1. Introduction
Relay protection testing is an essential part of commissioning, periodic inspection, and maintenance in substations. During the switching test, the operating logic of the protection system is verified by checking the interaction among protection outputs, circuit-breaker control circuits, and breaker position feedback signals. The test serves as an important method to verify the integrity of secondary circuits and the correctness of protection logic, which is important for equipment commissioning and maintenance [
1,
2,
3,
4,
5,
6].
However, conventional field testing relies heavily on the operation of physical circuit breakers. This practice becomes increasingly difficult when protection functions involve multiple breakers and complex logical relationships. For example, automatic bus transfer (ABT) schemes require the protection system to identify the operating states of both the main and standby power supplies. The verification of such functions therefore requires coordinated changes in multiple breaker position signals. In substations undergoing phased construction, technical modification, or periodic maintenance, however, physical breaker operation may be restricted by power supply reliability requirements. As a result, the complete control and feedback loop of the protection system cannot always be verified under actual operating conditions [
7,
8,
9,
10,
11].
Similar difficulties arise in the testing of protection systems with multiple trip outputs. Busbar protection, transformer protection, and under-frequency or under-voltage load-shedding systems may involve multiple circuit-breaker outputs, interlocking conditions, and sequential operations. Conventional point-by-point verification using test switches or multimeters can confirm individual signals, but it is difficult to reproduce the coordinated state transitions of several circuit breakers within a complete protection logic loop [
9,
12,
13]. Moreover, repeated manual operations at energized protection panels increase the possibility of wiring errors and unintended operations. Repeated mechanical operations of physical circuit breakers during testing may also introduce unnecessary mechanical wear [
14].
As summarized in
Table 1, conventional operational testing and point-by-point testing with multiple instruments mainly verify individual signals or local functions. When coordinated reproduction of multiple circuit-breaker states is required, extensive temporary wiring and manual switching are typically necessary, making it difficult to efficiently reproduce complex multi-breaker state sequences. Existing integrated testing platforms can provide various analog and digital input/output channels and support the generation of coordinated test sequences [
5,
6,
15]. However, these platforms are typically implemented in benchtop or rack-mounted configurations, which limits their flexibility in configuring distributed breaker-state signals and their portability for on-site applications. Therefore, a portable verification method for on-site applications is required to maintain closed-loop interaction with the relay protection system while enabling flexible reproduction, coordinated control, and centralized monitoring of multiple distributed circuit-breaker states [
1,
14].
The proposed method replaces the physical switching actions of selected high-voltage circuit breakers with electrically isolated simulated breaker interfaces. Multiple simulated breaker nodes can be distributed according to the physical locations of the tested circuits. Their states are acquired and coordinated through a master–slave communication architecture, while the protection-device outputs and simulated breaker position feedback form a closed verification loop. This approach enables complex multi-breaker protection logic to be reproduced without repeatedly operating the corresponding primary equipment.
LoRa communication is employed as the wireless communication medium because the proposed application requires communication between the master unit and distributed slave nodes in a substation environment. LoRa-based communication has been investigated for sensing and monitoring applications in electrical substations, demonstrating its applicability to distributed electrical equipment monitoring [
16,
17]. In addition, LoRa has been applied to power-grid data transmission systems, providing a basis for its use in distributed monitoring and communication applications [
18]. A polling-based communication mechanism is implemented to collect the states of multiple simulated breaker nodes and to detect communication abnormalities. The collected states are then transferred to a mobile human–machine interface (HMI), allowing the operator to monitor the complete set of simulated breaker states during testing.
Based on this approach, a portable relay protection auxiliary verification device is developed. The device integrates 220 V and 24 VDC simulated circuit-breaker interfaces to accommodate different protection and control circuits. The 220 V interface is intended to reproduce conventional breaker closing and tripping operations, whereas the 24 VDC interfaces are designed for protection logic verification involving multiple low-voltage outputs. The proposed architecture allows several simulated breakers to operate independently while their states are centrally monitored. This configuration is intended to support the verification of ABT, busbar protection, transformer protection, and under-frequency or under-voltage load-shedding logic without requiring repeated operation of physical high-voltage breakers [
19].
The remainder of this paper is organized as follows.
Section 2 introduces the proposed physical breaker state emulation method, including the overall verification architecture, simulated circuit-breaker state model, communication and synchronization mechanism, and protection logic verification strategy.
Section 3 describes the hardware and software implementation of the proposed device, including the simulated breaker interfaces and remote monitoring system.
Section 4 presents the experimental and field verification results, including single-breaker, coupled ABT, and multi-output protection tests, followed by a quantitative comparison with conventional testing approaches and a discussion of practical limitations. Finally,
Section 5 concludes the study and summarizes the main findings.
2. Methodology and System Design
This paper proposes a portable auxiliary verification device for relay protection applied to the on-site periodic inspection of substation relay protection systems. The proposed device integrates multi-channel circuit breaker simulator status display and wireless remote centralized monitoring functions, as shown in
Figure 1. A star topology architecture consisting of one master unit and n slave units is adopted in the system. Within the overall architecture, bidirectional data exchange between the master unit and the outdoor distributed sub-units is achieved through a LoRa wireless communication network, thereby realizing remote control of the entire distributed verification system. Additionally, a human–machine interface (HMI) based on mobile terminals is incorporated. Aggregated data are transmitted from the master control unit to Android-based mobile devices via a Bluetooth module. Consequently, test personnel can remotely and intuitively monitor the “Trip” and “Close” positions of all n circuit breaker simulator modules in real time via smartphones, tablets, or remote computer browsers.
Furthermore, utilizing the microcontroller units, the master and slave devices determine the status of data transmission and reception via broadcast packets. Optocoupler isolation circuits are employed to independently collect and transmit the operational status of each circuit breaker simulator module. When an anomaly occurs (e.g., a sub-unit fails to respond within the designated time window), the microcontroller initiates exception-handling logic and triggers an offline alarm via LED indicators on the device panel.
2.1. Circuit-Breaker State Model
The simulated circuit breaker is modeled according to the operating behavior required for relay protection verification. The model represents not only the breaker position but also the event that causes a state transition and the auxiliary memory required by specific protection logic. This enables the simulated breaker to reproduce the logical behavior of an actual circuit breaker without mechanically operating the primary equipment.
For the
-th simulated circuit breaker, the basic position state is defined as:
where OPEN and CLOSED represent the open and closed positions, respectively. These two states describe the physical position that is fed back to the relay protection system.
The operation event is separately defined as:
The TRIP event indicates that the opening operation is initiated by a protection output, and the MANUAL_OPEN event indicates manual opening command, whereas RESET represents a manual operation used to clear the corresponding latched logic when required by the ABT verification process.
For ABT verification, an additional auxiliary memory state is introduced to reproduce the event-dependent behavior of the simulated breaker. It can be represented by:
where
indicates that the protection-related post-closing/interlock memory is active. This auxiliary state allows the simulator to distinguish a protection-initiated trip from a manually initiated opening even when both operations result in the same open position.
Therefore, the complete state representation of a simulated circuit breaker can be expressed as:
The state-transition rules used by the simulated circuit-breaker interfaces are summarized in
Table 2.
2.2. Communication and Synchronization Mechanism
The distributed circuit-breaker state emulation method requires the states of simulated circuit breakers located at different nodes to be acquired and aggregated by the master unit. Therefore, a communication and synchronization mechanism is required to coordinate the distributed slave units and maintain a consistent representation of breaker states at the master side. As shown in
Figure 2, a master–slave polling mechanism is adopted. The master unit periodically initiates communication, while each slave unit responds to the broadcast request and reports the local simulated circuit-breaker states.
The communication process consists of four main stages: node availability detection, handshake response, local state acquisition, and state-frame transmission. The communication mechanism is implemented using LoRa wireless communication.
2.2.1. Master-Side Polling Mechanism
After system initialization, the master unit initializes the required communication interfaces and enters the slave-node polling process. For each polling cycle, the master first determines whether the corresponding slave unit is connected. If the node is available, its online status is read and the master proceeds to acquire the state information of the distributed simulated breakers. If no valid response is received within the specified communication period, the corresponding node is identified as offline and a single-point communication fault alarm is triggered.
After the slave-node status has been determined, the master unit reads the state of the locally connected simulated circuit breakers. The states received from the slave units and the local states are then aggregated into a unified state representation and transmitted to the human–machine interface (HMI).
This sequential polling mechanism allows the master unit to obtain the states of multiple distributed nodes within each communication cycle. Compared with independent point-to-point monitoring, the mechanism provides a unified channel for collecting and reconstructing the states of distributed simulated circuit breakers.
2.2.2. Slave-Side Response and Local State Acquisition
The operating sequence of a slave unit is shown in
Figure 3. After initialization, the slave unit remains in the communication waiting state and continuously monitors the wireless channel for a broadcast request from the master unit.
When a valid broadcast request is received, the slave unit first transmits a handshake response to indicate that the communication link is available. The slave unit then determines whether a state-read command has been received. If the command is valid, the slave controller acquires the local input/output status associated with the simulated circuit-breaker channels.
The acquired states are subsequently organized into a communication frame and transmitted to the master unit. After the transmission is completed, the slave unit returns to the waiting state for the next polling request. The communication frame contains the node-related and breaker-state information required by the master unit for subsequent state aggregation.
The master unit combines the state information obtained from all available slave units with the states of its locally connected simulated circuit breakers. When a valid response is received, the corresponding slave is marked as ONLINE, and its breaker-state information is incorporated into the global state vector. If no valid response is received within the predefined waiting interval, the slave is marked as TIMEOUT. The master unit then generates a single-point offline alarm while continuing the polling process for the remaining nodes.
4. Experimental and Field Verification
The circuit boards of the master unit and slave unit of the portable auxiliary verification device for relay protection developed and prototyped in this study are shown in
Figure 5 and
Figure 7, respectively.
Figure 12 illustrates the external view of the master unit, while
Figure 13 shows the external view of the slave unit. Additionally,
Figure 14 and
Figure 15 present the experimental configuration in which the master and slave units are connected to a relay protection device for on-site testing.
The proposed device was prototyped and tested against the relay protection panels of a 500 kV substation; in the test configuration, the master was placed in the main control room while the slaves were wired at the distributed protection panels and in the switchyard. Each test followed the standardized procedure summarized in
Figure 16: after a pre-test inspection of battery voltage and wireless link status, all wiring was performed with the protection outputs de-energized, exposed conductors were insulated and the supply polarity was verified with a multimeter; the simulators were then named in the HMI, driven either manually or by protection outputs, and observed centrally; after the test, power was removed before the wiring was restored against the recorded connection list.
4.1. Single-Breaker State Transition
A single-breaker state-transition test was first conducted to verify the basic state-emulation capability. The protection device generated closing and tripping commands according to the predefined test sequence. The corresponding simulated breaker received these commands and generated the expected position-feedback signals.
The expected and observed state sequences were recorded for each operation. The test focused on the transitions between the open and closed positions and on the consistency of the returned feedback signals.
Among the 12 tested state transitions, 12 transitions were reproduced correctly, resulting in a state sequence matching rate of 100%. The corresponding command-to-state response time ranged from 124 ms to 151 ms, with an average value of 138.2 ms.
4.2. Coupled ABT State Transition
The ABT test was performed to verify the coordinated operation of the main and standby simulated circuit breakers. The test sequence was defined according to the corresponding protection procedure. A trip command was first applied to the main breaker, after which the ABT logic was activated to initiate the standby-breaker operation. The simulated breaker responses were continuously monitored to verify the required operating sequence and logical coordination. The resulting condition was maintained until a manual reset was applied. This test therefore verified both the individual breaker responses and the overall consistency of the coupled operating sequence, including the required state-retention behavior.
For 12 repeated ABT sequences, 12 sequences were reproduced without state-order errors, corresponding to a sequence matching rate of 100%. The maximum measured transition time between two consecutive expected states was 154 ms.
4.3. Multi-Output Protection State Reproduction
The multi-output test was performed to verify the coordinated response of multiple simulated circuit breakers to independent protection outputs. Several breaker channels were connected to the corresponding protection outputs, and predefined simultaneous and sequential operating conditions were applied.
The responses of the simulated breakers were continuously monitored throughout the test to verify the correspondence between the protection outputs and their associated channels. The complete response sequence was evaluated to determine whether multiple outputs could be correctly identified and reproduced without interference between channels. Therefore, the test focused on the consistency of the resulting breaker states, the correctness of channel identification, and the timing relationships among multiple protection outputs.
The multi-output test was performed to verify the coordinated response of three simulated circuit breakers to independent protection outputs. Each simulated breaker underwent 12 state transitions, resulting in 36 transitions in total. All 36 transitions were correctly reproduced, giving a state transition accuracy of 100%. No channel misidentification was observed during the test.
4.4. Quantitative Comparison with Conventional Verification Approaches
To quantitatively evaluate the engineering efficiency of the proposed verification system, a benchmark comparison was conducted for the same six-breaker busbar protection verification task using three testing approaches: conventional physical breaker cycling, conventional point-by-point multimeter testing, and the proposed distributed verification method. The comparison focused on personnel requirements, total test duration, physical breaker operation, distributed state tracking, primary-system outage requirements, and secondary-wiring risks. For all three approaches, the timing interval started when the test preparation began and ended after all six breaker states and associated protection outputs had been verified and recorded. The results are summarized in
Table 4.
As shown in
Table 3, the proposed distributed verification method required only 38 min to complete the six-breaker verification task, compared with 185 min for conventional physical breaker cycling and 120 min for point-by-point multimeter testing, representing reductions of 79.46% and 68.3%, respectively, relative to the two conventional methods. In addition, the proposed method required no physical switching operations of the primary breakers, while the conventional physical-breaker method involved 12 switching operations for the six-breaker test. The proposed method also provided multi-node state tracking with a maximum measured synchronization delay of 154 ms, which was not available in the conventional point-by-point approach. These results indicate that the proposed method can reduce the time and physical intervention required for multi-breaker verification while providing centralized observation of distributed breaker states.
4.5. Field Application Result Analysis
To further validate its engineering application value, the device was utilized during routine relay protection inspections at a substation, facilitating the on-site verification of typical secondary circuits, including ABT, busbar protection, and main transformer protection systems.
During the testing process, it was entirely unnecessary to physically operate the primary high-voltage circuit breakers. The verification of protection trip outputs and the inspection of logical relationships were accomplished solely utilizing the circuit breaker simulators. Testing personnel could observe the status transitions of each circuit breaker simulator in real time via the mobile terminal, while leveraging the historical data export function to archive comprehensive testing records.
Compared to traditional on-site verification methods, the developed device offers the following advantages:
It eliminates the mechanical wear caused by the frequent opening and closing of high-voltage circuit breakers.
It enables the verification of complex protection logic without requiring primary equipment outages.
Multiple circuit breaker simulators can simultaneously provide status feedback, significantly improving the efficiency of overall scheme tests for complex protection systems.
Wireless communication substantially reduces the workload associated with long-distance on-site wiring, thereby enhancing both testing safety and operational efficiency.
The comprehensive field application results indicate that the device operates stably, fully satisfies the requirements for the on-site auxiliary verification of relay protection, and possesses significant value for broader engineering implementation.
5. Conclusions
To address the limitations of conventional on-site relay protection verification, this study develops a portable auxiliary verification device based on a distributed circuit-breaker state emulation method. The proposed method uses simulated breaker interfaces to reproduce the required breaker-state transitions and position-feedback signals without repeated operation of primary high-voltage circuit breakers. A master–slave architecture is employed to coordinate distributed breaker states and provide centralized monitoring. The system integrates 220 V and 24 VDC simulated breaker interfaces to support conventional breaker control, automatic bus transfer (ABT), and multi-output protection logic verification.
The results show that the proposed method reduced the total test duration to 38 min, compared with 185 min for conventional physical breaker cycling and 120 min for point-by-point multimeter testing, corresponding to reductions of 79.46% and 68.3%, respectively. The proposed method can complete the verification of relay protection logic without interrupting the power supply of the circuit breaker, while the maximum measured state-update or synchronization latency was 154 ms under the tested conditions. Field verification at a 500 kV substation further demonstrated that the proposed method could reproduce the required breaker-state sequences for ABT, busbar protection, and main-transformer protection without repeated operation of primary high-voltage breakers. The results demonstrate that the proposed distributed state-emulation method can reduce test duration and physical intervention while supporting coordinated verification of multiple breaker states.