1. Introduction
China’s energy system is accelerating its shift toward a clean, low-carbon path amid the “dual-carbon” targets, with wind power installed capacity continuing to rise. As a higher share of wind power is integrated into the grid, new challenges have emerged for power system frequency stability [
1]. On the one hand, the system’s frequency regulation load is exacerbated by the volatility and randomness of wind power generation [
2]. Conversely, the doubly fed induction generator (DFIG) is connected to the grid via power electronic devices, which reduces the system’s equivalent inertia by weakening the direct coupling between its mechanical spinning components and the grid frequency. As the proportion of conventional synchronous generators gradually declines, the grid’s frequency support capability is further weakened, making the insufficiency of primary frequency regulation (PFR) under high wind power penetration increasingly prominent [
3].
To meet the operational needs of new-type power systems, large-scale wind farms are increasingly required to provide PFR [
4]. Current approaches to DFIG primary frequency regulation can be broadly divided into two groups: power reserve control and rotor kinetic energy control [
5]. The former adjusts the rotor speed or pitch angle to move the turbine away from the maximum power point tracking (MPPT) operating state, thereby reserving a margin for active power regulation [
6]. As core technical methods, virtual inertia control and droop control are used in the latter to release rotor kinetic energy for system frequency support [
7]. Reference [
8] reserves part of the power for the DFIG through rotor overspeed control, enabling bidirectional frequency regulation capability. Reference [
9] coordinates rotor overspeed control and pitch angle control to achieve continuous active power support over the full wind speed range. Optimized control schemes for DFIGs involved in PFR are proposed in References [
10,
11]. The adoption of virtual inertia control and adaptive droop mechanisms helps improve DFIG frequency performance and better realize rotor speed recovery characteristics. Reference [
12] further combines power reserve control and rotor kinetic energy control to optimize power output during the inertia response stage and reduce the system frequency recovery time. However, the effectiveness of these methods is still constrained by factors such as wind speed conditions, operating scenarios, and turbine states. Under complex disturbances or sustained frequency regulation scenarios, their active power support capability remains somewhat limited [
13].
Characterized by fast response and flexible power regulation, the energy storage system (ESS) is commonly deployed to facilitate PFR of power systems. References [
14,
15] adaptively combine virtual inertia control with droop control, thereby achieving smooth coordination among different ESS control modes. By accounting for the state of charge (SOC), Reference [
16] introduces a strategy to recover the SOC of the ESS within the frequency regulation dead-band stage, which effectively prolongs its cycle life. These findings suggest that integrating the ESS significantly enhances the rate of change of frequency (ROCOF) and effectively mitigates steady-state frequency deviation. However, the ESS’s frequency regulation capability is constrained by rated capacity and SOC limits. If the control parameters cannot be dynamically adjusted according to operating conditions, overcharging or over-discharging may easily occur during frequency support, thereby weakening the system’s capability for sustained regulation.
Consequently, the integrated involvement of both the DFIG and the ESS in PFR has steadily gained traction as a key research focus [
17]. The DFIG provides sustained active power support, while the ESS offers rapid power compensation. The two are highly complementary in response speed, regulation sustainability, and operational constraints. Reference [
18] advances a strategy based on the principle of “the ESS first, wind power supplementation.” The coordinated allocation of output power between the DFIG and the ESS is realized in Reference [
19] through fuzzy logic control. However, because these control rules are highly dependent on empirical settings, ensuring the global optimality of the outcomes remains a significant challenge. To overcome these empirical limitations, advanced control techniques have been introduced to enhance wind-storage frequency regulation. For instance, model predictive control (MPC) has been applied to coordinate wind farms and energy storage systems for fast frequency response due to its multi-objective optimization capabilities [
20]. Simultaneously, adaptive control strategies integrating virtual inertia and droop mechanisms have been explored to dynamically adjust the frequency support from the ESS based on grid conditions [
21]. However, two critical gaps remain in the existing literature: conventional MPC methods often rely on simplified weighting configurations and struggle to seamlessly integrate continuous dynamic mode-switching during complex, sustained load fluctuations; and existing adaptive strategies frequently lack a higher-level rolling optimization framework to strictly constrain the SOC while economically allocating power between the DFIG and the ESS.
To bridge these literature gaps, the main novelty of this paper lies in proposing a coordinated control strategy that combines dynamic weighting with MPC. Unlike existing methods that rely on fixed parameters or simple logic switching, our approach dynamically coordinates both the internal control modes of the ESS and the overall power allocation of the wind-storage combined system. The main contributions of this study are summarized as follows:
First, a continuous dynamic weighting mechanism based on hyperbolic tangent and logistic functions is proposed. This allows the ESS to smoothly transition between virtual inertia and droop control based on frequency variations, avoiding abrupt power changes.
Second, introduce an SOC feedback loop. By directly integrating the operating state of the ESS into the control weights, the strategy effectively prevents the ESS from overcharging or over-discharging during continuous frequency regulation.
Finally, an MPC-based rolling optimization model is established. It determines the optimal active power allocation between the DFIG and the ESS in real-time, balancing frequency regulation performance with system operational constraints.
3. Analysis and Discussion of the Results
This section comprehensively evaluates the proposed control strategy.
Section 3.1 presents the quantitative simulation results under various typical operational scenarios in MATLAB/Simulink R2024b. Subsequently,
Section 3.2 provides an in-depth theoretical discussion of these results, focusing on the dynamic frequency support performance and the SOC recovery mechanism.
3.1. Results
This subsection presents the quantitative simulation results to evaluate the effectiveness and superiority of the proposed coordinated optimal control strategy. First,
Section 3.1.1 details the simulation model and corresponding parameter settings established in MATLAB/Simulink. The subsequent subsections comprehensively analyze the system’s dynamic frequency support performance under various typical operating conditions, including step load disturbances and continuous wind speed variations.
3.1.1. Simulation Model and Parameter Settings
To evaluate the performance of the proposed wind-storage coordinated control strategy incorporating dynamic weighting coefficients and MPC, the wind-storage combined frequency regulation system depicted in
Figure 9 is selected as the study case, and a simulation model is developed using the MATLAB/Simulink platform. To ensure the validity and practical relevance of the simulation modeling, the simulation platform is constructed based on the classic two-area four-machine power system model. The fundamental parameters of the DFIG, the ESS, and the equivalent synchronous generators are configured using typical values widely adopted in related power system stability and frequency regulation studies, ensuring that the dynamic responses reflect realistic operational characteristics.
The rated capacity of the conventional synchronous generator in the AC grid is specified as 150 MW, while the installed capacity of the wind farm is 100 MW. To balance generation efficiency and frequency regulation capability when the DFIG participates in primary frequency regulation, the de-loaded ratio of the DFIG is set to 0.15, thereby reserving a margin for active power adjustment. The ESS is configured with a power/capacity of 10 MW/5 MWh, and its initial SOC is set to 0.5. The frequency regulation dead bands for both the DFIG and the ESS are defined as ±0.03 Hz. The MPC sampling interval, prediction horizon, and control horizon are set to 0.1 s, 4 s, and 3 s, respectively. Other relevant parameters are provided in
Table 1.
To assess the effectiveness of the proposed strategy across different operating conditions, two representative scenarios are investigated: a step load disturbance and a continuous load variation. To ensure clarity in the visual presentation, three control approaches are defined as follows: Scheme 1 denotes the proposed Dynamic-weight MPC coordinated control; Scheme 2 represents the dynamic-weight control; and Scheme 3 refers to the droop control. In the subsequent analysis, the frequency regulation performance of these schemes is evaluated comprehensively, considering system frequency deviation, changes in SOC, and the power output distribution characteristics of the DFIG and the ESS.
3.1.2. Analysis of the Step Load Disturbance Condition
To evaluate the frequency regulation capability of the proposed strategy under a sudden power imbalance, a step load-disturbance scenario is simulated. The wind speed is fixed at 10 m/s, the initial SOC of the ESS is set to 0.5, and a 30 MW step load disturbance is introduced at 2 s. The system responses corresponding to three control methods are compared. The simulation results are presented in
Figure 10,
Figure 11,
Figure 12 and
Figure 13, and the associated frequency regulation metrics are summarized in
Table 2.
As shown in
Figure 10, under a step load disturbance, the system frequency drops to varying degrees, then gradually recovers toward stability. However, the frequency response processes under different control strategies show obvious differences. Under droop control, the system frequency experiences the deepest drop and a relatively slow recovery process. By comparison, dynamic-weight control mitigates the frequency dip following a disturbance and accelerates frequency restoration. When MPC is further incorporated, the system frequency response becomes smoother, with a higher minimum frequency and a faster recovery rate. As indicated in
Table 2, under dynamic-weight MPC coordinated control, the maximum frequency deviation is 0.55 Hz, representing a reduction of about 11.3% compared with 0.62 Hz under droop control. Meanwhile, the steady-state frequency deviation decreases from 0.36 Hz to 0.33 Hz, and the peak time is shortened from 4.21 s to 3.66 s. These findings demonstrate that the proposed strategy enables a more rapid coordinated response of wind power and the ESS after disturbances, effectively restraining frequency decline and improving the system’s dynamic performance.
As shown in
Figure 11, after the step load disturbance, the SOC of the ESS gradually decreases under all three control strategies, due to the continuous discharge of the ESS to support system frequency regulation. Compared with droop control, the SOC decline rate is slowed down under dynamic-weight control. After further adoption of dynamic-weight MPC-coordinated control, the SOC curve remains the highest overall and shows the smallest decrease. At 30 s, the SOC values under droop control, dynamic-weight control, and dynamic-weight MPC coordinated control are approximately 0.480, 0.482, and 0.484, respectively. This indicates that dynamic-weight MPC coordinated control can, while ensuring the frequency regulation effect, more reasonably coordinate the output allocation between the DFIG and the ESS, reduce the sustained discharge intensity of the ESS, and thus slow down energy consumption while preserving more frequency regulation margin.
Combining
Figure 12 and
Figure 13, the output-sharing characteristics of the DFIG and the ESS under the three strategies can be further analyzed. After the disturbance occurs, both the DFIG and the ESS rapidly increase their outputs to participate in system frequency regulation; the ESS responds faster, while the DFIG provides relatively sustained active power support. Under droop control, the ESS assumes a larger frequency regulation task after the disturbance. Dynamic-weight control improves, to a certain extent, the coordination between virtual inertia control and droop control across different frequency regulation stages by dynamically adjusting their weights. Dynamic-weight MPC-coordinated control further optimizes the coordinated output allocation between wind power and the ESS, enabling the DFIG to make fuller use of the reserved de-loaded power for frequency regulation in both the initial disturbance stage and the recovery stage, while suppressing the peak output and the subsequent sustained output level of the ESS.
3.1.3. Analysis of the Continuous Load Fluctuation Condition
To further evaluate the frequency regulation capability of the proposed control strategy under continuous disturbance conditions, a scenario with ongoing load fluctuations is simulated. The corresponding load profile is presented in
Figure 14.
In this case, the system load varies continuously over time, placing more stringent demands on both the frequency support and sustained regulation capabilities of the wind-storage combined system. The responses of the system under three control strategies—droop control, dynamic-weight control, and dynamic-weight MPC-based coordinated control—are comparatively analyzed. The simulation outcomes are illustrated in
Figure 15,
Figure 16,
Figure 17 and
Figure 18, and the corresponding quantitative evaluation indices are summarized in
Table 3.
As shown in
Figure 15 and
Table 3, under continuous load fluctuations, all three control strategies can suppress system frequency deviation to some extent, but their control performance differs significantly. Under droop control, the amplitude of fluctuations in system frequency deviation is largest, with a peak-to-peak frequency deviation of 0.62 Hz and an RMS frequency deviation of 0.138 Hz. Dynamic-weight control adjusts the contribution ratios of virtual inertia control and droop control based on the frequency state, thereby reducing the peak-to-peak and RMS frequency deviations to 0.54 Hz and 0.129 Hz, respectively. In contrast, under dynamic-weight MPC coordinated control, the frequency deviation curve is the smoothest overall. Its peak-to-peak and RMS frequency deviations are further minimized to 0.46 Hz and 0.122 Hz, respectively, indicating that this strategy has better frequency support and disturbance-rejection capabilities under continuous disturbance conditions. This is because MPC can perform rolling optimal allocation of the outputs of the DFIG and the ESS according to the current system state and the operating trend over the prediction horizon, thereby responding to load changes in a more timely and smoother manner and reducing system frequency fluctuations.
As shown in
Figure 16 and
Table 3, the SOC variation trends of the ESS also differ significantly under different control strategies. Under droop control, the SOC fluctuation amplitude is relatively large, with an SOC variation range reaching 0.25, and the overall SOC level is the lowest, indicating that the ESS undertakes a relatively heavy frequency regulation task and thus consumes energy more rapidly. Dynamic-weight control can slow the downward trend in SOC to some extent, narrowing the variation range to 0.18. Under dynamic-weight MPC coordinated control, however, the SOC curve remains overall the highest and fluctuates more smoothly, with the narrowest SOC variation range of 0.13. This indicates that this strategy can more reasonably constrain the energy release process of the ESS while satisfying the system frequency regulation requirements, maintaining a higher remaining charge level, and thereby enhancing the ability of the ESS to continuously participate in frequency regulation.
By combining
Figure 17 and
Figure 18, the output-sharing characteristics of the DFIG and the ESS under continuous disturbance conditions can be further analyzed. As shown in
Figure 17, the DFIG output power under all three control strategies varies with load fluctuations. However, under droop control, the fluctuation of the DFIG output is relatively larger. Dynamic-weight control improves the smoothness of the DFIG response during frequency regulation to some extent, whereas dynamic-weight MPC-coordinated control enables the DFIG output to maintain better coordination while tracking the system frequency regulation demand. As shown in
Figure 18, the ESS output power also varies frequently in response to load disturbances. Under droop control, the ESS’s power fluctuations are relatively large, indicating greater reliance on the ESS for rapid compensation. Dynamic-weight control can appropriately suppress excessively frequent and severe power variations of the ESS. Under dynamic-weight MPC-coordinated control, the fluctuation of the ESS output is further reduced, indicating that this strategy allows the ESS to primarily provide rapid and necessary power compensation through rolling optimization, while the DFIG provides relatively more sustained active power support. In this way, the complementary advantages of the DFIG and the ESS in terms of regulation stability and response speed can be more fully exploited.
3.2. Discussion
The results indicate that the proposed coordinated control strategy, based on dynamic weighting coefficients and MPC, provides better frequency support for the wind-storage combined system under both step load disturbances and continuous load fluctuations. Compared with droop control, the proposed method reduces the maximum and steady-state frequency deviations while accelerating frequency recovery. In addition, the ESS’s SOC decline is mitigated, and the output allocation between the DFIG and the ESS becomes more balanced. These results support the main idea of this study that frequency regulation performance can be improved by combining dynamic weighting-based comprehensive control with MPC-based coordinated optimization.
The improvement mainly comes from two aspects. The dynamic input weights allow virtual inertia control and droop control to shift smoothly across different stages of primary frequency regulation. This helps the ESS provide rapid support in the early stage of the disturbance and improves frequency restoration in the later stage. Compared with fixed-parameter or switching-based methods reported in previous studies, this continuous adjustment mechanism is better suited to reducing abrupt power variations during control transitions. The SOC-based feedback weights enable the ESS to participate in frequency regulation according to its operating state. This reduces the risk of excessive charging or discharging and helps preserve the ESS’s sustained regulatory capability. The smoother SOC trajectory under the proposed method reflects this effect.
The introduction of MPC further enhances coordination between the DFIG and the ESS. Compared with dynamic-weight control without MPC, the proposed dynamic-weight MPC coordinated control achieves better frequency quality and more balanced output sharing. This indicates that the front-end dynamic weighting design and the back-end predictive optimization play distinct but complementary roles. The ESS support is determined according to the instantaneous frequency state and SOC condition, while optimizing the actual power allocation of the DFIG and ESS over the prediction horizon under system constraints and operating costs. Therefore, the proposed framework is not merely a combination of two methods but a hierarchical coordination structure that integrates adaptive response shaping with rolling optimal dispatch. This distinguishes it from many existing wind-storage coordinated control methods based mainly on fixed rules or empirical logic.
From an engineering perspective, the findings are relevant to primary frequency regulation in power systems with high wind power penetration. As conventional synchronous generation is gradually displaced, equivalent inertia and frequency support capability decline. Under such conditions, neither wind turbines nor ESS alone can fully satisfy the requirements of rapidity, sustainability, and economy in frequency regulation. The results indicate that wind-storage coordination can improve transient frequency response while reducing the energy burden on storage, thereby enhancing the frequency resilience of future low-inertia power systems. In particular, allowing the DFIG to provide more sustained support and reserving the ESS mainly for fast compensation may improve both control performance and storage utilization efficiency.
Nevertheless, several limitations should be noted. First, the current study is based on a simplified simulation model under ideal operating conditions. In practical engineering applications, non-ideal factors such as communication delays, parameter mismatch, and measurement noise could potentially affect the performance of the proposed strategy. For instance, severe communication delays might degrade the real-time rolling optimization capabilities of the MPC, while measurement noise could introduce unexpected fluctuations in the dynamic weight calculations. Although the proposed framework demonstrates robust performance under idealized settings, evaluating and mitigating these non-ideal physical constraints remains a critical step for future practical deployment. Second, the ESS capacity is predefined, and the impact of storage sizing on coordinated frequency regulation performance and economic efficiency is not examined in depth. Third, although the proposed method performs well under the selected disturbance scenarios, its robustness under more complex multi-disturbance conditions and large-scale renewable integration still needs further verification. Future work may therefore focus on incorporating additional uncertainties and delays into the control design, jointly optimizing ESS sizing and coordinated control parameters, and extending the proposed strategy to more realistic multi-area or grid-connected renewable energy systems.
4. Conclusions
This paper investigated the primary frequency regulation problem for a wind-storage combined system under high wind power penetration and proposed a coordinated control strategy that integrates dynamic weighting coefficients with MPC. Based on theoretical modeling and simulation validations, the main conclusions are summarized as follows:
First, the dynamic input weights based on the frequency state allow the system to adjust the contributions of virtual inertia and droop control more adaptively. By incorporating SOC-dependent feedback weights, the ESS regulation capability is aligned with its operating conditions, which helps prevent excessive charging or discharging and maintains a stable SOC.
Second, the MPC layer optimizes the active power allocation between the DFIG and ESS while satisfying various operational constraints. Quantitative simulation results show that compared to conventional control methods, the proposed strategy reduces the maximum frequency deviation by 11.3% and shortens the peak recovery time by 13% under typical disturbance scenarios.
Overall, the proposed coordinated approach improves the frequency response of the system and ensures the sustained participation of the ESS. Future work will further examine the influence of ESS capacity allocation and more complex grid conditions on the control performance.