Experimental Study and FEM Analysis on the Strengthening of Masonry Brick Walls Using Expanded Steel Plates and Shotcrete with and Without Glass Fiber Reinforcement
Abstract
1. Introduction
2. Materials and Methods
2.1. Expanded Steel Sheets
2.2. Tie Rod
2.3. Brick
2.4. Mortar
2.5. Shotcrete
3. Experimental Setup
4. Experimental Observations and Discussion
5. Finite Element Modeling Analysis
6. Conclusions
- In comparisons among MW, MWS, and MWSG specimens, the MWS specimen showed a 30% increase in load-carrying capacity, while the MWSG specimen achieved a 70% increase compared to MW. Additionally, rigidity improved by 60% in MWS and 90% in MWSG; ductility increased by 20% and 40%, respectively; and energy absorption capacity rose by 40% and approximately 1.5 times. These findings clearly highlight the significant positive effects of sprayed concrete and glass fiber-reinforced sprayed concrete on the mechanical performance of masonry walls.
- Comparison of MWS 2-200, MWS 3-150, and MWS 3-400 test specimens with the MWSG series specimens revealed that glass fiber material incorporated into shotcrete significantly improved the performance of masonry walls. Load-bearing capacity increased by 16% to 25%, while stiffness decreased by 20% to 27%. Ductility increased by 2% to 33%, and energy dissipation capacity increased significantly by 15% to 33%.
- When MWS and MWS 3-100, MWS 3-150, MWS 3-200, and MWS 3-400 specimens were examined, it was observed that the use of tie rods had positive effects on the carrying capacity, rigidity, ductility, and energy absorption capacity of masonry walls. With the addition of tie rods, an increase from 58% to 190% was achieved in the carrying capacity, and this increase rate increased significantly with the decrease in the tie-rod spacing. Similarly, an increase from 48% to 108% was recorded in rigidity and from 20% to 82% in ductility. In addition, increasing the tie-rod frequency increased the energy absorption capacity from 1.06 times to 2.71 times.
- When comparing MWSG 1.5-150 and MWSG 3-150 wall specimens, increasing slab thickness results in approximately a 22% increase in bearing capacity, an 18% increase in stiffness, a 10% increase in ductility, and a 24% increase in energy absorption capacity.
- The MW specimen exhibited brittle behavior after the vertical main crack during the test, exhibiting sudden strength loss and limited displacement. In contrast, all of the strengthened walls exhibited a ductile behavior, maintaining their integrity up to maximum displacement and maintaining their load-carrying capacity without experiencing sudden load loss.
- It has been observed that the addition of glass fiber to shotcrete causes an increase in the carrying capacity of masonry brick walls by 16–25%, an increase in their ductility by 2–33%, an increase in their energy absorption capacity by 15–33%, and a decrease in their stiffness by 20–27%.
- Comparison of experimental (EXP) and finite element method (FEM) results showed small differences in load capacity, ranging from 0.2% (MW) to 8.9% (MWS). These findings confirm that FEM accurately predicts the load capacity of masonry walls and aligns well with experimental data, proving to be a reliable and effective evaluation method.
Author Contributions
Funding
Data Availability Statement
Acknowledgments
Conflicts of Interest
References
- Anania, L.; D’Agata, G.; Giaquinta, C.; Badalà, A. Out of plane behavior of calcareous masonry panels strengthened by CFRP. APCBEE Procedia 2014, 9, 401–406. [Google Scholar] [CrossRef]
- Calò, S.; Cascardi, A.; Aiello, M.A. Unified design-oriented model for the shear strengthening of masonry walls with Inorganic Mortar Composite systems. Eng. Struct. 2025, 336, 120394. [Google Scholar] [CrossRef]
- Saghafi, M.H.; Safakhah, S.; Kheyroddin, A.; Mohammadi, M. In-plane shear behavior of FRP strengthened masonry walls. APCBEE Procedia 2014, 9, 264–268. [Google Scholar] [CrossRef]
- Barsotti, R.; Bennati, S. Assessment of the in-plane shear capacity of masonry panels by elementary mechanical models. Eng. Struct. 2018, 175, 678–689. [Google Scholar] [CrossRef]
- Cumhur, A.; Altundal, A.; Kalkan, I.; Aykac, S. Behaviour of brick infill walls strengthened with expanded steel plates. Bull. Earthq. Eng. 2016, 14, 3231–3258. [Google Scholar] [CrossRef]
- Aykaç, B.; Özbek, E.; Babayani, R.; Baran, M.; Aykaç, S. Seismic strengthening of infill walls with perforated steel plates. Eng. Struct. 2017, 152, 168–179. [Google Scholar] [CrossRef]
- Özbek, E.; Aykac, B.; Aykac, S. The effects of brick walls strengthened with perforated steel plates on frame behavior. Eng. Struct. 2019, 189, 62–76. [Google Scholar] [CrossRef]
- Kalali, A.; Kabir, M.Z. Experimental response of double-wythe masonry panels strengthened with glass fiber reinforced polymers subjected to diagonal compression tests. Eng. Struct. 2012, 39, 24–37. [Google Scholar] [CrossRef]
- Sandoval, C.; Serpell, R.; Araya-Letelier, G.; Calderón, S. Shear behavior of single-and triple-thickness masonry panels strengthened by bed-joint structural repointing. Constr. Build. Mater. 2021, 286, 122925. [Google Scholar] [CrossRef]
- Yao, X.; Liang, B.; Zhang, H.; Zhang, Z.; He, Z. Typical brick masonry walls reinforced with high-strength mortar and steel bars in the horizontal joints. Adv. Struct. Eng. 2021, 24, 2767–2779. [Google Scholar] [CrossRef]
- Mazzotti, C.; Ferracuti, B.; Bellini, A. Experimental bond tests on masonry panels strengthened by FRP. Compos. Part B Eng. 2015, 80, 223–237. [Google Scholar] [CrossRef]
- Ferretti, E. A new Proposal for the Interpretation of the Diagonal Compression Test on Masonry Wallettes: The Identification of Young’s Modulus, Poisson’s Ratio, and Modulus of Rigidity. Buildings 2023, 14, 104. [Google Scholar] [CrossRef]
- Lim, W.Y. Failure mode dependent shear strength of unreinforced concrete brick masonry wall panels. Constr. Build. Mater. 2024, 414, 134976. [Google Scholar] [CrossRef]
- D’Altri, A.M.; de Miranda, S.; Castellazzi, G.; Sarhosis, V. A 3D detailed micro-model for the in-plane and out-of-plane numerical analysis of masonry panels. Comput. Struct. 2018, 206, 18–30. [Google Scholar] [CrossRef]
- Alecci, V.; Barducci, S.; D’Ambrisi, A.; De Stefano, M.; Focacci, F.; Luciano, R.; Penna, R. Shear capacity of masonry panels repaired with composite materials: Experimental and analytical investigations. Compos. Part B Eng. 2019, 171, 61–69. [Google Scholar] [CrossRef]
- Marcari, G.; Basili, M.; Vestroni, F. Experimental investigation of tuff masonry panels reinforced with surface bonded basalt textile-reinforced mortar. Compos. Part B Eng. 2017, 108, 131–142. [Google Scholar] [CrossRef]
- Sandoval, O.J.; Takeuchi, C.; Carrillo, J.; Barahona, B. Performance of unreinforced masonry panels strengthened with mortar overlays reinforced with welded wire mesh and transverse connectors. Constr. Build. Mater. 2021, 267, 121054. [Google Scholar] [CrossRef]
- Casolo, S.; Biolzi, L.; Carvelli, V.; Barbieri, G. Testing masonry blockwork panels for orthotropic shear strength. Constr. Build. Mater. 2019, 214, 74–92. [Google Scholar] [CrossRef]
- Autiero, F.; De Martino, G.; Di Ludovico, M.; Prota, A. Mechanical performance of full-scale Pompeii-like masonry panels. Constr. Build. Mater. 2020, 251, 118964. [Google Scholar] [CrossRef]
- Can, Ö. Investigation of seismic performance of in-plane aligned masonry panels strengthened with Carbon Fiber Reinforced Polymer. Constr. Build. Mater. 2018, 186, 854–862. [Google Scholar] [CrossRef]
- Vailati, M.; Mercuri, M.; Gregori, A. One-head masonry panels reinforced with industrial-waste fiber reinforced mortar: Investigating the effect of bed joints and coating reinforcement in the diagonal compressive behavior. Structures 2024, 63, 106474. [Google Scholar] [CrossRef]
- Mercuri, M.; Vailati, M.; Gregori, A. Two-heads brick masonry walls strengthened by basalt and glass chopped fiber mortar: Effect of bed joints and coating reinforcements. Structures 2024, 64, 106530. [Google Scholar] [CrossRef]
- Milosevic, J.; Lopes, M.; Gago, A.S.; Bento, R. Testing and modeling the diagonal tension strength of rubble stone masonry panels. Eng. Struct. 2013, 52, 581–591. [Google Scholar] [CrossRef]
- Shamim, S.; Ahmad, S.; Khan, R.A. Numerical study on dynamic response of hollow and cavity type clay brick masonry infill panels subjected to blast loading. Eng. Fail. Anal. 2023, 146, 107104. [Google Scholar] [CrossRef]
- Betti, M.; Galano, L. Shear strength of rubble stone-and-brick masonry panels. A new proposal for the interpretation of Sheppard test results. Constr. Build. Mater. 2021, 279, 121925. [Google Scholar] [CrossRef]
- D’Altri, A.M.; Carloni, C.; de Miranda, S.; Castellazzi, G. Numerical modeling of FRP strips bonded to a masonry substrate. Compos. Struct. 2018, 200, 420–433. [Google Scholar] [CrossRef]
- Abdulsalam, B.; Ali, A.H.; ElSafty, A.; Elshafey, N. Behavior of GFRP strengthening masonry walls using glass fiber composite anchors. Structures 2021, 29, 1352–1361. [Google Scholar] [CrossRef]
- Khan, H.A.; Nanda, R.P.; Das, D. In-plane strength of masonry panel strengthened with geosynthetic. Constr. Build. Mater. 2017, 156, 351–361. [Google Scholar] [CrossRef]
- Kafodya, I.; Okonta, F.; Kloukinas, P. Role of fiber inclusion in adobe masonry construction. J. Build. Eng. 2019, 26, 100904. [Google Scholar] [CrossRef]
- Wang, X.; Lam, C.C.; Iu, V.P. Comparison of different types of TRM composites for strengthening masonry panels. Constr. Build. Mater. 2019, 219, 184–194. [Google Scholar] [CrossRef]
- Sandoli, A.; Musella, C.; Lignola, G.P.; Calderoni, B.; Prota, A. Spandrel panels in masonry buildings: Effectiveness of the diagonal strut model within the equivalent frame model. Structures 2020, 27, 879–893. [Google Scholar] [CrossRef]
- Nie, Y.; Sheikh, A.; Griffith, M.; Visintin, P. A damage-plasticity based interface model for simulating in-plane/out-of-plane response of masonry structural panels. Comput. Struct. 2022, 260, 106721. [Google Scholar] [CrossRef]
- Grillanda, N.; Chiozzi, A.; Milani, G.; Tralli, A. Tilting plane tests for the ultimate shear capacity evaluation of perforated dry joint masonry panels. Part II: Numerical analyses. Eng. Struct. 2021, 228, 111460. [Google Scholar] [CrossRef]
- Luo, X.; Li, Y.; Yang, Y.; Pirsaheb, H. A simplified micro-model based on discrete elements and elastic bodies for non-linear static analysis of in-plane loaded masonry panels. Structures 2023, 58, 105383. [Google Scholar] [CrossRef]
- Xia, F.; Zhao, K.; Zhao, J.; Cui, X. Experimental Study on the Seismic Performance of Brick Walls Strengthened by Small-Spaced Reinforced-Concrete–Masonry Composite Columns. Buildings 2024, 14, 184. [Google Scholar] [CrossRef]
- Huang, D.; Albareda, A.; Pons, O. Experimental and Numerical Study on Unreinforced Brick Masonry Walls Retrofitted with Sprayed Mortar under Uniaxial Compression. Buildings 2023, 13, 122. [Google Scholar] [CrossRef]
- Joyklad, P.; Waqas, H.A.; Hafeez, A.; Ali, N.; Ejaz, A.; Hussain, Q.; Khan, K.; Sangthongtong, A.; Saingam, P. Experimental Investigations of Cement Clay Interlocking Brick Masonry Structures Strengthened with CFRP and Cement-Sand Mortar. Infrastructures 2023, 8, 59. [Google Scholar] [CrossRef]
- Thomoglou, A.K.; Jagadesh, P.; Voutetaki, M.E. Review of Out-of-Plane Strengthening Techniques of Unreinforced Masonry Walls. Fibers 2023, 11, 78. [Google Scholar] [CrossRef]
- Latifi, R.; Hadzima-Nyarko, M.; Radu, D.; Rouhi, R. A Brief Overview on Crack Patterns, Repair and Strengthening of Historical Masonry Structures. Materials 2023, 16, 1882. [Google Scholar] [CrossRef]
- ASTM, E.519-10; Standard Test Method for Diagonal Tension (Shear) in Masonry Assemblages. American Society for Testing and Materials: West Conshohocken, PA, USA, 2010.
- ASTM E8/E8M-16a; Standard Test Methods for Tension Testing of Metallic Materials. American Society for Testing and Materials: West Conshohocken, PA, USA, 2016.
- ASTM-E-519-07; Standard Test Method for Diagonal Tension (Shear) in Masonry Assemblages. American Society for Testing and Materials: West Conshohocken, PA, USA, 2007.
- ASTM. E 519-02; Standard Test Method for Diagonal Tension (Shear) in Masonry Assemblages. American Society for Testing and Materials: West Conshohocken, PA, USA, 2002.
- EN.1052-1:1998; Methods of Test for Masonry-Part 1: Determination of Compressive Strength. Comité Européen de Normalisation: Brussels, Belgium, 1998.
- EN 998-2:2010; Specification for Mortar for Masonry—Part 2: Masonry Mortar. Comité Européen de Normalisation: Brussels, Belgium, 2010.
- EN.197-1:2000; Cement. Composition, Specifications and Conformity Criteria for Common Cements. Comité Européen de Normalisation: Brussels, Belgium, 2000.
- EN.206-1:2000; Concrete, Specification, Performance, Production and Conformity. Comité Européen de Normalisation: Brussels, Belgium, 2001.
- Valente, M.; Brandonisio, G.; Milani, G.; Luca, A.D. Seismic response evaluation of ten tuff masonry churches with basilica plan through advanced numerical simulations. Int. J. Mason. Res. Innov. 2020, 5, 1–46. [Google Scholar] [CrossRef]
- Khan, I.; Gul, A.; Shahzada, K.; Khan, N.A.; Rehman, F.U.; Samiullah, Q.; Khattak, M.A. Computational seismic analysis of dry-stack block masonry wall. Civ. Eng. J. 2021, 7, 488–501. [Google Scholar] [CrossRef]
- Valente, M. Seismic behavior and damage assessment of two historical fortified masonry palaces with corner towers. Eng. Fail. Anal. 2022, 134, 106003. [Google Scholar] [CrossRef]
- Mathew, A.A.; Saibabu, S.; Mohan, V.; Varkey, D. Analysis of strains in Brick Masonry Prism using ABAQUS. In Proceedings of the SECON 2020: Structural Engineering and Construction Management 4, Angamaly, India, 14–15 May 2021; Springer International Publishing: Cham, Switzerland, 2021; pp. 883–897. [Google Scholar] [CrossRef]
- Akrami, A.S. Experimental Study for Improving the Behavior of The Masonry Brick Walls With The Diagonal Load Effect. Master’s Thesis, Sakarya University, Sakarya, Türkiye, 2020. [Google Scholar]
- Rasuly, A. Reinforced Masonry Brick Walls with Extended Steel Plate and Glass Fiber Added Spray Concrete Application. Master’s Thesis, Sakarya University, Sakarya, Türkiye, 2020. [Google Scholar]
Specimen | Plate Thickness (mm) | Anchor Spacing (mm) | Number of Tie Rods | |
MW | - | - | - | |
MWS | - | - | - | |
MWSG | - | - | - | |
MWS 2-200 | 2.0 | 200 | 25 | |
MWS 3-400 | 3.0 | 400 | 9 | |
MWS 3-200 | 3.0 | 200 | 25 | |
MWS 3-150 | 3.0 | 150 | 49 | |
MWS 3-100 | 3.0 | 100 | 100 | |
MWSG 1.5-150 | 1.5 | 150 | 49 | |
MWSG 2-150 | 2.0 | 150 | 49 | |
MWSG 2-200 | 2.0 | 200 | 25 | |
MWSG 3-150 | 3.0 | 150 | 49 | |
MWSG 3-400 | 3.0 | 400 | 9 |
Max Force (kN) | Max Stress (MPa) | Max Elongation (mm) | Max Time (sec) | |
306.2 | 722.1 | 23.5 | 352.5 | |
314.1 | 740.5 | 23.8 | 279.5 | |
310.4 | 731.9 | 23.4 | 251.1 | |
309.4 | 729.5 | 24.1 | 244.0 | |
307.8 | 725.8 | 24.6 | 241.5 | |
307.3 | 724.5 | 24.3 | 233.5 | |
Average | 309.2 | 729.1 | 23.9 | 267.0 |
Std Deviation | 2.6 | 6.0 | 0.4 | 40.8 |
Loading Area (mm2) | Failure Load (kN) | Compressive Stress (MPa) | Loading Area (mm2) | Failure Load (kN) | Compressive Stress (MPa) | Loading Area (mm2) | Failure Load (kN) | Compressive Stress (MPa) |
36,400 | 80.2 | 2.2 | 24,050 | 15.9 | 0.7 | 51,800 | 132.2 | 2.6 |
36,400 | 148.9 | 4.1 | 24,050 | 25.9 | 1.1 | 51,800 | 164.5 | 3.2 |
36,400 | 111.7 | 2.4 | 24,050 | 36.3 | 1.5 | 51,800 | 114.8 | 2.2 |
36,400 | 120.8 | 3.3 | 24,050 | 24.9 | 1.0 | 51,800 | 237.6 | 4.6 |
36,400 | 122.1 | 3.3 | 24,050 | 31.9 | 1.3 | 51,800 | 105 | 2.0 |
36,400 | 153.2 | 4.1 | 24,050 | 47.2 | 1.9 | 51,800 | 240.4 | 4.6 |
36,400 | 95.4 | 2.6 | 24,050 | 49.0 | 2.0 | 51,800 | 147.1 | 2.8 |
36,400 | 154.4 | 4.2 | 24,050 | 12.8 | 0.5 | 51,800 | 237.3 | 4.6 |
36,400 | 133.6 | 3.7 | 24,050 | 30.3 | 1.3 | 51,800 | 147.5 | 2.8 |
Average | 124.5 | 3.3 | Average | 30.5 | 1.3 | Average | 169.6 | 3.3 |
StdDeviation | 24.5 | 0.7 | StdDeviation | 11.7 | 0.5 | StdDeviation | 51.4 | 1.0 |
I. Series | II. Series | III. Series | ||||||
Loading Area(mm2) | Failure Load(kN) | Compressive Stress (MPa) | Loading Area (mm2) | Failure Load (kN) | Compressive Stress (MPa) | Loading Area (mm2) | Failure Load (kN) | Compressive Stress (MPa) |
7854 | 70.7 | 9.00 | 7854 | 84.4 | 11.00 | 7854 | 80.7 | 11.42 |
7854 | 90.7 | 11.36 | 7854 | 79.4 | 10.11 | 7854 | 91.9 | 11.70 |
7854 | 89.2 | 11.55 | 7854 | 78.6 | 10.01 | 7854 | 90.2 | 10.21 |
7854 | 93.6 | 11.92 | 7854 | 76.3 | 9.70 | 7854 | 93.1 | 11.85 |
7854 | 97.8 | 12.45 | 7854 | 74.2 | 9.45 | 7854 | 78.6 | 10.01 |
7854 | 87.9 | 11.19 | 7854 | 74.5 | 9.49 | 7854 | 96.1 | 12.24 |
7854 | 84.5 | 10.76 | 7854 | 85.0 | 10.84 | 7854 | 100.9 | 12.85 |
7854 | 83.2 | 10.59 | 7854 | 72.5 | 9.23 | 7854 | 80.9 | 10.30 |
7854 | 70.0 | 8.91 | 7854 | 80.6 | 10.26 | 7854 | 100.3 | 12.77 |
Average | 85.2 | 10.81 | Average | 78.4 | 10.01 | Average | 90.3 | 11.48 |
Std. Deviation | 8.9 | 1.13 | Std. Deviation | 4.2 | 0.58 | Std. Deviation | 7.98 | 1.02 |
Shotcrete | Glass Fiber-Reinforced Shotcrete (GFRC) | ||||||
Loading Area (mm2) | Fracture Load (kN) | Compressive Stress (MPa) | Elastic Modulus (GPa) | Loading Area (mm2) | Fracture Load (kN) | Compressive Stress (MPa) | Elastic Modulus (GPa) |
3848 | 73.1 | 55.69 | 14.31 | 3848 | 207 | 53.789 | 18.89 |
3848 | 72.6 | 55.38 | 14.53 | 3848 | 197.9 | 51.426 | 17.99 |
3848 | 71.3 | 54.59 | 13.98 | 3848 | 203.2 | 52.796 | 18.59 |
3848 | 72.3 | 55.21 | 14.75 | 3848 | 201.5 | 52.457 | 18.35 |
Average | 72.3 | 55.21 | 14.39 | Average | 202.4 | 52.617 | 18.45 |
Std. Deviation | 0.76 | 0.46 | Std. Deviation | 14.3 | 0.95 |
Test Specimens | Load Carrying Capacity (kN) | Stiffness (kN/mm) | Ductility Ratio | Energy Absorption Capacity (kJ) |
---|---|---|---|---|
MW | 62 | 3.1 | 3.8 | 10 |
MWS | 80 | 5 | 4.5 | 14 |
MWSG | 105 | 6 | 5.4 | 24 |
MWS 2-200 | 156 | 7.6 | 4.6 | 37 |
MWS 3-400 | 126 | 7.4 | 5.4 | 29 |
MWS 3-200 | 167 | 9.4 | 6.4 | 39 |
MWS 3-150 | 175 | 9.9 | 6.7 | 40 |
MWS 3-100 | 230 | 10.4 | 8.2 | 52 |
MWSG 2-200 | 180 | 6 | 4.7 | 42 |
MWSG 1.5-150 | 168 | 6.1 | 6.3 | 38 |
MWSG 2-150 | 186 | 6.4 | 6.6 | 43 |
MWSG 3-150 | 205 | 7.2 | 6.9 | 47 |
MWSG 3-400 | 158 | 5.5 | 7.2 | 30 |
MW | MWS | MWSG | MWS 2-200 | MWS 3-400 | MWS 3-200 | MWS 3-150 | MWS 3-100 | MWSG 1.5-150 | MWSG 2-150 | MWSG 2-200 | MWSG 3-150 | MWSG 3-400 | |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Pmax-EXP (kN) | 98.2 | 101 | 197 | 275 | 209 | 212 | 219 | 272 | 212 | 239 | 255 | 264 | 179 |
Pmax-FEM (kN) | 98 | 110 | 191 | 268 | 218 | 209 | 214 | 267 | 217 | 238 | 241 | 253 | 173 |
Convergence-Dif % | 0.2 | 8.9 | 3.14 | 2.6 | 4.3 | 1.03 | 2.3 | 1.8 | 2.3 | 0.4 | 5.8 | 4.3 | 3.4 |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2025 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license (https://creativecommons.org/licenses/by/4.0/).
Share and Cite
Yaman, Z.; Cumhur, A.; Ağcakoca, E.; Özyurt, M.Z.; Maraşlı, M.; Sadid, M.S.; Akrami, A.; Rasuly, A. Experimental Study and FEM Analysis on the Strengthening of Masonry Brick Walls Using Expanded Steel Plates and Shotcrete with and Without Glass Fiber Reinforcement. Buildings 2025, 15, 2781. https://doi.org/10.3390/buildings15152781
Yaman Z, Cumhur A, Ağcakoca E, Özyurt MZ, Maraşlı M, Sadid MS, Akrami A, Rasuly A. Experimental Study and FEM Analysis on the Strengthening of Masonry Brick Walls Using Expanded Steel Plates and Shotcrete with and Without Glass Fiber Reinforcement. Buildings. 2025; 15(15):2781. https://doi.org/10.3390/buildings15152781
Chicago/Turabian StyleYaman, Zeynep, Alper Cumhur, Elif Ağcakoca, Muhammet Zeki Özyurt, Muhammed Maraşlı, Mohammad Saber Sadid, Abdulsalam Akrami, and Azizullah Rasuly. 2025. "Experimental Study and FEM Analysis on the Strengthening of Masonry Brick Walls Using Expanded Steel Plates and Shotcrete with and Without Glass Fiber Reinforcement" Buildings 15, no. 15: 2781. https://doi.org/10.3390/buildings15152781
APA StyleYaman, Z., Cumhur, A., Ağcakoca, E., Özyurt, M. Z., Maraşlı, M., Sadid, M. S., Akrami, A., & Rasuly, A. (2025). Experimental Study and FEM Analysis on the Strengthening of Masonry Brick Walls Using Expanded Steel Plates and Shotcrete with and Without Glass Fiber Reinforcement. Buildings, 15(15), 2781. https://doi.org/10.3390/buildings15152781