Research on Single-Ended Protection for Multi-Terminal Flexible DC Lines Based on Line-Mode Reverse Traveling-Wave Covariance
Abstract
1. Introduction
- (1)
- Protection Methods Based on DC Reactor (DCR) Voltage
- (2)
- Protection Methods Based on Time-Domain TWs
- (3)
- Protection Methods Based on Time-Frequency Analysis
- (1)
- To tackle the issue where traditional methods fail to distinguish faults located on the left, right, or inside the T-zone due to the lack of DC reactors and noticeable high-frequency attenuation or TW front discrepancies, the proposed scheme relies on the overall backward TW trend over a 0.5 ms window. By eliminating dependence on high-frequency features and initial wavefronts, it not only accurately identifies T-zone faults but also significantly relaxes sampling rate requirements (operating effectively even at 50 kHz, and withstanding severe Gaussian white noise of up to 40 dB).
- (2)
- Unlike traditional covariance algorithms or magnitude-dependent protection schemes that are susceptible to transition resistance, the introduced normalization completely removes amplitude discrepancies, allowing the criterion to focus strictly on overall waveform trends. The algorithm operates reliably under high transition resistances of up to 300 Ω, with a simple mathematical formulation and low computational overhead that ensure easy engineering implementation.
- (3)
- Ultra-Fast Single-Ended Operation Performance: Operating exclusively on local single-ended electrical quantities, the scheme entirely eliminates communication latency. With minimal computational complexity, the calculation delay is practically negligible, accomplishing the full process from TW sampling to trip signal issuance within just 0.5 ms to deliver ultra-fast protection performance.
2. Analysis of Fault Traveling-Wave Propagation Characteristics
2.1. TW Propagation Characteristics of Internal T-Zone Faults and Line Faults
2.1.1. Fault Traveling-Wave Characteristics Along Line 1 on the Left Side of the T-Zone
- (1)
- The traveling-wave reflection and transmission process for a fault on Line 1 on the left side of the T-zone is illustrated in Figure 2.
2.1.2. Fault Traveling-Wave Characteristics Along Line 2 on the Right Side of the T-Zone
2.1.3. Fault Traveling-Wave Characteristics of Faults Within the T-Zone
2.2. Fault Traveling-Wave Characteristics Outside MMCs
3. Protection Criteria and Protection Scheme
3.1. Start-Up Criterion
3.2. Fault Region Identification Criterion
- (1)
- Fault Direction Criterion
- (2)
- Internal/External Fault Discrimination Criterion
3.3. Pole Selection Criterion
3.4. Lightning Disturbances
3.5. Protection Scheme
4. Simulation Verification
4.1. Simulation Verification of the Protection Principle
- (1)
- Fault on the Left Side of the T-zone
- (2)
- Faults on the right side of the
- (3)
- Internal T-zone Fault
- (4)
- External Faults Outside
- (5)
- External Faults Outside
4.2. Transition Resistance and Noise Interference
4.3. Lightning Disturbance
4.4. Compared with Existing Protection Schemes
5. Conclusions
- (1)
- A single-ended traveling-wave protection scheme applicable to the T-connection area of MMC-based multi-terminal flexible DC transmission systems is proposed. The protection devices are deployed inside the same converter station on both sides of the . Fault discrimination can be accomplished by relying solely on locally collected electrical quantities without the need for long-distance communication or time synchronization, thereby eliminating the adverse impacts of communication latencies and synchronization errors on protection performance.
- (2)
- A normalized covariance criterion based on the overall variation trend of the line-mode backward TW is constructed. Distinct from traditional protection methods that rely on frequency-domain features such as high-frequency energy or wavelet coefficients, the proposed criterion circumvents the extraction of specific high- or low-frequency components and directly quantifies the overall similarity of the waveforms. The normalization pre-processing effectively mitigates the impacts of waveform amplitude variations on the criterion, thereby reducing the sensitivity of the algorithm to fluctuations in sampling frequency and transition resistance.
- (3)
- Under the built PSCAD simulation model and test scenarios in this study, the proposed protection scheme can complete fault discrimination within a data window of only 0.5 ms after the protection is initiated. The protection remains entirely valid even when the sampling frequency drops to 50 kHz. Furthermore, the scheme can reliably identify faults under the conditions of a 300 Ω transition resistance and 40 dB Gaussian white noise, demonstrating that the proposed method possesses excellent operating speed, high robustness against transition resistance, and strong immunity to noise interference.
- (4)
- It should be noted that the proposed scheme is currently validated entirely via PSCAD simulations, without fully accounting for practical hardware delays and sampling jitter. Therefore, the lack of Hardware-in-the-Loop (HIL) or real-time simulation (e.g., RTDS) testing represents a limitation of this work. As a key direction for future research, an RTDS-based HIL experimental platform will be constructed to further evaluate the scheme’s reliability and engineering feasibility in real hardware environments.
Author Contributions
Funding
Data Availability Statement
Conflicts of Interest
References
- Ma, J.; Hong, L.; Zhou, X.; Deng, L.; Peng, H.; Zhu, R. Transient Response Analysis and System Fault Ride-Through Capability Optimization of HVDC Based on Hybrid Commutated Converter. IEEE Trans. Power Deliv. 2026, 41, 901–913. [Google Scholar] [CrossRef] [Scilit]
- Guo, C.; Liu, Y.; Zhao, C.; Wei, X.; Xu, W. Power component fault detection method and improved current order limiter control for commutation failure mitigation in HVDC. IEEE Trans. Power Deliv. 2015, 30, 1585–1593. [Google Scholar] [CrossRef] [Scilit]
- Xue, Y.; Zhang, X.P.; Yang, C. AC filter less flexible LCC HVDC with reduced voltage rating of controllable capacitors. IEEE Trans. Power Syst. 2018, 33, 5507–5518. [Google Scholar] [CrossRef] [Scilit]
- Guo, Z.L.; Hao, L.L.; He, J.H.; Chen, Z.G.; Wang, X.G. Complete protection strategy for loss of excitation in large-scale synchronous condensers applied to UHVDC transmission. CSEE J. Power Energy Syst. 2025, 11, 919–930. [Google Scholar] [CrossRef] [Scilit]
- Tang, Y.; Li, F.; Wang, Q.; Chen, B.; Jiang, Y.L.; Guo, X.J. Power stability analysis of UHVDC systems hierarchically connected to AC systems. Electr. Power Syst. Res. 2018, 163, 715–724. [Google Scholar] [CrossRef] [Scilit]
- Cai, H.; Wang, G.; Xie, Z.; Huang, J.; Zhang, J.; Xu, Z. Analysis on the safety and stability of flexible direct-current transmission technology in multi-infeed-direct-current receiving-end transmission power systems. In Proceedings of the 16th IET International Conference on AC and DC Power Transmission (ACDC 2020), Online Conference; Institution of Engineering and Technology (IET): London, UK; Stevenage, UK, 2020; pp. 238–243. [Google Scholar]
- Xing, C.; Liu, M.; He, X.; Xi, X. Research on flexible control technology of HVDC. In Proceedings of the 2019 IEEE 8th International Conference on Advanced Power System Automation and Protection (APAP), Xi’an, China, 21–24 October 2019; pp. 1186–1190. [Google Scholar]
- Cai, H.; Wang, G.; Xie, Z.; Huang, J.; Zhang, J.; Xu, Z. Research on the application of flexible direct-current transmission technology in the system planning integrated with large scale of offshore wind farms. In Proceedings of the 16th IET International Conference on AC and DC Power Transmission (ACDC 2020), Online Conference; Institution of Engineering and Technology (IET): London, UK; Stevenage, UK, 2020; pp. 339–343. [Google Scholar]
- Rao, H.; Zou, C.; Xu, S.; Cai, X.; Li, Y.; Zhao, X. The On-site Verification of Key Technologies for Kunbei-Liuzhou-Longmen Hybrid Multi-terminal Ultra HVDC Project. CSEE J. Power Energy Syst. 2022, 8, 1281–1289. [Google Scholar] [CrossRef] [Scilit]
- Pragati, A.; Mishra, M.; Rout, P.K.; Gadanayak, D.A.; Hasan, S.; Prusty, B.R. A comprehensive survey of HVDC protection system: Fault analysis, methodology, issues, challenges, and future perspective. Energies 2023, 16, 4413. [Google Scholar] [CrossRef] [Scilit]
- Xiao, H.; Li, Y.; Ren, S. Novel disturbance blocking criterion for reliable current differential protection of LCC-HVDC lines. IEEE Trans. Power Deliv. 2021, 36, 477–480. [Google Scholar] [CrossRef] [Scilit]
- Han, K.; Chen, Y.; We, M.; Ma, R. A novel pilot protection scheme based on differential voltage for hybrid LCC/MMC HVDC transmission lines. IEEE Trans. Power Deliv. 2024, 39, 1816–1826. [Google Scholar] [CrossRef] [Scilit]
- Tourn, D.H.; Florena, E.; Zamanillo, G.; Donolo, P.D.; Dissanayake, A.; Kulkarni, P.; Hartshorn, J.; Donolo, M. Signal processing for high impedance differential protection schemes. IEEE Trans. Ind. Appl. 2024, 60, 7702–7710. [Google Scholar] [CrossRef] [Scilit]
- Li, C.; Go, A.M.; Zhao, C. A fast DC fault detection method Using DC reactor voltages in HVdc Grids. IEEE Trans. Power Deliv. 2018, 33, 2254–2264. [Google Scholar] [CrossRef] [Scilit]
- Pérez-Molina, M.J.; Larruskain, D.M.; Eguía, P.; Santiago, V.V. Local derivative-based fault detection for HVDC grids. IEEE Trans. Ind. Appl. 2022, 58, 1521–1530. [Google Scholar] [CrossRef] [Scilit]
- Geddada, N.; Yeap, Y.M.; Ukil, A. Experimental validation of fault identification in VSC-based DC grid system. IEEE Trans. Ind. Electron. 2018, 65, 4799–4809. [Google Scholar] [CrossRef] [Scilit]
- Li, B.; Li, Y.; He, J.; Li, B.; Liu, S.; Liu, B.; Xu, L. An improved transient traveling-wave based direction criterion for multi-terminal Hvdc grid. IEEE Trans. Power Deliv. 2020, 35, 2517–2529. [Google Scholar] [CrossRef] [Scilit]
- Mu, D.; Lin, S.; He, P.; Li, X. An Improved Method of Traveling Wave Protection for DC Lines Based on the Compensation of Line-Mode Fault Voltage. IEEE Trans. Power Deliv. 2023, 38, 1720–1730. [Google Scholar] [CrossRef] [Scilit]
- Wu, J.; Li, H.; Wang, G.; Liang, Y. An Improved Traveling-Wave Protection Scheme for LCC-HVDC Transmission Lines. IEEE Trans. Power Deliv. 2017, 32, 106–116. [Google Scholar] [CrossRef] [Scilit]
- Wang, Y.; Zhang, B.; Fan, X. The overhead transmission line protection scheme for the voltage-source converter-based HVDC grids. J. Eng. 2019, 2019, 674–679. [Google Scholar] [CrossRef] [Scilit]
- Ha, H.X.; Yu, Y.; Yi, R.P.; Bo, Z.Q.; Chen, B. Novel scheme of travelling wave based differential protection for bipolar HVDC transmission lines. In Proceedings of the 2010 International Conference on Power System Technology, Hangzhou, China, 24–28 October 2010; pp. 1–6. [Google Scholar]
- Xie, F.; Hao, Z.; Ye, D.; Zhang, B.; Liu, Z. A RFTR based lightning disturbance identification scheme for VSC-HVDC line protection. In Proceedings of the Tsinghua University-IET Electrical Engineering Academic Forum: Constructing Green and Sustainable Energy System (2021), Beijing, China, 15–16 May 2021; pp. 75–80. [Google Scholar]
- Li, R.; Xu, L.; Yao, L. Dc fault detection and location in meshed multiterminal Hvdc systems based on Dc reactor voltage change rate. IEEE Trans. Power Deliv. 2017, 32, 1516–1526. [Google Scholar] [CrossRef] [Scilit]
- Silva, D.M.; Costa, F.B.; Franca, R.L.S.; Junior, F.C.S. Wavelet-Based Detection of Transients Induced by DC Faults Using Boundary Protection Principle. In Proceedings of the 2018 IEEE Power & Energy Society General Meeting (PESGM), Portland, OR, USA, 5–10 August 2018; pp. 1–5. [Google Scholar]
- Mishra, M.; Singh, J.G. Fault Detection and Localization in an MT-VSC-HVDC Network via a Hybrid CNN-Transformer Model With a Multi-Head Attention Mechanism. IEEE Access 2025, 13, 26365–26383. [Google Scholar] [CrossRef] [Scilit]

















| Fault Location | C1 | C2 | M | min(C1,C2) | K | Fault Direction | |
|---|---|---|---|---|---|---|---|
| External to f2 | 0.0332 | 0.0611 | 0.5433 | 0.0332 | 0.5066 | Left side of the T-zone | |
| Line 1 f1 | 0 km | −0.0151 | 0.0482 | 0.3132 | −0.0151 | 0.2634 | Left side of the T-zone |
| 20 km | −0.0266 | 0.0413 | 0.6440 | −0.0266 | 0.2785 | Left side of the T-zone | |
| 50 km | −0.0075 | 0.0579 | 0.1295 | −0.0075 | 0.3021 | Left side of the T-zone | |
| 90 km | 0.0099 | 0.0653 | 0.1516 | 0.0099 | 0.3859 | Left side of the T-zone | |
| 100 km | 0.0132 | 0.0652 | 0.2024 | 0.0132 | 0.4399 | Left side of the T-zone | |
| 120 km | 0.0159 | 0.0742 | 0.2143 | 0.0159 | 0.4403 | Left side of the T-zone | |
| 140 km | 0.0233 | 0.0752 | 0.3098 | 0.0233 | 0.4501 | Left side of the T-zone | |
| 160 km | 0.0165 | 0.0763 | 0.2162 | 0.0165 | 0.4651 | Left side of the T-zone | |
| 180 km | 0.0186 | 0.0797 | 0.2334 | 0.0186 | 0.4391 | Left side of the T-zone | |
| 200 km | 0.0172 | 0.0789 | 0.2180 | 0.0172 | 0.4552 | Left side of the T-zone | |
| 240 km | 0.0245 | 0.0810 | 0.3025 | 0.0245 | 0.3712 | Left side of the T-zone | |
| 260 km | 0.0198 | 0.0796 | 0.2487 | 0.0198 | 0.3018 | Left side of the T-zone | |
| 280 km | 0.0211 | 0.0776 | 0.2719 | 0.0211 | 0.4162 | Left side of the T-zone | |
| 300 km | 0.0278 | 0.0781 | 0.3560 | 0.0278 | 0.2675 | Left side of the T-zone | |
| External to f4 | 0.0500 | 0.0291 | 1.7182 | 0.0291 | 0.6652 | Left side of the T-zone | |
| Line 2 f3 | 0 km | 0.0531 | −0.0006 | 88.5000 | −0.0006 | 0.1359 | Right side of the T-zone |
| 30 km | 0.0543 | 0.0021 | 25.85 | 0.0021 | 0.1721 | Right side of the T-zone | |
| 60 km | 0.0622 | 0.0015 | 41.4667 | 0.0015 | 0.2029 | Right side of the T-zone | |
| 80 km | 0.0698 | 0.0020 | 34.9000 | 0.0020 | 0.3041 | Right side of the T-zone | |
| 120 km | 0.0616 | 0.0201 | 3.0640 | 0.0201 | 0.4623 | Right side of the T-zone | |
| 150 km | 0.0632 | 0.0213 | 2.9671 | 0.0213 | 0.6174 | Right side of the T-zone | |
| 180 km | 0.0661 | 0.0224 | 2.7500 | 0.0224 | 0.6372 | Right side of the T-zone | |
| 200 km | 0.0634 | 0.0233 | 2.8430 | 0.0233 | 0.4434 | Right side of the T-zone | |
| f9 T-zone | 0.0735 | 0.0723 | 1.0165 | 0.0723 | 0.5361 | Inside the T-zone | |
| Fault Location | C1 | C2 | M | min(C1,C2) | K | Fault Direction | |
|---|---|---|---|---|---|---|---|
| External to f6 | 0.0442 | 0.0603 | 0.733 | 0.0442 | 4.8352 | Left side of the T-zone | |
| Line 1 f5 | 0 km | −0.0023 | 0.0514 | 0.0447 | −0.0023 | 5.5627 | Left side of the T-zone |
| 20 km | −0.0116 | 0.0581 | 0.1996 | −0.0116 | 5.5938 | Left side of the T-zone | |
| 50 km | 0.0023 | 0.6014 | 0.0038 | 0.0023 | 6.0176 | Left side of the T-zone | |
| 90 km | 0.0105 | 0.5922 | 0.0177 | 0.0105 | 6.3424 | Left side of the T-zone | |
| 100 km | 0.0199 | 0.6634 | 0.0300 | 0.0199 | 6.5756 | Left side of the T-zone | |
| 120 km | 0.0201 | 0.7843 | 0.0256 | 0.0201 | 6.3439 | Left side of the T-zone | |
| 140 km | 0.0241 | 0.7645 | 0.3152 | 0.0241 | 5.9661 | Left side of the T-zone | |
| 160 km | 0.0189 | 0.0718 | 0.2632 | 0.0189 | 6.0211 | Left side of the T-zone | |
| 180 km | 0.0156 | 0.0723 | 0.2157 | 0.0156 | 5.5820 | Left side of the T-zone | |
| 200 km | 0.0133 | 0.0684 | 0.1944 | 0.0133 | 5.2191 | Left side of the T-zone | |
| 240 km | 0.0219 | 0.0885 | 0.2474 | 0.0219 | 5.1962 | Left side of the T-zone | |
| 260 km | 0.0228 | 0.0752 | 0.4130 | 0.0228 | 4.5642 | Left side of the T-zone | |
| 280 km | 0.0213 | 0.0771 | 0.2762 | 0.0213 | 4.4461 | Left side of the T-zone | |
| 300 km | 0.0291 | 0.0756 | 0.3849 | 0.0291 | 4.3324 | Left side of the T-zone | |
| External to f8 | 0.0512 | 0.0311 | 1.6463 | 0.0311 | 4.3021 | Left side of the T-zone | |
| Line 1 f7 | 0 km | 0.0582 | −0.0105 | 5.5428 | −0.0105 | 5.1362 | Right side of the T-zone |
| 30 km | 0.0506 | −0.0022 | 23.0000 | −0.0022 | 5.7721 | Right side of the T-zone | |
| 60 km | 0.0688 | 0.0141 | 4.8794 | 0.0141 | 5.7921 | Right side of the T-zone | |
| 80 km | 0.0733 | 0.0182 | 4.0274 | 0.0182 | 5.5509 | Right side of the T-zone | |
| 120 km | 0.0692 | 0.0287 | 2.4111 | 0.0287 | 5.4522 | Right side of the T-zone | |
| 150 km | 0.0643 | 0.0299 | 2.1505 | 0.0299 | 6.0065 | Right side of the T-zone | |
| 180 km | 0.0703 | 0.0251 | 2.8008 | 0.0251 | 4.3342 | Right side of the T-zone | |
| 200 km | 0.0629 | 0.0206 | 3.0533 | 0.0206 | 4.3341 | Right side of the T-zone | |
| f10 T-zone | 0.0721 | 0.0733 | 0.9836 | 0.0721 | 5.8129 | Inside the T-zone | |
| Fault Location | Transition Resistance (Ω) | C1 | C2 | M | min(C1,C2) | K | Fault Direction |
|---|---|---|---|---|---|---|---|
| External to f2 | 150 | 0.0297 | 0.0621 | 0.5442 | 0.0338 | 0.5623 | Left side of the T-zone |
| 300 | 0.0334 | 0.0618 | 0.5404 | 0.0334 | 0.5794 | Left side of the T-zone | |
| Line 1 f1 140 km | 150 | 0.0254 | 0.0718 | 0.3537 | 0.0254 | 0.4927 | Left side of the T-zone |
| 300 | 0.0299 | 0.0685 | 0.4365 | 0.0299 | 0.5113 | Left side of the T-zone | |
| External to f4 | 150 | 0.0516 | 0.0224 | 2.3035 | 0.0224 | 0.6883 | Right side of the T-zone |
| 300 | 0.0501 | 0.0277 | 1.8086 | 0.0277 | 0.6243 | Right side of the T-zone | |
| Line 2 f3 120 km | 150 | 0.0698 | 0.0193 | 3.6165 | 0.0193 | 0.5901 | Right side of the T-zone |
| 300 | 0.0701 | 0.0231 | 3.0346 | 0.0231 | 0.6001 | Right side of the T-zone | |
| f9 T-zone | 150 | 0.0711 | 0.0699 | 1.0171 | 0.0699 | 0.5370 | Inside the T-zone |
| 300 | 0.0692 | 0.0696 | 0.9942 | 0.0692 | 0.5466 | Inside the T-zone |
| Fault Location | Noise (db) | C1 | C2 | M | min(C1,C2) | K | Fault Direction |
|---|---|---|---|---|---|---|---|
| External to f2 | 20 | 0.0330 | 0.0613 | 0.5384 | 0.0330 | 0.5105 | Left side of the T-zone |
| 30 | 0.0335 | 0.0609 | 0.5500 | 0.0335 | 0.5082 | Left side of the T-zone | |
| 40 | 0.0299 | 0.0618 | 0.4838 | 0.0299 | 0.5114 | Left side of the T-zone | |
| Line 1 f1 140 km | 20 | 0.0218 | 0.0742 | 0.2938 | 0.0218 | 0.4881 | Left side of the T-zone |
| 30 | 0.0203 | 0.0715 | 0.2979 | 0.0203 | 0.5202 | Left side of the T-zone | |
| 40 | 0.0220 | 0.0731 | 0.3009 | 0.0220 | 0.4879 | Left side of the T-zone | |
| External to f4 | 20 | 0.0488 | 0.0288 | 1.6944 | 0.0288 | 0.6650 | Right side of the T-zone |
| 30 | 0.0482 | 0.0281 | 1.7153 | 0.0281 | 0.6642 | Right side of the T-zone | |
| 40 | 0.0475 | 0.0273 | 1.7399 | 0.0273 | 0.6648 | Right side of the T-zone | |
| Line 2 f3 120 km | 20 | 0.0612 | 0.0199 | 3.0753 | 0.0199 | 0.4829 | Right side of the T-zone |
| 30 | 0.0615 | 0.0203 | 3.0295 | 0.0203 | 0.5013 | Right side of the T-zone | |
| 40 | 0.0600 | 0.0201 | 2.9850 | 0.0201 | 0.5001 | Right side of the T-zone | |
| f9 | 20 | 0.0730 | 0.0729 | 1.0013 | 0.0729 | 0.5410 | Inside the T-zone |
| 30 | 0.0733 | 0.0734 | 0.9886 | 0.0733 | 0.5386 | Inside the T-zone | |
| 40 | 0.0728 | 0.0729 | 0.9986 | 0.0728 | 0.5620 | Inside the T-zone |
| Fault/Lightning Disturbance | Fault Identification Result | |
|---|---|---|
| Lightning strike (8/20 μs) | 0.12 | Lightning strike |
| Lightning strike (1.2/50 μs) | 0.17 | Lightning strike |
| Lightning strike (10/350 μs) | 0.23 | Lightning strike |
| Line 1 internal fault f1 = 50 km, Rf = 0 Ω | 0.75 | Fault |
| Line 1 internal fault f1 = 50 km, Rf = 300 Ω | 0.72 | Fault |
| Line 1 internal fault f1 = 180 km, Rf = 0 Ω | 0.74 | Fault |
| Line 1 internal fault f1 = 180 km, Rf = 300 Ω | 0.68 | Fault |
| Line 1 internal fault f1 = 320 km, Rf = 0 Ω | 0.97 | Fault |
| Line 1 internal fault f1 = 320 km, Rf = 300 Ω | 0.93 | Fault |
| Internal T-zone fault f10, Rf= 0 Ω | 0.79 | Fault |
| Internal T-zone fault f10, Rf = 300 Ω | 0.73 | Fault |
| Performance Metric | Ref. [23] | Ref. [24] | Ref. [25] | Proposed Method |
|---|---|---|---|---|
| System type | Multi-terminal VSC-HVDC | VSC-HVDC transmission system | Meshed multi-terminal MMC-HVDC | Three-terminal MMC-based flexible HVDC system with T-connection |
| Principle | Deep learning for fault temporal feature learning | Boundary reactor high-frequency attenuation | DCR voltage rate (equivalent to 2nd current derivative) | Waveform trend similarity of line-mode backward TWs quantified by normalized covariance |
| Methodology | CNN-Transformer hybrid model inference | First-scale SWT feature extraction | Dual-threshold time interval + polarity discrimination | Normalized covariance |
| Sampling Frequency | 50~100 kHz | 100 kHz~1 MHz | 13.5 kHz | 50 kHz |
| Operating Time | 1.4 ms | 1~3 ms | 4.89 ms | 0.5 ms |
| Transition Resistance Tolerance | 100 Ω | 1000 Ω | 100 Ω | 300 Ω |
| Noise Robustness | No quantitative noise test | 66.02 dB | 20 dB | 40 dB |
| Communication Requirement | None | None | None | None |
| Computational Complexity | Low. Requires only time-domain voltage threshold comparison and differential calculations; simple logic, easy engineering implementation. | Moderate. Requires first-scale stationary wavelet filter operations. | High. Deep learning model inference requires considerable computing power; high training costs, relying on high-performance processors. | Low. Involves only waveform normalization and covariance calculations. |
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content. |
© 2026 by the authors. Licensee MDPI, Basel, Switzerland. This article is an open access article distributed under the terms and conditions of the Creative Commons Attribution (CC BY) license.
Share and Cite
Yin, S.; Xing, X.; Zhang, B.; Hui, S.; Wang, P.; Feng, G.; Liu, W. Research on Single-Ended Protection for Multi-Terminal Flexible DC Lines Based on Line-Mode Reverse Traveling-Wave Covariance. Energies 2026, 19, 4400. https://doi.org/10.3390/en19184400
Yin S, Xing X, Zhang B, Hui S, Wang P, Feng G, Liu W. Research on Single-Ended Protection for Multi-Terminal Flexible DC Lines Based on Line-Mode Reverse Traveling-Wave Covariance. Energies. 2026; 19(18):4400. https://doi.org/10.3390/en19184400
Chicago/Turabian StyleYin, Shihao, Xiaodong Xing, Bin Zhang, Shixian Hui, Penglin Wang, Guangtao Feng, and Wei Liu. 2026. "Research on Single-Ended Protection for Multi-Terminal Flexible DC Lines Based on Line-Mode Reverse Traveling-Wave Covariance" Energies 19, no. 18: 4400. https://doi.org/10.3390/en19184400
APA StyleYin, S., Xing, X., Zhang, B., Hui, S., Wang, P., Feng, G., & Liu, W. (2026). Research on Single-Ended Protection for Multi-Terminal Flexible DC Lines Based on Line-Mode Reverse Traveling-Wave Covariance. Energies, 19(18), 4400. https://doi.org/10.3390/en19184400

