Next Article in Journal
A Physics-Guided Reduced-Order Digital Twin Prototype for Thermocable-Assisted SAGD: Scenario Screening of Spatial Heat Placement and Steam-to-Oil Ratio
Previous Article in Journal
Physics-Informed Validation of an XGBoost Decision Layer for SCADA-Based Wind Turbine Anomaly Detection
Previous Article in Special Issue
Demand Aware Dynamic Pricing for Smart Grid Communication Networks: A Stackelberg Game Approach
 
 
Font Type:
Arial Georgia Verdana
Font Size:
Aa Aa Aa
Line Spacing:
Column Width:
Background:
Article

Simulation Study on the Electric-Field Distortion Induced by Typical Assembly Defects in Cable Terminals

1
Guangdong Key Laboratory of Electric Power Equipment Reliability, Electric Power Research Institute of Guangdong Power Grid Co., Ltd., Guangzhou 510080, China
2
State Key Laboratory of Power Transmission Equipment Technology, School of Electrical Engineering, Chongqing University, Chongqing 400044, China
*
Author to whom correspondence should be addressed.
Energies 2026, 19(13), 3143; https://doi.org/10.3390/en19133143 (registering DOI)
Submission received: 27 May 2026 / Revised: 25 June 2026 / Accepted: 1 July 2026 / Published: 2 July 2026

Abstract

As a critical insulation component in cable systems, the cable terminal is susceptible to defects caused by human and environmental factors during manufacturing, installation, and service. Such defects may lead to local electric-field distortion and insulation weaknesses at the cable terminal, posing a severe threat to the safe operation of the cable system. In this study, an electric-field simulation model of a 10 kV cable terminal was implemented to investigate the effects of various defects, such as insufficient stress-cone overlap, axial scratch, ring-cut defect, and moisture ingress on the cable terminal. The results show that insufficient stress-cone overlap produces a severe field distortion, and the distortion level is strongly correlated with the misalignment distance. For mechanical damage defects, axial scratches and ring-cut defects mainly distort the electric field inside the air gap, and defect position induces a stronger distortion level than that of defect depth. With increasing ring-cut depth, the maximum value of distorted electric field first decreases and then rises slightly. For moisture defects, the distorted field primarily occurs at the angle between the water-film tip and the stress cone, where the maximum value appears near the XLPE/SIR interface. These results provide a theoretical basis for defect diagnosis, structural optimization, and assembly process control of cable terminals.

1. Introduction

Cable accessories are important components that are used for the connection of two sections of cable or as a bridge between XLPE cables and overhead lines. Their operational safety ensures the stability of power transmission. With the continuous development of power grids, the performance requirements for cable accessories have also been significantly raised [1,2,3]. However, various defects caused by human and environmental factors are difficult to eliminate during the assembly process of cable joints and terminals due to varying installation requirements from cable accessory manufacturers. Once these defects occur and are not detected timely, they may develop into severe failures such as short or open circuits in the power cable system [4,5].
Generally, defects generated in the assembly process of cable accessories may lead to severe electric-field distortion at the insulation shielding. This distortion increases local electric stress, which may accelerate insulation aging during operation and ultimately lead to power cable failures [6]. During the operation of the power cable, the silicone rubber at the cable joint or terminal expands because of the joule heat as the current flows through the conductor, which can cause air gaps at the interface between the silicon rubber and XLPE insulation. When the cable operates in a humid environment, moisture may enter the air-gap defect to induce an electric-field distortion at the interface [7,8]. The distorted electrical field is prone to inducing partial discharge and deteriorating the insulation performance of the cable joint, finally leading to cable accessory breakdown and lowering the reliable operation of the cable system [9].
In recent years, power cable faults caused by defects in accessories have received widespread concerns. Simulation models of cable joints with typical construction defects were built using finite-element theory to calculate the electric-field distribution at the defect area [10,11,12]. However, most of the two-dimensional simulation models exhibit a low similarity to the real defects in cable accessories. Meanwhile, the research often only focuses on a single type of defect, such as water-treeing degradation, and lacks analysis of the impact of spatial position on electric-field strength and comparative studies of different defects caused by environmental factors. Cable faults are closely related with different types that usually give rise to partial-discharge with various discharge characteristics [13,14]. For example, the characteristic parameters of partial discharge, including the quantity of partial discharge, discharge phase spectrums, pulse waveforms, and phase distributions, were widely adopted to assess the severity of different defects in the cable accessories [15,16,17]. Recently, most studies have mainly focused on the roles of thermal aging and impurity particles in cable joints. In contrast, the effects of stress-cone misalignment, main-insulation scratches, and moisture ingress on electric-field distribution and partial discharge activity on cable accessories remain unclear.
In this work, a three-dimensional finite-element model of a 10 kV cable terminal was established using COMSOL Multiphysics. Electric-field simulations were carried out to investigate typical defects, including stress-cone misalignment, mechanical damage, and moisture ingress. The simulation results reveal how defect types, position, and geometry modify the local electric-field distribution in the terminal structure. These findings provide a useful basis for optimizing stress-cone positioning, improving assembly quality control, and identifying defect-sensitive regions during maintenance.

2. Model Construction and Simulation Methodology

2.1. Geometric Model and Material Parameters of the Cable Terminal

A commercial 10 kV XLPE cable (YJV62-8.7/15 kV-1 × 185 mm2, Long Park Power Technology Co., Ltd., Zhuhai, China) with cold-shrinkable accessories were employed in this study. As illustrated in Figure 1, the 10 kV cold-shrinkable accessory exhibits a sophisticated multi-layer configuration. It primarily comprises the copper conductor, conductor shielding layer, XLPE insulation, insulation shielding layer, copper shield, semi-conductive tape, stress cone, and the secondary silicone rubber (SIR) insulation. A three-dimensional simulation model of the 10 kV cable accessory was constructed based on the assembly procedure and the dimensional specifications of the accessory. The internal stress cone of the cable terminal was designed with a bell-mouth profile, where a distinct arc-initiation point can be observed. The specific geometric parameters for each layer of the cable accessory structure are summarized in Table 1. The geometric dimensions and material parameters of the XLPE cable terminal used are listed in Table 1; it was provided by Long Park Power Technology Co., Ltd. (Zhuhai, China).

2.2. Boundary Conditions and Numerical Settings

For the 10 kV cable, the rated phase-to-ground voltage U0 of the copper conductor is 8.7 kV. Accordingly, the copper conductor was assigned a voltage of 8.7 kV, and the rated normal current was set to 350 A. The copper shield and the outer surface of the accessory main insulation were set to ground potential in the cable terminal model. The electric field was solved at the power frequency of 50 Hz. The electric field was calculated with the finite-element method using the governing equation of the electric current field, which is given in Equation (1) [18]:
J = Q j , v J = σ E + j ω D + J e E = φ
where ∇ is the vector differential operator, J is the current density vector in A/m2, Qj,v is the current source in A/m3, σ is the electrical conductivity in S/m, E is the electric-field vector in V/m, D is the electric displacement vector in C/m2, φ is the electric potential in V, and Je is the externally applied current density in A/m2. The basic variable φ will be solved and other parameters such as the electric-field strength can be derived from φ.
The simulations were carried out based on the finite-element method [19]. To ensure numerical reliability, a physics-controlled mesh with local refinement in the high-field regions was employed [20,21]. The final mesh parameters were determined based on mesh-refinement tests. This setting reduced numerical error effectively and ensured sufficient accuracy in regions with a thin copper shield and in regions containing multi-material composite structures. All finite-element simulations were performed using COMSOL Multiphysics 6.1 on a computer equipped with an Intel Core i7-12700 processor, 32 GB RAM, and a 64-bit Windows operating system. The mesh generation method is applied on the 10 kV XLPE cable terminal as shown in Figure 2.

2.3. Defect Configuration of the Model

The various defect configurations were selected according to common installation and service problems in cable terminals. Stress-cone misalignment usually occurs due to the insufficient stress-cone overlap caused by improper positioning or inaccurate cutting of the insulation shield during the cable terminal assembling. Axial scratches and ring-cut defects represent typical mechanical damage introduced during cable preparation or accessory installation. Moisture ingress represents the typical interfacial defects induced by sealing degradation and the breathing effect during service. These issues tend to induce severe local electric-field distortion at the insulation-shield cutback, XLPE/SIR interface, and air-gap regions in the cable terminal, which are critical locations for partial discharge initiation and insulation failure.

2.3.1. Stress-Cone Misalignment

According to the standard installation requirements for cable accessories, the end of the semi-conductive shielding layer in the cable should be chamfered to ensure a smooth electrical-field transition from the conductor to the XLPE insulation. Under ideal conditions, the stress-cone should fully cover the insulation shielding layer, and the designed positioning area is located about 12 mm from the chamfer to the initial point of the stress cone. In actual installation, position misalignment is generally caused by the improper positioning of the stress cone or inaccurate cutting of the insulation shielding layer, thereby resulting in an insufficient stress cone overlap. To reveal the relationship between the overlap misalignment distance and the electric-field distribution at the insulation shielding chamfer, a series of defect models were established as shown in Figure 3. In this case, the chamfer position is set as the reference point. The shield extension distance was designed from 0 to 50 mm with an interval of 5 mm.

2.3.2. Mechanical Damage Defects

During preparation and installation of cable accessories, improper manual force or inadequate tooling can inadvertently damage the XLPE insulation, leading to surface scratches or micro-air gaps. In this study, the axial scratch was designed as a four-sided prismatic defect with a length of 10 mm and a surface width of 0.2 mm. Based on this defect model, the effects of defect depth and axial position on the local electric-field distribution within the cable terminal were studied. Furthermore, the scratch defect along the axial position was varied from 0 to 90 mm from the insulation-shield chamfer (reference point) with an increment of 10 mm, as illustrated in Figure 4a. Moreover, the ring-cut scratch defect was designed about 5 mm away from the insulation-shield chamfer with a fixed width of 0.5 mm, and its depth followed gradient growth from 0.5 to 3 mm, as shown in Figure 4b.

2.3.3. Moisture Defect

Cable terminals can be frequently exposed to harsh service environments. Once the sealing system is compromised, environmental moisture can penetrate into the XLPE–SiR interface. Meanwhile, temperature fluctuations may induce repeated thermal expansion and contraction of the insulation materials, giving rise to the breathing effect that promotes further moisture ingress into the interior of the cable accessory. A large-area water film is probably generated at the interface between the XLPE insulation and stress cone in the cable terminal as shown in Figure 5. The water-film defect was modeled as a series of ellipsoidal subdomains, which were set 2.0 mm in length and 0.8 mm in both width and thickness. With the insulation-shield cutback taken as the axial reference point, the total interfacial length of the water-film defect was set to 50 mm.

3. Results

3.1. Electric-Field Simulation of Defect-Free Cable Terminals

Figure 6 shows the electric-field and equipotential distributions of the defect-free cable terminal. In Figure 6a, the electric-field intensity in the copper conductor and other equipotential metallic regions is approximately 0 kV/mm. The maximum electric-field intensity is 2.39 kV/mm, which occurs near the conductor-shield side of the XLPE insulation. Along the radial direction of the XLPE insulation, the electric-field intensity gradually decreases.
As shown in Figure 6b, the stress cone provides effective field grading, thereby mitigating the electric-field enhancement at the chamfer of the insulation shield. However, pronounced field concentration is still observed near the stress-cone tip and in the adjacent conductive structural region. This phenomenon is mainly ascribed to the fact that, under AC voltage, the electric-field distribution is governed predominantly by relative permittivity. At these locations, the interface between materials with high permittivity differences causes local field distortion. Moreover, the local curvature of the structure favors charge accumulation, which further intensifies the partial electrical-field concentration.
The radial electric-field intensity distribution near the stress-cone tip is shown in Figure 6c. The electric field inside the cable terminal decreases progressively along the radial direction, and most of the electric stress is concentrated in the XLPE insulation. The maximum electric-field intensity occurs at the interface between the XLPE insulation and the conductor shielding layer.

3.2. Simulation of Stress-Cone Misalignment

Figure 7 shows the potential, electric-field, and equipotential-contour distributions for cable terminals with stress-cone misalignment. A chamfer at the insulation shield forms a sharp cutback edge, which tends to distort the local electric field. In the defect-free case, the stress cone can limit the electric-field intensity to 1.58 kV/mm. As shown in Figure 7a,b, once the insulation shield protrudes beyond the stress-cone tip, the original equipotential distribution is disrupted, and the equipotential lines diverge from the edge of the insulation-shield cutback, indicating that the field-grading capability of the stress cone is weakened. In Figure 7c, when the edge of the insulation-shield cutback is located 15 mm from the reference position, it just extends beyond the stress-cone tip, and field distortion begins to appear with the maximum electric-field intensity of 2.40 kV/mm. When the edge of the insulation-shield cutback is located 25 mm from the reference point, as shown in Figure 7d, typical electric-field distortion occurs at the cutback tip. The maximum electric-field intensity increases to 3.67 kV/mm, which is 3.5 times that of the defect-free case, indicating a significant risk to the safe and reliable operation of the cable terminal.
Figure 8 shows the electric-field intensity along the XLPE/SIR interface in the axial range of 0–65 mm from the insulation-shield reference point. When the cutback is located beneath the stress-cone flare, corresponding to a distance of 15–20 mm from the reference point, the effective overlap between the stress cone and the insulation shield becomes insufficient. As a result, the field-grading capability of the stress cone is weakened, and the potential gradient becomes concentrated near the XLPE/SIR interface, causing the field intensity to rise rapidly above 2.4 kV/mm. When the cutback is further extended into the 25–50 mm range, the field distribution is mainly governed by the exposed cutback edge and the XLPE/SIR interface. Therefore, the field intensity remains at a high level of approximately 3.6–3.69 kV/mm, corresponding to an increase of about 133% relative to the defect-free condition.

3.3. Simulation of Mechanical Damage Defects

Figure 9 shows the effects of axial scratches at different locations and depths on the electric-field distribution inside the cable terminal. As shown in Figure 9a–c, three representative axial scratch cases are presented. The scratches are located 20, 50, and 80 mm from the insulation-shield reference point, with corresponding depths of 1, 2, and 3 mm, respectively. The maximum electric-field intensities associated with these three defects are 2.00, 1.36, and 1.49 kV/mm, respectively, indicating that the most severe distortion occurs in the case with a scratch position of 20 mm and a depth of 1 mm. In all three cases, the electric-field distortion is mainly localized in the defect region, whereas the field distribution within the defect remains markedly nonuniform. Moreover, the location of the peak distortion varies with scratch position, suggesting that scratch position has a stronger influence on the local field response.
Figure 9d shows that the average electric-field intensity at the defect varies non-monotonically with axial position, whereas its dependence on scratch depth is relatively weak. For all scratch depths, the average electric-field intensity follows a broadly similar variation with scratch position. Within the 0–10 mm region from the insulation-shield reference point, the average electric-field intensity remains relatively high and reaches the maximum of 1.78 kV/mm at 10 mm, which is mainly attributed to the proximity to the stress-cone tip, where the interaction between permittivity mismatch and the complex multi-material interface configuration intensifies the local field distortion. When the scratch is located more than 20 mm away from the insulation-shield reference point, it gradually moves away from the stress-cone tip region, where the local field distortion is strongest. As a result, the average electric-field intensity inside the defect decreases rapidly to a minimum of about 0.9 kV/mm. When the scratch moves farther away from the insulation-shield reference point, the SIR layer above the defect gradually becomes thinner. The resulting reduction in the local insulation path causes the potential drop to be concentrated over a shorter distance, and the average electric-field intensity therefore increases again. In the 70–90 mm range, where the SIR thickness remains nearly unchanged, the average field approaches a stable value of about 1.2 kV/mm. By comparison, increasing scratch depth causes only a slight monotonic increase of approximately 0.1 kV/mm in the average electrical field, indicating that axial position causes a much stronger effect on the local electric-field distribution than that of scratch depth.
Figure 10 shows that the maximum electric-field intensity in the ring-cut area varies non-monotonically with defect depth. As shown in Figure 10a–c, in the ring-cut defect with depth of 2.0 mm, the maximum field is relatively low at 1.81 kV/mm, whereas for depths of 1.0 mm and 3.0 mm it exceeds 1.9 kV/mm. For the shallow 1.0 mm ring cut, the high-field region is concentrated at the cut edge adjacent to the stress cone, as shown in Figure 10d, because the defect is located close to the stress-cone/air-gap interface, where a strong permittivity mismatch induces a steep local electric-field gradient. When the defect depth increases to 2.0 mm, the high-field region gradually extends from the stress-cone-side cut edge toward the inner region of the air gap, leading to a more distributed electric-field pattern with reduced local concentration, as shown in Figure 10e. This redistribution lowers the peak field and gives the minimum value among the three cases. When the depth further increases to 3.0 mm, a larger fraction of the local potential drop falls across the enlarged air gap, while the residual XLPE thickness is reduced to only 1.5 mm. Under this condition, the residual XLPE is no longer sufficient to effectively redistribute the defect-induced local electric stress, and the high-field region shifts toward the XLPE-side interface, causing the peak field to rise again, as shown in Figure 10f.
Figure 11 shows the variation in the average electric-field intensity in the ring-cut defects with depth of 0.5–3 mm. As the depth increases, the field strength of cable accessories first decreases and then slightly increases. For the cable terminal, the average electric-field intensity at the initial depth of 0.5 mm is 1.93 kV/mm, which is more than 21% higher than that in the defect-free case. Compared with axial scratches, ring-cut defects lead to more severe electric-field distortion because the circumferential cut disturbs the interfacial field over a larger region. In contrast, axial scratches mainly act as localized defects and therefore have a more limited influence on the overall field distribution. Moreover, the average electric-field intensity within the defect is strongly dependent on ring-cut depth. When the depth reaches 1.5 mm, the average field decreases to about 1.77 kV/mm, corresponding to a reduction of approximately 8.3% relative to the initial value of 1.93 kV/mm. As the cut depth increases further, the average field within the defect increases slightly.

3.4. Simulation of Moisture Defect

Figure 12 shows the distribution of potential, electric field, and their equipotential lines under the various moisture conditions at the terminal. As can be seen from Figure 12a, the presence of the water film significantly alters the original potential distribution. Specifically, the equipotential lines are deflected and diverge outward from the top of the water film. This behavior is similar to the field concentration observed at the edge of the insulation-shield cutback under insufficient stress-cone overlap. Unlike the stress-cone misalignment case, an evident potential gradient is established within the water film because of the permittivity and conductivity mismatch between the water film and its surrounding insulation material. As a result, the maximum electric-field intensity within the water film reaches 0.42 kV/mm. This peak appears near the stress-cone tip, where the equipotential lines are closely spaced, indicating pronounced local field concentration.
Figure 12b shows the electric-field distribution in the cable terminal with a moisture defect. Two major high-field regions are observed in the cable terminal: one at the corner where the water film meets the stress cone, and the other at the top of the water film. The maximum electric-field intensity, 3.47 kV/mm, occurs in the corner region. These regions therefore represent the dominant sites of local field enhancement, where geometric discontinuity and permittivity mismatch intensify the electric-field distortion.

3.5. Risk Implications for Cable Terminal Design and Maintenance

To evaluate the relative risk associated with different defect cases, the local electric-field intensity and its enhancement relative to the defect-free condition were taken as indicators of local dielectric stress. Previous studies have reported quantitative dielectric-performance references for cable termination insulation and XLPE-related interfacial defects. For example, the breakdown field strength of air was reported to be about 3 kV/mm, whereas the breakdown field strength of XLPE insulation was reported to be higher than 25 kV/mm [22]. Therefore, local field intensification near air gaps, moisture defects, and interfacial discontinuities is closely related to partial-discharge and breakdown risk.
Previous cable-termination studies further showed that internal defects can produce local electric-field intensities much higher than the air-breakdown level. The maximum distorted electric-field intensities caused by air-gap, water-droplet, semiconductor-impurity, and carbon-trace defects were reported to be 8.3, 14.3, 18.2, and 21.3 kV/mm, respectively [23]. In addition, a study combining finite-element simulation and partial-discharge tests on vehicle-mounted cable terminations showed that the maximum field strength during interfacial defect evolution could reach 14.1–18.3 kV/mm, and stable partial discharges could be formed at the operating voltage in certain defect-evolution stages [24].
It should be noted that the structures, material systems, voltage levels, and defect configurations in the cited studies are different from those in the present 10 kV XLPE cable termination model. Therefore, these reported values are used only as quantitative reference values for interpreting dielectric-performance risk, rather than as direct threshold criteria for the occurrence of partial discharge, electrical treeing, or dielectric breakdown in the present model. The simulated electric-field intensity in this work is therefore interpreted as a relative indicator of field intensification and defect sensitivity.
Based on this criterion, stress-cone misalignment and moisture ingress can be regarded as relatively high-risk defect conditions because they produce pronounced field concentration at the insulation-shield cutback and the water-film/stress-cone corner, respectively. Axial scratches cause more localized field distortion, whereas ring-cut defects disturb a larger interfacial region and therefore require closer attention. These results suggest that cable termination design should ensure sufficient stress-cone overlap and smooth field grading near the insulation-shield cutback, while operation and maintenance should focus on the XLPE/SIR interface, mechanically damaged regions, and moisture-sensitive sealing areas.

4. Conclusions

The effects of typical defects such as stress-cone misalignment, scratch defects, and moisture defects on the electric-field distribution in the 10 kV cable terminal were studied. It is found that the defect type, location, and geometry all play important roles in local field distortion in the cable terminal. Among the assembly defects, insufficient stress-cone overlap produces the most severe field distortion, with the peak electric-field intensity reaching 3.69 kV/mm, 133% higher than that in the defect-free case. For damage defects, axial scratches and ring-cut defects exhibit different distortion characteristics: the average field caused by axial scratches is governed primarily by scratch position, and the most severe distortion area occurs near the stress-cone tip, whereas the maximum field in ring-cut defects shows a non-monotonic dependence on defect depth. For moisture defects, field distortion is concentrated mainly at the water-film tip and at the angle between the water film and the stress cone. Overall, the results show that assembly quality and the defect location are the dominant factors affecting electric-field distortion in cable terminals.

Author Contributions

Conceptualization, X.Y.; data curation, X.Y. and Y.L.; methodology, Q.R.; validation, S.Y.; writing—original draft, M.Y.; writing—review and editing, X.Z. and X.Y. All authors have read and agreed to the published version of the manuscript.

Funding

This work was supported by the Innovation Project of China Southern Power Grid Co., Ltd. (Grant No. GDKJXM20222544).

Data Availability Statement

The original contributions presented in this study are included in the article. Further inquiries can be directed to the corresponding author.

Conflicts of Interest

Authors Xin Yu, Yinge Li and Shihu Yu were employed by the Guangdong Power Grid Co., Ltd. The remaining authors declare that the research was conducted in the absence of any commercial or financial relationships that could be construed as a potential conflict of interest. The authors declare that this study received funding from China Southern Power Grid. The funder was not involved in the study design; the collection, analysis, or interpretation of data; the writing of this article; or the decision to submit it for publication.

References

  1. Densley, J. Ageing mechanisms and diagnostics for power cables-An overview. IEEE Electr. Insul. Mag. 2001, 17, 14–22. [Google Scholar]
  2. Shi, Q.; Kanoun, O. Wire fault diagnosis in the frequency domain by impedance spectroscopy. IEEE Trans. Instrum. Meas. 2015, 64, 2179–2187. [Google Scholar] [CrossRef]
  3. Hamad, A.A.; Ghunem, R.A. A techno-economic framework for replacing aged XLPE cables in the distribution network. IEEE Trans. Power Del. 2020, 35, 2387–2393. [Google Scholar] [CrossRef]
  4. Ohki, Y.; Yamada, T.; Hirai, N. Diagnosis of cable aging by broadband impedance spectroscopy. In Proceedings of the Annual Report Conference on Electrical Insulation and Dielectric Phenomena, Cancún, Mexico, 16–19 October 2011; pp. 24–27. [Google Scholar]
  5. Yamada, T.; Hirai, N.; Ohki, Y. Improvement in sensitivity of broadband impedance spectroscopy for locating degradation in cable insulation by ascending the measurement frequency. In Proceedings of the IEEE International Conference on Condition Monitoring and Diagnosis, Bali, Indonesia, 23–27 September 2012; pp. 677–680. [Google Scholar]
  6. Ohki, Y.; Hirai, N. Location attempt of a degraded portion in a long polymer-insulated cable. IEEE Trans. Dielectr. Electr. Insul. 2018, 25, 2461–2466. [Google Scholar] [CrossRef]
  7. Xie, M.; Zhou, K.; Zhao, S.; He, M.; Zhang, F. A new location method of local defects in power cables based on reflection coefficient spectrum. Power Syst. Technol. 2017, 41, 3083–3089. [Google Scholar]
  8. Rao, X.; Zhou, K.; Xie, M.; Liu, L.; Wang, X.; Ye, B. Recovery technique of characteristic time-domain waveform based on frequency-domain reflection method. High Volt. Eng. 2021, 47, 1420–1427. [Google Scholar]
  9. Fantoni, P.F. Line Resonance Analysis System. U.S. Patent 0228222 A1, 10 September 2009. [Google Scholar]
  10. Fantoni, P.F. Line Resonance Analysis System. U.S. Patent 7996137 B2, 21 June 2011. [Google Scholar]
  11. Shi, Q.; Troeltzsch, U.; Kanoun, O. Detection and localization of cable faults by time and frequency domain measurements. In Proceedings of the 7th International Multi-Conference on Systems, Signals and Devices, Amman, Jordan, 27–30 June 2010; pp. 1–6. [Google Scholar]
  12. Hirai, N.; Yamada, T.; Ohki, Y. Comparison of broadband impedance spectroscopy and time-domain reflectometry for locating cable degradation. In Proceedings of the IEEE International Conference on Condition Monitoring and Diagnosis, Bali, Indonesia, 23–27 September 2012; pp. 229–232. [Google Scholar]
  13. Tozzi, M.; Cavallini, A.; Montanari, G.C.; Burbui, G.L.G. PD detection in extruded power cables: An approximate propagation model. IEEE Trans. Dielectr. Electr. Insul. 2008, 15, 832–840. [Google Scholar] [CrossRef]
  14. Ohki, Y.; Hirai, N. Effects of the structure and insulation material of a cable on the ability of a location method by FDR. IEEE Trans. Dielectr. Electr. Insul. 2016, 23, 77–84. [Google Scholar] [CrossRef]
  15. Li, R.; Zhou, K.; Wan, H.; Xie, M.; Liu, L.; Wang, X.; Miao, M. Study on moisture location of cable joints in medium-voltage distribution grid based on frequency-domain reflection method. Power Syst. Technol. 2019, 45, 825–832. [Google Scholar]
  16. Tian, J.; Chen, B.; Jiang, B.; Li, R.; Lei, S.; Hu, H. Reconfigurable frequency selective rasorber covering extremely wide transmission frequency range. IEEE Access 2020, 8, 225566–225580. [Google Scholar] [CrossRef]
  17. Yu, K.; Zeng, J.; Zeng, X.; Xu, F.; Ye, Y.; Ni, Y. A novel traveling-wave fault location method for transmission network based on directed tree model and linear fitting. IEEE Access 2020, 8, 122610–122625. [Google Scholar]
  18. Zhou, Z. Local Defects Diagnosis for Cable Based on Broadband Impedance Spectroscopy. Ph.D. Thesis, Huazhong University of Science and Technology, Wuhan, China, 2015. [Google Scholar]
  19. Ohki, Y.; Yamada, T.; Hirai, N. Precise location of the excessive temperature points in polymer-insulated cables. IEEE Trans. Dielectr. Electr. Insul. 2013, 20, 2099–2106. [Google Scholar]
  20. Zhou, Z.; Zhang, D.; He, J.; Li, M. Local degradation diagnosis for cable insulation based on broadband impedance spectroscopy. IEEE Trans. Dielectr. Electr. Insul. 2015, 22, 2097–2107. [Google Scholar] [CrossRef]
  21. Suzuki, H.; Endoh, T.; Sekii, Y. Experimental study on the causes of electrical breakdown of EHV XLPE insulation using prebreakdown partial discharge detection method. In Proceedings of the Annual Conference on Electrical Insulation and Dielectric Phenomena, Pocono Manor, PA, USA, 28–31 October 1990. [Google Scholar]
  22. Lai, Q.; Chen, J.; Hu, L.; Cao, J.; Xie, Y.; Guo, D.; Liu, G.; Wang, P.; Zhu, N. Investigation of tail pipe breakdown incident for 110 kV cable termination and proposal of fault prevention. Eng. Fail. Anal. 2020, 108, 104353. [Google Scholar] [CrossRef]
  23. Tang, Y.; Gao, G.; Liu, K.; Chen, K.; Xie, Y.; Xin, D.; Zhou, S.; Wu, G. Electric field distribution and performance optimization of high-speed train cable terminal with internal defects. Eng. Fail. Anal. 2023, 151, 107360. [Google Scholar] [CrossRef]
  24. Xin, D.; Wu, G.; Chen, K.; Liu, K.; Xie, Y.; Gao, G.; Xiao, S.; Tang, Y.; Sun, C.; Lin, M. Evolutionary characteristics of interfacial defects inside vehicle-mounted high-voltage cable termination for high-speed trains. CSEE J. Power Energy Syst. 2023, 12, 1072–1085. [Google Scholar]
Figure 1. 10 kV XLPE cable terminal structure. 1—Copper conductor; 2—conductor shielding layer; 3—XLPE insulation; 4—insulation shielding layer; 5—copper shielding layer; 6—semiconductive tape; 7—stress cone; 8—silicone rubber.
Figure 1. 10 kV XLPE cable terminal structure. 1—Copper conductor; 2—conductor shielding layer; 3—XLPE insulation; 4—insulation shielding layer; 5—copper shielding layer; 6—semiconductive tape; 7—stress cone; 8—silicone rubber.
Energies 19 03143 g001
Figure 2. The 10 kV XLPE cable terminal mesh division.
Figure 2. The 10 kV XLPE cable terminal mesh division.
Energies 19 03143 g002
Figure 3. Simulation model of assembly defect in 10 kV XLPE cable.
Figure 3. Simulation model of assembly defect in 10 kV XLPE cable.
Energies 19 03143 g003
Figure 4. Axial scratch and ring-cut defects in XLPE cable terminal. (a) Axial scratch; (b) ring-cut scratch.
Figure 4. Axial scratch and ring-cut defects in XLPE cable terminal. (a) Axial scratch; (b) ring-cut scratch.
Energies 19 03143 g004
Figure 5. Moisture defect in XLPE cable terminal.
Figure 5. Moisture defect in XLPE cable terminal.
Energies 19 03143 g005
Figure 6. Defect-free cable terminal. (a) Electric-field distribution of the cable terminal; (b) distribution of equivalent electric-field lines at the cable terminal; (c) radial electric-field distribution at the arc starting point of the stress cone.
Figure 6. Defect-free cable terminal. (a) Electric-field distribution of the cable terminal; (b) distribution of equivalent electric-field lines at the cable terminal; (c) radial electric-field distribution at the arc starting point of the stress cone.
Energies 19 03143 g006
Figure 7. Cable terminal stress cone overlapping not in place potential, electric field and its equipotential line distribution. (a) Potential distribution and equipotential contours for a misalignment of 15 mm; (b) potential distribution and equipotential contours for a misalignment of 25 mm; (c) electric-field intensity distribution under a 15 mm stress-cone misalignment; (d) electric-field intensity distribution under a 25 mm stress-cone misalignment.
Figure 7. Cable terminal stress cone overlapping not in place potential, electric field and its equipotential line distribution. (a) Potential distribution and equipotential contours for a misalignment of 15 mm; (b) potential distribution and equipotential contours for a misalignment of 25 mm; (c) electric-field intensity distribution under a 15 mm stress-cone misalignment; (d) electric-field intensity distribution under a 25 mm stress-cone misalignment.
Energies 19 03143 g007
Figure 8. The influence of stress-cone misalignment distance on electric-field strength of insulation-shield layer in cable terminals.
Figure 8. The influence of stress-cone misalignment distance on electric-field strength of insulation-shield layer in cable terminals.
Energies 19 03143 g008
Figure 9. Axial scratch electric-field distribution of cable terminal. (a) Distance 20 mm, depth 1 mm; (b) distance 50 mm, depth 2 mm; (c) distance 80 mm, depth 3 mm; (d) effect of axial scratch position and depth on the electric field in cable terminals.
Figure 9. Axial scratch electric-field distribution of cable terminal. (a) Distance 20 mm, depth 1 mm; (b) distance 50 mm, depth 2 mm; (c) distance 80 mm, depth 3 mm; (d) effect of axial scratch position and depth on the electric field in cable terminals.
Energies 19 03143 g009
Figure 10. Electric-field distribution for ring-cut defects in a cable terminal. (a) Electric-field distribution at a depth of 1 mm; (b) electric-field distribution at a depth of 2 mm; (c) electric-field distribution at a depth of 3 mm; (d) electric-field distribution of 1 mm air gap; (e) electric-field distribution of 2 mm air gap; (f) electric-field distribution of 3 mm air gap.
Figure 10. Electric-field distribution for ring-cut defects in a cable terminal. (a) Electric-field distribution at a depth of 1 mm; (b) electric-field distribution at a depth of 2 mm; (c) electric-field distribution at a depth of 3 mm; (d) electric-field distribution of 1 mm air gap; (e) electric-field distribution of 2 mm air gap; (f) electric-field distribution of 3 mm air gap.
Energies 19 03143 g010
Figure 11. Influence of ring-cut depth on electric-field intensity.
Figure 11. Influence of ring-cut depth on electric-field intensity.
Energies 19 03143 g011
Figure 12. Electric potential, field and equipotential line distribution in cable terminal with moisture-induced defect. (a) Electric potential and its equipotential line distribution; (b) electric field and its equipotential line distribution.
Figure 12. Electric potential, field and equipotential line distribution in cable terminal with moisture-induced defect. (a) Electric potential and its equipotential line distribution; (b) electric field and its equipotential line distribution.
Energies 19 03143 g012
Table 1. Material parameters of the cable terminal simulation model.
Table 1. Material parameters of the cable terminal simulation model.
ComponentRelative Permittivity (εr)Conductivity (σ, S/m)
Copper conductor/5.998 × 107
Conductor/insulation shielding1002
Main XLPE insulation2.31 × 10−18
Accessory insulation (SIR)2.853.125 × 10−16
Stress cone400.1
External shielding201.5
Epoxy resin block4.51 × 10−14
Semi-conductive tape105
Disclaimer/Publisher’s Note: The statements, opinions and data contained in all publications are solely those of the individual author(s) and contributor(s) and not of MDPI and/or the editor(s). MDPI and/or the editor(s) disclaim responsibility for any injury to people or property resulting from any ideas, methods, instructions or products referred to in the content.

Share and Cite

MDPI and ACS Style

Yu, X.; Ren, Q.; Li, Y.; Yang, M.; Yu, S.; Zhao, X. Simulation Study on the Electric-Field Distortion Induced by Typical Assembly Defects in Cable Terminals. Energies 2026, 19, 3143. https://doi.org/10.3390/en19133143

AMA Style

Yu X, Ren Q, Li Y, Yang M, Yu S, Zhao X. Simulation Study on the Electric-Field Distortion Induced by Typical Assembly Defects in Cable Terminals. Energies. 2026; 19(13):3143. https://doi.org/10.3390/en19133143

Chicago/Turabian Style

Yu, Xin, Qiyuan Ren, Yinge Li, Mingyuan Yang, Shihu Yu, and Xuetong Zhao. 2026. "Simulation Study on the Electric-Field Distortion Induced by Typical Assembly Defects in Cable Terminals" Energies 19, no. 13: 3143. https://doi.org/10.3390/en19133143

APA Style

Yu, X., Ren, Q., Li, Y., Yang, M., Yu, S., & Zhao, X. (2026). Simulation Study on the Electric-Field Distortion Induced by Typical Assembly Defects in Cable Terminals. Energies, 19(13), 3143. https://doi.org/10.3390/en19133143

Note that from the first issue of 2016, this journal uses article numbers instead of page numbers. See further details here.

Article Metrics

Back to TopTop