4.2. Quantitative Analysis
The five scenarios considered in this study describe the progressive change of the main grid from an SG-dominated generation structure to a system with a high proportion of GFL and GFM inverters. In addition to the qualitative comparison of the Bode plots, several quantitative indicators are introduced to characterize the changes in the bus admittance spectra. Let
denote the magnitude of the positive-sequence bus admittance at the
kth observation bus.
The selected observation buses are divided into two groups: buses close to generator buses, denoted by
, and buses electrically remote from generator buses, denoted by
. For each bus group
, the dominant low-frequency peak is defined as
where
represents the largest bus admittance magnitude observed within the selected low-frequency range for bus group
g. The corresponding frequency is denoted by
. These two quantities are used to describe the magnitude and location of the dominant low-frequency peak, respectively.
Second, to quantify the smoothness of the low-frequency admittance spectrum, the average low-frequency magnitude variation is defined as
A smaller
indicates a smoother low-frequency admittance spectrum with fewer abrupt magnitude variations. It should be emphasized that
is used only as a descriptive quantity for comparing the frequency responses and is not a stability margin.
Finally, the spatial dispersion among different observation buses is evaluated by
In the following discussion,
is used to compare the spatial dispersion among buses while avoiding the dominant low-frequency resonance region.
First, the benchmark case with 100% SGs represents the conventional SG-dominated main grid. As shown in
Table 9, the dominant low-frequency peak is approximately 66.2 dB at 2.03 Hz for the buses close to generator buses and 57.3 dB at 1.32 Hz for the electrically remote buses. The difference between the two bus groups is not limited to the dominant resonance. At 100 Hz, the magnitude dispersion among the close buses is approximately 4.9 dB, whereas that among the remote buses reaches approximately 9.4 dB. Therefore, even in the conventional SG-dominated system, the equivalent bus admittance is not spatially uniform. The larger dispersion observed at remote buses indicates that electrical distance and network topology already influence the dynamic boundary seen from different distribution network access points.
Second, the 20% GFL scenario illustrates the difference between increasing power-electronic generation while retaining synchronous machines and actually removing synchronous machines from service. When the SGs remain online with reduced active power, the dominant peaks are approximately 61.9 dB and 56.1 dB for the close and remote bus groups, respectively. When the corresponding SGs are disconnected, these values increase to approximately 67.6 dB and 58.0 dB. Thus, under the same 20% GFL penetration, SG disconnection increases the dominant peak by approximately 5.7 dB at the close buses and 1.9 dB at the remote buses. This comparison indicates that the change in bus admittance cannot be explained only by the active power share of GFL inverters. Whether the replaced SGs remain synchronously connected to the system also affects the observed frequency response because their electromechanical dynamics and synchronous support are retained in the former case but removed in the latter.
When the GFL share is further increased to 40%, the effect becomes more strongly dependent on the observation location. With SGs retained online, the dominant peaks are approximately 66.3 dB at 1.95 Hz for the close buses and 56.2 dB at 1.32 Hz for the remote buses. After the corresponding SGs are disconnected, the close bus peak changes only slightly to 65.1 dB, whereas the remote bus peak increases substantially to 66.0 dB. The dominant remote bus peak therefore increases by approximately 9.8 dB, and its frequency shifts from approximately 1.32 Hz to 2.44 Hz. The close bus dominant frequency also shifts from approximately 1.95 Hz to 2.46 Hz. These results show that SG decommissioning does not simply cause a uniform increase in the bus admittance peaks. Instead, it redistributes the low-frequency resonance characteristics among different locations and changes both their magnitude and dominant frequency. This location-dependent redistribution becomes particularly evident when the GFL share is high and synchronous support is substantially reduced.
The comparison between the 20% and 40% GFL cases further supports this observation. For the SG retained cases, increasing the GFL proportion from 20% to 40% raises the close bus dominant peak from 61.9 dB to 66.3 dB, while the remote bus peak remains almost unchanged at approximately 56 dB. In contrast, for the SG disconnected cases, the close bus peak decreases slightly from 67.6 dB to 65.1 dB, whereas the remote bus peak increases from 58.0 dB to 66.0 dB. Therefore, increasing GFL penetration should not be interpreted as producing a monotonic increase in resonance magnitude at all buses. A more appropriate interpretation is that the combination of GFL penetration and SG decommissioning changes the spatial distribution and frequency characteristics of the system modes, and these changes are reflected differently at different bus locations.
Third, the introduction of GFM inverters has a pronounced effect on the low-frequency bus admittance characteristics. Taking the 40% GFL case with the corresponding SGs disconnected as the reference before GFM integration, introducing 15% GFM capacity reduces the dominant low-frequency peak from approximately 65.1 dB to 56.2 dB for the close bus group, corresponding to a reduction of 8.9 dB. For the remote bus group, the peak decreases from approximately 66.0 dB to 52.0 dB, corresponding to a larger reduction of approximately 14.0 dB.
The smoothing effect is even more evident from
. It can be found in
Table 10 that, before GFM integration,
is approximately 32.9 dB for the close buses and 23.3 dB for the remote buses. After 15% GFM is introduced, these values decrease to approximately 12.3 dB and 8.6 dB, corresponding to reductions of 20.6 dB and 14.7 dB, respectively. Therefore, the effect of GFM integration is not limited to reducing an individual resonance peak. It substantially reduces the overall magnitude variation over the low-frequency range and makes the bus admittance spectra considerably smoother. This quantitatively supports the observation from the Bode plots that GFM inverters reshape the low-frequency dynamic characteristics of the main grid.
Finally, Scenario 5 represents a system with only 15% SG capacity, 25% GFM capacity, and 60% GFL capacity. Although the GFL share is further increased, the dominant peaks decrease to approximately 47.8 dB for the close buses and 45.8 dB for the remote buses. Compared with Scenario 4, these values are further reduced by approximately 8.4 dB and 6.2 dB, respectively. The corresponding values decrease from 12.3 dB to 5.0 dB for the close buses and from 8.6 dB to 4.5 dB for the remote buses. Hence, the high power-electronic penetration scenario does not reproduce the low-frequency spectrum of the original SG-dominated system. Instead, it exhibits a substantially smoother low-frequency admittance characteristic shaped by the control dynamics of the GFM and GFL inverters.
Nevertheless, GFM integration does not eliminate the dependence of the bus admittance on network location. Across all investigated scenarios, remains within approximately 4.9–6.7 dB for the buses close to generation sources, whereas the corresponding dispersion for the remote buses is approximately 9.4–11.0 dB. In Scenario 5, for example, the dispersion is approximately 6.4 dB for the close bus group and 11.0 dB for the remote bus group. Therefore, although GFM integration significantly smooths the low-frequency response, the differences caused by electrical distance and network topology remain clearly observable.
Overall, the quantitative results reveal three main characteristics of the evolution of the upstream grid bus admittance. First, SG decommissioning and increasing GFL penetration reshape rather than uniformly amplify the low-frequency resonance characteristics, and the resulting changes depend strongly on the observation location. Second, introducing GFM inverters significantly reduces both the dominant low-frequency peaks and the overall low-frequency magnitude variation, demonstrating their ability to reshape the dynamic bus characteristics of a system with high GFL penetration. Third, the spatial dispersion among different buses remains significant even at high GFM penetration. Consequently, the future upstream grid should not be represented by a single fixed equivalent that is independent of generation composition, observation location, and frequency range. From the perspective of transmission and distribution interface modeling, a dynamic bus admittance representation that reflects these factors is therefore more appropriate.
Although GFM inverters help the main grid exhibit characteristics closer to those of an ideal voltage source in modeling, their underlying shaping mechanism differs from that of conventional SGs. A conventional SG-dominated power system is typically a high-inertia, low-damping system. The large inertia of SGs is mainly determined by the mechanical structure of the rotor and is therefore difficult to change significantly over a short time scale. Although the damping level can be improved through supplementary control, it is still fundamentally constrained by the physical system and operating conditions.
In contrast, for GFM inverters adopting the classical droop control strategy with a low-pass filter, the equivalent inertia
J and damping
D are given by:
It can be readily observed that, for the droop-controlled GFM considered here, the equivalent inertia and damping are related through
Therefore,
J and
D should not be directly compared by their numerical magnitudes, since they represent different terms in the equivalent frequency dynamics. A more meaningful quantity is the damping-to-inertia rate
, which characterizes the relative strength of damping with respect to the equivalent inertia.
For conventional SGs, the dynamic response is generally dominated by the physical rotor inertia, while the damping is determined by the inherent machine and system damping together with supplementary control. In contrast, for the GFM inverter considered in this study, both the equivalent inertia and damping are control-dependent, and the ratio
is directly determined by the droop control bandwidth. Even for GFM inverters employing other control strategies, such as virtual synchronous generator control, the virtual inertia setting depends on the front-end energy storage. Therefore, with the parameter settings considered here, the GFM inverter exhibits a higher damping-to-inertia rate than the conventional SG representation used in this study. Given the high cost of energy storage deployment [
25] and the ongoing debate over whether future power systems require inertia levels as high as those of conventional systems [
26], the introduction of GFM inverters may drive power systems toward a low-inertia, high-damping paradigm. With the parameter settings adopted in this study, the GFM therefore exhibits a comparatively stronger damping effect relative to its virtual inertia. This distinction suggests that the dynamic support provided by GFM inverters is not simply an electronic reproduction of the inertia-dominated behavior of conventional SGs. A conventional SG-dominated main grid can be regarded as an ideal voltage source because, from the perspective of the distribution network, it can be treated as having almost infinite inertia and very high short-circuit capacity, making its frequency extremely difficult to perturb. In contrast, a future power system dominated by GFM inverters is more likely to shape ideal-voltage-source-like port characteristics through actively adjustable damping and voltage-forming capability. In other words, both systems may exhibit strong voltage-source characteristics externally, and the former is closer to high-inertia support determined by physical properties, whereas the latter is closer to high-damping support shaped by control dynamics.
It should be noted that the present study is based on small-signal frequency-domain models, and hardware-in-the-loop or experimental validation is beyond the scope of this work. Accordingly, several implementation-related effects are not included in the present modeling framework, such as sensor and measurement dynamics, sampling and modulation delays, switching nonlinearities, current limiting and saturation, and DC-side voltage dynamics. These factors may modify the measured bus admittance, particularly in the higher frequency range or under large disturbances and converter limiting conditions. Therefore, the conclusions of this study should be interpreted as characterizing the small-signal bus admittance around the specified steady-state operating points, rather than the complete nonlinear behavior of the physical system. Further validation incorporating detailed converter nonlinearities and hardware implementation effects will be considered in future work.