Next Article in Journal
Utilizing Phosphate Tailing-Based Compound Selenium Activator to Enhance Selenium Absorption and Fruit Quality in Citrus: Resource Utilization Strategy for Sustainable Agriculture
Previous Article in Journal
Spatial Distribution Characteristics of Marine Economy Based on AI-Assisted Multi-Source Data Fusion and Random Forest Analysis
Previous Article in Special Issue
Factors Influencing Water Point Functionality in Liberia: A Regression and Bayesian Network Analysis
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Determination of the Water Outflow Zone on the Ground Surface After a Pipe Failure Using Fractal Geometry

by
Małgorzata Iwanek
* and
Paweł Suchorab
Department of Water Supply and Wastewater Disposal, Faculty of Environmental Engineering and Energy, Lublin University of Technology, Nadbystrzycka 40B, 20-618 Lublin, Poland
*
Author to whom correspondence should be addressed.
Sustainability 2025, 17(24), 11093; https://doi.org/10.3390/su172411093
Submission received: 28 October 2025 / Revised: 24 November 2025 / Accepted: 9 December 2025 / Published: 11 December 2025

Abstract

Uncontrolled water outflows from water supply pipes can pose a serious threat to human safety and infrastructure due to the washing out of soil particles and the formation of subsurface voids, leading to soil subsidence (suffosion). One way to mitigate these hazards is by determining water outflow zones (WOZ) around underground pipes, within which water may emerge on the soil surface. This paper presents the final stage of a broader study on the use of fractal geometry for determining WOZ. Suffosion hole locations form point structures that exhibit features of probabilistic fractals, and their parameters depend on the number of points in the structure. The objectives of the study were: (1) to determine the minimum number of points required for a structure to be considered representative; (2) to establish a relationship for calculating the WOZ radius; and (3) to empirically verify the theoretical WOZ radius values. Representative structures were identified and used to calculate the Rfr parameter, which, after scaling to real conditions, enabled determination of the WOZ radius, ranging from 3.5 to 5.5 m. Empirical verification confirmed the method’s validity, as theoretical zones covered up to 100% of actual outflow points (96% overall). The developed method can be applied into decision-support systems for sustainable infrastructure planning, and more efficient use of water resources.

1. Introduction

The water distribution network (WDN) is a key component of urban infrastructure, responsible for ensuring a continuous supply of potable water to consumers in the required quantity, at the appropriate pressure, and in compliance with the quality standards defined by relevant legal regulations [1]. According to the water balance proposed by International Water Association (IWA), the difference between the water system input volume and the authorized water consumption is referred to as water losses, which are generally categorized into apparent losses and real losses [2]. The real losses occur primarily within the water supply network, as a result of failures, pipe bursts, and leaks from the underground infrastructure. On the other hand, the apparent losses refer to water that is consumed but not billed. It is lost due to the issues in meter inaccuracies, billing errors or data handling mistakes. Water utilities struggle to reduce both real and apparent losses in order to minimize the non-revenue water [3].
According to the requirements of the European Water Framework Directive [4] and the principles of sustainable water management [5], water utilities are obliged to monitor and report water losses. These data are not only a regulatory requirement but can also a support water system operation, regulation and planning [6,7]. Therefore, from both an environmental and economic standpoint, water utilities strive to reduce losses to the so-called economic level of leakage (ELL) [8]. This level represents the balance point at which the cost of leak detection and repair equals the economic value of the water saved, including the energy and treatment costs associated with its intake and distribution. In practice, achieving or maintaining the ELL requires a combination of preventive maintenance, hydraulic monitoring, and advanced leak detection techniques [9,10]. Recent policy developments emphasize the need for improving the efficiency and resilience of water supply networks [11]. Consequently, the detection, quantification, and mitigation of real water losses are becoming key components of integrated water resource management strategies. However, given the spatial complexity of water distribution systems, detecting and predicting water leakages remains a challenge. A wide range of leak detection approaches has been developed, including hardware-based methods, software-based methods, leakage localization methods, and smart water network approaches [12,13,14,15]. However, despite significant advances, the accurate localization of underground leaks and the prediction of potential water outflow zones on the surface remain difficult due to the complex interaction between hydraulic and geotechnical parameters [16,17].
The water supply systems are considered as components of the critical infrastructure, because their reliable operation is essential for public health, national security and economy [18,19]. Failures of water pipes can lead not only to interruptions in water delivery, but can also affect other infrastructure systems, such as transportation or energy. Although undesired, failures of water pipes are an inevitable aspect of system operation [20,21]. The nature and frequency of such failures, including their location, size, and the volume of water discharged—depends on a variety of factors such as pipe material and age, installation conditions, soil type, internal pressure, and local geological or hydrological conditions [22,23]. Additionally, cyclic pressure variations and temperature changes can accelerate material fatigue, further increasing the probability of leaks [24]. When a pipe failure occurs, the pressurized water flows into the surrounding soil matrix. The outflow of water into the soil can initiate suffosion processes—the washing out of fine particles from the soil structure [25], leading to local soil instability, subsidence, and even sinkhole formation. Such phenomena can endanger human safety, damage nearby underground utilities, and significantly increase the cost of emergency repairs [26].
One of the approaches to mitigating the negative effects of water pipe failures is the design of safety zones around the pipelines. These zones are defined as areas surrounding a water pipe where in the event of pipe failure, water is expected to reach the ground surface within a specific distance from the failure point. The identification of such zones are of great importance for spatial planning and urban engineering, as they allow for excluding sensitive areas from the construction of roads, pavements, or other underground installations. One way to determine the outflow zone is through a geometrical analysis of the distribution of water outflow points on the soil surface. These points create irregular sets that are difficult to be described on the concepts of classical Euclidean geometry but simultaneously meet the conditions for random fractals. The present paper is the third and final part of a research cycle devoted to the application of fractal geometry in identifying water outflow zones resulting from pipe failures. Building upon previous findings, the current study integrates theoretical and empirical approaches to propose a comprehensive methodology for determining the Water Outflow Zone (WOZ) on the ground surface after a pipe failure. The aim was to develop a mathematical formula that can be used by water utilities to predict the range of potential outflow areas under various operational and soil conditions.

2. Materials and Methods

The analyses presented in this article are the last part of a larger scope of research, the purpose of which is the WOZ determination in relation to the fractal characteristics of water outflows. The results of earlier analyses have already been published [27,28,29,30,31,32,33,34]. The full scope of research is presented in Figure 1.
The laboratory tests of an underground water pipeline failure scaled 1:10 were the basis of analyses. The tests were carried out for 5 different leak areas (2.83–18.84 cm2) and 7 values of pressure head in the tested pipe (3.0–6.0 m H2O) [27,28,29]. The pipe was buried in the compacted sand (93–94% of the Proctor density). As a result of a physical leakage simulation, water flowed onto the surface, washing out the soil and forming suffosion holes [30,31,32]. These holes were assigned points in a coordinate system originating at the location of leak from the pipe. The points corresponding to the suffosion holes formed 12 real structures (RSs) embedded in a 2D space, exhibiting fractal characteristics. These structures were simplified to forms embedded in a one-dimensional space while preserving their fractal features, creating 12 so-called theoretical linear structures (TLSs). For each TLS, a parameter Rfr was determined, defined as the product of the fractal (box-counting) dimension (Db) of the structure and the distance R w m a x from the leakage point to the outermost point of the structure [29].
The analyses of the TLSs showed that the number of points forming each structure affects the value of Rfr. To assess the extent of this effect, it was necessary to repeat the analysis for larger number of different linear structures, especially those composed of a high number of points. This task was made possible through the use of the Monte Carlo method to generate hypothetical linear structures (HLSs) [33]. A total of 1920 pseudorandom number sequences were generated, composed of various numbers of points nw (50, 100, 200, 300, …, 900, 1000, 1500, 2000, 3000, 4000, 5000). Each sequence constituted a single HLS, named depending on the corresponding TLS (Table 1). It should be emphasized that each HLS name (e.g., HF1) refers not to a single structure, but 160 structures—consisting of 50, 100, …, 5000 points (16 different numbers), each repeated 10 times.
For each HLS, the distance R w m a x , the fractal dimension Db and parameter Rfr were determined. It was observed that for each HLS there is a certain threshold value nw (denoted as n w   g r ), starting from which it can be assumed that both the Rfr values cluster around the mean (condition I) and that the mean value of Rfr remains almost constant with increasing nw (condition II). Therefore, it is necessary to determine n w   g r as the sufficient number of points needed to construct a representative linear structure that could serve as the basis for dimensioning the water outflow zone on the surface after an underground pipe failure.
Since the Rfr parameter proved to be crucial in determining the WOZ radius, Table 2 presents the mean Rfr values for all generated HLSs, as determined in previous studies [33]. The analyses preceding the research included in this article have been presented in detail in [27,28,29,30,31,32,33,34].

2.1. Determination of the Minimum Number of Points for Which the Rfr Values Are Concentrated Around the Mean (Condition I)

To assess the concentration of Rfr values around the mean, one of the descriptive statistics—the coefficient of variation (CV)—was used, defined as the ratio of the standard deviation to the mean. The CV of the Rfr parameter was calculated for 12 groups of HLSs for nw = 50, 100, …, 5000. Based on the results, CV(nw) plots were generated, and a trendline was fitted as the best match among exponential, linear, logarithmic, polynomial, and power functions.
Statistical textbooks do not provide a strict numerical threshold for the CV value that would indicate very low variability of the analyzed parameter. However, in literature examples, such values frequently do not exceed 5% (e.g., [35,36,37,38]). Therefore, we adopted the criterion that CV ≤ 5% indicates that the Rfr values are approximately equal to the mean. By substituting this threshold value into the trendline equations, the minimum number of points satisfying condition I was calculated (denoted as n w I ). In the final step of this stage, the resulting values of n w I were rounded to an accuracy of 50 if 25 < n w I < 100, and of 100 if n w I ≥ 100. If n w I ≤ 25, a value of 50 was adopted as the smallest analyzed number of structure points, even though rounding would yield zero.

2.2. Determination of the Minimum Number of Points for Which the Mean Values of Rfr Remain Almost Constant with Increasing nw (Condition II)

To determine from which values of nw the increase in Rfr (nw) can be considered negligible, unit differences r f r   i were calculated according to Equation (1):
r f r   i =   R f r   5000 R f r   i n w   5000 n w   i ,
where R f r   5000 and R f r   i denote mean Rfr values for structures consisting of 5000 and n w   i points, respectively ( n w   i ∈ { n w I , …, 4000}). Minimal value of n w   i is n w I , because conditions I and II must be met simultaneously.
These unit differences were then subjected to statistical evaluation. For this purpose, at a significance level of α = 0.05, a null hypothesis was tested—that starting from a certain value of nw (denoted as n w I I ) the unit differences r f r   i are equal to zero, against the alternative hypothesis—that r f r   i ≠ 0. The one-sample Student’s t-test was used to verify the hypothesis. The verification was carried out for all 12 groups of HLSs, and for each group, successive values of n w I I ∈ { n w I , …, 3000} were tested.
The hypothesis verification consisted in checking whether the critical interval C I according to Formula (2) included the t-statistic according to Formula (3) at the adopted significance level.
C I = , t c r t c r , + ,
t = r f r   i ¯ μ S D · n 1 ,
where t c r is the (1 − α/2) quantile of the t-distribution obtained from statistical tables for n 1 degrees of freedom, r f r   i ¯ —mean of r f r   i values for the analyzed n w range (from n w I I to 5000) for a given group of structures, μ —the expected value of the unit difference ( μ = 0), SD and n—the standard deviation [cm] and the number of unit differences r f r   i , respectively, for the analyzed n w range (from n w I I to 5000). All calculations were performed in MS Excel 2019.
If t C I , there were no reason to reject the null hypothesis at the significance level of α = 0.05. The smallest value of n w I I (denoted as n w   g r ) that satisfies condition t C I represents the minimum number of points required to create a representative structure, whose Rfr value is approximately equal to the Rfr values of structures composed of more than n w   g r points. Since Student's t-tests were performed for structures consisting of n w n w I points (based on the results of the analysis described in Section 2.2), the value of n w   g r can be considered the minimum number of points required to construct a representative structure.

2.3. WOZ Radius Determination

It was assumed that the WOZ is circular in shape, centered directly above the potential leak and covering the points of water outflow onto the ground surface. According to the conclusions presented in [33], if these points form a representative structure, i.e., composed of n w   g r points, then it can be assumed that the WOZ radius (RWOZ) corresponds to the Rfr parameter value of this structure. The Rfr values analyzed in this study were determined for HLSs developed based on laboratory tests conducted at a scale of 1:10 [29]. To use these Rfr values to determine the RWOZ, they must be scaled to actual conditions. As previously published dimensional analysis results indicate, this requires multiplying the Rfr values of individual representative structure by 10 [27]. Furthermore, for practical reasons, it was proposed to round the obtained values to 0.5.

2.4. Field Tests

To verify the results obtained from laboratory tests and statistical analyses, field tests were carried out under real construction site conditions. The purpose of the field tests was to create a controlled water outflow from a pressure pipe, simulating an underground water pipe failure. The field test setups were constructed in two different locations (called A and B). In each location, four open excavations trenches were made, in which PE-HD water pipes were laid. The single excavation dimensions were as follows: 4.0 m × 0.7 m × 1.65 m (length × width × depth) in location A, and 5.0 m × 0.5 m × 1.90 m (length × width × depth) in location B. The scheme of the field study setup is presented in Figure 2. To achieve a physical simulation of water leakage from the pressure pipe into the ground, each PE-HD pipe (4) was cut along nearly its entire circumference at the midpoint of its length (5), leaving a 5 mm uncut segment to maintain the coaxial alignment of the separated parts. At the cut location, a knitted band made of thin, water-permeable fabric was placed over the pipe to protect the interior of the pipe from soil intrusion during the backfilling process. During the field test, the pipe was supplied with water from a fire hydrant. At the inlet end (1), the measuring set was installed, consisting of 2 ball valves (2) and a pressure gauge (3). Additionally, 1 ball valve (2) was installed at the outlet end (6).
The field tests were carried out in 3 measurement series. The first series was conducted at location A, while the second and third were conducted at Location B. All three series were performed at least 6 months after the construction of the field test setups—specifically after 7, 9, and 22 months, respectively. In both locations A and B, the natural soil was sandy with good permeability—the hydraulic conductivity averaged 3.34 × 10−4 m/s at location A and 1.52 × 10−4 m/s at location B. At location A, the same pipes diameters were used (PE-HD 63 × 3.8) and tests were conducted under pressure of 41 m H2O for each trial (A1.1–A1.4). At Location A, the field test setup was differentiated by varying the pipe bedding. Two pipes were laid directly on the natural soil (series A1.1 and A1.2), while the other two (A1.3 and A1.4) were laid on a 10 cm sand bedding and backfilled with compacted 30 cm layers of sand. For series 2 and 3 conducted at location B, a uniform pressure was applied (36.5 m H2O for series B2.1–B2.4 and 45 m H2O for B3.1–B3.4), but the test setups differed in the pipe diameters used: PE-HD 110 × 4.2 mm for series B2.1, B2.2, B3.1, B3.2 and diameter 200 × 7.7 mm for B2.3, B2.4, B3.3, B3.4. Water pressure was measured using a digital hydrant logger (data recording interval: 0.1 s). No surges were recorded during the tests, Detailed information on the measurement series carried out is presented in Table 3. The data obtained during the physical simulations under real conditions included the location of water outflow at the ground surface and the time of water outflow, measured from the start of the experiment to the moment the water appeared on the surface. The location of the water outflow was determined using (x, y) coordinates relative to the outflow opening in the pipe (point 0,0). The measurements were carried out using a measuring tape with an accuracy of ±1 mm.

2.5. The Process of Empirical Verification

The proposed method for determining the radius of the water outflow zone on the soil surface after a failure of an underground water supply pipe was empirically verified based on the results of locating the outflow points during physical failure simulations conducted under real conditions at sites A and B (Section 2.4). The verification involved the radius values calculated from those laboratory data sets that corresponded to the conditions of the field experiments.
The leakage area of the pipe was strictly related to the pipe diameter, as the pipe had been damaged in such a way that water leakage occurred along the entire circumference. Therefore, when selecting the radius values calculated for HF1–HF5 to be used in empirical verification, the pipe diameter was taken into account. The internal pressure in the pipe during the laboratory tests served as the basis for selecting the radius values calculated for HH1–HF7. Based on this approach, the results of field tests A1.1–A1.4 were used to verify the WOZ radius determined for dataset HF1 (the 6 mm pipe diameter in the laboratory tests corresponded to a DN 63 × 3.8 mm pipe in the field tests), while the results of tests B2.1, B2.2, B3.1, and B3.2 were used to verify the WOZ radius determined for dataset HF2 (the 10 mm pipe diameter in the laboratory tests corresponded to a DN 110 × 4.2 mm pipe in the field tests). For tests B2.3, B2.4, B3.3, and B3.4, the verification concerned the outflow zones with radius determined for dataset HF3—a pipe diameter of 20 mm in the laboratory tests corresponded to a DN 200 × 7.7 mm pipe in the field tests (Table 4). Analogously, the results of field tests A1.1–A1.4 (pipe pressure 41 m H2O), B2.1–B2.4 (pipe pressure 36.5 m H2O) and B3.1–B3.4 (pipe pressure 45 m H2O) were used to verify the WOZ radius determined for dataset HH3, HH2 and HH4, which corresponded to laboratory conditions of 4.0, 3.5, and 4.5 m H2O, respectively (Table 5).
The empirical verification consisted in checking whether the actual water outflow points observed on the ground surface during field tests were located within the outflow zones whose size had been determined according to the methodology described in Section 2.1, Section 2.2, Section 2.3. The verification result was considered positive if at least 90% of the actual points were located within the theoretical zones.

3. Results and Discussion

3.1. The Minimum Number of Points for Which the Rfr Values Are Concentrated Around the Mean (Condition I)

The results of the CV calculations, which are the basis for assessing the clustering of Rfr values around the mean, are presented in Table 6. A clear decreasing trend in the CV values with increasing the number of points forming the structures was observed for all HLSs groups. The maximum CV value corresponded to nw = 50 for nearly all HLSs, except HF2 and HH5, for which it was nw = 100. The difference between the CV value at nw = 50 and the maximum was 3.53% and 1.39% for HF2 and HH5, respectively. The minimum CV values for most HLSs corresponded to nw = 5000. For HF1, HF4, and HH6, the minimum CV occurred at nw = 4000, with the difference of only 0.02%, 0.03%, and 0.06%, respectively, compared to the CV value at nw = 5000. For HH2 and HH3, the minimum CV was observed at nw = 3000, also with a very small difference compared to the CV at nw = 5000 (0.11% and 0.27%, respectively). Considering all the values presented in Table 6, the highest CV = 14.39% occurred for the HH3 structure with nw = 50, while the lowest CV = 0.01% was for the HH5 structure with nw = 5000.
The CV(nw) relationship proved to be a strictly decreasing function only for HF3. For the remaining structure groups, some deviations occurred, though the general decreasing trend was preserved. An example plot of the CV(nw) relationship with the trend line for the HH3 structure group is shown in Figure 3.
Among the tested functions, the power trendline provided the best fit (Table 7). The values of the coefficient of determination R2 were large for the vast majority of structure groups: R2 > 0.9 for 7 out of 12 structure groups, R2 less than but close to 0.9 for 2 groups, and R2 = 0.77 for one group. These large R2 values confirmed at least a satisfactory fit (very good in most cases) of the power trendline to the CV(nw) relationship. Unsatisfactory R2 values (0.5 < R2 < 0.6) were obtained for HF2 and HH5, where the maximum CV was reached at nw = 100 (not at nw = 50). After excluding the structures with nw = 50 from the correlation analysis, a good and very good fit of the power trendline was achieved—R2 > 0.8 for HF2 and R2 > 0.9 for HH5.
Inserting CV = 5% into the trend line equation made it possible to calculate the minimum number of points n w I satisfying condition I. The calculation results of n w I are presented in the last two columns of Table 7. The highest rounded value of n w I was 200 (for 3 structure groups), and the lowest was 50 (also for 3 structure groups). For half of the analyzed HLSs (6 structure groups), n w I = 100. It is worth noting that regardless of whether the structure consisting of 50 points was excluded when determining the trend line equation or not, n w I = 200 and n w I = 50 were obtained for the HF2 and HH5 structures, respectively. In summary, n w I 50,100,200 satisfies condition I.
The correctness of the obtained n w I values was confirmed by the sensitivity analysis of the CV coefficient of the parameter Rfr to small variations in n w I (Figure 4). A decrease in n w I results in a clearly larger change in CV than an increase by the same percentage. For example, reducing n w I by 50% causes a 2.4–3.5 times greater change in the CV value than increasing n w I by 50%. Since the CV( n w I ) relationship is a decreasing function, lowering n w I leads to an increase in CV, indicating a greater dispersion of the Rfr parameter values. The results of the analysis therefore confirm that the determined n w I values are indeed the smallest n w values satisfying condition I.

3.2. The Minimum Number of Points for Which the Mean Values of Rfr Remains Almost Constant with Increasing nw (Condition II)

The values of unit differences r f r   i , calculated according to Equation (1), are presented in Table 8. The highest absolute values of r f r   i were observed for the HF5s structure group; however, these values remained close to zero, ranging from 2.6 × 10−4 for n w = 3000 (omitting 0 for n w = 5000) to 25.03 × 10−4 for n w =   n w I . For the remaining HLSs, the absolute values of r f r   i were even lower: from the values of the order of 10−7 (HH5s), 10−6 (HF3s, HH1, HH2, HH7), or 10−5 (HF1, HF2s, HF4s, HH3s, HH4s, HH6s) for n w 2000 , to the values of the order of 10−3 for n w =   n w I .
Although all r f r   i values turned out to be close to zero, they were clearly higher (by 2–3 orders of magnitude) for lower nw values compared to the highest nw. Analyses using Student's t-test showed that for each HLSs group, there exists a structure of size n w I I for which statistic t C I , meaning there is no basis to reject the hypothesis that r f r   i = 0. An example illustrating the determination of the lowest n w I I for which t C I ( n w   g r ) for the structures HF1s is presented in Table 9, while the values of n w   g r for all structures are provided in Table 10. The highest value of n w   g r was n w   g r = 1000, obtained for half of the HLSs groups (6 out of 12). For three HLSs groups, the smallest possible values were obtained— n w   g r = n w I (50 or 100). It can thus be stated that the values of n w   g r vary considerably among the various HLS groups—therefore, one common value of n w   g r cannot be assumed for all HLSs.

3.3. Determination of the Radius of the Water Outflow Zone

The n w   g r values determine representative structures, based on which the radius of the water outflow zone following a failure of an underground water pipeline (RWOZ) can be identified. According to the methodology (Section 2.3), the RWOZ radius was adopted as the Rfr values determined for the representative structures, scaled to real-world conditions (RRC) and rounded to the nearest 0.5 m (Table 11). Final values of RWOZ ranged from 3.5 to 5.5 m.
The RWOZ radius can be expressed mathematically as follows:
R W O Z =     R R C ,    i f   R R C   R R C < 0.25 R R C + 0.5 ,    i f   0.25 R R C   R R C < 0.75 R R C + 1.0 ,    i f   R R C   R R C 0.75   ,
where R R C denotes the entier (the foor function) of R R C .
Taking into account that RRC is the product of Rfr and the inverse of the scale at which the laboratory tests were conducted, and that Rfr is the product of the fractal dimension of the structure ( D b W N ) and the distance (in the laboratory scale) of the point forming the structure that is farthest from the origin of the coordinate system ((Rw)max), the RRC radius can be expressed as follows:
R R C =   1 s   · R f r =   1 s   · D b W N · R w m a x   ,
where s denotes the scale of the laboratory model, Rfr [m], Db, and (Rw)max [m] are values of a representative structure.
Fractal (box-counting) dimension is defined as [39]:
D b W N   = lim δ 0 log N δ W N log δ ,
where W N is a non-empty, bounded subset of a finite-dimensional Euclidean space (in the presented investigations: W N = HF1, …, HF5, HH1, …, HH6 or HH7), D b W N is the box-counting dimension of the set W N , and N δ W N is the smallest number of sets of diameter δ (in the presented investigations: square of side δ) which can cover W N .
The distance (Rw)max can be expressed as:
R w m a x = max 1 i n w gr R w i i N ,
where Rw [m] is the distance in the laboratory scale of any point creating the HLS from the origin and N is the set of natural numbers.
Substituting Equations (6) and (7) into Equation (5), the following expression is obtained:
R R C =   1 s   · lim δ 0 log N δ W N log δ · max 1 i n w gr R w i i N .
Equations (4) and (8) form a system of equations that provides a mathematical description of the RWOZ radius, based on fractal geometry.

3.4. Field Tests Results

As a result of the controlled waterpipe failure in tests A1.1–A1.4, water outflowed at the ground surface through a total of 10 suffosion holes. As many as seven of these occurred during tests A1.3 and A1.4, where sand was used for backfilling the trench. Detailed results of field test experiments A1.1–A1.4 are presented in Table 12 and Figure 5. One outflow hole was observed in the first quadrant of the coordinate system according to drawing 4 (at setup A1.4), two in the second quadrant (at stations A1.1 and A1.2), and two in the third quadrant (at stations A1.1 and A1.3), with by far the most—five—occurring in the fourth quadrant (at stations A1.3 and A1.4). At station A1.2, only one suffosion hole formed—right next to the vertical section of the test pipe. Most likely, the water found a so-called path of least resistance outflow along the pipe. At stations A1.1 and A1.2, the water outflow occurred only within the excavation area, whereas at the other two stations, it extended beyond the excavation boundaries. The average time for water to reach the surface at location A, measured from the start of the experiment, was 18.77 s across all test setups. For tests A1.1 and A1.2, the difference between the outflow times was 3.89 s, with an average of 15.33 s. For setups A1.3 and A1.4, the difference was 6.35 s, and the average time was 22.2 s. Significant differences were therefore observed in the number and location of outflow points, as well as in the time of outflow, when comparing tests with natural soil versus sand backfilling.
In the B2.1–B2.4 series at location B, a total of 9 outflow holes were recorded. Detailed results of field test experiments B2.1–B2.4 are presented in Table 13 and Figure 6. Significantly fewer holes appeared at the stations where the leakage area was smaller (smaller pipe diameter). Only one hole formed in the first quadrant of the coordinate system (station B2.3), three holes in the second quadrant (one each at stations B2.1, B2.2, and B2.4), and five holes in the third quadrant (at stations B2.3 and B2.4). No water outflow hole was observed in the fourth quadrant. The average time for water to reach the ground surface in the B2.1–B2.4 test series was 95.78 s. At stations B2.1 and B2.4, the outflow times were comparable, the difference was only 3.19 s. The average times at stations B2.1 and B2.2, and B2.3 and B2.4, were 127.31 s and 101.65 s, respectively.
In the B3.1–B3.4 series of tests at location B, no water outflowed at station B3.1. The experiment was terminated after 660 s. The most likely reason for the lack of outflow was that the water found a so-called path of least resistance in the form of an underground corridor. At the remaining stations, water emerged in a total of 18 holes. Detailed results of field test experiments B3.1–B3.4 are presented in Table 14 and Figure 7. Station B3.3 was the only one where three water outflow holes were observed directly above the damaged water pipe. Among the other locations, one outflow point was found in both the first and fourth quadrants of the coordinate system (both at station B3.3), eight in the second quadrant (stations B3.2–B3.4), and five in the third quadrant (stations B3.2–B3.4). Excluding station B3.1, the water outflow times in the series B3.1–B3.4 were significantly more varied compared to series B2.1–B2.4. The difference between the longest outflow time (B3.4) and the shortest (B3.3) was 433.81 s, which was nearly twice the average outflow time for stations B3.2–B3.4, amounting to 217.72 s. Only at station B3.4 the outflow time in series B3.1–B3.4 was shorter than in series B2.1–B2.4.

3.5. Empirical Verification

In accordance with the adopted methodology, the results obtained for representative structures HF1–HF3 and HH2–HH4 (i.e., RWOZ = 4.0, 4.5 and 5.0 m) were selected for empirical verification (Table 15).
The verification results are shown in Figure 8a–c. The outflow zones with a radius RWOZ of 4.0 m and 5.5 m fully covered all corresponding actual water outflow points observed on the soil surface during the field tests. In the case of the zone with RWOZ = 4.0 m, 12 out of 18 points were situated no further than 1 m from the pipe leakage location, while the remaining six were no more than 1 m from the theoretical boundary of the zone. The point farthest from the leakage location was located 0.58 m from the zone boundary (Figure 8a). Among the points in the zone with 5.5 m, 8 out of 20 were no further than 1 m from the leakage location, and only one was located no further than 1 m (0.82 m) from the theoretical boundary of the zone (Figure 8c).
The only zone that did not cover all actual points was the one with RWOZ = 4.5 m. All points outside this zone (3 out of 29) corresponded to suffosion holes that formed during the failure simulation at location B: one in series B2.1 (located 0.18 m beyond the theoretical zone boundary) and two in series B2.4 (located 0.37 m and 0.13 m beyond the boundary, respectively). One of the points (also from series B2.4) was located exactly on the zone boundary. Most of the points (18 out of 29) were no further than 1 m from the pipe leakage location (Figure 8b).
The summary of the verification results is presented in Table 16. Two theoretically determined zones provided 100% coverage of the actual points corresponding to suffosion holes, and one provided 90% coverage. Taking into account all analyzed points, 3 out of 67 were located outside their respective zones, which represents only 4%. The overall result of the empirical verification of the proposed method for determining the WOZ radius was therefore considered positive.

4. Summary and Conclusions

This paper presents a method for determining the radius of the surface water outflow zone (RWOZ) resulting from the failure of an underground water pipeline. The development of this method was made possible by previously demonstrating the fractal nature of HLS, obtained using the Monte Carlo method based on laboratory test results, and by showing that the parameter Rfr, which characterizes an HLS and depends on its fractal dimension, plays a key role in determining the dimensions of the water outflow zone (WOZ). In this study, the focus was placed on identifying a representative HLS, i.e., a structure with the smallest possible number of constituent points that simultaneously satisfies two conditions: (I) the values of the Rfr parameter determined for HLSs with the same number of points are clustered around the mean, and (II) the value of Rfr remains statistically constant with increasing number of points in the structure. Statistical analysis (coefficient of variation and Student’s t-test) enabled the determination of the minimum number of points required to satisfy both conditions I and II. The range of the resulting minimum point counts was wide—from 50 to 1000 points—depending on the conditions corresponding to each HLS under which the pipeline failure occurred (i.e., size of leakage and internal pipe pressure).
Based on this analysis, representative structures were identified, for which the Rfr parameter was calculated under laboratory conditions. Subsequently, after scaling to real-world conditions and rounding to 0.5 m, the radius of the WOZ was determined. The resulting RWOZ values ranged from 3.5 to 5.5 m. Based on the performed analyses and the definition of the box-counting fractal dimension, a system of equations for determining the RWOZ was proposed. The theoretical results were empirically validated using measurement data obtained during field investigations under real conditions. The empirical verification confirmed the validity of the proposed method for determining the RWOZ. For zones with radii of 4.0 m and 5.5 m, 100% coverage of the actual outflow points was obtained, while the 4.5 m zone ensured 90% coverage. Considering all points recorded during the field tests, 96% were located within the boundaries of their corresponding theoretical zones.
Determining the WOZs sizes is only one of the issues related to inevitable water pipes failures. However, it is a highly important issue from the perspective of public safety and the protection of existing infrastructure. Therefore, research on water outflow from a pressurized pipe into the soil should be continued. This issue encompasses a wide spectrum of interrelated problems across various scientific disciplines—primarily fluid mechanics, hydrology, and soil rheology—thus a comprehensive understanding of these phenomena remains an open challenge. The determination of the WOZ using fractal geometry provides a novel framework for linking hydraulic processes with spatial risk assessment. The results obtained in this study can be incorporated into decision-support systems for sustainable infrastructure planning, promoting safer and more efficient use of water resources in urban environments. The developed method for determining the WOZ radius can find practical application by water utilities when routing new or renovating existing water pipelines. Including a buffer zone during GIS-based asset management or risk zoning, dependent on hydraulic flow parameters, can significantly reduce the impact of a potential water outflow and formation of suffosion holes on existing infrastructure, making it more resilient.
The research presented in this study focused on the geometric characterization of the set of points corresponding to suffosion holes. It therefore represents only one of the possible approaches to analysing water outflow from a leaking pressurized pipeline into the ground. Future research directions should also include the development of criteria for the location of proposed safety zones. This is a broad issue that requires, on the one hand, an analysis of the reliability of individual components of the water supply network, and on the other, consideration of the density and characteristics of the existing underground infrastructure and above-ground structures. The developed method for determining the WOZ radius can be further verified using CFD analyses and can also provide practical information for GIS and hydraulic modelling-supported spatial infrastructure management systems. It is worth noting that water supply networks are just one of many critical infrastructure systems, so appropriate planning and routing should also take into account interrelationships with other networks, such as transport, gas, and energy. The problem of the complex phenomenon of water flow in soil is currently analyzed not only in relation to water supply system failures [40,41,42,43,44,45], but is also widely examined in the context of other engineering structures [46,47,48,49,50,51,52,53]. The continuous interest of researchers in the water–soil interaction problem reflects the complexity of the phenomenon and highlights its importance in the broader context of safety.

Author Contributions

Conceptualization, M.I.; methodology, M.I.; validation, M.I.; formal analysis, M.I.; investigation, M.I. and P.S.; data curation, M.I.; writing—original draft preparation, M.I. and P.S.; writing—review and editing, M.I. and P.S.; visualization, P.S.; funding acquisition, M.I. and P.S. All authors have read and agreed to the published version of the manuscript.

Funding

This research was funded by internal projects of Lublin University of Technology, Poland, numbers FD-20/IS-6/015 and FD-20/IS-6/034.

Institutional Review Board Statement

Not applicable.

Informed Consent Statement

Not applicable.

Data Availability Statement

The raw data supporting the conclusions of this article will be made available by the authors on request.

Conflicts of Interest

The authors declare no conflicts of interest.

Abbreviations

The following abbreviations are used in this manuscript:
CIcritical interval
CVcoefficient of variation
ELLeconomic level of leakage
GISgeographic information system
HLSshypothetical linear structures
IWAInternational Water Association
RSsreal structures
SDstandard deviation
TLSstheoretical linear structures
WDNwater distribution network
WOZwater outflow zone

References

  1. Mays, L.W. Water Distribution System Handbook, 1st ed.; McGraw-Hill: New York, NY, USA, 2000. [Google Scholar]
  2. Lambert, A.; Hirner, W. Losses from Water Supply Systems: Standard Terminology and Recommended Performance Measures. IWA’s Blue Pages 2000, 1, 1–13. Available online: https://www.wes-med.eu/wp-content/uploads/2023/01/RW-6-REGST-2023.01.16-IWA-2000.pdf (accessed on 27 October 2025).
  3. Farley, M.; Trow, S. Losses in Water Distribution Networks: A Practitioner’s Guide to Assessment, Monitoring and Control; IWA Publication: London, UK, 2003. [Google Scholar]
  4. Drinking Water Directive 2020/2184 (DWD). Directive (EU) 2020/2184 of the European Parliament and of the Council of 16 December 2020 on the Quality of Water Intended for Human Consumption. Document 32020L2184. Available online: https://eur-lex.europa.eu/eli/dir/2020/2184/oj (accessed on 15 October 2025).
  5. Frone, D.F.; Frone, S. Principles for a Sustainable Water Management. In Prospects of Agriculture and Rural Areas in the Context of Durable Development; Scientific Papers “Management, Economic Engineering in Agriculture and Rural Development”; University of Agricultural Sciences and Veterinary Medicine: Bucharest, Romania, 2011; Volume 11, pp. 35–40. Available online: https://www.cabidigitallibrary.org/doi/pdf/10.5555/20123354269 (accessed on 15 October 2025).
  6. Żywiec, J.; Tchórzewska-Cieślak, B. Water Loss Analysis as an Element of Operation Management of Water Supply System. J. KONBIN 2019, 49, 55–77. (In Polish) [Google Scholar] [CrossRef]
  7. Berardi, L.; Laucelli, D.B.; Ripani, S.; Piazza, S.; Freni, G. Using Water Loss Performance Indicators to Support Regulation and Planning in Real Water Distribution Systems. Digit. Water 2025, 3, 1–20. [Google Scholar] [CrossRef]
  8. Arregui, F.J.; Cobacho, R.; Soriano, J.; Jimenez-Redal, R. Calculation Proposal for the Economic Level of Apparent Losses (ELAL) in a Water Supply System. Water 2018, 10, 1809. [Google Scholar] [CrossRef]
  9. Yilmaz, S.; Firat, M.; Ateş, A.; Özdemir, Ö. Analyzing the economic water loss level with a discrete stochastic optimization algorithm by considering budget constraints. AQUA—Water Infrastruct. Ecosyst. Soc. 2022, 71, 835–848. [Google Scholar] [CrossRef]
  10. Firat, M.; Yilmaz, S.; Ateş, A.; Özdemir, Ö. Determination of economic leakage level with optimization algorithm in water distribution systems. Water Econ. Policy 2021, 7, 2150014. [Google Scholar] [CrossRef]
  11. Water Resilience Strategy. Available online: https://commission.europa.eu/topics/environment/water-resilience-strategy_en (accessed on 15 October 2025).
  12. Farah, E.; Shahrour, I. Water Leak Detection: A Comprehensive Review of Methods, Challenges, and Future Directions. Water 2024, 16, 2975. [Google Scholar] [CrossRef]
  13. Joseph, K.; Sharma, A.K.; van Staden, R.; Wasantha, P.L.P.; Cotton, J.; Small, S. Application of Software and Hardware-Based Technologies in Leaks and Burst Detection in Water Pipe Networks: A Literature Review. Water 2023, 15, 2046. [Google Scholar] [CrossRef]
  14. Rajan, G.; Li, S. A Systematic Literature Review on Flow Data-Based Techniques for Automated Leak Management in Water Distribution Systems. Smart Cities 2025, 8, 78. [Google Scholar] [CrossRef]
  15. El-Zahab, S.; Zayed, T. Leak detection in water distribution networks: An introductory overview. Smart Water 2019, 4, 5. [Google Scholar] [CrossRef]
  16. Steffelbauer, D.B.; Fuchs-Hanusch, D. Efficient Sensor Placement for Leak Localization Considering Uncertainties. Water Resour. Manag. 2016, 30, 5517–5533. [Google Scholar] [CrossRef]
  17. Ali, H.; Choi, J.-h. A Review of Underground Pipeline Leakage and Sinkhole Monitoring Methods Based on Wireless Sensor Networking. Sustainability 2019, 11, 4007. [Google Scholar] [CrossRef]
  18. Directive (EU) 2022/2557 of the European Parliament and of the Council of 14 December 2022 on the Resilience of Critical Entities and Repealing Council Directive 2008/114/EC. Available online: https://eur-lex.europa.eu/eli/dir/2022/2557/oj/eng (accessed on 15 October 2025).
  19. Pamidimukkala, A.; Kermanshachi, S.; Adepu, N.; Safapour, E. Resilience in Water Infrastructures: A Review of Challenges and Adoption Strategies. Sustainability 2021, 13, 12986. [Google Scholar] [CrossRef]
  20. Laucelli, D.; Rajani, B.; Kleiner, Y.; Giustolisi, O. Study on relationships between climate-related covariates and pipe bursts using evolutionary-based modeling. J. Hydroinform. 2014, 16, 743–757. [Google Scholar] [CrossRef]
  21. Wéber, R.; Huzsvár, T.; Hős, C. Vulnerability analysis of water distribution networks to accidental pipe burst. Water Res. 2020, 184, 116178. [Google Scholar] [CrossRef]
  22. Barton, N.A.; Hallett, S.H.; Jude, S.R.; Tran, T.H. An evolution of statistical pipe failure models for drinking water networks: A targeted review. Water Supply 2022, 22, 3784–3813. [Google Scholar] [CrossRef]
  23. Beygi, S.; Van Zyl, J. Pilot study on the characteristics of different failure types in water distribution system pipes. J. Pipeline Syst. Eng. Pract. 2024, 15, 04024027. [Google Scholar] [CrossRef]
  24. Jara-Arriagada, C.; Stoianov, I. Pressure-induced fatigue failures in cast iron water supply pipes. Eng. Fail. Anal. 2024, 155, 107731. [Google Scholar] [CrossRef]
  25. Kovács, G.; Ujfaludi, L. Movement of fine grains in the vicinity of well screens. Hydrol. Sci. J. 1983, 28, 247–260. [Google Scholar] [CrossRef]
  26. Mao, J.; Wang, Y.; Zhang, H.; Jing, X. Study on the Influence of Urban Water Supply Pipeline Leakage on the Scouring Failure Law of Cohesive Soil Subgrade. Water 2024, 16, 93. [Google Scholar] [CrossRef]
  27. Iwanek, M.; Malesińska, A. Zastosowanie teorii podobieństwa w modelowaniu awarii sieci wodociągowych. Gaz Woda Tech. Sanit. 2015, 3, 82–86. (In Polish) [Google Scholar] [CrossRef]
  28. Iwanek, M.; Kowalska, B.; Hawryluk, E.; Kondraciuk, K. Distance and time of water effluence on soil surface after failure of buried water pipe. Laboratory investigations and statistical analysis. Eksploat. Niezawodn.–Maint. Reliab. 2016, 2, 278–284. [Google Scholar] [CrossRef]
  29. Iwanek, M.; Suchorab, P. Fractal Characteristics of Water Outflows on the Soil Surface after a Pipe Failure. Water 2024, 16, 1222. [Google Scholar] [CrossRef]
  30. Iwanek, M.; Suchorab, P.; Karpińska-Kiełbasa, M. Suffosion holes as the results of breakage of buried water pipe. Period. Polytech.–Civ. Eng. 2017, 4, 700–705. [Google Scholar] [CrossRef][Green Version]
  31. Iwanek, M. Set of suffosion holes occurring after a water supply failure as a structure with fractal features. J. Ecol. Eng. 2022, 23, 164–171. [Google Scholar] [CrossRef]
  32. Iwanek, M.; Suchorab, P.; Hawryluk, E.; Kondraciuk, K. Influence of chosen parameters on dimensions of suffosion hole after buried water pipe’s failure. In Water Supply and Wastewater Removal; Sobczuk, H., Kowalska, B., Eds.; Lublin University of Technology: Lublin, Poland, 2016; pp. 55–67. [Google Scholar]
  33. Iwanek, M.; Suchorab, P. Feasibility of Using Hypothetical Fractal Structures to Determine Water Outflow Zones After a Pipe Failure. Sustainability 2024, 16, 10640. [Google Scholar] [CrossRef]
  34. Iwanek, M. Parameters characterizing leakages from damaged water pipes in the aspect of environmental security. Appl. Water Sci. 2022, 12, 126. [Google Scholar] [CrossRef]
  35. Ng, B.; Quinete, N.; Gardinali, P.R. Assessing accuracy, precision and selectivity using quality controls for non-targeted analysis. Sci. Total Environ. 2020, 713, 136568. [Google Scholar] [CrossRef] [PubMed]
  36. Bruzzoniti, M.C.; Rivoira, L.; Castiglioni, M.; Cagno, E.; Kettab, A.; Fibbi, D.; Del Bubba, M. Optimization and validation of a method based on QuEChERS extraction and gas chromatographic-mass spectrometric analysis for the determination of polycyclic aromatic hydrocarbons and polychlorinated biphenyls in olive fruits irrigated with treated wastewaters. Separations 2022, 9, 82. [Google Scholar] [CrossRef]
  37. Gains, K.K.K.; Roland, N.G.K.; Urbain, K.Y.; Ardjouma, D. Determination of the glyphosate content in liquid and dry formulations by HPLC-UV: Pre-column derivation with 9-fluorenylmethyl chloroformate (FMOC). Chromatographia 2022, 85, 655–664. [Google Scholar] [CrossRef]
  38. Wei, L.; Li, J.; Zhang, J.; Qu, K.; Wang, M.; Ni, T.; Miao, Y.; Luo, M.; Feng, S.; Liu, D. Response surface modelling of six organic acids from Pinellia ternata (Thunb.) breit by ultrasound-assisted extraction and its determination by high-performance liquid chromatography coupled to triple quadrupole mass spectrometry. Chemosensors 2024, 12, 47. [Google Scholar] [CrossRef]
  39. Falconer, K. Fractal Geometry: Mathematical Foundations and Applications; John Wiley & Sons: Chichester, UK, 2004. [Google Scholar]
  40. Monzer, A.; Faramarzi, A.; Yerro, A.; Chapman, D. MPM investigation of the fluidization initiation and postfluidization mechanism around a pressurized leaking pipe. J. Geotech. Geoenviron. Eng. 2023, 149, 04023096. [Google Scholar] [CrossRef]
  41. Sharafodin, S.; Latifi, M.; Ghodsian, M. Experimental Investigation of Leakage Flow Rate and Fluidisation beneath Polyethylene Pipes in Non-Uniform Soils. Water 2024, 16, 1156. [Google Scholar] [CrossRef]
  42. Cui, J.; Liu, F.; Chen, R.; Wang, S.; Pu, C.; Zhao, X. Effects of Internal Pressure on Urban Water Supply Pipeline Leakage-Induced Soil Subsidence Mechanisms. Geofluids 2024, 2024, 9577375. [Google Scholar] [CrossRef]
  43. Wang, S.; Liu, F.; Wang, K.; Cui, J.; Zhao, X. Numerical Analysis of Seepage Damage and Saturation Variation in Surrounding Soil Induced by Municipal Pipeline Leakage. Appl. Sci. 2025, 15, 11088. [Google Scholar] [CrossRef]
  44. Abegaz, R.; Wang, F.; Xu, J.; Pierce, T.; Moody, M. Developing Soil Internal Erosion Indicator to Quantify Soil Internal Erosion around Defective Buried Pipes under Water Exfiltration. Geotech. Test. J. 2025, 48, 623–641. [Google Scholar] [CrossRef]
  45. Wang, H.; Zheng, Z.; Yu, T.; Ma, Y.; Zhang, Y. Experimental Study of Fluidization and Defluidization Processes in Sand Bed Induced by a Leaking Pipe. Appl. Sci. 2025, 15, 9618. [Google Scholar] [CrossRef]
  46. Bonelli, S.; Girolami, L. Internal erosion of sandy gravels and occurrence of open-framework gravels in the subsoil of a river dike. Geomech. Energy Environ. 2025, 42, 100690. [Google Scholar] [CrossRef]
  47. Greene, E.A.; Zheng, G.; Cheng, X.; Zhaolin, C. Multiple Water and Sand Leakage Model Tests for Shield Tunnels. Buildings 2024, 14, 3820. [Google Scholar] [CrossRef]
  48. Yu, J.; Zhang, Y.; Li, D.; Zheng, J.; Zhang, W. Analytical study of steady state seepage field in tunnels with localized water leakage under the effect of grouting circle. Tunn. Undergr. Space Technol. 2024, 150, 105854. [Google Scholar] [CrossRef]
  49. Qin, T.; Song, Z.; Wang, C.; Liang, F. Two-point MPM study of fluidized grains in internal erosion around metro tunnel characterized by an erosion law. Comput. Geotech. 2025, 183, 107227. [Google Scholar] [CrossRef]
  50. Sun, Q.; Liu, X.; Bao, Y.; De Corte, W.; Taerwe, L. Mechanistic Analysis of Leakage-Induced Tunnel Collapse: Case Study from Shanghai Metro Line 4. Geotech. Geol. Eng. 2025, 43, 398. [Google Scholar] [CrossRef]
  51. Shen, Z.; Zhao, Y.; Lv, Y.; Wang, P.; Hu, N.; Shu, F.; Gao, H.; Wang, Z. Upward propagation of ground disturbance induced by water–sand inrush into a defective tunnel in a dual-stratum geological condition. Tunn. Undergr. Space Technol. 2025, 158, 106422. [Google Scholar] [CrossRef]
  52. Xie, J.; Molins, C.; Huang, X. A hydro-mechanical coupled method for assessing the influence of localised leakage at gasketed joints on the long-term behaviour of shield tunnels. Tunn. Undergr. Space Technol. 2025, 159, 106492. [Google Scholar] [CrossRef]
  53. Xie, T.; Zhu, H.; Dong, Y.; Zhou, M.; Wang, B.; Zhang, W.; Zhao, J. Geo-interface modeling with material point method: A review. J. Rock Mech. Geotech. Eng. 2025, 17, 3950–3972. [Google Scholar] [CrossRef]
Figure 1. Block diagram of research of determining the water outflow zone.
Figure 1. Block diagram of research of determining the water outflow zone.
Sustainability 17 11093 g001
Figure 2. No-scale scheme of the field tests setup (1—water supply; 2—ball valve; 3—pressure gauge; 4—PE-HD water pipe; 5—leak location; 6—free discharge; 7—potential outflow localization, H—pipe depth; L—pipe length).
Figure 2. No-scale scheme of the field tests setup (1—water supply; 2—ball valve; 3—pressure gauge; 4—PE-HD water pipe; 5—leak location; 6—free discharge; 7—potential outflow localization, H—pipe depth; L—pipe length).
Sustainability 17 11093 g002
Figure 3. Plot of the relationship between the coefficient CV of the Rfr parameter and nw.
Figure 3. Plot of the relationship between the coefficient CV of the Rfr parameter and nw.
Sustainability 17 11093 g003
Figure 4. The effect of changing the n w I value within the range of ±50% on the percentage change in the CV value of the Rfr parameter.
Figure 4. The effect of changing the n w I value within the range of ±50% on the percentage change in the CV value of the Rfr parameter.
Sustainability 17 11093 g004
Figure 5. The distribution of points corresponding to water outflows during series A1.1–A1.4.
Figure 5. The distribution of points corresponding to water outflows during series A1.1–A1.4.
Sustainability 17 11093 g005
Figure 6. The distribution of points corresponding to water outflows during series B2.1–B2.4.
Figure 6. The distribution of points corresponding to water outflows during series B2.1–B2.4.
Sustainability 17 11093 g006
Figure 7. The distribution of points corresponding to water outflows during series B3.2–B3.4.
Figure 7. The distribution of points corresponding to water outflows during series B3.2–B3.4.
Sustainability 17 11093 g007
Figure 8. Coverage of actual points by the theoretical zone with radius RWOZ equal to (a) 4.0, (b) 4.5 and (c) 5.5 m.
Figure 8. Coverage of actual points by the theoretical zone with radius RWOZ equal to (a) 4.0, (b) 4.5 and (c) 5.5 m.
Sustainability 17 11093 g008
Table 1. Names of fractal structures depending on corresponding laboratory tests conditions.
Table 1. Names of fractal structures depending on corresponding laboratory tests conditions.
Type of Struct.Leak Area [cm2]Pressure Height [m H2O]
2.834.719.4215.0718.843.03.54.04.55.05.56.0
RSF1F2F3F4F5H1H2H3H4H5H6H7
TLSF1″F2″F3″F4″F5″H1″H2″H3″H4″H5″H6″H7″
HLSHF1HF2HF3HF4HF5HH1HH2HH3HH4HH5HH6HH7
Table 2. Mean values of the Rfr parameter for hypothetical linear structures [33].
Table 2. Mean values of the Rfr parameter for hypothetical linear structures [33].
nwRfr [cm] for HLSs:
HF1sHF2sHF3sHF4sHF5sHH1sHH2sHH3sHH4sHH5sHH6sHH7s
5030.1837.8934.8835.9134.3332.6133.8035.0032.9036.1338.3535.71
10034.0541.9241.2542.9339.8739.7839.4142.7839.4340.1844.8945.24
20038.3448.0745.5548.5445.9942.5142.0947.7642.9541.8748.7048.67
30040.5548.9146.6350.6648.2643.1244.1452.3643.8442.2850.8449.75
40042.2050.6446.6751.6050.6043.8144.7753.0743.9342.3551.2150.32
50042.3552.0746.7851.7652.1044.2745.0354.8644.3342.3652.3150.44
60043.1953.8946.9351.3452.9644.2444.9954.4744.5742.3952.2550.54
70043.3453.3746.9852.5754.3744.3145.1856.0144.5842.3652.8650.50
80043.2954.2047.0753.1753.7244.4645.2355.8344.7142.3852.5750.53
90043.0654.3547.1952.9153.8644.7145.4055.9144.6542.3752.1650.62
100043.3854.3747.2353.4854.7544.6545.3857.0344.7542.3752.8750.66
150043.5055.3447.2553.4355.7944.7745.4957.7644.6842.3952.9550.60
200043.7355.6747.1553.6656.8144.7945.5457.6544.7542.4053.1450.67
300043.6755.8547.1653.8257.4844.8045.5658.1544.7842.4153.1450.68
400043.6655.8847.1253.9557.6044.8145.5358.1344.8042.4053.1550.71
500043.6455.9347.1353.9458.0044.8245.5658.1944.8242.4153.1850.71
Table 3. Field tests setup details.
Table 3. Field tests setup details.
Field Tests SeriesBedding and Backfill SoilPipeExcavation TrenchTests Time in Months After ConstructionPressure
MaterialDiameterLengthWidthDepth
DN × g (mm)(m)(m)(m)(m H2O)
A1.1, A1.2
A1.3, A1.4
natural sandPE-HD63 × 3.84.00.71.65741.0
B2.1, B2.2naturalPE-HD110 × 4.25.00.51.90936.5
B2.3, B2.4200 × 7.7
B3.1, B3.2naturalPE-HD110 × 4.25.00.51.902245.0
B3.3, B3.4200 × 7.7
Table 4. Representative structures (HLSs) selected for empirical verification according to pipe diameter.
Table 4. Representative structures (HLSs) selected for empirical verification according to pipe diameter.
HLSField TestsLaboratory Tests
SiteSeriesDiameter (mm)In. Diameter (mm)Data Set (RS)
HF1AA1.1–A1.463 × 3.86.0F1
HF2BB2.1, B2.2, B3.1, B3.2110 × 4.210.0F2
HF3BB2.3, B2.4, B3.3, B3.4200 × 7.720.0F3
Table 5. Representative structures HLSs selected for empirical verification according to internal pressure in the pipe.
Table 5. Representative structures HLSs selected for empirical verification according to internal pressure in the pipe.
HLSField TestsLaboratory Tests
SiteSeriesPressure (m H2O)Pressure (m H2O)Data Set (RS)
HH2BB2.1, B2.2, B2.3, B2.436.53.5H2
HH3AA1.1–A1.441.04.0H3
HH4BB3.1, B3.2, B3.3, B3.445.04.5H4
Table 6. CV of the Rfr parameter.
Table 6. CV of the Rfr parameter.
nwCV [%] of Rfr for HLSs:
HF1sHF2sHF3sHF4sHF5sHH1sHH2sHH3sHH4sHH5sHH6sHH7s
508.985.343.875.4611.808.146.9614.399.202.237.956.98
1008.208.873.455.287.054.864.137.313.133.626.982.23
2003.605.971.724.114.313.273.844.061.800.754.621.59
3002.474.501.102.676.602.091.526.551.810.221.791.52
4002.084.311.241.753.341.571.473.390.950.122.790.69
5002.094.841.053.533.790.890.822.560.630.171.480.67
6001.223.140.781.862.990.610.763.390.840.051.430.51
7001.112.360.731.032.210.620.601.310.390.120.500.46
8000.771.800.430.573.390.420.611.920.390.061.630.51
9001.501.300.350.653.720.460.421.620.420.101.650.41
10001.481.530.380.951.250.350.420.880.250.090.810.36
15000.591.140.380.881.980.150.160.880.270.090.660.44
20000.890.550.350.851.280.140.071.360.180.030.410.42
30000.460.330.360.601.260.070.040.390.110.010.380.35
40000.360.310.280.171.210.060.150.660.050.020.290.33
50000.380.310.310.200.430.040.050.590.040.010.350.32
Table 7. Trend lines of the CV(nw) relationships.
Table 7. Trend lines of the CV(nw) relationships.
HLSsTrendline Equation R2 n w I
CalculatedRounded
HF1sCV = 181.00nw−0.7430.9331125.27100
HF2sCV = 380.82nw−0.8160.5147202.33200
HF2s *CV = 492.19nw−0.8840.8294179.77200
HF3sCV = 44.298nw−0.630.945831.9050
HF4sCV = 180.43nw−0.7650.7729108.58100
HF5sCV = 134.21nw−0.6000.9049240.63200
HH1sCV = 1807.5nw−1.2440.9331113.86100
HH2sCV = 1210.0nw−1.1830.8947103.53100
HH3sCV = 260.3nw−0.7450.9350201.39200
HH4sCV = 763.04nw−1.1250.980887.29100
HH5sCV = 382.51nw−1.2420.598432.8650
HH5s *CV = 199.34nw−1.1970.940821.7450
HH6sCV = 214.91nw−0.7870.9007118.94100
HH7sCV = 39.432nw−0.6200.884527.9650
* The HLS composed of 50 points was excluded from the analysis.
Table 8. Results of the relative difference r f r   i calculations.
Table 8. Results of the relative difference r f r   i calculations.
nw r f r   i · 10 4 for HLSs:
HF1sHF2sHF3sHF4sHF5sHH1sHH2sHH3sHH4sHH5sHH6sHH7s
5024.7512.6730.30
10019.5712.0022.4710.2812.5511.004.5416.9211.16
20011.0416.363.2911.2425.034.807.2321.743.891.139.334.25
3006.5614.941.056.9720.733.633.0114.262.080.274.982.04
4003.1311.500.995.0916.082.191.7211.131.930.124.280.86
5002.868.570.774.8513.121.221.187.411.090.111.930.60
6001.034.640.445.9011.461.311.308.460.570.042.100.39
7000.695.960.333.198.451.200.885.080.570.120.750.49
8000.834.110.151.8310.200.860.775.610.270.051.450.42
9001.403.85−0.152.5110.110.280.395.560.430.082.470.22
10000.643.91−0.251.158.130.420.452.910.190.090.760.12
15000.411.69−0.361.456.310.150.183.320.420.040.660.30
2000−0.300.86−0.090.923.970.090.071.810.230.030.140.28
3000−0.160.41−0.160.612.600.11−0.030.200.210.000.180.14
4000−0.250.450.06−0.154.040.120.270.660.210.040.30−0.02
50000.000.000.000.000.000.000.000.000.000.000.000.00
Table 9. Determination of the n w   g r value for the structures HF1s.
Table 9. Determination of the n w   g r value for the structures HF1s.
n w Degrees of Freedomt t c r t C I ?
100132.17512.1604no
200122.27262.1788no
300112.36922.2010no
400102.55572.2281no
50092.26812.2622no
600 *82.23022.3060yes
70071.77602.3646yes
80061.39632.4469yes
90050.96952.5706yes
100040.31042.7765yes
15003−0.40783.1824yes
20002−1.85324.3027yes
30001−3.243712.706yes
* n w =   n w   g r as the lowest n w for which t C I .
Table 10. Results of the one-sample Student’s t-test for HLSs consisted of n w   g r points.
Table 10. Results of the one-sample Student’s t-test for HLSs consisted of n w   g r points.
HLS n w   g r SD [cm]t t c r t C I ?
HF16000.0000602.23022.3060yes
HF210000.0001462.00542.7765yes
HF34000.0000432.14852.2281yes
HF410000.0000612.58702.7765yes
HF510000.0002192.57192.7765yes
HH110000.0000142.59512.7765yes
HH210000.0000182.02172.7765yes
HH310000.0001362.61282.7765yes
HH41000.0002892.05692.1604yes
HH5500.0003361.43682.1448yes
HH69000.0000881.90852.5706yes
HH7500.0007971.61342.1448yes
Table 11. The Rfr values of representative structures and RWOZ.
Table 11. The Rfr values of representative structures and RWOZ.
HLS n w   g r Rfr [cm] (Table 1)RRC [m]RWOZ [m]
HF160043.194.324.5
HF2100054.375.445.5
HF340046.674.674.5
HF4100053.485.355.5
HF5100054.755.485.5
HH1100044.654.474.5
HH2100045.384.544.5
HH3100057.035.705.5
HH410039.433.944.0
HH55036.133.613.5
HH690052.165.225.0
HH75035.713.573.5
Table 12. Field tests results—series A1.1–A1.4.
Table 12. Field tests results—series A1.1–A1.4.
Field Tests SeriesType of Soil in the ExcavationDiameterPressureOutflow Time tNumber of Outflows
DN × g
(mm)(m H2O)s
A1.1natural63 × 3.841.013.392
A1.2natural63 × 3.841.017.281
A1.3sand63 × 3.841.025.384
A1.4sand63 × 3.841.019.033
Table 13. Field tests results—series B2.1–B2.4.
Table 13. Field tests results—series B2.1–B2.4.
Field Tests SeriesType of Soil in the ExcavationDiameterPressureOutflow Time tNumber of Outflows
DN × g
(mm)(m H2O)s
B2.1natural110 × 4.236.574.811
B2.2natural110 × 4.236.5105.001
B2.3natural200 × 7.736.5125.302
B2.4natural200 × 7.736.578.005
Table 14. Field tests results—series B3.1–B3.4.
Table 14. Field tests results—series B3.1–B3.4.
Field Tests SeriesType of Soil in the ExcavationDiameterPressureOutflow Time tNumber of Outflows
DN × g
(mm)(m H2O)s
B3.1natural110 × 4.245.0>6600
B3.2natural110 × 4.245.0147.988
B3.3natural200 × 7.745.037.197
B3.4natural200 × 7.745.047.103
Table 15. RWOZ results of representative structures (HLSs) selected for empirical verification with corresponding field test series.
Table 15. RWOZ results of representative structures (HLSs) selected for empirical verification with corresponding field test series.
HLSHF1HF2HF3HH2HH3HH4
RWOZ4.55.54.54.55.54.0
Field Test SeriesA1.1–A1.4B2.1, B2.2, B3.1, B3.2B2.3, B2.4, B3.3, B3.4B2.1, B2.2, B2.3, B2.4A1.1–A1.4B3.1, B3.2, B3.3, B3.4
Table 16. Summary of the empirical verification results.
Table 16. Summary of the empirical verification results.
RWOZRwNumber of Actual PointsPercentage of Points Outside the Zone
TotalInside the ZoneOutside the Zone
4.00.00–3.42181800%
4.50.00–4.872926310%
5.50.13–4.68202000%
Total for zones676434%
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Iwanek, M.; Suchorab, P. Determination of the Water Outflow Zone on the Ground Surface After a Pipe Failure Using Fractal Geometry. Sustainability 2025, 17, 11093. https://doi.org/10.3390/su172411093

AMA Style

Iwanek M, Suchorab P. Determination of the Water Outflow Zone on the Ground Surface After a Pipe Failure Using Fractal Geometry. Sustainability. 2025; 17(24):11093. https://doi.org/10.3390/su172411093

Chicago/Turabian Style

Iwanek, Małgorzata, and Paweł Suchorab. 2025. "Determination of the Water Outflow Zone on the Ground Surface After a Pipe Failure Using Fractal Geometry" Sustainability 17, no. 24: 11093. https://doi.org/10.3390/su172411093

APA Style

Iwanek, M., & Suchorab, P. (2025). Determination of the Water Outflow Zone on the Ground Surface After a Pipe Failure Using Fractal Geometry. Sustainability, 17(24), 11093. https://doi.org/10.3390/su172411093

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop