, despite achieving some degree of drying (maximum dryness rate ≤ 22.10%), still showed signs of mold risk, suggesting that microclimatic conditions conducive to mold growth can persist even under drying conditions.
Notably, in the Hot Summer and Cold Winter Zone and the Hot Summer and Warm Winter Zone, among the 10 cases adopting Type 4, 2 were classified as moderate risk, 3 as elevated risk, and 3 as high risk. This outcome highlights the unsuitability of this wall assembly type under humid and high-temperature climatic conditions, which is consistent with the results of the moisture content assessment and the dryness potential assessment. The only two cases identified as low risk were located in Fuzhou and Yuanmou, where the DR were 98.42 mm/a and 61.13 mm/a, respectively. By contrast, the remaining eight locations exhibited a much higher average DR of 197.50 mm/a, thereby resulting in considerably greater mold growth risks.
Based on both dryness rate and mold growth risk, the suitability of the tested wall assembly types varies significantly across the four thermal zones.
In the Severe Cold Zone, Types 1, 2, and 3 exhibit optimal climatic suitability as all cases achieved drying, with only one case presenting a moderate risk of mold growth. While these types in the Cold Zone rank second in suitability, 13 of 15 cases achieved drying, with two cases presenting a moderate risk of mold growth.
In the Hot Summer and Warm Winter Zone, the commonly used Types 4 and 5 showed poor suitability, with only 30% of cases achieving drying and 30% facing moderate or elevated mold growth risk.
In the Hot Summer and Cold Winter Zone, Type 1, Type 2, Type 3, Type 4, and Type 5 showed relatively worse suitability, with 44% of cases drying, but over half faced elevated or even high mold growth risk.
This indicates that determining wall assembly types in different zones based solely on U-value has limitations, and the impact of WDR must be considered simultaneously. For the former three zones, types using external insulation types like EPS and rock wool, or sandwich insulation types, demonstrated favorable performance and are recommended. Interestingly, Type 4, using autoclaved aerated concrete block, which is frequently regarded as suitable for humid climates, did not exceed the drying performance of external insulation types, and even fell slightly behind. This outcome contrasts with earlier expert-based assessments in a previous study [64], which reported that in Nanchang, a location in the Hot Summer and Cold Winter Zone, aerated concrete walls achieved the best overall performance among four wall assembly types. This discrepancy may stem from the fact that the earlier study employed the Analytic Hierarchy Process (AHP) to recommend aerated concrete as a suitable solution for humid climates, an approach inherently influenced by subjective judgment and weighting.

3.4. Correlation Between Wdr Load and Moisture Content

To further explore the relationship between WDR load and wall moisture performance, a correlation analysis was performed to quantify the strength and direction of their associations. The Spearman correlation coefficient (C) ranges from −1 to 1, where values closer to ±1 indicate stronger monotonic relationships, while values near 0 suggest weaker associations. Statistical significance was assessed at significance levels of α = 0.05 and 0.01. Correlations with p-values less than 0.05 were considered statistically significant. The results are illustrated in Figure 8.

3.4.1. Correlation by Wall Assembly Type

The relationship between WDR load and moisture content varied significantly across wall assembly types, with distinct climatic zone-dependent patterns observed for each type:
(1) Type 1
Type 1 exhibited strong climate-dependent correlation variability. In the Severe Cold Zone, WDR showed a weak, non-significant correlation with total moisture content (TMC, C = 0.468, p = 0.329) but a strong, significant association with insulation layer moisture content (IMC, C = 0.934, p = 0.005). This contrast suggests differential moisture response mechanisms between total and inner-layer metrics. In the Cold Zone, both TMC (C = 0.900, p = 0.002) and IMC (C = 1.000, p < 0.001) displayed robust positive correlations, indicating WDR is the primary driver of moisture accumulation in this region. Conversely, negligible correlations were observed in the Hot Summer and Cold Winter Zone (TMC: C = −0.100, p = 0.624; IMC: C = 0.000, p = 0.957), implying minimal WDR influence under hot-humid summer conditions.
(2) Type 2
Type 2 was characterized by layer-specific WDR sensitivity, with the outermost layer consistently showing the strongest associations. In the Severe Cold Zone, only outermost layer moisture content (OMC) exhibited a significant correlation (C = 0.943, p < 0.001), while TMC (C = 0.429, p = 0.397) and IMC (C = 0.029, p = 0.957) correlations remained weak and non-significant. A similar pattern emerged in the Cold Zone, where OMC again demonstrated significance (C = 0.900, p = 0.037), whereas TMC (C = −0.300, p = 0.624) and IMC (C = 0.800, p = 0.104) showed no statistical significance. In the Hot Summer and Cold Winter Zone, all three metrics (TMC, IMC, OMC) displayed uniformly weak correlations (C = 0.300, p = 0.624), confirming minimal WDR impact on moisture dynamics for this assembly type in humid climates.
(3) Type 3
Type 3 showed the weakest overall sensitivity to WDR across climatic zones. In the Severe Cold Zone, both TMC (C = 0.429, p = 0.397) and IMC (C = 0.600, p = 0.208) correlations were weak and non-significant. The Cold Zone similarly exhibited negligible OMC correlation (C = −0.100, p = 0.873) and a moderate but non-significant IMC association (C = 0.800, p = 0.104). Notably, the Hot Summer and Cold Winter Zone displayed a strong negative correlation for IMC (C = −0.900, p = 0.037), though this was offset by weak overall TMC correlation (C = −0.359, p = 0.553), suggesting complex moisture-WDR interactions unique to this climate-assembly combination.
(4) Type 4
Type 4 demonstrated climate-specific WDR responsiveness, with negligible influence in temperate zones and dominant control in hot-humid regions. In the Hot Summer and Cold Winter Zone, TMC and IMC showed moderate non-significant correlations (C = 0.700, p = 0.188), indicating limited WDR impact. In contrast, the Hot Summer and Warm Winter Zone exhibited perfect positive correlations (C = 1.000, p < 0.001) for both metrics, implying WDR entirely determines moisture levels in this assembly type under persistent high humidity.
(5) Type 5
Type 5 mirrored Type 4’s climatic sensitivity but with weaker layer-specific associations. In the Hot Summer and Cold Winter Zone, TMC (C = 0.600, p = 0.285) and IMC (C = −0.300, p = 0.624) correlations were weak and non-significant. The Hot Summer and Warm Winter Zone showed a dichotomous pattern: TMC displayed a perfect positive correlation (C = 1.000, p < 0.001), while IMC showed only a moderate non-significant association (C = 0.500, p = 0.391), suggesting differential moisture accumulation mechanisms between total and inner layers.
Collectively, these results confirm a significant positive correlation between WDR load and moisture content across all cases (p < 0.05), aligning with previous studies that identify WDR as a primary driver of exterior wall moisture damage [14,35,65]. However, the magnitude and significance of this relationship were strongly modulated by wall assembly type and climatic zone, highlighting the need for context-specific durability assessments.

3.4.2. Key Influencing Factors

Wall assembly type significantly modulated WDR sensitivity. Type 3 exhibited minimal responsiveness with a minimum p-value of 0.037 and no evident WDR-moisture correlation. In contrast, Type 1 and Type 4 demonstrated strong statistically significant positive associations with p-values less than 0.001, indicating direct WDR-driven moisture accumulation. Climatic zone further mediated these relationships. The Hot Summer and Cold Winter Zone displayed inconsistent correlations, including positive, negative, and non-significant patterns, reflecting complex interactions between seasonal humidity and temperature fluctuations. Meanwhile, the Cold Zone and Hot Summer and Warm Winter Zone showed uniformly robust positive correlations with p-values less than 0.001, highlighting WDR’s dominant role in extreme climates. Notably, the outermost layer consistently exhibited the strongest positive correlation with WDR load, with a p-value less than 0.001, confirming surface exposure as a primary moisture ingress pathway and validating the selection of outermost layer annual average moisture content as a representative metric for subsequent DR and U-value analyses.
Overall, the results revealed divergent moisture responses to prolonged WDR exposure among wall assemblies with identical U-values, underscoring the limitations of U-value as a standalone durability indicator. In northern regions, including Severe Cold and Hot Summer and Warm Winter Zones, Type 1 and Type 3 exhibited satisfactory drying capacity but remained susceptible to WDR-induced moisture damage. Conversely, Type 4 and Type 5 in hot-humid zones demonstrated high moisture retention and WDR sensitivity. These findings emphasize that envelope design must integrate region-specific moisture-WDR correlation patterns alongside thermal performance criteria to mitigate durability risks.

3.5. Sensitivity of DR and U-Value on the Outermost Layer Moisture Content

The sensitivity analysis results showed significant differences in the sensitivities of DR and mean U-value across different wall assembly types, as shown in Figure 9. For external insulation types like Type 1 and Type 3, the sensitivity of the mean U-value was significantly higher than that of DR, with the first-order Sobol index of mean U-value (S1_U) and first-order Sobol index of DR (S1_DR) equal to 0.940 and 0.058 for Type 1, and 0.986 and 0.008 for Type 3, respectively. The total Sobol index of mean U-value (ST_U) and total Sobol index of DR (ST_DR) are equal to 0.945 and 0.062 for Type 1, and 0.993 and 0.015 for Type 3, respectively. The small differences between ST and S1 indices (ranging from 0.004 to 0.011 across all wall types) indicate negligible interaction effects between DR and U-value, suggesting their influences on moisture content are primarily independent and additive. This may be related to the outermost layer of the external insulation system being a hydrophobic thermal insulation material, whose barrier effect against rainwater penetration results in low sensitivity to wind-driven rain.
In contrast, the remaining three non-external insulation types, namely Type 2, Type 4, and Type 5, exhibited noticeably higher or at least comparable sensitivity to the DR compared to the mean U-value. Specifically, Type 2 showed almost equal contributions from DR and U-value, with S1_DR of 0.498 and ST_DR of 0.507, while S1_U and ST_U were 0.497 and 0.507, respectively. Type 4 was predominantly affected by DR, as indicated by S1_DR and ST_DR of 0.731 and 0.740, compared to S1_U and ST_U of 0.265 and 0.276. Type 5 presented an intermediate pattern, where DR still exerted a stronger effect, with S1_DR of 0.589 and ST_DR of 0.596, while S1_U and ST_U were 0.410 and 0.421. These results consistently reinforce that for non-external insulation types, WDR plays a more dominant role in influencing moisture content than thermal resistance.
Results from the sensitivity analysis indicated that for non-external insulation types, the impact of WDR on the moisture content of the outermost wall layer is comparable to, or even greater than, that of the U-value. Combined with the findings from the moisture content assessment and dryness rate assessment, it was observed that in the Hot Summer and Warm Winter Zone, internal and self-insulated wall assemblies not only exhibited higher moisture accumulation but also extremely low dryness rates, highlighting their limited hygrothermal resilience under such climatic conditions. The sensitivity analysis results are also consistent with the conclusions of the Spearman correlation analysis, which confirmed that in approximately 80% of climate–type combinations, WDR and wall moisture content were significantly positively correlated, particularly in hot and humid climates. Therefore, when non-external insulation types are selected in the early building design stage, equal consideration should be given to both WDR and U-value to reduce the risk of moisture damage.
Given these findings, WDR should be regarded as a critical factor alongside U-value during the design of building envelopes. If moisture-related risks are not adequately addressed at the design stage, they may lead to premature material deterioration, compromised insulation function, and increased energy consumption over time. Therefore, it is advisable to adopt climate-responsive strategies, such as the use of capillary-inactive materials, integration of ventilated rain screens, and improved detailing based on local weather conditions, to improve envelope durability and hygrothermal resilience.
The findings of this study provide a dataset to support climate-responsive design of building envelopes, thereby facilitating improvements in energy efficiency, operational cost reduction, and overall economic performance. In addition, the results showed an integration of machine learning and building physics simulations to predict drying performance and hygrothermal dynamics of wall assemblies under varying climatic conditions. Such integration will enhance the durability and adaptability of envelope types under the combined impacts of wind-driven rain and climate change, contributing to the development of technical pathways for achieving carbon peaking and carbon neutrality targets in the building sector.

4. Conclusions

The innovation of this study lies in the fact that current wall assembly designs in China primarily follow the Code for Thermal Design of Civil Building (GB 50176-2016) [36], which mainly considers temperature and heat transfer while insufficiently accounting for the impact of WDR. To bridge this gap, this study conducted comprehensive hygrothermal simulations of five typical wall insulation types across 21 representative cities in China’s four major thermal zones, systematically evaluating the hygrothermal effects of WDR on these assemblies, the associated mold growth risk, and further assessing the applicability of different wall assemblies in each thermal zone. The main conclusions are as follows.
Moisture accumulation in Type 1 (thin plastered EPS external insulation system) was found to be high, sensitive to annual WDR exposure, with this effect being particularly pronounced in the Cold Zone.
Type 2 (precast concrete sandwich insulation panel system), characterized by a high vapor diffusion resistance in the insulation layer, exhibited relatively higher overall moisture content in both the Severe Cold and Cold Zones.
Type 4 (autoclaved aerated concrete block self-insulation system) was more suitable for climates with smaller relative humidity fluctuations and lower annual WDR loads. However, it remained highly susceptible to WDR and thus more vulnerable to external moisture loads.
The following design guidelines for thermal zones are proposed to optimize both thermal performance and WDR considerations: In the Severe Cold Zone, Types 1, 2, and 3 exhibit consistent applicability for thermal performance requirements, with no significant dependency on WDR inclusion. For the Cold Zone, while Types 1, 2, and 3 are all viable when thermal performance is the sole criterion, Type 2 emerges as the superior choice when both thermal performance and WDR are simultaneously evaluated, outperforming Types 1 and 3 in integrated performance. In the Hot Summer and Cold Winter Zone, the applicability range expands to include Types 1–5 under thermal performance-only scenarios. However, when thermal performance and WDR are considered in combination, Types 2, 4, and 5 demonstrate enhanced suitability compared to Types 1 and 3, highlighting their balanced performance under dual constraints. For the Hot Summer and Warm Winter Zone, Types 4 and 5 are identified as applicable for thermal performance alone, yet Type 4 is recommended over Type 5 when both thermal performance and WDR are prioritized, reflecting its optimized adaptability to the region’s climatic characteristics.
China exhibits a clear north-to-south declining trend in dryness rate, with values of 100% in the Severe Cold Zone, 91.67% in the Cold Zone, 44% in the Hot Summer and Cold Winter Zone, and 30% in the Hot Summer and Warm Winter Zone. This gradient reflects the influence of regional climate on moisture dissipation within wall assemblies.
In the thermal design of building envelopes, annual WDR load should be considered of comparable importance to U-value, especially for non-external insulation types, as the total Sobol index of DR ranged from 0.507 to 0.740.
This study offers a reproducible framework for evaluating moisture behavior across a variety of wall assemblies and climate conditions. The findings provide actionable support for material selection and design decision-making in both new construction and retrofit applications. Nonetheless, several limitations should be acknowledged. The simulations were based on typical-year meteorological data, which may not fully capture interannual climatic variability. Furthermore, the modeling approach did not account for construction imperfections or material aging, and the results have yet to be validated through in situ measurements. Future research could extend the analysis to include multi-year climate scenarios, a broader range of insulation configurations, and experimental validation. Incorporating climate change projections and retrofit considerations would further improve the practical relevance and engineering value of hygrothermal design recommendations.
Declaration of generative AI and AI-assisted technologies in the writing process.
During the preparation of this work, the author(s) used Deepseek to improve the language and readability of the article. After using this tool/service, the author(s) reviewed and edited the content as needed and took full responsibility for the content of the publication.

Author Contributions

Conceptualization, L.H.; Methodology, L.H.; Software, M.L.; Validation, J.W.; Formal analysis, M.L.; Resources, J.W.; Writing—original draft, M.L.; Writing—review and editing, L.H.; Supervision, L.H.; Project administration, J.W.; Funding acquisition, J.W. All authors have read and agreed to the published version of the manuscript.

Funding

National Key Research and Development Program of China: 2022YFC3801600.

Data Availability Statement

The data used to support the findings of this study are available from the authors upon request.

Conflicts of Interest

Author Juan Wang was employed by the company Shanghai Research Institute of Building Sciences (China). The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest.

References

  1. Gholamalipour, P.; Ge, H.; Stathopoulos, T. Wind-driven rain (WDR) loading on building facades: A state-of-the-art review. Build. Environ. 2022, 221, 109314. [Google Scholar] [CrossRef]
  2. Mukherjee, S.; Biswas, N.; Roy, D.K.S. Interaction of open-top, short, cylindrical tank with wind-driven rain. Mater. Today Proc. 2023. [Google Scholar] [CrossRef]
  3. Van Den Bossche, N.; Van Linden, S. Modelling Rain Water Ingress in Hygrothermal Simulations. J. Phys. Conf. Ser. 2023, 2654, 012051. [Google Scholar] [CrossRef]
  4. Frost, A.; Wilson, L.; Orr, S.A.; Grau-Bove, J. Combining high-resolution 3D models with computational SPH for understanding WDR loads and run-off on heritage buildings. In Multiphysics and Multiscale Building Physics; Berardi, U., Ed.; Lecture Notes in Civil Engineering; Springer: Singapore, 2025; Volume 552, pp. 177–182. [Google Scholar] [CrossRef]
  5. Blocken, B.; Carmeliet, J. A review of wind-driven rain research in building science. J. Wind Eng. Ind. Aerodyn. 2004, 92, 1079–1130. [Google Scholar] [CrossRef]
  6. Liu, X.; Wu, B.; Guo, X.; Luo, N.; Du, L. Wind-driven rain catch characteristics of building complex facades. Huaxue Gongcheng/Chem. Eng. 2025, 53, 23–28,35. [Google Scholar] [CrossRef]
  7. Kubilay, A.; Derome, D.; Blocken, B.; Carmeliet, J. High-resolution field measurements of wind-driven rain on an array of low-rise cubic buildings. Build. Environ. 2014, 78, 1–13. [Google Scholar] [CrossRef]
  8. Pu, S.; Zhang, H. Assessment of Building Wind-driven Rain Exposure in China in the Future Climate of 2050. In Proceedings of the Building Simulation 2023: 18th Conference of IBPS, Shanghai, China, 4–6 September 2023. [Google Scholar] [CrossRef]
  9. Zhan, Q.; Xue, S.; Yin, S.; Lin, Z.; Zou, Y.; Xiao, Y. Hygrothermal resilience of typical lightweight steel-framed wall assemblies in hot-humid areas under future climate uncertainty. Energy Build. 2024, 321, 114625. [Google Scholar] [CrossRef]
  10. Pakkala, T.A.; Lahdensivu, J. Wind-driven rain load in Finland in present and future projected climates. J. Phys. Conf. Ser. 2023, 2654, 012012. [Google Scholar] [CrossRef]
  11. Choi, E.C.C. Determination of wind-driven-rain intensity on building faces. J. Wind. Eng. Ind. Aerodyn. 1994, 51, 55–69. [Google Scholar] [CrossRef]
  12. Moujalled, B.; Ouméziane, Y.A.; Moissette, S.; Bart, M.; Lanos, C.; Samri, D. Experimental and numerical evaluation of the hygrothermal performance of a hemp lime concrete building: A long term case study. Build. Environ. 2018, 136, 11–27. [Google Scholar] [CrossRef]
  13. Dang, X.; Vereecken, E.; Janssen, H.; Roels, S. Hygrothermal response of masonry facades with vapour-tight or capillary-active internal insulation under current and future climate scenarios. Built Herit. 2025, 9, 23. [Google Scholar] [CrossRef]
  14. Qian, T.; Zhang, H. Assessment of long-term and extreme exposure to wind-driven rain for buildings in various regions of China. Build. Environ. 2021, 189, 107524. [Google Scholar] [CrossRef]
  15. ISO 15927-3:2009; Hygrothermal Performance of Buildings—Calculation and Presentation of Climatic Data Part 3: Calculation of a Driving Rain Index for Vertical Surfaces from Hourly Wind and Rain Data. CEN: Brussels, Belgium, 2009.
  16. Choi, E.C.C. Simulation of wind-driven rain around a building. J. Wind. Eng. Ind. Aerodyn. 1993, 46–47, 721–729. [Google Scholar] [CrossRef]
  17. Blocken, B.; Carmeliet, J. Driving rain on building envelopes—I. Numerical estimation and full-scale experimental verification. J. Therm. Envel. Build. Sci. 2000, 24, 61–85. [Google Scholar] [CrossRef]
  18. Blocken, B.; Carmeliet, J. On the validity of the cosine projection in wind-driven rain calculations on buildings. Build. Environ. 2006, 41, 1182–1189. [Google Scholar] [CrossRef]
  19. Künzel, H.M. Simultaneous Heat and Moisture Transport in Building Components: One- and Two-Dimensional Calculation Using Simple Parameters; Fraunhofer IRB Verlag: Stuttgart, Germany, 1995. [Google Scholar]
  20. Yu, S.; Cui, Y.; Shao, Y.; Han, F. Simulation research on the effect of coupled heat and moisture transfer on the energy consumption and indoor environment of public buildings. Energies 2019, 12, 141. [Google Scholar] [CrossRef]
  21. Palani, H.; Khaleghi, H.; Salehi, P.; Karatas, A. Assessing hygrothermal performance in building walls engineered for extreme cold climate environments. Sustainability 2023, 15, 16597. [Google Scholar] [CrossRef]
  22. Nath, S.; Dewsbury, M.; Künzel, H.; Watson, P. Mould growth risks for a clay masonry veneer external wall system in a temperate climate. Atmosphere 2022, 13, 1755. [Google Scholar] [CrossRef]
  23. Almeida, R.M.S.F.; Barreira, E. Monte Carlo simulation to evaluate mould growth in walls: The effect of insulation, orientation, and finishing coating. Adv. Civ. Eng. 2018, 2018, 8532167. [Google Scholar] [CrossRef]
  24. Huang, Z.; Sun, Y.; Florian, M. Hygrothermal modeling and analysis of building envelopes in typical North American climate zones. J. Hunan Univ. 2019, 46, 130–140. (In Chinese) [Google Scholar] [CrossRef]
  25. Cannon, A.; Jeong, D.I.; Zhang, X.; Zwiers, F. Climate-Resilient Buildings and Core Public Infrastructure: An Assessment of the Impact of Climate Change on Climatic Design Data in Canada; Environment and Climate Change Canada: Gatineau, QC, Canada, 2020.
  26. Cornick, S.; Dalgliesh, W.A. Adapting rain data for hygrothermal models. Build. Environ. 2009, 44, 987–996. [Google Scholar] [CrossRef]
  27. Jeong, D.I.; Cannon, A.J. Projected changes to risk of wind-driven rain on buildings in Canada under +0.5 °C to +3.5 °C global warming above the recent period. Clim. Risk Manag. 2020, 30, 100261. [Google Scholar] [CrossRef]
  28. Hu, X.; Zhang, H.; Yu, H. Numerical simulation study on the hygrothermal performance of building exterior walls under dynamic wind-driven rain condition. Build. Simul. 2024, 17, 207–221. [Google Scholar] [CrossRef]
  29. Parracha, J.L.; Veiga, R.; Gomes, M.G.; Flores-Colen, I.; Nunes, L. Hygrothermal behaviour of external thermal insulation composite systems (ETICS) to withstand biological colonisation. J. Build. Eng. 2024, 86, 108932. [Google Scholar] [CrossRef]
  30. Ibrahim, M.; Wurtz, E.; Biwole, P.H.; Achard, P.; Sallee, H. Hygrothermal performance of exterior walls covered with aerogel-based insulating rendering. Energy Build. 2014, 84, 241–251. [Google Scholar] [CrossRef]
  31. Choi, E.C.C. Parameters affecting the intensity of wind-driven rain on the front face of a building. J. Wind. Eng. Ind. Aerodyn. 1994, 53, 1–17. [Google Scholar] [CrossRef]
  32. Bastien, D.; Winther-Gaasvig, M. Influence of driving rain and vapour diffusion on the hygrothermal performance of a hygroscopic and permeable building envelope. Energy 2018, 164, 288–297. [Google Scholar] [CrossRef]
  33. Hamid, A.A.; Wallentén, P. Hygrothermal assessment of internally added thermal insulation on external brick walls in Swedish multifamily buildings. Build. Environ. 2017, 123, 351–362. [Google Scholar] [CrossRef]
  34. Xian, G.; Qi, X.; Shi, J.; Tian, J.; Xiao, H.G. Toughened and self-healing carbon nanotube/epoxy resin composites modified with polycaprolactone filler for coatings, adhesives and FRP. J. Build. Eng. 2025, 111, 113207. [Google Scholar] [CrossRef]
  35. TenWolde, A. ASHRAE standard 160 P-Criteria for moisture control design analysis in buildings. ASHRAE Trans. 2008, 114, 167–169. [Google Scholar] [CrossRef]
  36. GB 50176-2016; Code for Thermal Design of Civil Building. China Architecture & Building Press: Beijing, China, 2016.
  37. Sawadogo, M.; Godin, A.; Duquesne, M.; Hamami, A.E.A.; Belarbi, R. A Review on Numerical Modeling of the Hygrothermal Behavior of Building Envelopes Incorporating Phase Change Materials. Buildings 2023, 13, 3086. [Google Scholar] [CrossRef]
  38. Chen, C.; Zhang, H.; Feng, C.; Xuan, Y.; Qian, T.; Xie, J. Analysis of wind-driven rain characteristics acting on building surfaces in Shanghai based on long-term measurements. J. Build. Eng. 2022, 45, 103572. [Google Scholar] [CrossRef]
  39. Chen, C.; Zhang, H.; Qian, T. Wind-driven rain study of buildings based on semi-empirical models. Build. Energy Effic. 2021, 49, 95–102. (In Chinese) [Google Scholar]
  40. Blocken, B.; Dezsö, G.; van Beeck, J.; Carmeliet, J. Comparison of calculation models for wind-driven rain deposition on building facades. Atmos. Environ. 2010, 44, 1714–1725. [Google Scholar] [CrossRef]
  41. Ge, H.; Chiu, V.; Stathopoulos, T.; Souri, F. Improved assessment of wind-driven rain on building façade based on ISO standard with high-resolution on-site weather data. J. Wind. Eng. Ind. Aerodyn. 2018, 176, 183–196. [Google Scholar] [CrossRef]
  42. Kim, S.; Zirkelbach, D.; Künzel, H.M. Wind-driven rain exposure on building envelopes taking into account frequency distribution and correlation with different wall orientations. Build. Environ. 2022, 209, 108665. [Google Scholar] [CrossRef]
  43. Dang, X.; Vereecken, E.; Janssen, H.; Roels, S. Impact of semi-empirical methods implemented in heat, air, and moisture (HAM) models on predicted wind-driven rain (WDR) loads and hygrothermal responses. Build. Environ. 2024, 262, 111770. [Google Scholar] [CrossRef]
  44. Hu, X.; Zhang, H.; Qian, T.; Feng, C. Modeling of wind-driven rain absorption ratio of building exterior finishing materials based on field measurements. Front. Archit. Res. 2024, 13, 1145–1157. [Google Scholar] [CrossRef]
  45. Pérez-Bella, J.M.; Domínguez-Hernández, J.; Cano-Suñén, E.; Alonso-Martínez, M.; del Coz-Díaz, J.J. Equivalence between the methods established by ISO 15927-3 to determine wind-driven rain exposure: Reanalysis and improvement proposal. Build. Environ. 2020, 174, 106777. [Google Scholar] [CrossRef]
  46. Delgado, J.; Ramos, N.; Barreira, E.; Freitas, V. A critical review of hygrothermal models used in porous building materials. J. Porous Media 2010, 13, 221–234. [Google Scholar] [CrossRef]
  47. Hersbach, H.; Bell, B.; Berrisford, P.; Biavati, G.; Horányi, A.; Sabater, J.M.; Nicolas, J.; Peubey, C.; Radu, R.; Rozum, I.; et al. ERA5 Hourly Data on Single Levels from 1959 to Present; Copernicus Climate Change Service (C3S) Climate Data Store (CDS): Reading, UK, 2018. [Google Scholar] [CrossRef]
  48. Komutunga, E.; Oratungye, J.K.; Ahumuza, E.; Akodi, D.; Agaba, C. New procedure in developing adjustment algorithm for harmonizing historical climate data sets. J. Dyn. Agric. Res. 2015, 2, 21–30. [Google Scholar]
  49. DIN EN 15026; Hygrothermal Performance of Building Components and Building Elements—Assessment of Moisture Transfer by Numerical Simulation. Beuth Verlag: Berlin, Germany, 2007.
  50. GB50736-2012; Design Code for Heating Ventilation and Air Conditioning of Civil Buildings. Construction Science and Technology: Beijing, China, 2015; pp. 31–32. (In Chinese)
  51. Kong, F.; Guo, X.; Xie, Y.; Liu, Q.; Chen, X. Influence of wall material layers and arrangement on drying process of new energy-saving buildings. J. Build. Energy 2017, 45, 9. (In Chinese) [Google Scholar] [CrossRef]
  52. GB 55015-2021; General Code for Energy Efficiency and Renewable Energy Application in Buildings. China Architecture & Building Press: Beijing, China, 2021. (In Chinese)
  53. Fakultät, D.; Sedlbauer, D.-P.K. Vorhersage von Schimmelpilzbildung auf und in Bauteilen. Ph.D. Thesis, University of Stuttgart, Stuttgart, Germany, 2001. [Google Scholar]
  54. Tihomirovs, P.; Korjakins, A. Porous Ceramics Produced from Glass and Clay. J. Sustain. Archit. Civil. Eng. 2022, 30, 183–191. [Google Scholar] [CrossRef]
  55. Adewoyin, O.; Adesina, A.; Das, S. Performance Evaluation of Thermal-Efficient Lightweight Mortars Made with Expanded Glass as Aggregates. J. Mater. Civil. Eng. 2022, 34, 04022068. [Google Scholar] [CrossRef]
  56. Zhu, Q.Y.; Xie, M.H.; Yang, J.; Li, Y. Investigation of the 3D model of coupled heat and liquid moisture transfer in hygroscopic porous fibrous media. Int. J. Heat Mass Transf. 2010, 53, 3914–3927. [Google Scholar] [CrossRef]
  57. Kočí, V.; Vejmelková, E.; Čáchová, M.; Koňáková, D.; Keppert, M.; Maděra, J.; Černý, R. Effect of Moisture Content on Thermal Properties of Porous Building Materials. Int. J. Thermophys. 2017, 38, 28. [Google Scholar] [CrossRef]
  58. Abuku, M.; Janssen, H.; Roels, S. Impact of wind-driven rain on historic brick wall buildings in a moderately cold and humid climate: Numerical analyses of mould growth risk, indoor climate and energy consumption. Energy Build. 2009, 41, 101–110. [Google Scholar] [CrossRef]
  59. Künzel, H.M. Long-Term Thermal Performance of Insulations Under Moisture Loads; Springer International Publishing: Cham, Switzerland, 2022; pp. 37–53. [Google Scholar] [CrossRef]
  60. Breiman, L. Random Forests. Mach. Learn. 2001, 45, 5–32. [Google Scholar] [CrossRef]
  61. Saltelli, A.; Annoni, P.; Azzini, I.; Campolongo, F.; Ratto, M.; Tarantola, S. Variance based sensitivity analysis of model output. Design and estimator for the total sensitivity index. Comput. Phys. Commun. 2010, 181, 259–270. [Google Scholar] [CrossRef]
  62. Yu, H.; Zhang, H. A new method for predicting wind-driven rain catch ratios on building facades in urban residential areas using machine learning models. Build. Environ. 2025, 270, 112467. [Google Scholar] [CrossRef]
  63. Herman, J.; Usher, W. SALib: An open-source Python library for Sensitivity Analysis. J. Open Source Softw. 2017, 2, 97. [Google Scholar] [CrossRef]
  64. Guo, X.; He, S.; Wu, Y.; Liu, Y.; Liu, X. Study on the Optimization Wall Structure in Hot and Humid Climate Region Based on Analytic Hierarchy Process. In Proceedings of the International Conference on Sustainable Development, Virtual, 21–22 September 2020; pp. 211–219. [Google Scholar] [CrossRef]
  65. Coelho, G.B.A.; Henriques, F.M.A. Influence of driving rain on the hygrothermal behavior of solid brick walls. J. Build. Eng. 2016, 7, 121–132. [Google Scholar] [CrossRef]
Figure 1. Information on selected simulation locations.
Figure 1. Information on selected simulation locations.
Buildings 15 04198 g001
Figure 2. Comparison between simulated data and validated data [43] of water content.
Figure 2. Comparison between simulated data and validated data [43] of water content.
Buildings 15 04198 g002
Figure 3. Surrogate model performance evaluation plot.
Figure 3. Surrogate model performance evaluation plot.
Buildings 15 04198 g003
Figure 4. Temporal variation of overall moisture content in wall assemblies in the Severe Cold Zone.
Figure 4. Temporal variation of overall moisture content in wall assemblies in the Severe Cold Zone.
Buildings 15 04198 g004
Figure 5. Temporal variation of overall moisture content in wall assemblies in the Cold Zone.
Figure 5. Temporal variation of overall moisture content in wall assemblies in the Cold Zone.
Buildings 15 04198 g005
Figure 6. Temporal variation of overall moisture content in wall assemblies in the Hot Summer and Cold Winter Zone.
Figure 6. Temporal variation of overall moisture content in wall assemblies in the Hot Summer and Cold Winter Zone.
Buildings 15 04198 g006
Figure 7. Temporal variation of overall moisture content in wall assemblies in the Hot Summer and Warm Winter Zone.
Figure 7. Temporal variation of overall moisture content in wall assemblies in the Hot Summer and Warm Winter Zone.
Buildings 15 04198 g007
Figure 8. Spearman correlation between WDR load and moisture metrics. Note: Asterisks denote statistical significance levels: “*” for p < 0.05, “**” for p < 0.01, and “***” for p < 0.001.
Figure 8. Spearman correlation between WDR load and moisture metrics. Note: Asterisks denote statistical significance levels: “*” for p < 0.05, “**” for p < 0.01, and “***” for p < 0.001.
Buildings 15 04198 g008
Figure 9. Sobol sensitivity analysis results.
Figure 9. Sobol sensitivity analysis results.
Buildings 15 04198 g009
Table 1. Details of wall assemblies.
Table 1. Details of wall assemblies.
U-Value [W/(m2·K)]TypeLayer Thickness (mm) from Exterior to InteriorAssembly Diagram
Exterior Interior
ABCDEFGHIJKLM
0.411010-91--1200-----Buildings 15 04198 i001
2--60--78-200----10Buildings 15 04198 i002
31010--101-1200-----Buildings 15 04198 i003
0.4511010-80--1200-----Buildings 15 04198 i004
2--60--68-200----10Buildings 15 04198 i005
31010--88-1200-----Buildings 15 04198 i006
1.211010-23--1200-----Buildings 15 04198 i007
2--60--30-200----10Buildings 15 04198 i008
31010--28-1200-----Buildings 15 04198 i009
41020-------115-20-Buildings 15 04198 i010
510------2001-18-10Buildings 15 04198 i011
1.541020-------86-20-Buildings 15 04198 i012
510------2001-18-10Buildings 15 04198 i013
Note: A, the Coating/Finishing Layer; B, the Base Coat with Adhesive Mortar; C, the Cast-in-Place Concrete Wall; D, the EPS Board; E, the Rock Wool Board; F, the XPS Board; G, the Adhesive; H, the Cast-in-Place Concrete Wall; I, the Adhesive; J, the Autoclaved aerated concrete block (AAC) Block; K, the EPS Composite Panel; L, the Cement Plaster Mortar; and M, the Exterior Coating Finish.
Table 2. Thermophysical parameters used in the simulation.
Table 2. Thermophysical parameters used in the simulation.
MaterialThickness d/mmInitial Moisture Content (kg/m3)Porosity η/(m3/m3)Thermal Conductivity λ/[W/(m·K)]Density/(kg/m3)Water Vapor Diffusion Resistance FactorSpecific heat Capacity Cp/(J/kg)
Concrete Wall60/2001100.1801.74220092.00850
Adhesive1.000.0010.2125075001400
EPS Board91/80/23/18/1300.9500.0 415301500
The Base Coat with Adhesive Mortar20/15/102100.2800.93188050850
Coating102400.2800.7178515850
The Rock Wool Board101/88/2800.9670.041881.3850
The XPS Board78/68/3000.9500.035401001500
The AAC Block115/862000.7200.186008.3850
Table 3. Results of Kruskal–Wallis H Test.
Table 3. Results of Kruskal–Wallis H Test.
Thermal Zone LocationType 1 (N = 8760)Type 2 (N = 8760)Type 3 (N = 8760)Type 4 (N = 8760)Type 5 (N = 8760)H-Valuep-Value
Severe Cold ZoneQumalai5.23 (5.01,6.04)9.01 (8.37,11.44)5.12 (4.88,5.93) 17,640.97<0.001
Seda6.41 (6.01,7.29)10.68 (9.65,12.96)6.34 (5.87,7.15) 17,431.02<0.001
Yushu5.89 (5.58,6.32)9.63 (9.21,10.15)5.75 (5.40,6.20) 17,809.00<0.001
Erlianhaote5.45 (5.25,5.61)9.25 (8.30,9.90)5.38 (5.14,5.58) 17,167.94<0.001
Datong6.46 (6.17,6.88)10.73 (10.24,12.50)6.40 (6.08,6.84) 17,302.30<0.001
Ganzi6.35 (6.10,7.06)9.99 (9.75,11.91)6.22 (5.93,6.94) 17,562.50<0.001
Cold ZoneTaiyuan9.41 (8.88,10.12) b14.94 (14.14,16.53)9.47 (8.88,10.15) 17,155.19<0.001
Daofu7.28 (6.86,7.86)11.96 (11.32,12.96)7.28 (6.84,7.94) 17,030.30<0.001
Shijiazhuang7.10 (6.62,8.01)10.85 (10.08,13.10)7.04 (6.51,7.94) 17,548.02<0.001
Xuzhou8.10 (7.63,8.65)13.24 (12.11,13.24)8.14 (7.63,8.75) 16,878.77<0.001
Qingdao8.67 (8.48,9.26)14.04 (13.48,14.79)8.67 (8.47,9.32) 16,954.12<0.001
Hot Summer and Cold Winter ZoneHefei8.90 (8.60,9.36)15.15 (14.18,15.92)9.12 (8.71,9.74)24.13 (16.74,33.38)27.11 (25.69,30.55)34,871.45<0.001
Nanjing9.48 (9.05,9.96)15.57 (14.88,16.21)9.66 (9.20,10.34)23.17 (17.49,33.49)27.70 (26.53,30.02)36,815.25<0.001
Yibin9.11 (8.89,9.42)14.34 (13.33,16.08)9.20 (8.95,9.57)21.26 (14.13,29.71)27.30 (23.91,32.05)34,541.31<0.001
Guangchang9.01 (8.88,9.46)14.81 (13.34,15.79)9.30 (9.14,9.70)14.24 (9.68,25.12)25.03 (23.55,28.79)29,784.00<0.001
Fuding9.84 (9.71,10.21) a15.64 (14.71,16.47)10.01 (9.75,10.56)10.68 (7.27,13.76)27.30 (24.69,29.75)31,316.61<0.001
Hot Summer and Warm Winter ZoneFuzhou 2.95 (1.80,4.43)20.36 (19.24,22.72)13,139.25<0.001
Fogang 11.90 (6.91,25.74)26.12 (24.20,32.71)4780.91<0.001
Yuanmou 1.18 (0.96,1.62)9.55 (8.58,10.39)13,139.25<0.001
Guangzhou 16.28 (9.02,31.91)26.94 (24.45,33.48)2283.63<0.001
Shantou 11.94 (5.96,18.03)25.12 (22.21,30.11)6368.46<0.001
Note: (a) The adjusted significance level compared with the Type 4 is 0.289, which exceeds 0.05, indicating no statistically significant difference. (b) The Bonferroni-corrected p-value for comparison with Type 3 is 0.865, also above 0.05, indicating no statistically significant difference.
Table 4. Drying performance of each case.
Table 4. Drying performance of each case.
Thermal ZoneLocationTypeDrying StatusInitial Moisture Content (kg/m3)Final Moisture Content (kg/m3)Dryness rate (%)Mold Growth Risk
Severe Cold Zone (100%)Datong1Y11.0846246.252753743.59%
2Y13.98474710.40666125.59%
3Y11.0492356.209400243.80%
Erlianhaote1Y11.0846245.291942652.26%
2Y13.9847479.157707234.52%
3Y11.0492355.25515752.44%
Qumalai1Y11.0846244.996687954.92%Moderate Risk
2Y13.9847478.685505937.89%
3Y11.0492354.920570455.47%
Seda1Y11.0846246.215182343.93%
2Y13.98474710.33016426.13%
3Y11.0492356.126136344.56%
Yushu1Y11.0846245.687743748.69%
2Y13.9847479.400160832.78%
3Y11.0492355.568396649.60%
Ganzi1Y11.084626.3196142.99%
2Y13.9847510.3664125.87%
3Y11.049246.2178743.73%
Cold Zone (93.33%)Xuzhou1Y11.0649638.645397221.87%Moderate Risk
2N13.96687314.119068-Moderate Risk
3Y11.0328558.67617821.36%
Daofu1Y11.0649636.8058238.49%
2Y13.96687310.27111626.46%
3Y11.0328556.740421338.91%
Shijiazhuang1Y11.0649637.727256330.16%
2Y13.96687312.6234819.62%
3Y11.0328557.782804529.46%
Taiyuan1Y11.0649636.959822737.10%
2Y13.96687311.80292215.49%
3Y11.0328556.99841236.57%
Qingdao1Y11.0649638.84775820.04%
2Y11.0328558.87298419.58%
3Y13.96687313.8211831.04%
Hot Summer and Cold Winter Zone (44%)Fuding1Y10.9630849.507788713.27%Moderate Risk
2Y13.89895313.7208041.28%
3Y10.9572559.554570212.80%Elevated Risk
4N2.3223935.3343225-Moderate Risk
5N10.79550722.847885-
Guangchang1Y10.9630848.797505419.75%Moderate Risk
2Y13.89895312.7608558.19%
3Y10.9572558.968983718.15%Moderate Risk
4N2.32239311.424164-Elevated Risk
5N10.79550722.672428-
Hefei1Y10.9630848.540231722.10%Moderate Risk
2N13.89895315.907869-
3N10.95725526.012888-Moderate Risk
4N2.3223939.6453981-High Risk
5N10.79550722.85907-
Nanjing1Y10.9630848.899057418.83%Moderate Risk
2N13.89895316.001381-
3Y10.9572558.973453518.10%Moderate Risk
4N2.32239321.296913-High Risk
5N10.79550724.911299-
Yibin1Y10.9630848.821979519.53%
2Y13.89895313.6322251.92%
3Y10.9572558.904540118.73%
4N2.32239324.278095-High Risk
5N10.79550735.455517-
Hot Summer and Warm Winter Zone (30%)Fogang4N2.01209287.4825592-Elevated Risk
5N10.78657123.154131-
Fuzhou4Y2.01209281.59677720.64%
5N10.78657119.076666-
Guangzhou4N2.012092810.945501-Elevated Risk
5N10.78657123.292662-
Shantou4N2.01209289.2919588-Moderate Risk
5N10.78657122.933239-
Yuanmou4Y2.01209281.062809147.18%
5Y10.7865719.651469210.52%
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Liu, M.; Huang, L.; Wang, J. Hygrothermal Performance of Exterior Wall Assemblies Under Wind-Driven Rain Across China’s Thermal Zones. Buildings 2025, 15, 4198. https://doi.org/10.3390/buildings15224198

AMA Style

Liu M, Huang L, Wang J. Hygrothermal Performance of Exterior Wall Assemblies Under Wind-Driven Rain Across China’s Thermal Zones. Buildings. 2025; 15(22):4198. https://doi.org/10.3390/buildings15224198

Chicago/Turabian Style

Liu, Meirong, Lingjiang Huang, and Juan Wang. 2025. "Hygrothermal Performance of Exterior Wall Assemblies Under Wind-Driven Rain Across China’s Thermal Zones" Buildings 15, no. 22: 4198. https://doi.org/10.3390/buildings15224198

APA Style

Liu, M., Huang, L., & Wang, J. (2025). Hygrothermal Performance of Exterior Wall Assemblies Under Wind-Driven Rain Across China’s Thermal Zones. Buildings, 15(22), 4198. https://doi.org/10.3390/buildings15224198

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Article metric data becomes available approximately 24 hours after publication online.
Back to TopTop