Optimal On-Load Tap Changer Tap Control Method for Voltage Compliance Rate Improvement in Distribution Systems, Based on Field Measurement Data

1
Power Distribution Laboratory, KEPCO Research Institute, Daejeon 34056, Republic of Korea
2
Department of Electrical Engineering, Chungnam National University, Daejeon 34134, Republic of Korea
*
Author to whom correspondence should be addressed.
Energies 2025, 18(2), 439; https://doi.org/10.3390/en18020439
Submission received: 2 December 2024 / Revised: 10 January 2025 / Accepted: 16 January 2025 / Published: 20 January 2025
(This article belongs to the Special Issue Measurement Systems for Electric Machines and Motor Drives)

Abstract

This paper proposes an optimal control method for the on-load tap changer (OLTC) of a substation’s main transformer (M.TR), to maximize the voltage compliance rate (VCR) in distribution system feeders. The conventional auto voltage regulator (AVR)’s line-drop compensation (LDC) control method struggles with accurately determining load centers and has limitations in managing voltage due to the variability of distributed energy resources (DERs). To address these challenges, this study defines sample number-based VCR (SNB-VCR) as the performance index function to be maximized. The optimal tap positions for the OLTC are obtained using the gradient ascent method. Since the SNB-VCR evaluates voltage compliance using 15 min interval data collected from all the load and DER connection points in the distribution system, the tap position obtained by the gradient ascent method maximizes voltage quality for every feeder included in the system. Using a simulation, it is verified that the proposed tap control method improves the overall voltage quality and reduces the occurrence of overvoltage or undervoltage compared to LDC control. The proposed control strategy offers a practical solution for enhancing voltage management efficiency in modern distribution systems, particularly those with high penetration of DERs.
Keywords: distribution system; OLTC tap control; voltage compliance rate; smart meter distribution system; OLTC tap control; voltage compliance rate; smart meter

Share and Cite

MDPI and ACS Style

Lim, H.; Jo, J.; Chun, K.-H. Optimal On-Load Tap Changer Tap Control Method for Voltage Compliance Rate Improvement in Distribution Systems, Based on Field Measurement Data. Energies 2025, 18, 439. https://doi.org/10.3390/en18020439

AMA Style

Lim H, Jo J, Chun K-H. Optimal On-Load Tap Changer Tap Control Method for Voltage Compliance Rate Improvement in Distribution Systems, Based on Field Measurement Data. Energies. 2025; 18(2):439. https://doi.org/10.3390/en18020439

Chicago/Turabian Style

Lim, Hanmin, Jongmin Jo, and Kwan-Ho Chun. 2025. "Optimal On-Load Tap Changer Tap Control Method for Voltage Compliance Rate Improvement in Distribution Systems, Based on Field Measurement Data" Energies 18, no. 2: 439. https://doi.org/10.3390/en18020439

APA Style

Lim, H., Jo, J., & Chun, K.-H. (2025). Optimal On-Load Tap Changer Tap Control Method for Voltage Compliance Rate Improvement in Distribution Systems, Based on Field Measurement Data. Energies, 18(2), 439. https://doi.org/10.3390/en18020439