Article

Examining the Gap Between Simulated and Actual Measured Performance of Buildings in the Context of the Israeli Green Building Standard

by
Sara Khair Abbas
* and
Isaac Guedi Capeluto
Faculty of Architecture and Town Planning, Technion—Israel Institute of Technology, Haifa 3200003, Israel
*
Author to whom correspondence should be addressed.
Buildings 2025, 15(13), 2320; https://doi.org/10.3390/buildings15132320
Submission received: 6 May 2025 / Revised: 17 June 2025 / Accepted: 23 June 2025 / Published: 2 July 2025
(This article belongs to the Section Building Energy, Physics, Environment, and Systems)

Abstract

Considering the climate crisis, global environmental awareness, and the pursuit of sustainable architecture, various methodologies and global standards have been developed to assess and reduce the environmental impact of construction projects. Green Building Codes (GBCs) and rating systems have been implemented worldwide to support green building practices based on the use of simulation models to evaluate energy consumption, such as the ENERGYui and others to rate buildings based on their simulated energy performance. Israel has also established green building standards, such as SI 5281, which provide practical tools for architects to promote the use of green building methods. However, several studies have cast doubt on the actual measured performance of certified buildings. This study evaluates the effectiveness of the Israeli green building certification process (SI 5281/SI 5282) through a comparison between simulation-based ratings with measured post-occupancy electricity consumption. Through four case studies, the research identifies discrepancies, explores their causes, and proposes refinements to certification assumptions and evaluation methods. The research is intended to enhance the effectiveness of assessment tools in architectural design and contribute to more precise and sustainable green building practices. This study identifies significant gaps between simulated and actual energy consumption in Israeli green buildings, highlighting that, within this framework, educational buildings tend to exceed predicted usage, while residential buildings often consume less, thereby exposing limitations in current simulation assumptions and standard evaluation criteria.

1. Introduction

The growing discourse on environmental concerns to reduce pollution and energy consumption has led to the development of a wide variety of methods for rating buildings and standards for green building [1] in an attempt to determine a set of values by which the degree of impact of a planned project on the environment can be assessed [2].
In Israel, based on an economic review conducted by the Knesset on the Israeli electricity sector [3], there is a consistent increase in electricity consumption (Figure 1). Therefore, standards have been developed in recent years for green building and rating buildings according to their predicted energy consumption. These standards aim to equip planners with practical planning tools for achieving high-performance architectural solutions while providing designers and tenants with clear criteria for identifying and understanding product quality, thereby fostering demand for, and implementation of, green buildings [4]. Through the adoption of such tools, entities ranging from organizations to individuals can transition their existing or proposed dwellings into environmentally conscious spaces, thereby enhancing their image, reducing costs, and minimizing environmental damage [2,5].
The core contribution of this study is an assessment of the alignment between certified, simulation-based energy ratings and measured energy performance in Israeli buildings. By identifying discrepancies and examining their underlying causes, this research offers a methodological foundation for refining national green certification practices to better reflect real usage conditions.

2. Literature Review

2.1. Green Building Standards in Israel

The Israeli standard, SI 5281 “Sustainable buildings (green buildings)” [6,7,8], establishes a multidisciplinary framework for evaluating buildings of various types. This standard comprises a system of criteria and requisites across various domains, wherein new constructions and renovated buildings accrue points and fulfill threshold conditions. Beyond facilitating environmentally friendly construction goals [6,7,8], SI 5281 serves as a comparative tool akin to similar global standards worldwide, enabling the analysis and ranking of buildings’ environmental performance.
SI 5281 shares structural and conceptual similarities with leading international frameworks such as LEED (USA), BREEAM (UK), and HQE (France). Like these systems, it uses a point-based structure to assess environmental performance across categories like energy, water, materials, and indoor environmental quality. It combines both prescriptive and performance-based methods, aligning with global certification trends, while also incorporating climate-adapted parameters and local construction practices unique to the Israeli context [9].
Checking compliance with the requirements of the energy section of the above standard can be achieved by examining the theoretical energy performance of the building according to SI 5282 “Energy Rating of Buildings”, using either a prescriptive method offering pre-tested alternatives or a performance method utilizing energy simulation models of buildings that compare the planned building to a reference building as defined in the standard [9]. Despite their potential to improve performance outcomes, these advanced tools are often applied late in the design process. Additionally, the reliance on standardized assumptions in tools like ENERGYui—required by SI 5281 in its Energy Chapter—limits their ability to accurately predict actual energy consumption, contributing to the performance gap observed in this study.

2.2. Energy Consumption Calculation in Israel in the Context of SI 5282

The determination of energy consumption in Israel for compliance according to standard 5282 (SI 5282) entails the utilization of the ENERGYui software. Figure 2 describes the ENERGYui software’s workflow, devised by researchers from the Faculty of Architecture and Town Planning at the Technion, which forecasts post-occupancy energy usage, establishes energy efficiency ratings, and streamlines simulation procedures, thereby enhancing data accuracy and reliability [9,10].
ENERGYui was selected for this study as it is the officially approved simulation tool under Israeli Standard SI 5282. It is a standard-based platform for performing structural energy evaluations, ensuring controlled and consistent data input for certified simulations. The tool is built on the EnergyPlus calculation engine, a well-established simulation platform that has undergone extensive international validation. While other tools like EnergyPlus or IES-VE are widely used globally, ENERGYui enables regulatory compliance within Israel’s green certification process and aligns with common practice among certified energy assessors.

2.3. Challenges in Achieving Energy Efficiency Goals Within the Context of Israel’s Green Building Standard

While simulation tools can enhance the efficiency of the design process and building performance, there often exists a disparity between predicted and actual measured performance due to variances in real-world conditions. Despite the widespread adoption of green building regulation in Israel, electricity consumption continues to rise, underscoring concerns regarding the efficacy of green building methods in achieving energy efficiency goals.
Furthermore, a significant challenge that has arisen is the “performance gap” between predicted and actual measured performance. Indications of the performance gap began to appear from the mid-1990s and with continuous coverage until today [11]. The performance gap, spanning various aspects such as energy efficiency, thermal comfort, and indoor air quality, has garnered attention within the sustainable construction domain since the mid-1990s [12]. As mentioned above, the rating under Israel’s building standard is based on a comparison between the actual design performance and a reference building. Therefore, special attention must be given to the assumptions used to define the reference buildings, ensuring they reflect real-world usage patterns. Moreover, since the standard applies to different building types, it is important to assess the consistency of rating requirements across these categories.

2.4. Energy Performance Gap

The most common definition of the performance gap refers to the difference or discrepancy between predicted (or calculated) performance and measured (or actual) performance [13,14,15,16]. However, the concept of the performance gap can be understood and interpreted more broadly. De Wilde [11] noted that the discussion of the performance gap is complicated by different approaches to both prediction and construction regulations.
In his work, he indicates that the actual energy consumption may exceed the predicted values by up to 2.5 times, highlighting significant gaps observed in the energy consumption after occupancy and in the energy use predicted by advanced simulation tools, thus posing potential obstacles for achieving energy efficiency goals [17].
Many studies in the literature raise different findings regarding the energy consumption and performance of buildings with a green standard, with some pointing to advantages [18] and others expressing skepticism [19,20].
The recurring theme across various studies highlights the challenges associated with accurately predicting energy consumption, which require continuous efforts and the refinement of existing methodologies for more accurate results.

3. Research Objectives and Methodology

This research aims to evaluate the effectiveness of Israel’s green building certification system (SI 5281 and SI 5282) by identifying and analyzing the performance gap between simulation-based energy predictions and measured post-occupancy consumption in certified buildings. Furthermore, it assesses the magnitude and origins of the performance gap, explores avenues for its mitigation in future projects, and investigates its correlation with the utilization of evaluation tools in architectural design processes. This research examines buildings’ compliance during the design phase and the certification phase and calculates the performance after occupancy, discerning contributing factors and proposing strategies for improvement.

3.1. Examining the Gap Between Simulated and Actual Energy Performance Methodology

A comparison was made between the simulated energy consumption and the actual energy consumption, for the purpose of assessing the existence and magnitude of gaps. We compared the value of the expected annual energy consumption EPdes (designed energy performance) and the value of the actual annual energy consumption EPact (the definition formulated for the research needs, referring to measured post-occupancy electricity consumption). The values were derived using different calculation methodologies. The EPdes value was calculated based on ENERGYui simulation results conducted according to the SI 5282 certification process and defined by a strict methodological framework. The EPact value was determined based on information gathered from various general electricity reports and bills that were available, allowing us to estimate the actual measured energy consumption of the building.

3.2. EPdes (Designed Energy Performance) Value Calculation Method

After collecting materials and computational results derived from the use of software applications during the construction planning phase, a suitable equation (Equation (1)) was formulated for determining the annual energy requirement, EPdes, by combining the improvement percentage (IP) derived from the relevant sections of SI 5282.
I P = 100 × E P r e f E P d e s E P r e f   T h e n   E P d e s = E P r e f E P r e f × I P 100
The EPdes value depends on two separate factors, both of which are subject to change based on project details. The first factor is the IP (improvement percentage), referring to the building’s designation and climate zone. The IP determines the degree of energy efficiency of the tested unit compared to a reference building; according to its value, the rating of the unit can be determined according to the various tables used in SI 5282. The second factor is the EPref (energy performance reference) value, which characterizes the annual energy consumption as the reference values obtained from the use of the ENERGYui software, which vary according to the purpose of the building and the climate zone. The EPref value was derived from the use of ENERGYui software according to each suitable space.
The EPdes value per square meter is calculated for each space using relevant data from the SI 5282 tables and simulation reports (Equation (1)), and then the overall average EPdes is determined through a weighted average (Equation (2)), which involves multiplying each space’s area by its EPdes value, summing these products, and dividing by the total area of all spaces included in the simulation.
E P d e s a v g = n A r e a 1 E P r e f 1 + + ( A r e a n E P r e f n ) A r e a 1 + + A r e a n

3.3. EPact (Actual Energy Performance) Value Calculation Method

After collecting and presenting detailed monthly electricity consumption reports for each project and calculating data regarding average actual energy consumption per square meter for comparative analysis, adjusting reported consumption for air conditioning and lighting relative to total monthly electricity use was required, facilitated by applying reduction factors from the Ministry of Energy’s reports [21] for more accurate results. For commercial and educational buildings, the factor is 0.75, and for residential buildings, the factor is 0.35.

3.4. Comparison of Calculated and Actual Energy Consumption

To compare the calculated and actual energy consumption (EPdes and EPact) values, this study employed two methodologies. Firstly, a numerical comparison method assessed the average expected and actual annual energy consumption per square meter (measured in kWh/m2·year).
Secondly, a rating-based evaluation methodology was used to compare the initial energy consumption value determined during planning stages with a value obtained based on actual electricity consumption, as per the criteria of Israeli energy rating standard SI 528, calculating the average rating of all floors, taking into account their relative areas (Equation (3)):
G B = S i × G i S i + V b
where Si is the Surface Area of unit i, Gi the Energy rating of unit i, Vb the rating value, and GB is the overall building energy rating according to energy demand.
Following the comparison between the EPdes and EPact values, identifying disparities between actual consumption and simulation results involved examining various planning processes and their alignment with SI 5282 criteria for green building certification. This entailed analyzing simulation results at different design stages to discern their impact on compliance with green standards. Subsequently, we aimed to identify reasons for these gaps and propose recommendations for improvement, as presented in Section 4.
SI 5282 applies a consistent performance evaluation method across different building typologies by comparing each proposed design to a predefined reference building. These reference models are defined using standard assumptions regarding internal loads, comfort conditions, and operational schedules. Our research aims to assess whether the mismatch between these assumptions and real-world conditions contributes to the performance gap observed in various types of certified buildings.
In addition to numerical and rating-based comparisons, we conducted a qualitative analysis to identify the root causes of performance gaps observed across the case studies. This involved reviewing simulation outputs, certification documentation, and design reports. Where possible, we conducted informal interviews and held correspondence with architects, facility managers, and municipal representatives. These inputs were synthesized to map out the sources of discrepancies at various project stages—design, simulation, and occupancy—as summarized in Section 5.

4. Case Study

This study focuses on four buildings with diverse programs and ratings, including two public buildings—the Porter Building School of Environmental Studies at Tel Aviv University, located in climate zone A, characteristic of the coastal plain, and Rakafot School in Kiryat Bialik (which will be detailed next), both certified under SI 5281 with different ratings—and two residential buildings—the Lev Alonim building in Yokneam, certified under SI 5281, and a residential building in the Hasavyon neighborhood in Nesher, both situated in climate zone B, characteristic of the inner coastal plain; the latter was constructed in the 1990s without GB certification and was selected to assess and compare the situation in buildings designed prior to the implementation and introduction of GBCs.

4.1. Rakafot School in Kiryat Bialik

The school campus, covering 6060 square meters with five buildings totaling 4434.97 square meters, features a central linear design with a shaded main walkway connecting building A and building B, also including two-story buildings with a total of 12 classrooms dedicated to teaching (Figure 3). This case study will be used in the following section to demonstrate the methodology used for the calculations.
Located in the climate zone B of Kiryat Bialik (inner coastal plain), the complex of buildings, underwent a certification assessment for buildings A and B (see Figure 3) according to standard SI 5282 part 2. Despite the lack of a specific standard for educational buildings at that time, it obtained a rating of B and a final score of 69.5, equivalent to 2 stars, using prescriptive and performance assessment methods assisted by ENERGYui software.

4.2. Rakafot School EPdes Calculation and Results

As part of the methodology, energy consumption assessments were carried out in accordance with SI 5281 requirements. The simulation focused on 11 defined spaces across buildings A and B, each evaluated separately based on their designated use and occupancy profiles. For methodological consistency, certain areas—specifically building C, the sports hall, and the security guard’s pavilion—were excluded from the simulation and certification process, as they were not part of the original evaluation scope. Based on the assessment data, the average energy consumption per square meter per year (EPdes) derived using Equation (2) for the spaces included in the calculations for buildings A and B was 28.72 kWh/m2. Figure 4 presents some of the spaces included in the calculation.

4.3. Rakafot School EPact Calculation and Results

Electricity reports for Rakafot School for the year 2019, provided by the municipality in collaboration with the school and the electricity company, report an annual consumption of 286,880 kWh for the entire school complex—including buildings A, B, and C; the sports hall; and the security guard’s pavilion—excluding the kindergarten, which has a separate meter. The combined area of these buildings is 4434.97 square meters (Figure 5). To overcome this limitation and enable comparison, we referred to energy consumption in per-square-meter terms, based on the area of the buildings included in the calculation.

4.4. Numerical Comparison Method

The numerical comparison between the calculated and actual energy consumption shows a significant discrepancy: the calculated average energy consumption is 28.72 kWh/m2/year (EPdes), reflecting a B rating, while the actual consumption post-construction is 48.5 kWh/m2/year (EPact). This indicates that the actual energy use is approximately 1.7 times higher than the calculated value, suggesting that the building’s energy performance is lower than initially planned and challenging the validity of the B rating.

4.5. Rating-Based Comparison Method

Using the evaluation method based on actual consumption values and following the methodology outlined in Section 3, the building would receive an F rating(see Figure 6). This indicates that it fails to meet the basic grade requirements (see Figure 7), contrasting to the B rating assigned to the building in the certification process.

5. Results

Figure 8 presents a comparison of the results obtained for the different cases analyzed during this study.
The Porter Building underwent extensive simulations during various design stages, reflecting a commitment to enhancing energy efficiency. However, significant disparities between predicted and actual consumption emerged, as shown in Figure 8.
Conversely, Rakafot School and the Lev Alonim residential building in Yokneam primarily relied on basic simulations for certification, while the Hasavyon Nesher residential building underwent no computerized analysis during design. Despite employing both basic and advanced simulation methods, a substantial energy consumption gap persisted across these cases as well.
The energy consumption of the Porter Building revealed significant discrepancies between the simulated and actual energy usage across two separate calculations conducted in different years for certification under SI 5281. Specifically, the actual energy consumption value was 1.1 times higher than the calculated consumption value needed for a B rating and 2.2 times higher than that for an A+ rating.
In addition, the analysis of Rakafot School indicated that its actual energy consumption was 1.7 times larger than the estimated values. Consequently, based on the observed energy consumption levels, both the Porter Building and Rakafot School warrant an F rating.
In contrast, the analysis of the two residential buildings highlighted a different trend compared to the educational ones. Both residential buildings exhibited actual energy consumption values that were 0.55 times lower than the calculated values. This indicates that these buildings consumed approximately half of the expected energy consumption values upon which their assumptions and ratings were based.
The analysis (Figure 9) indicates that discrepancies in the cases primarily stem from discrepancies in design and simulation. Moreover, discrepancies arise from variations in apartment occupancy hours and climatic conditions compared to simulation assumptions. The categories were derived from a combination of simulation analysis, documentation reviews, and stakeholder interviews, highlighting the role of assumptions, occupancy patterns, and standard version inconsistencies in different project phases. It is noteworthy that research tenant inspections occur annually, with additional inspections conducted in other seasons. Limitations in simulation for modeling complex buildings must also be acknowledged, alongside the impact of different standard versions on outcome.
The findings indicate that the energy consumption standards applied to educational buildings were more adequate compared to those for residential buildings. This discrepancy suggests that the educational standards may not accurately reflect real-world energy consumption when defining the reference building, resulting in more favorable assessments than what is observed in practice. Conversely, the residential standards and reference building appear to impose stricter conditions relative to actual consumption levels, highlighting a gap that adversely affects their performance ratings.

6. Discussion

This study offers a case-based evaluation of the Israeli green building certification framework by directly comparing its simulation-driven energy ratings to real-world performance data. The analysis includes conclusions for each case study, followed by a cross-case comparison and recommendations for narrowing the identified gaps in future rating practices.
While limited in scope, this study identified performance gaps in both public and residential buildings, indicating that such discrepancies are not restricted to a single typology. However, this observation is based on a limited sample size and should be considered exploratory rather than generalizable. Given the structure of Israeli Standard SI 5282, in which all buildings are evaluated using predefined reference buildings with fixed assumptions for each building type (e.g., internal loads, temperature setpoints, and operational schedules), our goal was to examine whether these assumptions contribute to the observed discrepancies across typologies.
The gap is evident in both educational and residential settings. Public buildings often underestimated consumption, while residential buildings tended to overestimate it. This aligns with previous international studies [17,21], which demonstrate that performance gaps vary with building type—often due to differences in occupancy, use patterns, and modeling assumptions. Our analysis found that unrealistic EPref values in SI 5282, particularly in residential contexts, contribute significantly to the discrepancies. For example, residential simulations assume constant comfort temperatures year-round, which often deviates from typical Israeli user behavior.
Furthermore, past studies have shown that discrepancies also result from mismatched occupancy hours and climatic assumptions. All buildings in our study were located in similar Mediterranean climate zones, minimizing variability due to climate. However, significant mismatches in actual occupancy behavior were observed. For instance, residential buildings were often occupied during daytime hours, contrary to the assumptions in SI 5282, which focus on night-time energy use. Public buildings also saw irregular usage beyond standard operational hours. Additionally, not all case studies were certified under the same version of SI 5282, leading to inconsistencies in input assumptions and modeling processes. These factors further contributed to the performance gaps observed and underscore the need for more adaptable and behaviorally informed certification tools. Our findings support the need to revise standard-based assumptions—particularly regarding occupancy and system usage—which often fail to reflect real-world behavior in residential settings.
Limitations in simulation tools further affect accuracy, especially for modeling complex geometries and mixed-use facilities. This is especially relevant in the Israeli context, where multiple evolving versions of SI 5281 have led to inconsistencies in modeling guidance. These findings highlight the need for harmonizing and updating the standard to align with current building use trends.
The observed performance gaps appear to stem from a combination of factors: (1) the use of standardized assumptions in SI 5282 that diverge from actual usage, (2) limited modeling flexibility for atypical designs or usage patterns, and (3) post-occupancy operational variations. Additionally, changes between different versions of the standard introduce inconsistencies in modeling procedures and expected performance outcomes.
These findings reinforce the study’s main objective: to evaluate whether Israel’s simulation-based certification framework reliably reflects post-occupancy energy performance. By identifying how embedded assumptions contribute to inaccuracies, the study emphasizes the need to align certification models with real-world operation. This strengthens the relevance of our methodology and supports the case for refining green building evaluation systems.
Further, discrepancies also emerge in cases where building function diverges from classification. For example, the Porter Building—though classified as an educational building—also contains office and meeting spaces, resulting in energy use patterns not fully captured by standards meant for educational facilities alone.
In conclusion, this study contributes to the growing evidence that fixed reference-based simulation methods, as used in SI 5282, often fail to represent dynamic user behavior and real-world energy consumption. By applying a case-based analysis across building typologies, we highlight structural and methodological gaps that affect certification accuracy. We recommend that future research focus on adaptive simulation models, integrated with real-time data and post-occupancy feedback, to improve both predictive precision and policy relevance.

6.1. Limitations and Difficulties in Research

In the initial stages of selecting test cases for the study, significant challenges were encountered. Identifying green-rated projects was complicated by incomplete records from the Ministry of Environmental Protection prior to 2018, leading to difficulties in contacting architects and obtaining necessary documents. Data collection faced obstacles such as privacy concerns from tenants in the Lev Alonim residential building, initial non-cooperation and COVID-19 disruptions at Rakafot School, and a lack of disaggregated consumption data in the Porter Building due to functional issues with the maintenance company. Additionally, the lack of construction details for the Hasavyon residential building in Nesher necessitated detailed permit analysis and physical inspections. The analysis of results was hindered by limited available data, requiring manual extraction and calculations, while the pandemic further disrupted observations and data collection, necessitating special permits and coordination with various authorities. Since the results of this study are based on a limited number of buildings and climate zones, further research is needed to draw more generalizable conclusions.
As this study included only four buildings, the findings are case-specific and should be considered exploratory. Broader validation across a more diverse and statistically significant sample is necessary to generalize the observed trends.

6.2. Recommendations for Improvement

To promote sustainable construction, advanced simulation tools must be integrated into the design process early. However, achieving accurate energy consumption predictions not only requires advanced simulation tools but also a deep understanding of user behaviors. Discrepancies are attributed partially to user behavior patterns and design phases, highlighting the importance of aligning preparatory efforts with simulation outcomes. Moreover, to advance green construction practices, public access to building consumption data is imperative. Furthermore, additional analyzed case studies that support a re-evaluation of the reference values used to determine building ratings must be conducted, ensuring these values more accurately reflect real-world conditions.

6.3. Future Research

This article emphasizes the importance of standardizing methodologies for assessing and reporting the performance gap across diverse building contexts. It advocates for an expanded scope of test cases and further data availability and collection efforts focusing on variables like user behavior to deepen our understanding of factors contributing to this gap. Additionally, it stresses the necessity of effective performance monitoring post-occupancy, proposing integration into green certification processes. Furthermore, it highlights the need to investigate the temporal aspects of the performance gap, which have been overlooked in current research. Lastly, the article proposes exploring the potential of artificial intelligence and machine learning algorithms in future research to enhance simulation tools for more dynamic and responsive energy efficiency models.

Author Contributions

Conceptualization, S.K.A. and I.G.C.; methodology, S.K.A. and I.G.C.; software, S.K.A.; validation, S.K.A. and I.G.C.; formal analysis, S.K.A. and I.G.C.; investigation, S.K.A. and I.G.C.; resources, S.K.A. and I.G.C.; data curation, S.K.A.; writing—original draft preparation, S.K.A.; writing—review and editing, S.K.A. and I.G.C.; visualization, S.K.A.; supervision, I.G.C.; project administration, S.K.A. and I.G.C.; funding acquisition, S.K.A. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by the Technion — Israel Institute of Technology, as part of a scholarship awarded to S.K.A.

Data Availability Statement

The data presented in this study are available on request from the corresponding author. The data are not publicly available due to privacy issues.

Conflicts of Interest

The authors declare no conflict of interest.

References

  1. Berardi, U. Sustainability Assessment in the Construction Sector: Rating Systems and Rated Buildings. Sustain. Dev. 2012, 20, 411–424. [Google Scholar] [CrossRef]
  2. Marchi, L.; Antonini, E.; Politi, S. Green Building Rating Systems (GBRSs). Encyclopedia 2021, 1, 998–1009. [Google Scholar] [CrossRef]
  3. The Knesset, Research and Information Center. The Electricity Sector in Israel—Data and Forecasts. 2022; pp. 1–15. Available online: https://fs.knesset.gov.il/24/Committees/24_cs_bg_623784.pdf (accessed on 20 March 2023).
  4. Illankoon, I.M.C.S.; Tam, V.W.Y.; Le, K.N.; Tran, C.N.N.; Ma, M. Review on green building rating tools worldwide: Recommendations for Australia. J. Civ. Eng. Manag. 2019, 25, 831–847. [Google Scholar] [CrossRef]
  5. Meena, C.S.; Kumar, A.; Jain, S.; Rehman, A.U.; Mishra, S.; Sharma, N.K.; Bajaj, M.; Shafiq, M.; Eldin, E.T. Innovation in Green Building Sector for Sustainable Future. Energies 2022, 15, 6631. [Google Scholar] [CrossRef]
  6. SI 5281; Building with Reduced Environmental Impact (“Green Buildings”). The Standards Institution of Israel: Tel Aviv, Israel, 2005.
  7. SI 5281; Sustainable Building. The Standards Institution of Israel: Tel Aviv, Israel, 2011.
  8. SI 5282; Energy Rating of Buildings. The Standards Institution of Israel: Tel Aviv, Israel, 2011.
  9. Capeluto, I.G. The Unsustainable Direction of Green Building Codes: A Critical Look at the Future of Green Architecture. Buildings 2022, 12, 773. [Google Scholar] [CrossRef]
  10. Yezioro, A.; Capeluto, I.G. Energy rating of buildings to promote energy-conscious design in Israel. Buildings 2021, 11, 59. [Google Scholar] [CrossRef]
  11. de Wilde, P. The gap between predicted and measured energy performance of buildings: A framework for investigation. Autom. Constr. 2014, 41, 40–49. [Google Scholar] [CrossRef]
  12. Shi, X.; Si, B.; Zhao, J.; Tian, Z.; Wang, C.; Jin, X.; Zhou, X. Magnitude, causes, and solutions of the performance gap of buildings: A review. Sustainability 2019, 11, 937. [Google Scholar] [CrossRef]
  13. Menezes, D.; Kossmann, A.C.; Cripps, A.; Bouchlaghem, D. Predicted vs. actual energy performance of non-domestic buildings: Using post-occupancy evaluation data to reduce the performance gap. Appl. Energy 2019, 97, 355–364. [Google Scholar] [CrossRef]
  14. Demanuele, C.; Tweddell, T.; Davies, M. Bridging the gap between predicted and actual energy performance in schools. In Proceedings of the World Renewable Energy Congress XI, Abu Dhabi, United Arab Emirates, 23–30 September 2010; pp. 1–6. [Google Scholar]
  15. Petersen, S.; Hviid, C.A. The European Energy Performance of Buildings Directive Comparison of Calculated and Actual Energy Use in a Danish Office Building. DTU Library 2012. Available online: https://orbit.dtu.dk/en/publications/the-european-energy-performance-of-buildings-directive-comparison/fingerprints/ (accessed on 20 March 2023).
  16. Herrando, M.; Cambra, D.; Navarro, M.; de Cruz, L.; Millán, G. Energy Performance Certification of Faculty Buildings in Spain: The gap between estimated and real energy consumption. Energy Convers. Manag. 2016, 125, 141–153. [Google Scholar] [CrossRef]
  17. van Dronkelaar, C.; Dowson, M.; Burman, E.; Spataru, C.; Mumovic, D. A Review of the Energy Performance Gap and Its Underlying Causes in Non-Domestic Buildings. Front. Mech. Eng. 2016, 1, 17. [Google Scholar] [CrossRef]
  18. Fowler, K.M.; Rauch, E.M.; Henderson, J.W.; Kora, A.R. Re-Assessing Green Building Performance: A Post Occupancy Evaluation of 22 GSA Buildings; Pacific Northwest National Laboratory, U.S. Department of Energy: Richland, WA, USA, 2010. [Google Scholar]
  19. Scofield, J.H. Do LEED-certified buildings save energy? Not really…. Energy Build. 2009, 41, 1386–1390. [Google Scholar] [CrossRef]
  20. Scofield, J.H. Efficacy of LEED-certification in reducing energy consumption and greenhouse gas emission for large New York City office buildings. Energy Build. 2013, 67, 517–524. [Google Scholar] [CrossRef]
  21. Ministry of Energy, State of Israel. National Plan for Energy Efficiency for 2030. 2020. Available online: https://www.gov.il/BlobFolder/news/energy_2030/he/energy_2030_updated.pdf (accessed on 20 March 2023).
Figure 1. Israel’s electricity demand, in billions of kWh in generation terms, years 2000–2020 [3].
Figure 1. Israel’s electricity demand, in billions of kWh in generation terms, years 2000–2020 [3].
Buildings 15 02320 g001
Figure 2. The workflow of ENERGYui [11].
Figure 2. The workflow of ENERGYui [11].
Buildings 15 02320 g002
Figure 3. The rating of the different spaces at Rakafot School, obtained using both prescriptive and performance methods based on ENERGYui simulations in 2013 during the design stage, is noted by the letters A–E.
Figure 3. The rating of the different spaces at Rakafot School, obtained using both prescriptive and performance methods based on ENERGYui simulations in 2013 during the design stage, is noted by the letters A–E.
Buildings 15 02320 g003
Figure 4. Rakafot School calculated energy consumption values (EPdes values) for the different parts and spaces in buildings A and B according to the submitted method for certification.
Figure 4. Rakafot School calculated energy consumption values (EPdes values) for the different parts and spaces in buildings A and B according to the submitted method for certification.
Buildings 15 02320 g004
Figure 5. Summary of the electricity consumption data; general consumption of the building for a year was calculated, and accordingly, the average actual energy consumption per square meter per year was obtained (kWh/m2·year).
Figure 5. Summary of the electricity consumption data; general consumption of the building for a year was calculated, and accordingly, the average actual energy consumption per square meter per year was obtained (kWh/m2·year).
Buildings 15 02320 g005
Figure 6. Calculation of the building grades according to the actual electricity consumption after construction and occupancy for 2019.
Figure 6. Calculation of the building grades according to the actual electricity consumption after construction and occupancy for 2019.
Buildings 15 02320 g006
Figure 7. Calculation table for Rakafot School building according to the actual electricity consumption in accordance with SI 5282 part 2. The building is a 2011 office building, and it received a B rating.
Figure 7. Calculation table for Rakafot School building according to the actual electricity consumption in accordance with SI 5282 part 2. The building is a 2011 office building, and it received a B rating.
Buildings 15 02320 g007
Figure 8. Numerical rating-based comparison of the different study cases, focusing on their actual consumption values and simulated consumption values: (a) Porter Building, (b) Rakafot School, (c) Lev Alonim residential building in Yokneam, and (d) Hasavyon residential building in Nesher.
Figure 8. Numerical rating-based comparison of the different study cases, focusing on their actual consumption values and simulated consumption values: (a) Porter Building, (b) Rakafot School, (c) Lev Alonim residential building in Yokneam, and (d) Hasavyon residential building in Nesher.
Buildings 15 02320 g008
Figure 9. Mapping of the observed causes of performance gaps across the four case studies.
Figure 9. Mapping of the observed causes of performance gaps across the four case studies.
Buildings 15 02320 g009
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Abbas, S.K.; Capeluto, I.G. Examining the Gap Between Simulated and Actual Measured Performance of Buildings in the Context of the Israeli Green Building Standard. Buildings 2025, 15, 2320. https://doi.org/10.3390/buildings15132320

AMA Style

Abbas SK, Capeluto IG. Examining the Gap Between Simulated and Actual Measured Performance of Buildings in the Context of the Israeli Green Building Standard. Buildings. 2025; 15(13):2320. https://doi.org/10.3390/buildings15132320

Chicago/Turabian Style

Abbas, Sara Khair, and Isaac Guedi Capeluto. 2025. "Examining the Gap Between Simulated and Actual Measured Performance of Buildings in the Context of the Israeli Green Building Standard" Buildings 15, no. 13: 2320. https://doi.org/10.3390/buildings15132320

APA Style

Abbas, S. K., & Capeluto, I. G. (2025). Examining the Gap Between Simulated and Actual Measured Performance of Buildings in the Context of the Israeli Green Building Standard. Buildings, 15(13), 2320. https://doi.org/10.3390/buildings15132320

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop